White Paper. The Victaulic Vortex Fire Suppression System Fire Suppression for Electrical and Electronic Applications

Similar documents
TECHNICAL NOTES. Literature Review on Hybrid Fire Suppression Systems. Peter Raia Michael J. Gollner University of Maryland

Application of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

BOC FS125 The Fire Extinguishing Solution

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE

Fire suppression systems for server rooms and data centres

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

The Science Behind Water Mist Protection of Typical Building Hazards

PRICELESS PROTECTION INERGEN Clean Agent Fire Suppression Systems

GAS EXTINGUISHING SYSTEMS INERT GAS. Argon Extinguishing Systems. Fire Protection Systems

FIRE SUPPRESSION SYSTEM

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

An Overview of Extinguishing Systems for Computer Equipment

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

FM Approvals & Water Mist Systems. Paul Bardsley Engineer, FM Approvals

CO2 COCO GAS FLOODING SYSTEM

KD Innovative extinguishing with Novec TM 1230 by 3M TM

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

FIRE PROTECTION, NATURALLY AQUASONIC Water-Atomizing Fire Suppression System

Rick Seidel Fike Corporation Regional Sales Manager

HKIE CPD Training Course (II) 23, 25 June and 7, 9 July 2009

WAS STARTED BY CARLOS BAHAMONDES MASAFIERRO

Superior by Design The Kidde ADS TM FM-200 System

SECTION FM-200 FIRE SUPPRESSION SYSTEM

How can I protect invaluable assets and the environment from the effects of a fire?

GAS EXTINGUISHING SYSTEMS INERT GAS. Argotec with argon or nitrogen

Safe, Effective, Environment-friendly

MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle.

STAT X - SPECIAL HAZARD FIRE PROTECTION

What extinguishes fires without pressure peaks?

FM-200 In-Cabinet Series

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

WATER MIST CONVENTION AND EXHIBITION

CertifiedSafetyPassion. CertifiedSafetyPassion. Distributors and UL AML

PRODUCT LISTING DATA SHEET (Active Fire Protection Equipment)

FIRE PROTECTION TECHNOLOGY Solutions never thought of before

NEC Requirement Guidelines 2002 Code Options for the Installation of Listed Less-Flammable Liquid-Filled Transformers

MINIMAX FIRE PRODUCTS WHITE PAPER THE COST-BENEFIT ADVANTAGES OF REPLACING HALON WITH 725 PSI MX 1230 CLEAN AGENT FIRE SUPPRESSION SYSTEMS

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

Water Mist Fire Suppression

ODS & SGG Alternatives for the Fire Protection Industry 2018

DuPont FE-25 FIRE EXTINGUISHANT. Preferred Replacement for Existing Systems and the Choice for New Applications

Fire Suppression Tests Using a Handheld Water Mist Extinguisher Designed for Spacecraft Applications

SPECIFICATION: ARGONITE Engineered Fire Suppression System

Emergency shutdown systems. Procedures for bypassing ESD s

Certificate of Conformity Certificate num. Registration date Version Valid until

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

PREVENT SYSTEMS WHEN SAFETY IS TAKEN SERIOUSLY

Installation and Maintenance Requirements

CONTENTS. B. System Design and Performance Requirements

Element C3.4 Fire Fighting Equipment

How can you minimize consequential damages in case of a fire?

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers

XC10 combined fire detection and extinguishing control

Watermist Systems. Versatile, Affordable Water Mist Fire Suppression. your TRUSTED partner in fire safety

Safer.Smarter.Tyco. Watermist fire protection Technology you can trust

PRICELESS PROTECTION INERGEN Clean Agent Fire Suppression Systems

Technologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230

I wish I could protect my business with the most suitable Water Mist solution to fit my needs.

International Safety Guide Chapter 30 for Inland Navigation Tank-barges and Terminals. Chapter 30 FIRE-FIGHTING

HFC-227ea FIRE SUPPRESSION SYSTEM

CLEAN AGENTS & CLASS C FIRE HAZARDS

Water Mist Fire Protection Systems for the Protection of Industrial Oil Cookers. 8th March 2016 Dr Tim Nichols CPhys MIFireE

MISSION CRITICAL FIRE PROTECTION

HI-FOG for buildings. Technical introduction. Protecting people, property and business continuity. Jussi Tiainen

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

w-fog RG-SYSTEMS W-FOG WATER MIST CO-OPERATI

What is HI-FOG? The natural enemy of fire

AccuJet Electrostatic systems

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS

Welcome to Argonite fire protection from Ginge-Kerr

Appendix 3 Fire Suppression Systems For AASA sanctioned events V0.1

Technologies Gas extinguishing systems. MX 200 Fire Extinguishing Systems Fighting Fire using HFC-227ea

Fire Suppression. Water-Mist : A Revolutionary Green Technology in. - by Nimit Sheth TALL, SMART, SAFE BUILDINGS FOR SMART CITIES.

Suppression of Class C Fires

DRY BULK HANDLING SYSTEM

Hospitals and Major Medical Centers

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

SAFETY THE BEST FOR YOUR EQUIPMENT

SAPPHIRE. Gaseous Fire Suppression Systems. Delivering 3M Novec 1230 Fire Protection Fluid

XC10 combined fire detection and extinguishing control

Nirvana. Cycling Refrigerated Dryers

Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches

Significant Advancements in Water Based Fire Suppression for Storage Occupancies

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

ON THE BUTTON A reference guide to environmental ratings used for push button enclosures

AccuJet Electrostatic systems

The Effect of Large Orifice Sprinklers on High-Challenge Fires

Air Quality Control System

Corrosion in Fire Sprinkler Systems Increasing Your Liability, Increasing Your Costs, and Shortening System Life

WATER MIST SYSTEMS. Table of Contents

FIGHTING FIRE as easy as blowing out a match

TAMUCC Fire Safety Training

Identify RISKS. Design SOLUTIONS. Prevent DISASTERS

CLEAN AGENT SYSTEMS. TABLE 1 Agents Recognized in NFPA 2001

Fire Protection for Cable Tunnels

Transcription:

White Paper The Victaulic Vortex Fire Suppression System Fire Suppression for Electrical and Electronic Applications Matthew Puzio, Senior Project Engineer, Fluid Control Technology, Victaulic updated April, 2011-1 -

Table of Contents 1. Introduction..... 3 2. Problem Statement... 3 a. Equipment Enclosure Challenges and Water Mist Solutions b. Gaseous Suppression Systems and Oxygen Reduction c. Maintenance of Room Integrity d. Protecting the Environment e. System Downtime and Reset 3. The Victaulic Solution... 4 4. Victaulic Vortex System Testing and Benefits a. Effective Fire Extinguishment b. Safety of Sensitive Electronics i. Fire Test: Energized Computer Equipment ii. System Test: ANSI/FM 5560 Appendix G c. Safe for use on High Voltage Equipment i. System Test: Local Application, Charged Plate ii. System Test: Total Flooding, Enclosed Bus Bar iii. System Test: Total Flooding, Unshielded Bus Bar 5. Implementation 14 6. Summary..15 7. End Notes.16 8. Work Cited 16-2 -

Introduction From a smoldering circuit board to a switch gear explosion, the risk of electrical fire in data, power generation and telecommunication centers is an everincreasing concern for the owners and operators of these facilities. Today s data center and electronics industries are looking for a fire suppression solution that is safe, effective and mindful of the environment (See SNAP Listing 1 ). The Victaulic Vortex Fire Suppression system is a unique, hybrid technology, utilizing both water and nitrogen in a combined suspension to both cool the hazard area and remove the oxygen that sustains the fire with a high velocity, low pressure delivery. This swirling, vortex-like distribution fills the hazard space and quickly extinguishes the fire with little or no water residue. Electronics are kept dry and there are absolutely no toxic agents or chemicals involved. Problem Statement Equipment Enclosure Challenges and Water Mist Solutions Equipment enclosures, commonly found in data center and electronics facilities, present significant fire suppression challenges and are considered local application hazards. Traditional single-agent water mist systems often need to be installed directly within an enclosure to suppress a fire. An internal installation would require the equipment to be de-energized before a water mist system discharge occurs in order to prevent damage and injury. Further, a shunt trip can be triggered when the current draw is excessive for the equipment. If fire suppression is required in a larger area, where multiple enclosures or pieces of equipment may need to be protected, this is considered a total flooding application. In a total flooding scenario, the water mist concentration that enters an enclosure will not be great enough to cool and suppress the fire unless the top is open. In either scenario the equipment inside the enclosure would be subject to extreme wetting conditions along with possible damage. Gaseous Suppression Systems and Oxygen Reduction In most cases, gaseous systems require hold time concentrations and must pass a fan test to be accepted as a viable option. Some systems require the space to - 3 -

be modified to provide room integrity seals so the gaseous agents remain in the hazard area during a fire event. Where water mist systems are designed to reduce the temperature in the fire space, inert gas systems work to reduce the amount of oxygen available to sustain the fire. These systems do not allow for cooling in the space, leaving open the possibility of re-ignition if room integrity is not maintained for a defined period of time. Maintaining Room Integrity Effective maintenance of the concentration of suppressing agent is a value of room integrity. Proper room integrity for many inert gas systems requires significant custom construction to control air flow. Sealing a room to meet specified leak rates can be a large and costly challenge for facility owner and contractors. Protecting the Environment Inert gas suppression systems also present several challenges in today s sustainability-focused marketplace. These systems utilize chemical agents and halocarbons to achieve fire suppression which often raises environmental concerns. Therefore, efforts have been made to find alternative solutions that are friendly to the environment and occupants (no HF or ozone depletion). System Downtime and Reset Beyond room integrity and environmental concerns, the full life-cycle of a system must be considered, including the cost and complexity of system reset after a discharge. In many cases, agent storage cylinders need to be returned to the manufacturer for refill with proprietary agents or removed from the system for weighing, costly in both time and money. Facility owners and operators who are focused on minimizing facility downtime are in need of more time and costeffective solutions. The Victaulic Solution The Victaulic Vortex Fire Suppression System uniquely uses hybrid technology to deliver a blend of water and nitrogen to suppress and extinguish both local application and total flooding fires. The Victaulic Vortex system has been proven effective for small, smoldering enclosed fires and large, heat-releasing fires in open spaces. - 4 -

By combining nitrogen and water, the Victaulic Vortex System creates a homogeneous suspension of nitrogen and sub 10 micron water droplets that can penetrate through vented type enclosures to extinguish a fire. When the mixture enters the enclosure, both the nitrogen and water attack the fire simultaneously, the water cooling the space and the nitrogen reducing the oxygen content and generating steam. This results in complete fire suppression without significant wetting or the chance for re-ignition. The Victaulic Vortex System is completely friendly to the environment, utilizing no toxic agents and has been identified by the Environmental Protection Agency as having a Global Warming Potential of zero. Since the system discharges with high velocity under low pressure, the hybrid suspension swirls through the space, overpowering the fire plume and not requiring room integrity to remain effective. Since the system does not require room integrity to remain effective, this additional construction or retrofit cost can be avoided. Also, since the Victaulic Vortex system only requires water and pure nitrogen, storage bottles can be quickly and cost-effectively refilled on site or cylinders can be replaced by a local gas supplier. This minimizes system and facility downtime, increasing productivity and profit. The system can be designed to receive water piped in or stored in a portable tank. De-ionized water is recommended for systems where electrical equipment is in the hazard space to minimize potential conductivity. Victaulic Vortex System Testing and Benefits Benefit 1 - Effective Fire Extinguishment Factory Mutual, Underwriter s Laboratories and many clients have witnessed a broad range fire tests demonstrating the effectiveness of the Victaulic Vortex system. (See Vortex FM approval 2, UL 2127 equivalency report 3 and applicable fire test results). As an example, the Victaulic Vortex system was tested in accordance with requirements listed in ANSI/FM 5560 Appendix G, demonstrating the successful extinguishment of a cable bundle fire with the Vortex System (See Figure 1). - 5 -

Figure 1 - Cable Bundle-Post Fire Benefit 2 - Safety of Sensitive Electronics Unlike other technologies, the Victaulic Vortex System can be installed in a total flooding configuration and remain completely effective at fire extinguishment inside an enclosure. With system emitters installed outside the enclosure, live circuits do not have direct exposure to the water and nitrogen suspension discharged by the system. This greatly minimizes the moisture level in the enclosure. Due to the high velocity, vortex distribution effect of the system, the mixture of nitrogen and water travels into the enclosure through ventilation openings. This ensures that circuit boards and components are not damaged due to high levels of moisture or excessive wetting. Fire Test 2.1 - Energized Computer Equipment The described fire scenario was performed at the Victaulic Edison Hydraulics Laboratory in Stewartsville, NJ. A vented enclosure containing microprocessor-based electronics was placed inside a 4624 ft 3 (130 m 3 ) room along with laptop and desktop computers. A cup of heptane and a wax-based candle were ignited inside the enclosure (Figure 2 and 3) and allowed to burn for 15 seconds. A dish of Anhydrous Calcium Sulfate (Drierite) was placed in the desktop computer tower and another inside the vented enclosure to compare the moisture levels inside and outside the enclosures. A relative humidity sensor and thermal couple were placed inside the vented enclosure to monitor the conditions before, during and after the fire. - 6 -

Figure 2 - PLC Configuration Figure 3 - Laptop and Desktop PC The Victaulic Vortex System was discharged for 1 minute, 36 seconds (See data report), at which point the two fires inside the enclosure were extinguished (note: the Victaulic Vortex System can be configured to increase or decrease extinguishment time by changing the emitter size or count). The equipment remained energized throughout the fire tests and remained powered for 60 days after completion of the test. After discharge, the internal circuit boards were completely dry and the equipment was operating as designed. The relative humidity reached a peak valve of 73.29 % (See graph 1) with a net increase of 30% RH. The Anhydrous Calcium Sulfate remained its natural blue color (See figure 4) showing no increase in moisture. - 7 -

80 70 60 50 %RH 40 30 20 10 0 0 2 4 6 8 Time (Min) 10 Graph 1 Relative Humidity Inside Enclosure Outside Enclosure Blue Pink Figure 4 - Anhydrous Calcium Sulfate After 60 days of operation, circuit boards and various components were examined and photographed (See figure 5). The samples show no signs of corrosion or damage. Generally, electrical components will show pitting and green discoloration a few days after exposure to water. - 8 -

Figure 5 - No Corrosion Between Pins Test 2.2 (No Fire) - ANSI/FM 5560 Appendix G. A computer enclosure similar to that used with an IBM AS 400 system was placed on a vented sub-floor. Two dishes of Anhydrous Calcium Sulfate were placed in the enclosure, along with two mirrors to indicate moisture levels inside the cabinet (See figure 6). Two additional samples of Anhydrous Calcium Sulfate were placed outside the enclosure for comparison. - 9 -

Figure 6 Computer Enclosure Figure 7 Anhydrous Calcium Sulfate samples The Victaulic Vortex System was discharged and all four dishes of Anhydrous Calcium Sulfate and mirrors showed little to no moisture levels (all blue). (See Figure 7). Benefit 3 - Safe For Use On High Voltage Equipment - 10 -

During the following tests, the Victaulic Vortex System was installed in both local and total flooding configurations. Three types of high voltage tests were successfully performed up to 10KV (limited by equipment). Test 3.1 - Local Application, Charged Plate A Victaulic Vortex emitter that was electrically isolated from the rest of the system was discharged onto a copper plate with a 10KV potential (See figure 8). A milliamp meter was placed between the emitter and the ground to measure any current flow. The distance between the plate and emitter was varied from 10 to 2 inches. At a distance of 1.5 inches the air broke down and an arc was created. Figure 8 Emitter discharge set up with copper plate An arc was not witnessed or measured during or after a discharge. At no time did the potential 23mA flow through the emitter and ground. The maximum current was 168.58μA. NIOSH defines the maximum let go current to be 16mA and 1mA is barely noticeable. All currents measured in these tests were far below these levels. The above tests are similar to ANSI/UL711 for rating class C fire extinguishers. Reference Table 1 for test results: - 11 -

Base Line Current Discharge Current Total Current TEST 1 μa 13.71 170.6 156.89 TEST 2 μa 20.87 173.5 152.63 TEST 3 μa 31.69 184.41 152.72 TEST 4 μa 44.22 212.8 168.58 Table 1 Current values during high voltage discharge tests Test 3.2 - Total Flooding, Enclosed Bus Bar Two copper bus bars were charged to 10KV and placed into a vented enclosure 1.5 inches apart form each other (See figure 9). Two power supplies, PLC and an LCD display were also energized during the testing. Inside the enclosure, a candle and a heptane fire were lit in the enclosure and allowed to burn for 15 seconds. The Victaulic Vortex System was discharged for approximately five minutes while current flow was measured from one bus bar to the ground. Figure 9 Vented enclosure with copper bus bars - 12 -

An arc condition was never created during the duration of the test nor did the current flow exceed 68.87μA (See graph 2). All readings were well below the NIOSH standard of 16mA. All equipment remained powered and undamaged during and after the discharge. 70 60 Current ua 50 40 30 20 10 0 0 10 20 30 40 50 60 70 80 90 100 Concentration % Graph 2 Current measurement during enclosed bus bar test Test 3.3 - Total Flooding, Unshielded Bus Bar Similar to Test 2, two copper bus bars were placed seven feet directly below a Victaulic Vortex emitter. The system was then discharged for a total of five minutes (100% concentration) on the 10KV bars. During the discharge, current was read and recorded (See table 2). % Concentration Current ua 0 51.56 10 52.94 20 73.28 30 97.1 40 515 50 471 60 437 70 444 80 446 90 449 100 450 Table 2 current values during second test with copper bus bars - 13 -

The results above show a maximum current flow of 515μA (.515mA). This value is far below the 1mA of barely noticeable current, proving this type of application would be effective on charged equipment. At no time did an arc condition occur. Implementation When the Victaulic Vortex system is installed in data centers, computer rooms or any other sensitive electrical application; system emitters should be placed so that they have no direct impingement on the device. The preferred installation practice would be to have emitters mounted in a sidewall configuration and arranged so that the blended suspension of water and nitrogen would be directed down hot and cold aisles. The water source should be a captive supply of deionized water with a blanket of nitrogen to ensure the purity of the water over time. These applications shall use a water flow cartridge of.26 gpm along with 5/8 inch emitter or equivalent gas/water ratio. A pendent orientation can be used but a sidewall installation is preferred. For sub-floor applications, or tight spaces, a specialized fan-type foil shall be used so excessive wetting will not occur on the floor and ceiling. The same system design practices shall also apply to high voltage installations. The Victaulic Vortex emitter shall be placed so that the water and nitrogen suspension does not have any direct impact upon the charged device. Whenever possible, a means of equipment shut down before a discharge would be preferred but is not mandatory. Summary The hybrid technology of the Victaulic Vortex System provides an innovative, safe and effective fire protection solution for installations that contain electronic equipment. The vortex effect created by the patented system emitter design allows the mixture of sub micron water droplets and nitrogen to effectively enter vented enclosures and suppress fires within the enclosure. Water mist systems that use single fluid technology cannot provide the same level of protection as the Victaulic Vortex system. Since a single fluid system will need a nozzle placed inside of the enclosure to extinguish a fire, it is certain that the powered equipment would be damaged due to extreme wetting conditions. - 14 -

Facility owners and operators will benefit from the Victaulic Vortex system s minimal wetting operation, simple maintenance, environmentally-friendly design and rapid return to normal operations after system discharges. - 15 -

End Notes 1) U.S Environmental Protection Agency http://www.epa.gov/ozone/snap/fire/lists/flood.html 2) FM Global http://www.approvalguide.com/cc_host/pages/custom/templates/fm/index. cfm?product=111216 3) Contact Victaulic For Underwriter s Laboratory (UL) Report http://ulstandardsinfonet.ul.com/scopes/scopes.asp?fn=2127.html Work Cited 1) William Reilly, Victaulic Victaulic Vortex vs. Clean Agent and Water Based Systems (WP-04, April, 2008) 2) Andrew Hills, Terence Simpson and David Smith, Fire Safety Internal Water Mist Systems For Telecommunication Switch Gear And Other Electronic Facilities - 16 -