ICMIEE Experimental Investigation of an Air to Air Heat Pipe Heat Exchanger for Moderate Temperature Waste Heat Recovery

Similar documents
Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

EXPERIMENTAL INVESTIGATION OF HYBRID NANOFLUID ON THERMOSYPHON TYPE WICKLESS HEAT PIPE HEAT EXCHANGER THERMAL PERFORMANCE

EXPERIMENTAL AND THEORTICAL STUDY OF THE THERMAL PERFORMANCE OF HEAT PIPE HEAT EXCHANGER

Experimental Study on Waste Heat Recovery from the Pyrolysis Stack using Heat Pipe

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

0Effect of Fin on the Performance Characteristics of Close and Open Loop Pulsating Heat Pipe

Mechanical Engineering Department Sheet (1)

Experimental Investigation of Two Phase Closed Thermosyphon Using Propylene Glycol As A Working Fluid

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Performance Study of Triple Concentric Pipe Heat Exchanger

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Global Journal of Engineering Science and Research Management

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Mallikarjun 1, Anandkumar S Malipatil 2

American International Journal of Research in Science, Technology, Engineering & Mathematics

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

A study of Transient Performance of A Cascade Heat Pump System

EXPERIMENTAL PERFORMANCE OF AN R410A-FILLED C-SHAPE THERMOSYPHON

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Review of Thermosyphon heat exchanger charged with hybrid nanofluid for waste heat recovery applications

EFFECT OF DIVERSE STREAM PATTERNS ON THE PERFORMANCE OF SOLAR AIR HEATER

A Statistical Analysis of a Liquid Desiccant Dehumidifier/Regenerator in an Air Conditioning System

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Heat Exchanger. The purpose may be either to remove heat from a fluid or to add heat to a fluid.

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector

Experimental Evaluation of a Gas Engine Driven Heat Pump Incorporated with Heat Recovery Subsystems for Water Heating Applications

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

Design and Development of Water Cooled Condenser for Domestic Refrigerator

NOVEL COMPACT SORPTION GENERATORS FOR HEAT PUMP APPLICATIONS

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

SOLAR WATER DISTILLATION BY USING WATER IN THE INNER GLASS EVACUATED TUBES

HEAT PIPES

Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful

ENSC 388: Engineering Thermodynamics and Heat Transfer

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

IJIRST International Journal for Innovative Research in Science & Technology Volume 1 Issue 12 May 2015 ISSN (online):

Experimentation of Heat Pipe Used In Nano-Fluids

Compression of Fins pipe and simple Heat pipe Using CFD

An Experimental Study on Evacuated Tube Solar Collector for Heating of Air in India Avadhesh Yadav, V.K. Bajpai

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Experimental Study and Analysis of Condenser Performance under Dual Backpressure Operation Mode

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Adsorption refrigeration system using waste heat

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

EFFECTIVE UTILIZATION OF SOLAR ENERGY IN AIR DRYER

Thermal Performance of a Loop Thermosyphon

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air

Effect of Parameters on Internal Flow Patterns of a Top Heat Mode Closed-loop Oscillating Heat Pipe with Check Valves (THMCLOHP/CV)

Experimental Analysis of Open, Simple and Modified Greenhouse Dryers for Drying Potato Flakes under Forced Convection

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Measurement of internal pressure and thermal performance in a closed-loop oscillating heat-pipe with check valves (CLOHP/CV)

COOLING OF DESKTOP COMPUTER USING HEAT PIPES

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

Modelling the Performance of a Diffusion Absorption Refrigeration System

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

Residential Building Walls and Environment in Amman, Jordan

PERFORMANCE OF WATER FILLED THERMOSYPHONS BETWEEN OC

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

STUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

AXIAL TEMPERATURE DISTRIBUTION AND PERFORMANCE OF R410A AND WATER FILLED THERMOSYPHON AT VARIOUS FILL RATIOS AND INCLINATIONS

THERMODYNAMIC PERFORMANCE EVALUATION OF AN AIR-AIR HEAT PIPE HEAT EXCHANGER

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Heat Transfer in Evacuated Tubular Solar Collectors

To investigate the surface properties for increasing efficiency of solar water heater

Internal flow Patterns of the Horizontal Heat Mode Closed-Loop Oscillating Heat Pipe with Check Valves (HHMCLOHP/CV)

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET) AN EXPERIMENTAL STUDY OF HEAT TRANSFER IN A CORRUGATED PLATE HEAT EXCHANGER

Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina

Transcription:

International Conference on Mechanical, Industrial and Energy Engineering 2018 23-24December, 2018, Khulna, BANGLADESH ICMIEE18-227 Experimental Investigation of an Air to Air Heat Pipe Heat Exchanger for Moderate Temperature Waste Heat Recovery Saddam Hossen *, Mahmud-Or-Rashid, Mantaka Taimullah, Farhan Ahmed Shakil, and Dr.A K M Monjur Morshed Department of Mechanical Engineering, Bangladesh University of Engineering & Technology, Dhaka-1000, BANGLADESH ABSTRACT Due to environmental concern and high price of the fuel, waste heat recovery has become a central issue for industrial and commercial energy users. Heat pipe heat exchanger (HPHE) could be employed in this regard economically. In this study, an HPHE consisting of heat pipes arranged in stages has been developed. Water was used as the heat carrying fluid inside the heat pipe and square fins were used in the cooling and heating zone of the heat pipe. The constructed HPHE was placed between two ducts carrying hot and cold air. The hot fluid temperature was varied from 60 to 80 o C which resembles waste heat and cold air was atmospheric air. The hot and cold air s mass flow rate was varied between 0.037 and 0.087 kg/s and heat transfer between two air streams were measured as 228.5 to 362.2W and heat transfer coefficient varies from 4.22 to 8.09 W/m 2 -K. Keywords: Heat pipe, Heat pipe heat exchanger, Air to air heat exchanger, Waste heat recovery 1. Introduction Energy is the key element in modern life and at the same time is responsible for environmental pollution and global warming. To keep pace with modern life and at the same time to reduce environmental footprints, efficient utilization of the energy resources has become a key concern. A large amount of energy is being wasted while converting the energy into useful work. At present, about 20% to 50% of energy used in the industry is rejected as waste heat [1]. Recovering the waste heat from the industrial processes is one of the ways to reduce energy consumption without hampering the quality of the processes. With the increase of fuel price and environmental concern, waste energy recovery is becoming popular. Waste heat from processes comes in both high quality energy, where the temperature varies between 220 o C and 700 o C (e.g. generator exhaust, boiler exhaust, reheating furnace exhaust, etc.) and low quality energy, where the temperature is less than 100 o C (e.g. compressed air cooling, stenter machine exhaust, bakery dryer, HVAC system, etc.). Waste heat recovery system and technology is well established for the high quality waste energy sources whereas for the low grade waste energy sources, heat recovery is not popular due to technological and economical limitations. To recover the waste heat from the low temperature sources, heat pipe heat exchanger (HPHE) is an efficient way [1-10], where heat can be extracted at a very low temperature difference. Heat pipe is a known technology. The idea of heat pipe was first presented by Gaugler in General Motor Company in 1942. The first heat pipe was designed and manufactured by Grover in National Lab, Los Alamos, in the US in 1964 [1]. Since then, heat pipes are being used in many applications such as, heat exchangers (air pre-heaters or systems that use in economizers for waste heat recovery), HVAC system, cooling of electronic components, solar energy conversion systems, spacecraft thermal control, cooling of gas turbine rotor blades etc. In recent days, some common applications of HPHE are in medicine and * Corresponding author. Tel.: +88-01 E-mail addresses: saddamme170@gmail.com human body temperature control [2], spacecraft cooling [3], electrical and electronics equipment cooling [4, 5], waste heat recovery applications [6-11] etc. In a heat pipe heat exchanger (HPHE), a group of vertical heat pipes is arranged in such a manner that two streams of fluid can flow over them through two separate ducts or pipelines. A high temperature fluid flows on one end of the HPHE (known as evaporation section) and a low temperature fluid flows on the other end (known as condensation section), thereby transfers heat from the high temperature fluid to the low temperature one using the fluid sealed in heat pipes as heat carrier. The heat pipes in a heat pipe heat exchanger are arranged in stages, each stage consisting of a single row of heat pipes, all of which are at the same temperature. Hagens et al. [12] studied experimentally the heat exchanger consisting of heat pipes with two different filling ratios of R-134a: 19% and 59% which demonstrated that a heat pipe heat exchanger is a good alternative for air air exchangers in process conditions when air water cooling is not possible. S.H Noie-Baghban and Majideian [13] studied experimentally the performance of distilled water filled heat pipe equipped heat exchanger at low temperatures (15-55 C) and concluded that appropriate method of vacuum, filling ratio and sealing of the heat pipe are necessary for increasing the effectiveness of heat pipe heat exchanger. Nguyen-Chi et al. [14] investigated experimentally the performance of vertical two-phase close thermosiphon and used water as a working fluid. They investigated the influence of operating parameters on the maximum performance either by dry out or burn out limits. Li et al. [15] investigated experimentally the steady-state heat transfer characteristics of a vertical two-phase closed thermosiphon at low temperature differences with R-11, R-22 and water as working fluids. Park and Lee [16] made an experimental study on the performance of stationary two-phase closed thermosiphon with three working fluid mixtures (water glycerin, water-ethanol, and water ethylene glycol).

Shiraishi et al. [17] investigated experimentally a critical heat transfer rate in thermosiphons by taking into account the aspect ratio, filling ratio, working fluid property, and operating pressure. In this paper, a vertical heat pipe (thermosiphon) heat exchanger is designed to recover heat from low temperature region (from 55 o C air to ambient temperature air). The design of the HPHE is presented and the results for experimental investigations are reported. The performance of the HPHE is evaluated by varying the filling ratio of the heat pipes and mass flow rates of hot and cold air for an optimum operating condition thus optimizing the effectiveness of the HPHE. 2. Experimental apparatus and procedure To investigate the heat transfer performance and evaluate the effectiveness of a HPHE and also to determine the optimum filling ratio and operating conditions of HPHE system for low temperature waste heat recovery application, an experimental setup was designed and constructed. The test system consisted of a HPHE, a data collection system, two fans for cold and hot air passing, an air pre-heater, four k-type thermocouples etc. as showing in the figure: 1 (a), (b), (c) and (d). In this study the designed HPHE was consisting of thirty eight heat pipes that are arranged vertically on the separation plate with two different rows and in seven columns, where 1 st row consists of five tubes and 2 nd row consists of 6 tubes total (5+6+5+6+5+6+5) = 38 tubes. Tubes are arranged in triangular formation for creating the turbulent flow in both condensation and evaporation section. Each heat pipes consists of a seven square fins (1.5 1.5 inch) of copper plate. Fins are arranged in the heat pipes in such way that, the flow becomes zigzag and create more turbulence and thus increase the heat transfer rate. The working fluid selected for the heat pipes is water as it is cheap and has high latent heat of evaporation. Water is inserted into the copper pipe after sealing its one end, then it is heated up to its boiling point to make it air free and then the other end is sealed up.when the steam condense; vacuum is created by the vacuum inside the tube. The filling ratio of the working fluid (distilled water) in the heat pipe is varied form 33% and 50% of the heat pipe volume and then performance of the heat pipes were tested under those filling ratios. Thus an optimum filling ratio is obtained that ensures the maximum performance of heat pipe. The length of heat pipe 558 mm with inner and outer diameter of 13 and 15 mm. The lengths of the evaporator and condensation section in HPHE are 277 mm and 277 mm respectively. Two ducts were arranged with the constructed HPHE in both condensation and evaporation section for passing the cold and hot air receptively with the help of two fans that are fitted at the two ends of the ducts. An air preheater of 4500 W is used in the duct of evaporation side for heating the air. The temperature of air is controlled to 40 C to75 C by a temperature controller. The cold air in the condensation section is taken from the atmosphere. (a) (b) (c) (e) (d) Fig.1 (a) Experimental setup; (b) Drawing for the experimental setup; (c) Drawing of the heat exchanger; (d) Front view of the heat exchanger; (e) Heat pipe arrangement. For measuring the temperature of hot and cold air in condensation and evaporation inlet, outlets there are four k-type thermocouples were used. The mass flow rate of air is measured by anemometer. ICMIEE18-227- 2

C HA HAC pha (7) C CA CA C pca (8) C max is the larger one of the hot (C HA ) and cold air (C CA ) specific heat capacities.r is the ratio of the minimum and maximum heat capacity of the two fluid streams: R = C min / C max (9) Fig.2 Anemometer 3. Data reduction The heat transfer rate for the HPHE from the hot flow air can be calculated by the following equation: = HAC pha (T HA,in T HA,out ) (1) Where, is the mass flow rate of hot air, C p is the specific heat capacity, T HA,in and T HA,out refer to the inlet and outlet temperature of hot air respectively. Similarly, can be also obtained by the cold air from the following formula, = CAC pca (T CA, in T CA, out ) (2) This heat is not same to previously calculated heat transfer from the hot air due to uncertain heat loss.the overall heat transfer coefficient, U of the HPHE is defined as follows, W/ (m 2 K): U = / A. T lm (3) Where, A is the overall heat transfer area of the HPHE,(m 2 ) and logarithmic mean temperature difference T lm, (K), which is calculated for a counterflow arrangement as follow: The number of heat transfer units (NTU), an important parameter for the heat exchanger, is expressed as follows: NTU = UA / C min (10) Where, U is the overall heat transfer coefficient, A is heat transfer surface area.the ε-ntu method is a thermodynamic calculation method of dividing wall type of heat exchanger, which is derived by the dimensionless equation when the logarithmic mean temperature difference is discussed. The relationship between ε and NTUcanbe expressed by: Ɛ (11) 4. Results and discussions 4.1 Performance of the Heat Pipe In this experiment water is selected as working fluid because of its availability, low cost and also depending on its performance. Tests were performed and performances of a water filled heat pipe, an ethanol filled heat pipe and an empty copper tube were compared. The performance results reveal that water filled heat pipe shows better heat transfer performance over the other two. The test results are presented the following figures. - - - ( - ) ( - ) (4) The effectiveness of HPHE is defined as the ratio of the actual heat transfer rate in a given heat exchanger to the maximum possible heat transfer rate max ε = / max (5) The following equation can be used to calculate the maximum theoretical heat transfer rate: max= C min (T HA,in T CA,in ) (6) Where, C min is the smaller one of the heat capacities of hot air (C HA ) and cold fresh air (C CA ), kj/k. C HA and C CA are calculated by following relations: Fig.3 Variation of pipe end temperature with time when pipes other ends inserted into water initially at 57 C ICMIEE18-227- 3

Temperature ( C) coefficient increase with the increase of hot and cold air mass flow rates and effectiveness decrease. Fig. 4 Variation of pipe end temperature with time when pipes' other ends inserted into water initially at 53 C 35 30 In the experiment, the heat transfer rate changes between 228.5 and 1003.4 W and the overall heat transfer coefficient varies between 4.22 and 13.88 W/m 2 -K. The heat transfer rate and overall heat transfer coefficient gets the minimal value, when the hot air mass flow rate is 0.034 kg/s, maximum values when the hot air flow rate is 0.124 kg/s. The pattern is nearly similar for comparison with cold air mass flow rate also. The heat transfer coefficient is very low when the air flow rate is small. There are several reasons behind this phenomenon. One of the main causes is the turbulence. When the air flow rate is small, laminar flow is predominant and under laminar flow condition heat transfer coefficient is small because of lack of mixing of the fluid. When flow rate is high, turbulence is created and proper mixing takes place and thus heat transfer coefficient is also increased. The same reason is for the variation of heat transfer rate. So heat transfer can be increased by increasing the air flow rate. 25 20 0 2 4 6 8 Time (min) Half filled One third filled Fig.5Variation of heat pipe performance with filling ratio The filling ratio has a significant effect on the performance of the HPHE. For analyzing the performance of heat pipe by varying the filling ratio, a heat pipe is selected which length is 568 mm with 15 mm outer diameter and 1mm thickness.working fluid was filled to 50% and 33% of total heat pipe volume for the performance test. The performance results are expressed with respect to the increase of top end temperature of heat pipe with time. In the initial period, the one-third filled heat pipe showed better performance than the half-filled heat pipe. But after a certain period of time, the situation had reversed. The half-filled heat pipe showed better performance than the one-third filled heat pipe. So in this experiment 50% filling ratio is taken as optimal filling ratio, then all heat pipes are constructed and assembled for HPHE. Fig.6 Effect of hot air and cold air mass flow rates onheat transfer rate. 4.2 Analysis on the performance of the HPHE The variations of heat transfer rate,overall heat transfer co-efficient and effectivenesswith hot air mass flow rates at different cold air mass flow rates are presented in Fig. 6, Fig.7 and Fig. 8. From the results, it is clear that both the heat transfer rate and overall heat transfer Fig.7Effect of hot air and cold air mass flow rates on overall heat transfer coefficient. The relationship between effectiveness and mass flow rate was different from previous patterns. Here effectiveness decreased with increasing of hot air mass ICMIEE18-227- 4

flow rates at a constant cold air mass flow rate. It was summarized from analyzing data of an experiment that for cold air mass flow rate 0.244 kg/s, effectiveness was decreased from 0.19 to 0.13 when hot air mass flow rate increased from 0.04 to 0.124 kg/s. So it was concluded that this HPHE was more effective and suitable for lower mass flow rate. Fig.8Effect of hot air and cold air mass flow rates on effectiveness of HPHE. In this paper, the effectiveness-ntu method regarding heat exchanger operation has been applied, and the nature of the relationship between effectiveness and NTU at different air mass flow rates is shown in Fig 9. From the figure, it is clear that that the effectiveness of HPHE increases with the increasing of NTU and the pattern of the relationship between effectiveness and NTU is nearly linear. It is because NTU is directly proportional with heat transfer coefficient and as heat transfer co-efficient increases with increasing air mass flow rates, NTU is also increased and when NTU increases effectiveness of HPHE also increases as the nature of their relationship described in theory. Here the effectiveness varying from 0.08 to 0.202, and the relationship can be expressed as ε = 0.8183 NTU + 0.008 from the best fit straight line. Fig.9Relationship between effectiveness and NTU 5. Conclusions In this study, experimental work was carried out to investigate the effectiveness of a low cost HPHE in recovering low grade waste heat. From the results of the experimental investigation following conclusions can be drawn: 1. Low cost HPHE can be constructed without any sophisticated equipment at laboratory with water as the working fluid. 2. The performance of heat pipe in steady stateis better for half-filled heat pipe than one-third filled heat pipe. 3. The heat transfer rate and overall heat transfer coefficient increases with increasing mass flow rate of air butthe effectiveness of the HPHE decreases. 4. The relation between effectiveness and NTU is linear, where the effectiveness varying from 0.08 to 0.202. The relationship can be expressed as ε = 0.8183 NTU + 0.008. 5. The heat exchanger is very sensitive to the dust accumulation and automatic cleaning of the heat exchanger would be necessary to get the maximum performance. NOMENCLATURE WHRS waste heat recovery system HPHE heat pipe heat exchanger NTU number of heat transfer units HVAC heating, ventilation and air conditioning. WHRS waste heat recovery system heat transfer rate (kw) mass flow rate (kg/h) HA hot air mass flow rate (kg/h) CA cold air mass flow rate (kg/h) C p specific heat (kj/(kg K)) C pha specific heat of hot air (kj/(kg K)) C pca specific heat of cold air (kj/(kg K)) T temperature (K) T HA,in inlet temperature of hot air (K) T HA,out outlet temperature of hot air (K) T CA,in inlet temperature of cold air (K) T CA,out outlet temperature of cold air (K) U overall heat transfer coefficient (W/(m 2 K)) A overall heat transfer surface area (m 2 ) T lm logarithmic temperature difference (K) C heat capacity (kj/k) C HA heat capacity of hot air (kj/k) C CA heat capacity of cold air (kj/k) ε heat exchanger effectiveness C min Minimum heat Capacity(kJ/K) Maximum Heat capacity(kj/k) C max ICMIEE18-227- 5

REFERENCES [1] BCS, Waste Heat Recovery: Technology and Opportunities in US industry, March 2008, www1.eere.energy.gov/industry/intensive processes/pdfs/waste_heat_recovery.pdf [2] A. Faghri, 1993. Temperature Regulation System for the Human Body Using Heat Pipes, US Patent 5,269,369 Issued Des. 14. [3] R. Brown et al., 1990. Performance evaluation of the grumman prototype space erectable radiator system, AIAA Paper No. 90-1766. [4] L.L. Vasilier, et al., 1990. Heat pipes for electronic equipment cooling systems, in: Proc. 7th Int. Heat Pipe Conference, Minsk, USSR. [5] A. Basiulis, et al., 1987. Heat pipes for cooling of high density printed wiring board, in: Proc. 6th Int. Heat Pipe Conf., Grenoble, France, pp. 685-691. [6] M.S. Soylemez, 2003. On the thermoeconomical optimization of heat pipe heat exchanger HPHE for waste heat recovery, Energy Convers. Manage., vol. 44, pp. 2509 2517. [7] Hongting Ma, Lihui Yin, XiaopengShen, Wenqian Lu, Yuexia Sun, Yufeng Zhang, Na Deng, 2016. Experimental study on heat pipe assisted heat exchanger used for industrial waste heat recovery, Applied Energy, vol. 169, pp. 177 186. [8] W. Srimuang, P. Amatachaya, 2012. A review of the applications of heat pipe heat exchangers for heat recovery, Renewable and Sustainable Energy Reviews, vol. 16, pp. 4303 431. [9] Abd El-Baky MA, Mohamed MM, 2007. Heat pipe heat exchanger for heat recovery in air conditioning, Applied Thermal Engineering, vol. 27, pp. 795 801. [10] Leonard L. Vasiliev, 2005. Heat pipes in modern heat exchangers,applied Thermal Engineering, vol. 25, pp. 1 19. [11] HongtingMaa, N. Dua, ZeyuZhanga, Fan Lyua, Na Denga, Cong Lia. AndShaojieYua, 2017. Assessment of the optimum operation conditions on a heat pipe heat exchanger for waste heat recovery in steel industry,renewable and Sustainable Energy Reviews, vol. 79, pp. 50 60. [12] H. Hagens, F.L.A. Ganzevles, C.W.M. van der Geld, 2007. Air heat exchangers with long heat pipes: experiments and predictions, Applied Thermal Engineering, vol. 27, pp. 2426 2434. [13] S.H. Noie-Baghban, G.R. Majideian, 2000. Waste heat recovery using heat pipe heat exchanger (HPHE) for surgery rooms in hospitals, Applied Thermal Engineerin, vol. 20, pp.1271±1282. [14] H. Nguyen-Chi, M. Groll, Th. Dang-Van,1979. Experimental investigation of closed two-phase thermosiphons. AIAA 14 th Thermophysics Conference, Orlando, Florida, pp. 239 246. [15] H. Li, A. Akbarzadeh, P. Johnson, 1991.The thermal characteristics of a closed two-phase thermosiphon at low Temperature difference, Heat Recovery Systems & CHP 11:6, pp. 533 540. ICMIEE18-227- 6