TONY ESPOSITO LIGHTING/ELECTRICAL TECHNICAL REPORT II SEPTEMBER 15, 2011 HUNTER S POINT SOUTH INTERMEDIATE SCHOOL AND HIGH SCHOOL QUEENS, NY

Similar documents
Chang Liu Lighting + Electrical M.A.E./B.A.E. Integrated Degree. Technical Assignment 2 October 12, 2012 Faculty Consultants: Ron Dodson

Corbin Building. Technical Assignment 2. Matthew Trethaway Lighting/ Electrical AE 481W 10/26/2011 Advisor: Ted Dannerth

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

NYC Department of Education

NYC Department of Education

Technical II Report Electrical Systems

Chandler City Hall Chandler, Arizona

NYC Department of Education

NYC Department of Education

PART 1. Executive Summary. The Frederick College of Cardiology

GARCIA GALUSKA DESOUSA Consulting Engineers

Lindsay Frederick. Lighting + Electrical. Ron Dodson Faculty Advisor. Native American Cultural Center Arizona. Technical Report 2

Executive Summary. CNBC Global Headquarters Christine Cajilig

NYC Department of Education

Lord Stirling Community School Electrical Systems Existing Conditions & Building Load Summary Technical Assingment#2 Due October 26, 2004

NYC Department of Education

Electrical Design Guidelines Table of Contents

NYC Department of Education

NYC Department of Education

NYC Department of Education

NYC Department of Education

ELECTRIC SERVICE EVALUATIONS ELECTRICAL / BOILER REPLACEMENTS. Clarkstown Central School District. June Arch Proj. #

NYC Department of Education

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

ELECTRICAL EXISTING CONDITIONS AND DESIGN ANALYSIS

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

NYC Department of Education

Page 1 of General

NYC Department of Education

Element D Services Electrical

Alex Masterton, PE Electrical Engineer Reviewer AHCA Neal Boothe, PE Electrical Engineer/Principal

Technical Report Two

S AGE E NGINEERING A SSOCIATES, LLP

NYC Department of Education

Ho-Chunk Gaming THUNDERBIRD ENGINEERING, INC. MILWAUKEE: (414) MADISON: (608)

Technical Report 2: Electrical Systems Criteria and Existing Conditions

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School

SECTION EMERGENCY POWER SYSTEMS

ELECTRICAL POWER SYSTEMS

Division 26 ELECTRICAL TABLE OF CONTENTS

Building Electrical System Overview

NYC Department of Education

16620 EMERGENCY POWER SYSTEMS

NYC Department of Education

NYC Department of Education

A. Shop Drawing submittals shall include, but not be limited to, the following:

NYC Department of Education

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

NYC Department of Education

EMERGENCY POWER SYSTEMS

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT

NYC Department of Education

NYC Department of Education

NYC Department of Education

NYC Department of Education

NYC Department of Education

NYC Department of Education

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

Air Flow Diagram. Orange County Sanitation District SP-194 Section 05 Conceptual Design

Technical Report #2. Newseum and Freedom Forum Headquarters. Washington, D.C. Ryan Wise Lighting/Electrical Prof. Dannerth November 2, 2007

Prefunctional Checklist

NYC Department of Education

NYC Department of Education

NYC Department of Education

NYC Department of Education

Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus

NATIONAL TRAINING BOARD (ELECTRICIAN) REGULATIONS 2008 BR 54/2008 NATIONAL OCCUPATIONAL CERTIFICATION ACT :38

SECTION AUTOMATIC TRANSFER SWITCHES

ELECTRICAL/MECHANICAL INFRARED INSPECTION REPORT. The Corporate Facility 2001 Freedom Way United City, USA

Technical Report 2: Electrical Systems Existing Conditions and Building Load Summary Report. 100% Submission. Sherrerd Hall, Princeton University, NJ

CONNECTICUT. Downloaded

ELECTRICAL Seminar. B A L A Consulting Engineers, Inc. Edward J. Lynch, PE Vice President, Electrical Department Manager.

NYC Department of Education

Renovate MCRC Facilities Great Lakes, IL

Electrical Inspection Service & Distribution

Construction Management at Risk Services. New North East Branch Library Project. August 3, 2018

NYC Department of Education

Infrared Electrical Inspection Report

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1

UNIVERSITY OF PENNSYLVANIA NEURAL AND BEHAVIORAL SCIENCES BUILDING 415 University Ave, Philadelphia, PA 19104

Introduction Consultant shall incorporate the material in the DSS into the project specifications.

ELECTRICAL DESIGN BRIEF

NYC Department of Education

MEP Syllabus CAREER DEVELOPMENT CENTRE SHRISTI MEP. Trichy-26

ASCO Series 185 Power Transfer Switches

Technical Assignment #2 Electrical Systems Existing Conditions & Building Load Summary

Proposed Mechanical, Plumbing, and Electrical Systems For the LEDYARD POLICE DEPARTMENT LEDYARD, CT

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

PART 4 ELECTRICAL STANDARDS

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

UNIFIED FACILITIES CRITERIA (UFC)

F. GENERAL REQUIREMENTS Electrical Design Criteria 2009 Edition 11/23/2009 School District Palm Beach County Page-1 of 17

NYC Department of Education

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15

NYC Department of Education

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems

Related Sections: TBD. Effective Date: January 1, 2016

CHAPTER 8 ELECTRICAL

Transcription:

LIGHTING/ELECTRICAL TECHNICAL REPORT II SEPTEMBER 15, 2011 HUNTER S POINT SOUTH INTERMEDIATE SCHOOL AND HIGH SCHOOL QUEENS, NY

1 1A. POWER DISTRIBUTION SYSTEMS a. EXECUTIVE SUMMARY b. SUMMARY DESCRIPTION OF DISTRIBUTION SYSTEM This buildings electrical distribution system is a simple radial system in that there is a single entry point into the building, and everything else branches out radially from there. The main service entry point for this building is in the main electric closet located on the (plan) North wall of the building. Main Switchboard #1 (MS1) is the center point of this radial system. It is from MS1 that all other loads in the building are connected. The two side-by-side electric rooms on each floor serve as the main means of routing conduit and wire. One room is dedicated to panelboards that only connected to normal power, and the other contains panelboards connected to the emergency generator. Each room contains its own riser shaft for wire and conduit. The purpose of this is to keep the normal power and emergency power wiring separate. The generator, located on the room of the building in the emergency generator room, provides power to the critical building loads in the event of a power outage. Some of these loads include: emergency/egress lighting, two (2) elevators, telecom equipment, and the fire and jockey pump which are critical to the operation of the schools sprinkler system. c. UTILITY COMPANY INFORMATION Name: conedison (of New York Address: ConEdison Cooper Station P.O. Box 138 New York, NY 10276-0138 Website: http://www.coned.com/ NOTE: I still need to find the rate schedule. I may need some help. I do not understand the rates and tariffs portion of CON-EDISONs website. Rate Schedule Goes Here

2 d. SERVICE ENTRANCE The service enters this building on the north wall from four (4) CON-EDISON underground vaults. Main Switchboard 1 (MS1) is 4000A, and fed directly from these CON-EDISON vaults by twelve (12) sets of four (4) 500 MCM wire in four inch (4 ) conduit. This configuration is shown in Figure 1. This building is fed directly from the utility company and is not connected in any way to an ownermaintained campus distribution system. This service is metered in the CT cabinet located within MS1. Figure 1 (a) Shows the location of the main Electrical Service Room as it is located in the floor plan. (b) An enlarged plan of the main Electrical Service room showing the four (4) CON-EDISON underground vaults and how they feed Main Switchboard #1 (MS1). e. VOLTAGE SYSTEMS The building utilization voltage is 208Y/120V. After hitting the main transformer in the underground CON-EDISON vault, the voltage is reduced to 208Y/120V. There are no other transformers in the building, and as a result (for better or worse) all the building loads are at this voltage. f. EMERGENCY POWER SYSTEMS The 400kW generator located on the roof, is the primary source of power generation in the event of an outage. The switchboard SWBD-G also located on the roof in the same room, acts as the main distribution In the event of a power failure, the generator provides power to panels 1ELP-LS (which feeds the emergency lighting on the 1 st floor), 3ELP-LS (which feeds the emergency lighting on the 2 nd and 3 rd floor), and 5ELP-LS (which feeds the emergency lighting on the 4 th and 5 th floors). The lighting is fed via distribution panel 1EDP-EQ and the 400A automatic transfer switch ATS-EQ. In addition, the generator powers panels 4EAP-EQ and 2EAP-EQ. These panels feed the critical IT loads in the buildings telecom closets. Also powered by the emergency generator is the 1600A emergency switchboard located on the 1 st floor that feeds the buildings elevators and a single air handling unit (AHU-3) via the 800A automatic transfer switch ATS-LS.

3 The fire and jockey pump, also powered by the emergency generator, are critical to the water supply and pressure maintenance of the buildings fire sprinkler system. g. LOCATION OF SWITCHGEAR The two main switchboards, MS1 and MS2 are located in the main electrical room on the first floor. This room is the location of the main service entrance to the building. Also on the first floor, is the emergency power room which contains the main emergency switchboard, two (2) emergency panelboards, and 2 of the buildings 3 automatic transfer switches. There are two side by side electric rooms on each floor - one for normal power panelboards, and one for panels that are connected to the emergency generator. The primary mode of wiring and conduit routing is by two shafts that connect these stacked electric rooms on each floor. There is one shaft in each of the rooms so that the conduit for the emergency system is separate from the normal system. Major Equipment Name Type Floor Room Name Room # Enlarged Plan Emergency MS1 SB 1 ELECTRICAL SERVICE ROOM 117 N MS2 SB 1 ELECTRICAL SERVICE ROOM 117 N SWBD-EM SB 1 EMERGENCY POWER ROOM 123A Y 1EDP-LS DP 1 EMERGENCY POWER ROOM 123A Y 1EDP-EQ DP 1 EMERGENCY POWER ROOM 123A Y 1DP-MER DP 1 FIRE PUMP/PLUMBING/LAB SUPPORT 123 N ATS ATS 1 ELECTRICAL SERVICE ROOM 117 Y ATS-EQ ATS 1 EMERGENCY POWER ROOM 123A Y ATS-LS ATS 1 EMERGENCY POWER ROOM 123A Y 5DP-K1 DP 5 KITCHEN COMPLEX 534 N MCC-MER MCC Roof BOILER RM 603 N SWBD-G SB Roof EM GEN RM 604 Y GEN GEN Roof EM GEN RM 604 Y ATS: Automatic Transfer Switch DP: Distribution Panel SB: Switchboard GEN: Generator MCC: Motor Control Center Table 1 Information regarding the major electrical equipment in the building

4 Lighting and Appliance Panels Name Voltage Main Type Main Size Bus Size Floor Room Name Room # Enlarged Plan Emergency 1LP-A 208/120 1 ELECTRICAL CLOSET 133A N 1AP-A 208/120 1 ELECTRICAL CLOSET 133A N 1AP-B 208/120 1 ELECTRICAL CLOSET 133A N 1AP-MER 208/120 1 FIRE PUMP/PLUMBING/LAB SUPPORT 123 N 1ELP-LS 208/120 1 ELECTRICAL CLOSET 133B Y 1ELP-ELEV 208/120 1 ELEVATOR MACHINE ROOM 114 Y 1EP-EQ-TEL 208/120 1 TELECOM ROOM 112 Y 2LP-A 208/120 2 ELECTRICAL CLOSET 233A N 2AP-A 208/120 2 ELECTRICAL CLOSET 233A N 2AP-B 208/120 2 ELECTRICAL CLOSET 233A N 2EAP-EQ 208/120 2 ELECTRICAL CLOSET 233B Y 3ELP-DIM 208/120 3 AUDITORIUM STORAGE 354A Y 3LP-DIM-1 208/120 3 AUDITORIUM STORAGE 354A N 3LP-DIM-2 208/120 3 AUDITORIUM STORAGE 354A N 3LP-A 208/120 3 ELECTRICAL CLOSET 333A N 3AP-A 208/120 3 ELECTRICAL CLOSET 333A N 3AP-B 208/120 3 SCIENCE PREP 321 N 3AP-B1 208/120 3 SCIENCE LAB 319 N 3AP-B2 208/120 3 SCIENCE LAB 323 N 3ELP-LS 208/120 3 ELECTRICAL CLOSET 333B Y 4LP-A 208/120 4 ELECTRICAL CLOSET 433A N 4AP-A 208/120 4 ELECTRICAL CLOSET 433A N 4AP-A1 208/120 4 HS PROJECT ROOM 417/419 N 4AP-B 208/120 4 ELECTRICAL CLOSET 433A N 4EAP-EQ 208/120 4 ELECTRICAL CLOSET 433B Y 5PP 208/120 5 ELECTRICAL CLOSET 533A N 5LP-A 208/120 5 ELECTRICAL CLOSET 533A N 5AP-A 208/120 5 ELECTRICAL CLOSET 533A N 5AP-A1 208/120 5 HS SCIENCE LAB 519 N 5AP-A2 208/120 5 HS SCIENCE DEMO 523 N 5AP-A3 208/120 5 HS SCIENCE DEMO 525 N 5AP-K1 208/120 5 KITCHEN COMPLEX 534 N 5AP-K2 208/120 5 KITCHEN COMPLEX 534 N 5AP-K3 208/120 5 KITCHEN COMPLEX 534 N 5ELP-LS 208/120 5 ELECTRICAL CLOSET 533B Y RAP-MER 208/120 Roof BOILER RM 603 N SUP-RAP 208/120 Roof BOILER RM 603 N REAP-EQ 208/120 Roof BOILER RM 603 Y Table 2 Information regarding the Lighting and appliance panels in the building.

5 h. OVER-CURRENT DEVICES The main service switchboards, MS1 and MS2, utilize fused switches as their over-current protection devices. MS2 (fed from MS1) is protected by a 2000A fused switch. MS2 (the main service switchboard) is protected by a 4000A fused switch. All fused switches are UL listed class L which is time-delay and current limiting. Other distribution panels (SWBD-G, 1EDP-EQ, 1EDP-LS, 1EDP-MER, and SWBD-EM) have no main over-current protection, but utilize thermal-magnetic circuit breakers to protect the equipment they distribute power to. Lighting and equipment panels also utilize thermal-magnetic circuit breakers for both main overcurrent protection as well as branch circuit protection. i. TRANSFORMERS There are no transformers in this building. The only transformer in this system is the transformer at the main service entrance which is owned by the utility company CON-EDISON. The building utilization voltage is 208Y/120V, and all of the loads in the building are at this voltage. j. GROUNDING Grounding is not shown very extensively for this building. There is a drawing (E003.00) showing the lightning protection system located on the room, and another drawing (E004.00) showing a few grouding rods on the first floor. There are a few grounding details located in this drawing set and are as follows: DWG E601.00 Terminal Base Swivel Adapter Offset Air Terminal Base Lighting Protection at Roof Top Unit Alum. Air Terminal at Exhaust Fans Downlead to Lower Roof Downlead to Ground DWG E602.00 Grounding: Grounding with Ground Bus and Neutral Bus Grounding: Raceway Equipment Grounding system DWG E603.00 Grounding: Water Pipe Ground Connections and Ground Bus

6 k. SPECIAL EQUIPMENT Some panelboards in this building are equipped with a transient voltage surge suppression (TVSS) system. The panels that have this feature are as follows: MS1 1EP-EQ-TEL 2EAP-EQ 4EAP-EQ 1AP-A (2 section) 1AP-B 2AP-A (2 section) 2AP-B (2 section) 3AP-A (2 section) 3AP-B (2 section) 4AP-A (2 sections) 4AP-B (2 sections) 5AP-A (2 sections) The 400kW generator locater in the emergency generator room on the roof is a purely diesel generator. The generator contains the following items: Day tank: o Diesel fuel only o 10 gauge steel minimum o 75 gallons Voltage Regulator Starting Battery Battery Charger Remote Stop Switch Muffler Remote Annunciator Vibration Isolators Automatic Transfer Switches In addition, the generator is resistant to seismic forces. It has supports for internal and external components, fastening for batteries, and wiring and piping are designed and constructed to withstand static or anticipated seismic forces. l. LIGHTING LOADS m. LIGHTING CONTROL

7 n. MECHANICAL AND OTHER LOADS o. SERVICE ENTRANCE SIZE p. ENVIRONMENTAL STEWARDSHIP DESIGN Occupancy Sensors Daylighting Controls High Efficiency Lighting q. DESIGN ISSUES I do not know of any specific design problems encountered in the design of the electrical system. One thing I am curious about is the voltage that this system utilizes. I know it has something to do with the power company, but I will further investigate it for the next submission. For the investigation of the electrical system next semester, I would like to do a cost analysis of stepping up the voltage in part of the building for the mechanical equipment. The goal would be to see if a single transformer could be put into the building to serve the mechanical loads with the goal of reducing the size of the equipment. 1B. DRAWINGS a. SINGLE-LINE DIAGRAM DRAWING LIST E401.00: POWER SINGLE LINE AND RISER DIAGRAM b. SINGLE-LINE DIAGRAM DRAWING II. COMMUNICATIONS SYSTEMS a. TELEPHONE/DATA b. VIDEO SURVEILLANCE c. AUXILIARY ALARM d. INTRUSION ALARM e. FIRE RESCUE INTERCOM f. AUDIOVISUAL