AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Similar documents
AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP)

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

GWP Alternative Refrigerants

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Update on Codes and Standards Research. Karim Amrane, Ph.D. Senior Vice President

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Low GWP Refrigerants for Air Conditioning Applications

Research to Assist in the Development of Safety Standards and Building Codes for the Use of Flammable Refrigerants

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

January 16 th, 2014 New York City

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Study of R161 Refrigerant for Residential Airconditioning

R32 Compressor for Air conditioning and Refrigeration applications in China

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

R-404A Alternative with Low Compressor Discharge Temperature

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Research for the Development of Safety Standards

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

Purdue e-pubs. Purdue University

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

2016 Annual Conference

March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies

A2L Refrigerants Leaks and Ignitions Testing under Whole Room Scale

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

Efficiency of Non-Azeotropic Refrigerant Cycle

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

Effects of Refrigerant-Lubricant Combinations on the Energy Efficiency of a Convertible Split-System Residential Air-Conditioner

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

R-407A R-448A R-449A

Refrigerant Glide and Effect on Performances Declaration

Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Update on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Higher Efficiency, Lower Sound, and Lower Cost Air Conditioning Compressors: Part 1 Efficiency

TEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a

Understanding Applications for Alternative Refrigerants

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

PRACTICAL EXPERIENCE WITH AN ALTERNATIVE TO R-22 BASED ON R-32lR /R a. R E Low, B E Gilbert, T W Dekleva.

High Efficiency R-134a Compressor for Domestic Refrigerator

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Understanding Applications for Alternative Refrigerants

Performance Measurement of R32 Vapor Injection Heat Pump System

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Compressor Capacity Control: A New Direction

Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units

New High Performance, Low GWP Refrigerants for Stationary AC and Refrigeration

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

2017 Climate & Refrigerants Outlook. Stephen Yurek President & CEO

Comparison of Energy Efficiencies of Commercial Refrigeration Direct and Indirect Systems

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Sustainable Refrigerant Solutions for HVAC-R. Laurent Abbas, Wissam Rached, Brett Van Horn

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

Air-Cooled Heat Exchanger Performance for R410A

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results Xudong Wang Air-Conditioning, Heating, and Refrigeration Institute, United States of America, xwang@ahrinet.org Karim Amrane Air-Conditioning, Heating, and Refrigeration Institute, United States of America, kamrane@ahrinet.org Follow this and additional works at: http://docs.lib.purdue.edu/iracc Wang, Xudong and Amrane, Karim, "AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results" (2016). International Refrigeration and Air Conditioning Conference. Paper 1586. http://docs.lib.purdue.edu/iracc/1586 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2064, Page 1 AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase II Testing Results Xudong WANG*, Karim AMRANE Air-Conditioning, Heating, and Refrigeration Institute, Arlington, Virginia, USA Tel: 703-524-8800, Fax: 703-562-1942 xwang@ahrinet.org, kamrane@ahrinet.org * Corresponding Author ABSTRACT The Air-Conditioning, Heating, and Refrigeration Institute (AHRI) recently completed the second phase of its Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP). This industry-wide cooperative research program identified and evaluated promising alternative refrigerants over the past five years. Seventeen low-gwp refrigerants were tested during the second phase of the program in a variety of products; including air conditioners, heat pumps, chillers, ice makers and commercial refrigeration displace cases. Phase II also included performance testing under high ambient conditions up to 52 o C. This paper provides a comprehensive high level summary of the refrigerants tested and results obtained during phase II. 1. INTRODUCTION AHRI is currently leading an industry-wide cooperative research program, the Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP). The program aims at identifying and evaluating promising low-gwp alternative refrigerants for major air conditioning and refrigeration products. Phase I testing of the program was completed at the end of 2013 and produced 40 test reports (Wang et al., 2014). Phase II testing started in 2014, and produced 33 test reports. Phase II reports included compressor calorimeter testing, system dropin testing, and soft-optimized system testing. Seventeen refrigerant were tested by U.S. and international manufacturers and laboratories. The intent of the program is to help industry select promising alternative refrigerants, understand technical challenges and identify the research needed to implement these refrigerants. The program s objectives are to identify potential replacements for high GWP refrigerants, test and present the performance of these replacements in a consistent manner. However, the program will not prioritize the alternative refrigerants. This paper is an overall summary of the test results obtained in Phase II. 2. LOW GWP REFRIGERANTS In Phase II testing, twenty-nine refrigerants were proposed by refrigerant producers, and seventeen of them were actually tested according to test companies interest. The tested refrigerants and their compositions are listed in Table 1. Neither an upper numerical limit on refrigerants GWP values nor the safety classifications were limitations to nominating refrigerants, as long as the alternative candidate had a significant reduction in its GWP relative to the refrigerant it is intended to replace. 3. TESTING Tests conducted during Phase II of the program included: (1) compressor calorimeter tests, (2) drop-in system tests, and (3) soft-optimized system tests. Compressor calorimeter tests were conducted in accordance with ASHRAE Standard 23-2010 (testing companies in Europe may alternatively use EN 13771.). The drop-in tests were conducted with the alternative refrigerants placed in systems designed for baseline refrigerants with only minor adjustment, if any, such as charge or superheat setting. Soft-optimized tests were performed using baseline refrigerant systems.

2064, Page 2 These systems were modified for the alternative refrigerants using standard production line components. In addition, the heat transfer area of the soft-optimized system s evaporator and condenser may be changed, provided that the sum of the total area remains the same as the baseline system. Manufacturers conducting tests may change components to get optimized performance, but are required to provide enough information to show these changes. All tests were conducted by following the latest industry-wide accepted standards. The following subsections summarize the low-gwp refrigerants tested, and the type of test conducted in Phase II for different product categories. The Low-GWP AREP Report Number corresponding to a particular equipment tested is also listed, in order to direct readers to the detailed test information and results. Table 1: List of low GWP refrigerant candidates in Phase II Baseline Refrigerant Composition (Mass%) Classification (Note 1) GWP 100 (Note 2) DR-93 R-32/R-125/R-1234yf/R-134a 20/20/31/29 A1 1251 N-20b R-32/R-125/R-134a/R-1234yf 13/13/31/43 A1 988 R22/R- R-449B R-32/R-125/R-1234yf/R-134a 25.2/24.3/23.2/27.3 A1 1412 407C ARM-20b R-32/R-1234yf/R-152a 35/55/10 A2L 251 DR-3 R-32/R-1234yf 21.5/78.5 A2L 148 L-20a (R-444B) R-32/R-1234ze/R-152a 41.5/48.5/10 A2L 295 ARM-35 R-32/R-125/R-1234yf 12.5/61/26.5 A1 2220 DR-34 (R-452A) R-32/R-125/R-1234yf 11/59/30 A1 2140 R404A N-40c (R-448A) R-32/R-125/R-134a/R-1234yf/R-1234ze 26/26/21/20/7 A1 1387 ARM-20a R-32/R-1234yf/R-152a 18/70/12 A2L 139 HDR110 R-32/R-1234yf/CO2 21.5/75.5/3 A2L 148 ARM-71a R-32/R-1234yf/R-1234ze(E) 68/26/6 A2L 460 DR-5A (R-454B) R-32/R-1234yf 68.9/31.1 A2L 466 R410A DR-55 R-32/R-125/R-1234yf 67/7/26 A2L 698 HPR2A R-32/134a/1234ze(E) 76/6/18 A2L 600 L-41-1 (R-446A) R-32/R-1234ze/Butane 68/29/3 A2L 461 L-41-2 (R-447A) R-32/R-1234ze/R-125 68/28.5/3.5 A2L 583 Notes: 1. Refrigerants classifications or intended classifications according to the ASHRAE Standard 34 (ASHRAE, 2013). 2. GWP values are calculated based on IPCC AR-4 100 year. 3.1 Compressor Calorimeter Tests Eight hermetic compressors were tested at four different testing facilities. The compressors included reciprocating, scroll, and rotary types. Specific information on the tested compressors is listed in Table 2. Table 2: Tested compressors with low-gwp refrigerants No. Compressor Type Voltage Disp. Volume Baseline Refrigerants Refrigerant Tested AREP Report No. 1 hermetic 115V, 60Hz, 8.77 cm3 R-404A HDR-110, DR3 49 and 50(Sedliak, 2015a reciprocating single phase and 2015b) 2 Semi-hermetic 380-420v, 50Hz, 971.2 cm3 R-404A DR-33 (R449A) 51 (Boscan et al, 2015) reciprocating three phase hermetic 230V, 50 Hz, 74.2 cm3 R-404A DR-7, ARM-25 64 and 67 (Pérouffe et al, 3 reciprocating, Low back pressure single phase 2016a and 2016b) 4 5 6 7 8 hermetic reciprocating, High back pressure hermetic scroll hermetic reciprocating hermetic scroll hermetic scroll 230V, 50 Hz, single phase 230V, 50 Hz, single phase 230/208, 60Hz, single phase 380V, 50 Hz, three phase 400V, 50 Hz, three phase 74.2 cm3 R-404A DR-7, ARM-25 64 and 67 (Pérouffe et al, 2016a and 2016b) 29.5 cm3 R-410A DR-5A 58 (Rajendran et al, 2016) 30.5 cm3 R-410A L41-1, DR-5A, 59 (Lenz et al, 2016) ARM-71a, D2Y-60 and R-32 112.3 cm3 R-410A L-41-2 (R-447A) 65 (Rajendran et al, 2016) 151.7cm3 R-410A HPR2A 66 (Suindykov et al, 2016)

2064, Page 3 3.2 Air-conditioners, Heat Pumps, and Water Chillers Thirteen air-conditioners and heat pumps as well as a water chiller were tested with different low-gwp refrigerants. Information about the equipment tested and the type of tests conducted is summarized in Table 3. Eight of them were tested under a high ambient condition of 52 C. Table 3: Tested air-conditioners, heat pumps and water chiller Unit Equipment Baseline Test Standard Refrigerants Tested Test type No. Type Refrigerant 1 3-ton air R-410A R-32 softoptimization source, split 2 3-ton air R-410A ARM-71a, DR-5A, drop-in source, split HPR2A, L-41-1, L-41-2 3 3-ton air R-410A R-32, DR-5A, L-41-2 drop-in source, split 5-ton air R-410A R-32, ARM-71a, DR- drop-in 4 source, 5A, DR-55, HPR2A, L- rooftop 41-2 packaged unit 6-ton air R-410A R-32 softoptimization 5 340/360 source, rooftop packaged unit 4-ton air R-410A R-32, DR-5A, DR-55 softoptimization 6 source, rooftop packaged unit 2.5-ton air R-22 R-410A, R-32 softoptimization 7 source, rooftop packaged unit 1.5-ton air R-410A R-32, ARM-71a, DR- softoptimization 8 source, minisplit 55, HPR2A, L-41-2 1.5-ton air R-22 N-20b, DR-3, ARM- softoptimization 9 source, minisplit 20b, L-20a, DR-93, R- 290 1-ton waterto-water, R-410A R-32, L-41-1, L-41-2 drop-in ISO Standard 10 heat 13256-2 and EN pump Standard 14511-2 1-ton, single R-410A R-32 drop-in 11 packaged 390 vertical heat pump (SPVH) 3-ton waterto-air, R-410A R-32, DR-5A, DR-55, drop-in and ISO Standard 12 heat L-41-2 soft- 13256-1 pump optimization 4.5-ton air-towater R-407C DR-3, L-20a, R-290 drop-in EN Standards 13 heat 14511 and 14825 pump 14 2-ton air-towater chiller L-41-2 conditions R-410A R-32, DR-5A, L-41-1, drop-in Tester defined * :Standard rating conditions and high ambient conditions up to 52 o C AREP Report No. 42 (Li et al, 2015) 52 (Burns, et al, 2015) 54 (Stöben et al, 2015) 47 and 53 (Uselton et al, 2015a and b) 55 (Abbadi et al, 2015) 56 and 63 (Schultz et al., 2015 and 2016) 57 (Allen et al, 2015) 62 (Abdelaziz et al., 2016) 62 (Abdelaziz et al., 2016) 43 (Park et al., 2015) 44 (Wuesthoff et al, 2015) 60 (Brown et al., 2016) 61 (Stöben et al, 2016) 46 (Hanna et al, 2015) 3.4 Refrigeration Equipment Two commercial ice machines, one trailer refrigeration unit and one commercial bottle cooler/freezer were tested by three manufacturers participating in the program. Information about the equipment tested and the test procedures is summarized in Table 4.

2064, Page 4 Table 4: Tested refrigeration equipment Unit No. 1 2 3 Equipment Type Baseline Refrigerants Test AREP Test Standard Refrigerant Tested type Report No. trailer refrigeration unit R-404A DR-34 (R-452A) drop-in 1110 41 (Hegar et al, 2015) a split system air-cooled R404A ARM-20b, N-40c drop-in 810 and 45 (Olson, commercial ice machine ASHRAE Standard 29 2015) a split system air-cooled R-404A L-20a (R-444B), drop-in 810 and 48 (Urbieta, commercial ice machine N-40c (R-448A) ASHRAE Standard 29 2015) 4. TEST RESULTS SUMMARY Test results are summarized according to equipment types. The performance of the low GWP refrigerants is normalized to their baseline refrigerants. Therefore, the comparison figures only show their relative performance to their respective baselines. To keep the paper concise, only partial results are shown (e.g. at one particular test condition, a particular baseline refrigerant etc.). Readers should refer to the individual test reports for all the data. The Coefficient of Performance (COP) is defined as a ratio of the capacity to the power consumption; and the Energy Efficiency Ratio (EER) is defined as a ratio of the cooling capacity in Btu/h to the power input value in watts 4.1 Compressors The results shown in this subsection were obtained from compressor performance maps. Test companies used multiple test points to generate compressor performance maps in accordance with 540. These maps were used to predict the performance of the compressors at any given set of evaporating and condensing temperatures within operating envelopes. Figure 1 shows the test results of compressors No. 1 and 3 in Table 2 under a typical refrigeration condition (40 C condensing temperature, and -25 C evaporating temperature). The compressors were both tested at 10~11K superheat. The compressor No. 1 was tested under two different sets of superheat (11K and 22K). Figure 1a shows that the four low GWP refrigerants have higher COP (4%~13%) at ~11K superheat compared to R- 404A; however only DR-7 has a higher capacity (8%) at the same time. The other three refrigerants experienced some capacity degradation although the degree varies (-16%~-9%). When the compressor No.1 was tested at a higher superheat (22K), the low GWP refrigerants performance decreased. Their relative capacity decreased further apart from the R-404A, and relative COP got closer to the R-404A.

2064, Page 5 (a) (b) Figure 1: Low GWP refrigerants relative performance to R-404A 4.2 Air-conditioners and Heat Pumps Test results for rooftop packaged units and residential split air-conditioners and heat pumps are summarized in Figures 2 and 3 (Unit No.1~7 in Table 3). The relative cooling performance to the baseline R-410A under the standard rating condition of 35 C and a high ambient condition of 52 C is shown in both figures. R32, DR-5A, and DR-55 were tested in multiple units from different manufacturers. Figure 2 generally shows that it is possible for R-32, DR-5A and DR-55 to achieve higher capacity and EER than R-410A after simple softoptimization. Other blends had lower capacity but higher efficiency than R-410A on a drop-in basis. It is also shown

2064, Page 6 that these low GWP refrigerants relative performance to R-410A improved under the high ambient condition. They all showed very close or higher capacity and, in most of case, higher efficiency than R-410A. Similarly, Figure 3 indicates that R-32 has a higher capacity than R-410A, and that it is also possible to achieve higher EER with soft-optimization. DR-5A, ARM-71a and L-41-2 showed comparable EER with slightly lower capacity than R-410A for drop-in test at 35 C ambient temperature. When performing under the high ambient temperature, these low GWP refrigerants demonstrate an improved relative performance to R-410A. They showed comparable capacity closely matching R-410A, and their efficiency is higher than or almost equal to R-410A. R-32 was not tested in the Units 2 and 3 under the 52 C ambient condition due to high discharge temperatures. Unit 1 used a specially formulated POE lubricant for R-32 (different from R-410A), and was able to operate and complete the test. (a) (b) Figure 2: Low GWP refrigerants relative performance to R-410A in rooftop packaged units

2064, Page 7 (a) (b) Figure 3: Low GWP refrigerants relative performance to R-410A in residential split systems 4.3 Refrigeration Equipment ARM-20b, L-20a and N-40c were tested as drop-in refrigerants in two commercial ice machines (Units 2 and 3 in Table 4). Both were split systems. Figure 4a illustrates the low GWP refrigerants relative performance to the baseline R-404A at the AHRI rating condition (ambient temperature: 32 C; water temperature 21 C). N-40c consumed comparable or less power than R-410A and its relative capacity to R-410A is within 4%. ARM-20b and L-20a showed slightly increased power consumption (<3%), and reduced capacity compared to R-404A. Figure 4b showed the relative performance changes of the ARM-20b and N-40c at the high ambient condition when compared to the standard rating condition. Both refrigerants relative performance to R-410A improved with less energy consumption and higher capacity than R-410A.

2064, Page 8 (a) (b) Figure 4: Low GWP refrigerants relative performance to R-404A in commercial ice machines 5. DISCUSSION The Low-GWP AREP compressor tests were performed at a refrigerant s dew point temperature for suction and discharge pressure conditions. This does not have an impact when comparing compressor performance between two or more refrigerants that do not exhibit temperature glides. However, when refrigerants exhibit temperature glides, it is important to note that actual systems operate closer to the mid-point condition. When comparing compressor performance of one refrigerant with glide to another without, or comparing two refrigerants with significantly different glides, using pressures corresponding to the midpoint of the temperature glide rather than the dew point will yield results that are more representative of actual operation in a system (AHRI, 2015). The results presented in Section 4 are for a quick initial comparison only. Cautions should be used when analyzing the data. It should be stressed that the capacity and efficiency are not strictly comparable among refrigerants when their suction vapor densities are different in drop-in testing, and when different test companies use different drop-in or soft-optimization procedures. The test procedure and results must be interpreted to account for charge quantity,

2064, Page 9 expansion device, and/or compressor speed adjustment. Some test companies vary low GWP refrigerant charge quantity and/or adjust the expansion device to obtain comparable subcooling and superheating degrees to the baseline refrigerants. Some companies simply used the same charge quantity and the same expansion devices without any adjustment. As a consequence, different results may be obtained, and premature conclusions could be drawn if readers do not understand the source of variations. For example, R-32 was originally tested in Unit 2 in Figure 3 with the same charge quantity as the R-410A. The subcooling and superheat were shown in Figure 5. The R-32 with original charge had a subcooling 3K higher than the baseline suggesting that the system may be overcharged. The R-32 charge amount was reduced to 90% of the original charge. Its relative efficiency to R-410A increased 3% as shown in Figure 3. Figure 5: Unit 2 R-32 charge vs. subcooling and superheat Another example is the N-40c test in two ice machines in Section 4.3. Results show that N-40c has different relative capacity to the baseline. This variation is likely the result of different drop-in methods used in the testing. The charge quantity of N-40c in Ice Maker-1 was optimized under the ambient temperature of -29 C and the water temperature of 10 C. This is to determine the minimum amount of refrigerant necessary for the system to operate correctly at the low end of the operating envelope (Olson, 2015). The expansion valve was adjusted under the ambient temperature of 43 C and the water temperature of 32 C. Once the adjustment was completed, the test under the standard rating condition was conducted without further adjustment. However, the Ice Maker-2 used the same charge quantity for all tested refrigerants, and no adjustment was made to the expansion valve setting. 6. CONCLUSIONS The test results obtained from the Low-GWP AREP showed that there are several alternative candidates with comparable performance than the baseline refrigerants they intend to replace. It should be noted that most results were obtained from drop-in and soft-optimized tests performed on equipment designed for the baseline refrigerants and not the alternatives. Therefore, the results should not be viewed as universally applicable. The normalized comparison only provide initial quick understanding of improvement potential. The test results should be carefully interpreted along with system modifications, test procedure variations etc. Additional study is required to evaluate the potential improvement through further soft optimization. Full optimization of systems will likely improve the performance of these refrigerants; however, this work is outside the scope of the Low-GWP AREP, and will be undertaken by individual manufacturers. REFERENCES Abbadi, M., Khawaldeh, M., 2015, System Soft-optimization Tests of Refrigerant R-32 in a 6-ton Rooftop Packaged Air- Conditioner, AHRI Low-GWP AREP Report NO. 55 Abdelaziz, O., Shrestha, S., 2016, Soft-Optimized System Test of Alternative Lower GWP Refrigerants in 1.5-ton Mini- Split Air Conditioning Units, AHRI Low-GWP AREP Report NO. 62 AHRI, 2015, Low-GWP Alternative Refrigerants Evaluation Program Participants Handbook, www.ahrinet.org Allen, H., Li, H., By, R., 2015, System Soft-optimization Tests of Refrigerant R-32 in a 2.5 ton Rooftop Heat Pump, AHRI Low-GWP AREP Report NO. 57

2064, Page 10 Boscan, M., Sanchez, J., 2015, Compressor Calorimeter Test of Refrigerant DR-33 (R-449A) in a R-404A Reciprocating Compressor, AHRI Low-GWP AREP Report NO. 51 Brown, R. R., Obosu, C. B., 2016, System Drop-in Tests of DR-5A, DR-55, L41-2 and R-32 in Water-To-Air Heat Pump, AHRI Low-GWP AREP Report NO. 60 Burns, L., Chen, C., 2015, System Drop-in Tests of Refrigerant Blends ARM-71a, DR-5A (R-454B), HPR2A, L-41-1 (R- 446A), L-41-2 (R-447A) in a R-410A Split System Heat Pump, AHRI Low-GWP AREP Report NO. 52 Hanna, R., Ortego, E., Zoughaib, A., 2015, System Drop-in Test of Refrigerants R32, DR-5A, L-41-1 and L-41-2 in a Water Chiller, AHRI Low-GWP AREP Report NO. 46 Hegar, M., Kolda, M., 2015, System Drop-in Tests of Refrigerant DR-34 (R-452A) in a Trailer Refrigeration Unit Designed for R-404A, AHRI Low-GWP AREP Report NO. 41 Lenz, J. R., Shrestha, S., 2016, Compressor Calorimeter Test of Refrigerant L41-1, DR-5A, ARM-71a, D2Y-60 and R-32 in a R-410A Reciprocating Compressor, AHRI Low-GWP AREP Report NO. 59 Li, H., By, R., 2015, System Soft-optimization Tests of Refrigerant R-32 in a 3-ton Split System Air-Conditioner, AHRI Low-GWP AREP Report NO. 42 Olson, W., 2015, System Drop-in Test of Refrigerant Blends ARM-20b and N-40c (R-448A) in Automatic Commercial Ice Maker Designed for R404A, AHRI Low-GWP AREP Report NO. 45 Park, S., Ahn, B., 2015, System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to-Water Heat Pump, AHRI Low-GWP AREP Report NO. 43 Pérouffe, L., Renevier, G., 2016a, Compressor Calorimeter Test of Refrigerant DR-7 (R-454A) in a R-404A Reciprocating Compressors, AHRI Low-GWP AREP Report NO. 64 Pérouffe, L., Renevier, G., 2016b, Compressor Calorimeter Test of Refrigerant ARM-25 in a R-404A Reciprocating Compressors, AHRI Low-GWP AREP Report NO. 67 Rajendran, R., Pham, H., Bella, B., Skillen, T., 2016, Compressor Calorimeter Test of Refrigerant DR-5A in a R-410A Scroll Compressor, AHRI Low-GWP AREP Report NO. 58 Rajendran, R., Pham, H., Bella, B., Skillen, T., 2016, Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor, AHRI Low-GWP AREP Report NO. 65 Schultz, K., Perez-Blanco, M., Kujak, S., 2015a, System Soft-optimization Tests of Refrigerant R-32, DR-5A, and DR-55 in a R-410A 4-ton Unitary Rooftop Heat Pump-Cooling Mode, AHRI Low-GWP AREP Report NO. 56 Schultz, K., Perez-Blanco, M., Kujak, S., 2016, System Soft-optimization Tests of Refrigerant R-32, DR-5A, and DR-55 in a R-410A 4-ton Unitary Rooftop Heat Pump-Heating Mode Performance, AHRI Low-GWP AREP Report NO. 63 Sedliak, J., 2015a, Compressor Calorimeter Test of Refrigerant Blend HDR110 in a R-404A Reciprocating Compressor, AHRI Low-GWP AREP Report NO. 49 Sedliak, J., 2015b, Compressor Calorimeter Test of Refrigerant Blend DR-3 in a R-404A Reciprocating Compressor, AHRI Low-GWP AREP Report NO. 50 Stöben, T., Wesch, S., Jepsen, J. J., 2015, System Drop-In Test of Refrigerants DR-5A, R-32, and L-41-2 in a 2.5-Ton R- 410A Heat Pump, AHRI Low-GWP AREP Report NO. 54 Stöben, T., Wesch, S., Jepsen, J. J., Jessen, L. M., 2016, System Drop-in Tests of DR-3, L-20 (R-444B), and R-290 in Airto Water Heat Pump-Heating Mode, AHRI Low-GWP AREP Report NO. 61 Suindykov, S., Zhang, L., Gernemann, A., 2016, Compressor Calorimeter Test of Refrigerant HPR2A in a R-410A Scroll Compressor, AHRI Low-GWP AREP Report NO. 66 Urbieta, H., 2015, System Drop-in Tests of Refrigerants N-40 and L-20 in a R-404A Ice Machine, AHRI Low-GWP AREP Report NO. 48 Uselton, D., Crawford, T., 2015a, System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R 410A Rooftop Packaged Unit, AHRI Low-GWP AREP Report NO. 47 Uselton, D., Crawford, T., 2015b, System Drop-In Test of Refrigerant DR-55 in a Five-Ton R-410A Rooftop Packaged Unit, AHRI Low-GWP AREP Report NO. 53 Wang, X., Amrane, K., 2014, AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low- GWP AREP)-Summary of Phase I Testing Results, 15th International Refrigeration and Air Conditioning Conference at Purdue Wuesthoff, E., 2015, System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH), AHRI Low-GWP AREP Report NO. 44 ACKNOWLEDGEMENT The AHRI Low-GWP AREP is strongly desired and supported by the HVACR industry. AHRI gratefully thanks all the companies conducting tests and supplying refrigerants, and the Low-GWP AREP Technical Committee Members for contributing their expertise and resources to the program.