Mounting Instructions Adapter for ventilation duct BWP-143A-SS, Stainless Steel version

Similar documents
ADAPTER FOR VENTILATION DUCT BWP-143A-SS (STAINLESS STEEL)

Instructions AutroFlame IR Flame Detector BG-201/BG-21

DM60-xxx Antennas. 1. Assembly. Installation Instruction for CMAX Antennas

System Description AutroMaster V Presentation System

Installation Handbook. Interactive Fire Alarm System Release 3. Operator Panel, BS-330. Protecting life, environment and property...

Instructions. Duct Mount Accessory Q Rev: 11/

SINGLE MONITORED INPUT UNIT BN-303

Operator's Handbook. Interactive Fire Alarm System Release 3. Information Panel, BV-320. Protecting life, environment and property...

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

AutroVoice voice alarm system AUTROVOICE VOICE ALARM. Loud and clear information

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

THE UNIT IS DELIVERED WITH INSTALLED ZERO CLEARANCE MANTEL.

ARIN THERMOSTATIC SHOWER SYSTEM

Condair Esco. Steam humidification system INSTALLATION INSTRUCTIONS EN 1310

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Heat Exchanger Block Replacement Instructions

Installation Instruction Venturi-Air Duct Kit. (Part No. S )

AD SP. Air Dryer Maintenance Manual. Innovation with Integrity. Version 001 NMR

Rhino AB Upper Check Valve Replacement

AUTROSAFE 4 A new level in interactive fire detection systems

TIMES SQUARE TWO-HANDLE THERMOSTAT

Model: 1100 Float-Controlled Condensate Trap, PN 25

BMW E36 Thermostat Removal And Coolant Flush

Easy Reliable Flexible. Interactive fire detection system

AUTROSAFE. An interactive fire detection system for larger vessels

INSTRUCTIONS. Duct Mount Kit Q900. Description. Operation

SERVICE MANUAL MULTI DECK 60 HOT MERCHANDISER MULTI DECK 100 HOT MERCHANDISER MULTI DECK 120 HOT MERCHANDISER CLASSIC DECK HOT MERCHANDISER

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

STREBEL S-CB + Cascade Kits

TP970 SERIES ASPIRATING WALL BOX ASSEMBLIES BEFORE INSTALLATION

019 ASSEMBLING THE HOTEND

Installation instructions Air drying unit for Bubble Sensor OTT CBS. English

Parenzo Range. Basin Mixer, Bath Filler & Bath Shower Mixer. Assembly instructions

Branching and Connection Box AAB. Operating manual AAB EN11. GTE Industrieelektronik GmbH

DR. E. HORN GmbH / Schoenaich, Germany

INSTALLATION INSTRUCTIONS M SHOWER SLIDING RAIL

IMMERSION HEATERS GAS AND BSP

BWT ECO. Fitting and operating instructions. Ultra Violet Water Disinfection System. ECO Range: LC 8 UV LC19 UV LC36 UV LC51 UV

Commercial Flat Concealed Sprinkler, Pendent, Quick & Standard Response, Standard Coverage, Model: CN-QR, K-Factor: 5.

Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Standard Coverage, Model: RC-QR, K-Factor: 5.6, SIN: SS9561

INSTALLATION INSTRUCTIONS

AutroSafe interactive fire detection system AUTROSAFE. An interactive fire detection system for complex installations

Model TY-FRFS, TY-FS Special, and TY-FS 57, 80, and 115 K-factor Upright and Pendent Flat Spray Sprinklers General Description

INSTALLATION MANUAL SPLIT TYPE ROOM AIR CONDITIONER (PART NO )

In the event of this condition, consult the Authorities Having Jurisdiction for guidance and approval.

INSTALLATION, INSTRUCTION AND SERVICE MANUAL

Installation Instructions EFS Hand Washing Station

Aplos Single Handle Basin Bathroom Faucet

PROPANE CONVERSION INSTRUCTIONS. Applies to: Gas-Fired, Tubular Radiant, Low-Intensity Infrared Heater

TECHNICAL INSTRUCTIONS

EX-TECH SIGNALLING SAS SD100-1 WEATHERPROOF SOUNDER/HORN TECHNICAL MANUAL

Mariner Microspray and Low-Flow Electrospray Fused Silica Spray Tip and Capillary Kit. Operating Instructions. 1 Product Description.

HERZ-DR-T-90. Radiator Control Valves with Pre-Setting Function by Means of Double Cone, Suitable for Conversion to Thermostatic Operation. H max.

Installation and Operating Instructions

Pressure equalization by Venting

Pressure equalization by Venting

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description

ACQUITY UPLC HT Column Heater Instructions

Projector. Flush Mount

AD XT. Air Dryer Service Manual. Innovation with Integrity. Version 003 NMR

MNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions

NetworkAIR RM Air Distribution Unit

Models: FM FM WARNING

Residential Flat Concealed Sprinkler, Pendent, Model: CN-RES, K-Factor: 4.9, SIN: SS8421

Installation Manual PS-200 & PS-201

INSTALLATION, INSTRUCTION AND SERVICE MANUAL

Installation & Service Manual. Models ALF 20, 30, 40, 50, 60, 80

Screw plug immersion heaters

Model: 1200 Model: 1200-G Model: 1200-N Float-Controlled Condensate Trap, PN 40

Installation. Leveling

Installation Manual PS-225 & PS-275

Technical Manual for the Alarm Pull Station PH1

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

HERSHEY S Classic Syrup Dispenser

Akva Vita Instantaneous water heater

Water level controller and limiter

TECHNICAL INSTRUCTIONS

F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual

Operating Manual. Model: Float-Controlled Condensate Trap, PN Safety instructions. 2 General description and usage

FIGURE 1. Model RD107

LIGHTING TEF 9980 STATUS LIGHT, MAIN LIGHT & REPEATER LIGHT ZONE 1, ZONE 2 & SAFE AREA USER MANUAL

Platen Heater Pad Replacement

Eco Pump. Thank You MODELS: BP-1/4 BP-1/2

STOP! Read this notice. STOP! Read before proceeding. These instructions are for gas conversion of the Evergreen boiler only.

Model TY-FRFS, TY-FS Special, and TY-FS Flat Spray Sprinklers, Upright and Pendent 57, 80, and 115 K-factor General Description

Installation Instructions for SHD Series Drawers

Data Sheet 4.24 Issue F

Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Extended Coverage (Light Hazard) Model: RC-QR-EC, K-Factor: 5.

Retrofit Instructions CLEARVIEW DAY COVER CAUTION: Please read this manual completely before attempting to install, operate or service this equipment

569, 570, 571, 572 Series

INSTALLATION, INSTRUCTION AND SERVICE MANUAL

IECEx TEST REPORT IEC Explosive atmospheres Part 0: Equipment General requirements

569, 570, 571, 572 Series

Snifter ATEX22 VERSION. User Manual. Distributor

DUPLEX COMPACT. 11. CONNECTIONS (1/2",3/4, 1") BRINE VALVE 5. (floater)

Data Sheet 4.19 Issue C

INSTALLATION. Glass Panel Doors (select models) CAUTION

INSTALLATION, INSTRUCTION AND SERVICE MANUAL

TCB-DP22CUL. Drain Pump Kit. Model name : AIR CONDITIONER (SPLIT TYPE) Installation Manual. Installation Manual 2 Air Conditioner (Split type) English

Solinder Single Lever Basin Faucet

Transcription:

Mounting Instructions Adapter for ventilation duct BWP-143A-SS, Stainless Steel version 116-P-BWP143ASS/DGB Rev A, 2015-11-20, Autronica Fire And Security AS

COPYRIGHT This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose. Autronica Fire and Security AS and its subsidiaries assume no responsibility for any errors that may appear in the publication, or for damages arising from the information in it. No information in this publication should be regarded as a warranty made by Autronica Fire and Security AS. The information in this publication may be updated without notice. Product names mentioned in this publication may be trademarks. They are used only for identification. Page 2

Table of Contents 1. Part Numbers... 1 2. Overview... 3 3. Air Sampling Tubes... 4 4. Mounting... 5 4.1 Preparations... 5 4.2 Inserting the Pipes... 6 5. Connections... 9 6. Final Mounting... 10 7. Position of the duct adapter... 11 8. Maintenance... 12 8.1 General... 12 8.2 Recommended actions 6-12 months after installation... 12 8.2.1 Visual inspection... 12 8.2.2 Check and re-tighten... 12

Part Numbers 1. Part Numbers Part number 116-BWP-143A-SS Description Adapter for ventilation duct, stainless steel version (ANSI316) for interactive systems (Autroprime, AutroSafe) 116-BWP-43A-SS* Adapter for ventilation duct, stainless steel version (ANSI316) for analog addressable systems (BS-100) *Note: The instructions of the manual also apply for BWP-43A-SS. Autronica delivers the following pipe kits in different lengths: Part number 116-BJ-358/100 116-BJ-358/150 116-BJ-358/300 116-BJ-358/550 116-BJ-358/800 116-BJ-358/1000 116-BJ-358/1500 Description Pipekit L=100mm, Ø16x1,5mm Pipekit L=150mm, Ø16x1,5mm Pipekit L=300mm, Ø16x1,5mm Pipekit L=550mm, Ø16x1,5mm Pipekit L=800mm, Ø16x1,5mm Pipekit L=1000mm, Ø16x1,5mm Pipekit L=1500mm, Ø16x1,5mm The length of the sampling tubes should be (approximately) between 2/3 and the full width of the duct. When using sampling tubes above the length of 800mm, it should be considered whether mechanical support inside the duct is needed. Mechanical support should be done by the installer. The BWP-143A-SS is delivered with 6 holes for glands or plugs Ø20 mm. Plastic plugs for transport is included. Glands, plugs and locking nuts are NOT part of delivery and shall be specified separately. Here is a overview of some available fittings in Autronica s portfolio: Page 1

Part Numbers Part number Description 116-6571-070.2020 CABLE GLAND A2LBFNP20M20 - (Ø20mm) - Nickel plated brass - IP66 and IP68 - Cable dia. min 9,4mm / max 14,0mm 116-6530-030.0020 SPMH/NP/M20 BLIND PLUG - (Ø20mm) - Nickel plated brass - IP66 and IP68 116-6531-006.0920 GLAND NUT M20X1.5 BRASS - (Ø20mm) - Nickel plated brass 116-6571-072.2020 CABLE GLAND M20 A2LDSSF/20 SS - (Ø20mm) - Stainless steel - IP66 and IP68 - Cable dia. min 9,4mm / max 14,0mm 116-6530-030.0120 BLIND PLUG M20 SPMH1SF/M20 - (Ø20mm) - Stainless steel - IP66 and IP68 116-6531-020.0020 GLAND NUT ACSLN/M20X1.5 SS - (Ø20mm) - Stainless steel Type of glands and plugs must be according to local regulations and requirements. Page 2

Overview 2. Overview The picture below shows the bottom of the box and the position of the glands for the pipes. Bottom view: Top view: Mounting plate NOTE: Do not unscrew or remove the mounting plate. The plate has been correctly positioned by the factory to precisely align the holes with the glands and pipes. If the mounting plate is removed and re-placed it may no longer be precisely aligned, and the pipes may be damaged. Side view: Page 3

Air Sampling Tubes 3. Air Sampling Tubes Intake pipe (longest with longest thread) Outlet pipe (shortest with shortest thread) Page 4

Mounting 4. Mounting 4.1 Preparations After the position and orientation of the duct adapter is decided (see chapter 4 for advises), it is ready to be installed Drill the needed holes in the mounting position in the duct. Diameter of aperture for sampling tubes: 34mm. See footprint: Page 5

Mounting 4.2 Inserting the Pipes Unscrew and remove the cover from the box 90 O Hole for sampling tube 135 O Hole for sampling tube Unscrew and remove the nuts (M16) on both pipes IMPORTANT Note that the guiding slots on the threaded ends of the pipes match with the taps on the holes (both indicated by arrows on the drawing below). This ensures easy and correct fitment of the pipes. Taps Guiding slots At the bottom of the box, loosen the nuts on both glands Page 6

Mounting Nut on gland Insert the longest pipe (inlet sampling pipe) with the longest threaded end of the pipe pointing towards the box, through the gland into its position (see drawing below) Insert the shortest pipe (outlet sampling pipe) with the threaded end of the pipe pointing towards the box, through the gland into its position (see drawing below) Make sure that the pipes are fitted firmly and as far as possible against the mounting plate Shortest pipe Longest pipe Turn the box around and make sure that each pipe is correctly and properly fitted Screw and fasten the nuts (M16) firmly onto each pipe with a 19 mm wrench Be sure to direct the edges on the back nut towards the mounting plate for locking The picture above shows the pipes correctly inserted through the glands with the nuts fastened. Page 7

Mounting Turn the box around again, then screw and properly tighten the nuts on both glands (use a 30 mm wrench) Place the duct adapter in position in the predrilled holes Check the gaskets around the tubes Fasten the 4 mounting screws for the duct adapter. Torque: 1 Nm Page 8

Connections 5. Connections Page 9

Final Mounting 6. Final Mounting Make sure to remove the red protection cap from the detector head Mount the detector head onto the detector base Consult the picture below. Note the location of the label on the transparent smoke chamber and the location of the small cable entry. Mount the chamber onto the detector (make sure that the cable runs into the small cable entry, and that the cover fits perfectly over the nuts of the sampling tubes) To ensure that the transparent smoke chamber is kept in its position (see picture), place the small bracket on top of it, and tighten the screw. Fasten the top cover onto the box again, then fasten the screws. Torque for the cover screws: 1Nm. When mounting the cover BWP-143A-SS ensure that there is no damages, especially inspect the gasket and cover of the unit. Page 10

Position of the duct adapter 7. Position of the duct adapter Inside the duct adapter several stickers indicate the air direction in the duct. Make sure to orient the duct adapter correct regarding the air direction in the duct. Please take these rules of thumbs into consideration when positioning the duct adapter in order to achieve the best possible performance of the unit: Page 11

Maintenance 8. Maintenance 8.1 General The interval for inspections and actions is very dependent on the local environment, but as a rule of thumb, once every 12 month is recommended. The enclosure is made of acid resistant stainless steel, and thereof not subject to corrosion. For cleaning, use soap and water only. Regarding maintenance of the smoke detector inside the box, please see separate instructions for the smoke detector and detector base. 8.2 Recommended actions 6-12 months after installation The recommended actions to be executed depends on the environment - salt spray/humidity/vibration/etc. 8.2.1 Visual inspection Check for any signs of moisture intrusion. If any, the leak must be fixed. Check for any signs of corrosion. If any, replace the corroded part/unit. After opening the cover of the unit, always ensure that there is no damages to the gasket on the cover. If damaged, please replace the cover. 8.2.2 Check and re-tighten Check and re-tighten the glands and blind plugs. Check and re-tighten the screws on the internal terminal block for the cable connections. Re-tighten the four screws for the top cover. Torque for the cover screws: 1Nm Re-tighten the four mounting screws for the unit. Torque for the screws: 1Nm Page 12

Autronica is a leading innovator, manufacturer and supplier of fire safety equipment. Our products ensure safety in applications on land and sea worldwide. The company is owned by United Technologies Corporation (UTC) and employs more than 380 people with great skill and experience in the developing, manufacturing and marketing of fire safety equipment. Autronica Fire and Security AS is an international company based in Trondheim, a dynamic city known as the technological hotspot of Norway. Protecting life, environment and property Autronica Fire and Security AS Haakon VIIS gt. 4, NO-7041 Trondheim, Norway Tel: +47 73 58 25 00 Fax: +47 73 58 25 01 E-mail: info@autronicafire.no www.autronicaifre.com