DESIGN MANUAL. The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0)

Similar documents
DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR

S AFETY SYSTEMS TECHNOLOGY Mill Creek Drive, Suite 215 Laguna Hills, California 92653, USA Tel (949) Fax (909)

Design Manual Installation Operation Maintenance

MODEL GT812 NOVA-SENSOR ELITE TOXIC GAS DETECTOR

MODEL GC802 NOVA-SENSOR ELITE COMBUSTIBLE GAS DETECTOR

RK CO 2 Transmitter Operator s Manual

Design Manual Installation Operation Maintenance

SEC 2000 Millenium Infrared Gas Detector

RK-05 Combustible Gas Transmitter Operator s Manual

INSTRUCTIONS. PointWatch Infrared Hydrocarbon Gas Detector PIR9400

TOXIC GAS AND OXYGEN DETECTOR DTX 420 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS DTX420_MAN01_EN_V1R2

CT-7 Series Toxic Gas Transmitter Operator s Manual

Instructions Model MIR MSHA Approved IR Gas Detector 3.1 7/

SAFETY MANUAL. FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors

RK Combustible Gas Transmitter Operator s Manual

Lamp Supply (Recommended)

RK Carbon Monoxide Transmitter Operator s Manual

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

SAFETY MANUAL. IR5000 Open Path Hydrocarbon Gas Monitoring System

Models TX-KE and TX-KP Toxic Gas Transmitters

RK-05 Carbon Monoxide Transmitter Operator s Manual

Operation and Maintenance Manual

Operations Manual GMA 313 CO 2. Gas Monitor for one detection point

Instructions

SEC Millenium Carbon Dioxide Gas Detector

RK Hydrogen Sulfide Transmitter Operator s Manual

OPTISENS TUR 2000 Technical Datasheet

RK Transmitter Technical Notice

Analog Room Pressure Monitor RPC Series

UNI-TRAN PREMIUM PLUS TOXIC GAS DETECTOR USER MANUAL UT-P+-STXXXX

RK-CH4-4 Combustible Gas Transmitter Operator s Manual

SIMRAD GD10 IR GAS DETECTOR

Instruction Manual CHHC-1

SIMRAD GD10P - IR GAS DETECTOR OPERATING MANUAL

Carbon Dioxide Sample-Draw Detector Operator s Manual

DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION

SEC Signature Process Gas Analyzer

RK Carbon Monoxide Transmitter Operator s Manual

RK/ RK Carbon Monoxide Detector Operator s Manual

INFRARED PRODUCTS FOR MONITORING SMOKELESS FLARES, PILOTS, AND FLAME INTENSITY

Design Manual Installation Operation Maintenance

IR4000. Point Infrared Combustible Gas Detection System. The Reliable and Flexible Safety Solution That s Low Maintenance

Key Features. General Description

Hydrocarbon Gas Detector

SIL 2. Ultima X Series Gas Monitors CERTIFIED

SEC 5000 IREvolution Gas Detector

MODEL: O ELECTROCHEMICAL O2 DETECTOR (Used with ST1400 O2 Sensor) Part Number: MAN Rev. 0

RK Carbon Monoxide Transmitter Operator s Manual

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

Model D12-IR. Digital Gas Transmitter...

Nanotechnology Metal Oxide Semiconductor (NTMOS) H 2 S Gas Sensor

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors

SIMRAD GD10PE IR GAS DETECTOR

Duct and Rough Service Carbon Monoxide Sensor

RK / RK CO 2 Detector Operator s Manual

Instructions R8471J Gas Controller for use with Model OPECL Open Path Eclipse IR Gas Detector 1.1 1/

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER

Carbon Monoxide Transmitter

ULTIMA XL/XT Series Gas Monitors. [ Ultimate Features Extreme Design ]

Pioneer-R16 Gas Monitor Operator s Manual

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications

Instruction Manual Model A

SEC Millenium Hydrocarbon Gas Detector

1228s Multidrop INSTRUCTIONS. Installation and Operation of the AMC-1228s Electrochemical Sensor Module For Use With Multidrop AMC Monitors

SAFEYE XENON 700. Hydrocarbons and ethylene detection. Heated optics. 10-year Warranty for the Xenon flash bulb. SIL 2 according to IEC 61508

RK-05 Carbon Monoxide Detector Operator s Manual

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

RK / RK Methane Detector Operator s Manual

Furnace Gas Monitor SD Operating Manual (PT2-163)

Instructions. PointWatch TM Infrared Hydrocarbon Gas Detector Model PIR Rev: 9/

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE

HGM300/RDM800 PREVENTATIVE MAINTENANCE AND TECHNICAL SUPPORT. SECTION 1 HGM300 CPU reset, RDM800 CPU reset, WARM UP notes and HGM300 Self Test

INSTRUCTION MANUAL. DECKMA HAMBURG GmbH. Type OMD-12. Oil-in-Water Monitor

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL

RK/ RK Combustible Gas Detector Operator s Manual

Model C Combustible Gas Transmitter. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

Operating Instructions

Model 3300 Technical Support and Installation Manual

Controllers. Instruction Manual WARNING

Operation and Maintenance Manual

RK-03 Hydrogen Detector Operator s Manual

Combustible Gas Sample-Draw Detector Operator s Manual

! "! # Please read these installation and operating instructions completely and carefully before starting.

URD20SE. Gas detectors Carbon dioxide (CO 2 ) ATEX certified (II 2G Ex d IIC T6) Use. Operation. Ordering

UNI-TROL TM GAS CONTROLLER

SIMRAD GD10L - IR GAS DETECTOR OPERATING MANUAL

Gas Safety Products. Installation, operating and maintenance. Merlin CO2 Monitor 4500PPM. Merlin CO2 Monitor. Rev: 11 Date:

ACCURATE ELECTRONICS INC

PureAire Combo O 2 / CO 2 Monitor

Oxygen Analyzer Manual

RED1. Technical Support And Installation Manual. Models ST, E1, E2, E3, E4, and 420. Approved

Hygro Transducer / Hygrothermal Transducer and CO 2 Measuring Probe for Climate Monitoring

FLT93 Installation, Operation and Troubleshooting Guide

Public Safety DAS Annunciator Panel

Model IR4000M. Multi-Point Monitor. Instruction Manual 12-10

Model IR5500. Infrared Open Path Detector for Hydrocarbon Gas Applications

ULTIMA X5000. MSAX5000.com

RKA-LEL Sample Draw Combustible Gas Detector

Transcription:

DESIGN MANUAL MODEL GIR910 INFRARED CARBON DIOXIDE (CO 2 ) GAS SENSOR 70091 The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0) The information and technical data disclosed by this document may be used and disseminated only for the purposes and to the extent specifically authorized by Safety Systems Technology in writing. Such information and technical data are proprietary to Safety Systems Technology and may not be used or disseminated except as provided in the foregoing sentence. 23282 Mill Creek Drive, Suite 215, Laguna Hills, California 92653 USA Tel 1-949-583-1857 Fax 1-949-340-6643 e-mail support@safetysys.com

Contents MODEL GIR910 INFRARED CARBON DIOXIDE SENSOR... 910-1 DESCRIPTION... 910-1 Principle of Operation... 910-1 TECHNICAL SPECIFICATIONS... 910-2 INSTALLATION... 910-2 Locating and Mounting the Sensor... 910-2 Wiring... 910-3 OPERATION... 910-4 Power-Up... 910-4 Calibration... 910-4 Recalibration Schedule... 910-6 MAINTENANCE... 910-6 Replacing the Infrared Gas Sensor Electronics Module... 910-6 TROUBLESHOOTING... 910-6 Sensor output constantly 2 ma... 910-6 Sensor output pulses between 0 ma and 2 ma every second... 910-6 SPARE PARTS... 910-7 DESIGN MANUAL September, 2009 i

Blank Page

MODEL GIR910 INFRARED CARBON DIOXIDE SENSOR DESCRIPTION The SST Model GIR910 Infrared Carbon Dioxide Sensor is a completely self-contained device that measures and displays the concentration of gas accumulated in a protected area and transmits this information to a central control point. Principle of Operation The GIR910 Infrared Carbon Dioxide Sensor uses the proven non-dispersive infrared (NDIR) principle to detect and monitor the presence of CO 2. Using an infrared Figure 910-1 GIR910 Sensor source lamp and an optical sensor with a narrow-band filter, an analysis of the optical absorption through the gas allows the concentration of the target gas to be determined. A second infrared sensor operating at a wavelength not affected by the target gas is used to eliminate effects resulting from ambient and physical variations. These include temperature changes, source and filter degradation and particle scattering. The GIR910 is available in versions to operate in ranges from 2% to 100% CO 2 by volume with a resolution of less than 2% of full scale. Operating over 0-100% relative humidity and ambient temperatures between 14 F and 122 F [-10 C and +50 C], the GIR910 is particularly suitable for the reliable monitoring of lethal CO 2 levels in industrial safety applications. Each GIR910 includes a high-reliability microprocessor based transmitter. The transmitter converts the output from the infrared sensor elements to a standard 0-20 ma signal which may be connected to a suitable NOVA-5000 Gas Detection Module, or to any other device with a standard 0-20 ma input. Output levels between 4 and 20 ma indicate the measured concentration of carbon dioxide. An output of 2 ma indicates that the detector is in the calibration mode, while 0 ma indicates a malfunction or fault. Calibration of the transmitter output is initiated by activating the calibrate input on the transmitter. Calibration is completely automatic, requiring no hand adjustment of potentiometers. Calibration data is stored in the nonvolatile RAM of the transmitter. DESIGN MANUAL September, 2009 910-1

TECHNICAL SPECIFICATIONS Power Supply...24 volts DC nominal. Will operate within specifications at any supply voltage between 16 and 30 volts @ 120 ma Range...0 to 2%, 5%, 30% or 100% by volume Carbon Dioxide 0 to 1,000,000 PPM Warm-up time...10 seconds operational 20 minutes to specification Operating Temperature...-14 to +122 o F. -10 to +50 o C Relative Humidity...0-95% non-condensing Ingress Protection... IP40, IP52 with optional dust cover, IP66 with optional spray shield Repeatability...Zero ±0.1% of full scale Signal ±0.05% of full scale Maintenance Interval...6 months for verification of performance only Analog Output...Standard 0 to 20 ma self-powered source INSTALLATION A complete GIR910 unit consists of an explosion-proof stainless steel housing with self-contained Infrared gas sensor element and transmitter electronics that converts the sensor signal to the standard 0 to 20 milliamp signal. The sensor is normally installed on an accessory junction box, which contains a terminal block for use in connecting the sensor wires to the required 24 volt DC power source and the measuring equipment. The incoming wires may be installed in rigid metal electrical conduit, or a ¾ inch NPT cable gland may be installed in the junction box to permit wiring with incoming multiconductor cable. Locating and Mounting the Sensor Figure 910-2 Wall Mounting The location of the sensor is important. Carbon Dioxide Gas is approximately 1.5 times as heavy as air. This means that for leaking CO, the gas will accumulate near the floor inside a building, or near the ground when out-of doors. For heavier than air 2 gasses, locate the sensor below the expected leak. However, always locate the sensors at least one foot (30.5 cm) above the floor or ground to prevent damage from water, dust, etc. When used inside a building, the sensor may be mounted on a wall, partition or post. Use the two mounting holes in the junction box to secure the unit. When used outside where the sensor can be subject to rain, wind or dust, the sensor should always be mounted with the porous metal filter for gas entry pointed downward. You may need a mounting bracket to do this. Figure 910-3 Wall Mounting with bracket 910-2 September, 2009 DESIGN MANUAL

Wiring A typical installation is shown in the schematic diagram. This setup uses three wires between the Sensor and the associated control modules. These wires carry the 24 VDC operating power for the sensor, and transmit the 20 ma signal to the controls. Note that the COM wire is the common return for DC power and the 4-20 ma signal. The connection wires should be shielded or installed in metal conduit to prevent undesirable noise pickup. Remove the 4 screws from the junction box cover for access to the wiring terminals. The sensor may be mounted in the box cover, or in one of the side outlets of the junction box. If the sensor is mounted in the box cover, use the provided nylon strap to temporarily hold the cover while connecting the sensor wires to the terminal block. Do not let the cover and sensor hang on the connection wires, as the wires may be loosened from the terminal blocks due to the weight of the stainless steel housing. Then connect 24 volt DC power supply and monitoring equipment wires to the screw terminals in the junction box as shown in the drawing. Figure 900-4 Wiring!IMPORTANT: The location of the sensor wires on the terminal block in the junction box is not important, and may be different than as shown on this drawing. Be sure to connect the external devices to the correct insulation color of the sensor wires to prevent damage to the sensor. Calibrate Pushbutton The optional calibrate pushbutton may be wired to the sensor as shown. Due to the extreme stability of the infrared sensor, recalibration will not regularly be required, so this button would be used only in special cases where more regular calibrations are desired. Figure 910-5 Typical Installation Schematic DESIGN MANUAL September, 2009 910-3

OPERATION Power-Up Calibration When power is first applied, the Sensor begins a 90 second countdown period to allow time for proper temperature stabilization. The sensor will output 4.0 milliamps during this warm up period, but it will not respond to gas during that time. At the end of the warm up, the Sensor begins normal operation.!do not depress the calibrate button (if installed) during the first 10 seconds of the initial warm up period. Depressing the button during this time erases the previously saved calibration data, and will make recalibration necessary. An output signal of 2.0 ma indicates no calibration data is stored in the memory. The GIR910 Sensor is pre-calibrated at the factory to output a current of 12 milliamps when the percentage of CO 2 in the air being sensed is equal to one-half of the range marked on the sensor housing (Usually 2, 5, 30 or 100%). Recalibration after installation is not necessary, but should be performed occasionally to verify that the sensor is properly installed and functioning normally. During the calibration procedure, the presence of clean air, i.e. air without any excess CO 2, is absolutely necessary to provide the electronics module with a reference point for 0% gas concentration. In locations where clean air cannot be assured, you may need to purge the sensor with clean air from a gas bottle before starting the calibration procedure.!note: The sensor has been factory configured to a specific CO2 gas concentration. To recalibrate, you must use CO 2 gas mixed with air to a concentration of exactly one-half of the range marked on the sensor housing IMPORTANT: The sensor cannot be recalibrated to a different CO 2 range without returning it to the factory for reconfiguration.!the GIR910 must warm up for at least 90 seconds after power is first applied before starting calibration. Calibration will be more accurate if you can wait 20 minutes before starting. Do not push the calibrate button on the housing during the first 10 seconds of warm up, or previous calibration data will be erased from the nonvolatile memory. Figure 910-6 Calibration setup using milliamp meter 910-4 September, 2009 DESIGN MANUAL

During the calibration procedure, you need to read the signal at the analog output of the sensor. If possible, have someone at the location where the analog signal is monitored read the values (in percent or in milliamps) for you as you apply the test gas. If this is not possible, disconnect the BLUE sensor wire from the terminal block in the junction box and insert a milliamp meter as shown in figure 910-6. Calibration Procedure!During calibration, the sensor output will increase to 12 milliamps or one-half of the full scale percentage. Be sure that any alarm equipment connected to the sensor is inhibited or isolated during the calibration procedure. Carefully follow the below listed steps to properly calibrate the sensor electronics module: 1) Apply power to the Gas Sensor and wait at least 90 seconds for the warm up period to expire. During this 90 second period the sensor will not respond to any gas. The longer the unit is allowed to warm up, the more stable the signal will be and thus more reliable. 2) Verify the sensor output is reading approximately 4 ma (milliamps) or 0%. If the reading is 2 ma or a negative percentage, the unit has never been calibrated, or the last calibration data has been erased. If the reading is 0 ma or a negative percentage, either the test setup is not correct or the sensor electronics has failed. 3) Press and hold the calibrate pushbutton (if installed), or if a pushbutton is not installed, start the calibration sequence by connecting a jumper between the yellow and black sensor wires. Be sure that no Carbon Dioxide is present at this time. Do not release the pushbutton or remove the jumper until the meter shows 0 ma or a negative percentage. 4) Release the button or remove the jumper when the meter shows 0 ma or a negative percentage. The sensor is now setting the zero gas values into memory. Wait for the meter to increase to 2 ma or to increase to a less negative percentage. 5) When the reading changes as specified in 4) above, apply calibration gas. Calibration gas should be regulated to a flow rate of 1 liter per minute. Wait for the meter to display 12 ma or one half of the full scale percentage reading 6) Remove the calibration gas and wait for the sensor output to return to 4 ma or 0%. The calibration is now complete and unit is operational. Failed or Incomplete Calibrations If the calibration procedure is aborted (e.g. by not applying calibration gas), the Sensor will return to normal operation after a time-out period of 3½ minutes. In this case the Sensor will use its original, pre-calibration data. Turning the power off will also abort the calibration procedure. Common causes for incomplete calibration are: 1) Calibration gas runs out during calibration. In this case, wait for the Sensor to return to normal operation and repeat procedure with a fresh calibration gas bottle. 2) Gas applied at wrong time. Gas applied during step 4 of the calibration procedure above (too early, during clean air sampling) will result in negative displays and inaccurate readings. If the gas is applied too late (which may occur due to the pipe length when remote sensors are used) it may not reach significant levels before the 3½ minute time-out and thus abort the calibration procedure. DESIGN MANUAL September, 2009 910-5

Recalibration Schedule Due to the extreme stability of the infrared gas sensor, recalibration is rarely required. Under normal operating conditions, SST recommends that the gas detectors should be checked every 90 days per the instructions above. Test gas should be applied to the sensors on a scheduled basis to verify proper sensor operation. Before testing, do a visual inspection to check for contamination of the sintered metal sensor cover, loose parts, etc. Be sure to deactivate any connected equipment before applying test gas to the detector to prevent false alarms! MAINTENANCE The GIR910 is easy to service. Most service activities will require removal of the sensor front cover or junction box cover for servicing. CAUTION: Before opening lids or enclosures, the area must be free of any combustible gasses! Replacing the Infrared Gas Sensor Electronics Module After extended use, the incandescent lamp in the detection element may fail. In this failure mode, the analog output of the detector will be about 2 ma, and there will be no response when gas is applied to the gas detector. To replace, follow this procedure: 1) Remove the sintered metal cover from the sensor head by loosening the set screw and then turning the front part of the enclosure with the sintered metal cap counterclockwise. 2) Grasp the detection element and pull to remove it, along with the PC board assembly, from the housing. Replace with the new electronics module. Discard the failed module. 3) Replace the sensor cover and tighten set screw. 4) Wait for the 90 second warm up to occur, then test the newly installed electronics by applying calibration gas of proper concentration. This is only an operational test. Complete calibration is not required, as the electronics have already been calibrated at the factory. TROUBLESHOOTING Sensor output constantly 2 ma This indicates that the IR gas sensing element has failed or that no calibration data is saved in nonvolatile memory. Perform a complete calibration per instructions in this manual. If sensor will not calibrate, then the sensor element has failed. Replace the electronics module with a new one. Sensor output pulses between 0 ma and 2 ma every second Indicates a thermal fault, which occurs when the sensor is exposed to temperatures greater than 70 degrees C or 158 degrees F. Normal sensor operation will resume when sensor is cooled to lower temperature. 910-6 September, 2009 DESIGN MANUAL

SPARE PARTS The following spare parts for this item are available from Safety Systems Technology. Order No. Description 40910-25-2 Plug-in transmitter module with sensor element, 2% by volume CO 2 40910-25-5 Plug-in transmitter module with sensor element, 5% by volume CO 2 40910-25-30 Plug-in transmitter module with sensor element, 30% by volume CO 2 40910-25-100 Plug-in transmitter module with sensor element, 100% by volume CO 2 DESIGN MANUAL September, 2009 910-7

Blank Page 910-8 September, 2009 DESIGN MANUAL