Technical Bulletin Developed with Glow-worm

Similar documents
M07. Wunda Premium Manifold. Before you start: Check the contents THE BRAND YOU CAN TRUST

PIPING APPLICATION GUIDE

ENERSTORE. Vented Hot Water Storage System INSTRUCTIONS PLEASE LEAVE WITH HOUSEHOLDER

HazLoc Essential Guides:

Trade of Plumbing. Module 2: Domestic Hot and Cold Water Service Unit 10: Hot Water Supply Phase 2

Technical Bulletin. Concealed extended flues

Water Heating UK 14 th May 2016

INSTALLATION & COMMISSIONING INSTRUCTIONS Model: 990 CH

Go Greener, with Gas.

INSTALLATION & TECHNICAL MANUAL

EZ TANKLESS EZ DELUXE OPERATION & INSTALLATION MANUAL

WHAT LURKS BELOW THE WATERS OF YOUR CENTRAL HEATING SYSTEM?

Technical Checklist - Plumbing and Heating Fittings - UK Sizes

Part J of the Building Regulations: Changes for 2010 Tuesday 28 th September 2010 Presenter: David Bleicher

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Incident Summary (II )

Commercial product range

Technical Bulletin 005(B) Developed with Building Standards Scotland

WHAT TO DO IF YOU SMELL GAS

Assessment Schedule - TS.6

Trials of Vexo inhibitor in domestic central. heating systems

Fire Safety in Communal Areas Policy

Spring/Summer Incentives

Spring/Summer Incentives

SEALED THERMAL STORE

Case Study and 700 HP Steam Boilers - Scale

IMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS

Gas Equipment. Volume 4 June/July Issue date: June 25, 2008

INSTALLATION & TECHNICAL MANUAL

Descaler & Prevention

GOLD. User s Information Manual. Water Boiler Series 4

DOMESTIC STEAM GENERATOR Installation Instructions

Incident Summary (Reference # II )

Installers Awareness Booklet. Please read before installation as this booklet contains important Information

Eliminator TotalGuard Installation Manual

User s Operation Instructions & Important Warranty Information

H 2. Hot Water Storage/ Booster Tanks. For Single Tank Installations INSTALLATION, OPERATION & MAINTENANCE MANUAL

Double Door - Dual Zone Wine Cooler

Technical Bulletin 149 Developed with Baxi

User s Operation Instructions & Important Warranty Information. High-efficiency wall-hung boilers Baxi Avanta Heat Only 15h - 18h - 24h - 30h

T UNI 7000 F. Operating instructions For the user (2006/05) AU/GB

AS/NZS :2008

CHAPTER 6. HEATING PRODUCTION EQUIPMENT AND SYSTEMS

Domestic Gas Safety Assessments (DGA) Competency Assessment Certification Scheme for Registered Gas Installers

The NEW advanced electrolytic scale inhibitor with intelligent LED monitoring technology from Sentinel

Eligibility criteria

Stress Corrosion Technical Bulletin

UNIQ HEAT BATTERIES REFERENCE MANUAL_V2.2. Version: 2018_07_19_v2.2

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS.

Clyde Alkon 90. Floor standing condensing boilers. Natural Gas. 90 kw. LP Gas. 90 kw

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

GOLD CGt. User s Information Manual. Natural gas-fired water boiler with tankless heater

Space Saver. New easy guide. Connecting your Space Saver to a central heating system. Issue 001 February 2018 ENGLISH UK IRL SmithsEP.co.

Common central heating problems

Pedestal Range. Installation and user manual. Kiosk. Trafalgar. Tube. Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk

Baxi System 100 HE Plus. User s Operating Instructions. Wall Mounted Powered Flue Condensing Gas Fired Central Heating Boiler

A GUIDE TO THE REGULATORY REFORM ORDER (FIRE SAFETY) 2005 (RRO)

Health and Safety Documents in connection with offshore oil and gas operations

Amptec. Electric flow boiler

robus thinking alternative ENERGY

NT1-P CONDENSATE NEUTRALIZATION TANK WITH PUMP INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

LST Plus Vertical. Plus Vertical 3 models. Lengths: 560mm, 660mm & 760mm. Outputs: 1335 to 1862 watts, 4555 to 6353 Btu/hr

Technical Bulletin. Gazco Riva2 800 & 1050 Gas Fires- Installation and servicing issues resulting in Glass Panel Failure.

Unvented Hot Water Criteria

Technical information. Remeha P 500. Pressurized boiler. Heat output: kw

GASEOUS HYDROGEN SYSTEMS

Avanta 24c - 28c - 35c - 39c 18s - 24s - 30s

Boiler protection kit guide

Space Saver. New Easy Guide. Connecting your Space Saver to a central heating system BEFORE AFTER

For commercial & industrial systems. Large volume dirt collection capacity

Application Bulletin AB170628: Maximizing flow center pump longevity for Geothermal Systems

Hydroflame. Flame-effect fan convectors Installation and User Guide Elite and Classic Models. Contents

Design & Use of Ground Based Pumps Guidance Document

30 VIENNARAIL DESIGN RADIATORS & TOWEL WARMERS VIENNARAIL.

Steam Station IRSG Portable DVD Player

Jetflush 4 Instruction Manual

Unit 2 Fire Safety (Zone 2)

Please take time to carefully read through these guidelines before using your Kamco pump.

INDIRECT WATER HEATERS

REG NO FM BS EN ISO HEADER TANK HEAT EXCHANGER. Installation, Operation & Maintenance Guide

Installation and servicing instructions

Electrical Product Pathfinder Group Electric kettles

Sovereign Double CC/DD

Title: Room-sealed fanned draught flue systems concealed within voids

Please take time to carefully read through these guidelines before using your Kamco pump.

PREVENTING COOKING FIRES

Kamco. Issue: March 2008 Section C FAQ about Power Flushing Page C.1 SECTION C FREQUENTLY ASKED QUESTIONS ABOUT POWER FLUSHING

INSTRUCTION MANUAL (English version) Water still

Installation and Operating Manual for the EcoStar 500 Oil Condensing Floor Standing Range Output Range kw

Please take time to carefully read through these guidelines before using your Kamco pump.

ferroli Boiler Replacement Maxima 35C- Modena HE

LST i PLUS. Safety Series

AFUE 95% Heating Input 50,000 to 200,000 Btuh

Technical Bulletin 008 (Edition 2) CIP-RACL Developed by Industry

HHIC consumer guide to gas boiler servicing

Cistern-fed water heating

USER INSTRUCTIONS & CUSTOMER CARE GUIDE Si II SERIES

Risk Assessment and Control Measures for Household Hot Water Systems

HeatExchangerSpares.com Ltd HRS Heat Exchangers Ltd HRS Hevac Ltd HRS Hevac Engineering Ltd HRS International Ltd HRS Investments Ltd

A guide to the changes of Amendment 1 of BS

Transcription:

Technical Bulletin Developed with Glow-worm Title: Product information and servicing reminder Glow-worm Flexicom boiler range, internal ignition overpressure. Date issued: 22 nd October 2018 Glow-worm has identified a potential issue with excessive ignition overpressure in a very small number of older Flexicom boilers as a consequence of poor system water quality. Glow-worm have issued additional guidance to support the ongoing maintenance and servicing of these appliances. Introduction This Technical Bulletin has been published in conjunction with Glow-worm to provide information for the ongoing service, inspection and maintenance of Flexicom boiler systems. Glow-worm have identified a small number of boilers that have experienced accelerated corrosion in heating systems which have been very poorly treated or not maintained with suitable water treatment chemicals. This has been particularly evident in systems using Flexicom boilers. This accelerated corrosion has led, in a small number of incidents, to excessive ignition overpressure within the appliance combustion case which can damage the appliance casing. Background Glow-worm has become aware that there are a very small number of Flexicom appliances which have been left dormant for an extended period particularly after several years in service, being subject to excessive ignition overpressure, which can cause casing damage. The root cause of these events has been positively traced to the poor system water quality in these systems giving rise to metallic corrosion in the system aluminium or steel dependant on ph levels - and the subsequent release of flammable gas*. This gas finds its way into the boiler and increases the intensity of ignition. These types of events are extremely rare, and have occurred predominantly in those systems left dormant for longer periods of time which allows the corrosion process (and flammable gas) to build up rather than being released over time. In particular, aluminium corrosion can be excessive when the system has a high ph value. Glow-worm recommends a ph of no higher than 8.5 to ensure corrosion of the aluminium heat exchanger cannot occur. *Found to be Hydrogen gas in a number of cases

The ultimate solution to the issue rests with the correct water treatment practices of complete cleansing, flushing and inhibition of the system during commissioning and thereafter, correct maintenance and monitoring of inhibitor levels and ph levels. However, Glow-worm has created a vent kit for those installations that may present specific challenges in ensuring the above criteria is achieved. The vent kit is easily fitted on to the automatic air vent and through the base grommet of the appliance and will ensure any gases will not vent into the appliance. This operation, for those systems that require it, could be completed during normal servicing and inspection activities. Glow-worm Flexicom vent Kit Part Number 0020212869. This kit can be applied to the ranges of appliances as detailed below: Glow-worm Flexicom cx combination boilers Glow-worm Flexicom sx system boilers The guidance contained in this Technical Bulletin only applies to the above model ranges which ceased in production in August 2015. Service and Maintenance Advice Key Issues found with poorly treated systems The main issues found with the poorly treated systems are: The cleansing process has been performed with a chemical cleanser, mobilizing all the system debris, however the flushing out of this mixture has not been properly completed. Consequently this has led to enhanced electrolytic corrosion with mixed metal debris (iron, copper, aluminium) eventually deposited in radiators, pumps and heat exchangers. Any inhibitor added has either been insufficient or ineffective due to the amount of debris in the system. An alkaline water treatment product has been used there are not many of these on the UK market but they are not suitable for aluminium systems (aluminium boilers or radiators) and lead to enhanced aluminium corrosion.

Insufficient inhibitor (or no inhibitor) has been used in the system, leading to low corrosion protection and subsequent electrolytic corrosion. Very high ph levels of the system water caused by one or more of the issues above. High ph levels (above 8.5) are increasingly more corrosive. All of the above issues can lead to the formation of flammable gas from corrosion processes which impairs heating system and boiler performance. Boiler Inspection/servicing When servicing or maintaining a Flexicom appliance, particularly one left dormant for a period of time, it is advisable to remove the outer case front before operating the appliance to let any gases in the water system vent freely into the atmosphere and avoid any potential ignition overpressure event. Key symptoms of gases accumulating in the system are cold radiators and gurgling noises from the system. Also, due to gas formation the system water pressure can increase sometimes enough to open the system pressure relief valve. Key Do s/don ts for Installers servicing and maintaining Flexicom Boilers Do s All Water Treatment products must be suitable for use with aluminium, otherwise accelerated corrosion of the aluminium heat exchanger could occur. It is ESSENTIAL that the system is thoroughly flushed to prevent electrolytic corrosion due to mixed metal debris and flux materials ALL system debris MUST be removed, together with the cleanser before adding inhibitor. This will prevent electrolytic corrosion due to mixed metal debris and flux materials. This will also ensure that the inhibitor is fully effective The ph value of the system water after treatment should be between 6.5 and 8.5. Above 8.5 the system water will be increasingly more corrosive Don ts DO NOT use alkaline water treatment products. Above a ph of 8.5 the system water will be increasingly more corrosive. DO NOT mix water treatment product types to avoid compromising the performance of either. Insufficient or ineffective cleansing or inhibition can lead to accelerated corrosion DO NOT use artificially softened water to fill the central heating system (as BS 14743) Artificially softened water, particularly in higher ph systems can lead to enhanced Aluminium corrosion.

Potential additional Action As a responsible manufacturer Glow-worm want to ensure that our customers have minimal inconvenience and are provided with a quick resolution in the event that a troublesome system is discovered. The system should of course be re-flushed and re-inhibited, but the addition of the vent kit, provided free of charge as a goodwill gesture, can be easily and quickly fitted during servicing. It can also be fitted as a matter of course during servicing to provide peace of mind throughout the lifetime of the boiler Registered businesses and engineers can contact Glow-worm using the contact details below to receive free of charge vent kits when servicing the affected Flexicom boilers. Registered businesses and engineers will be asked to provide the following details relating to the boiler and where it is installed:- First line of the address and postcode of the property Boiler serial number Boiler model name The provision of the vent kit on a free of charge basis applies to the affected Flexicom model ranges only and is a gesture of goodwill from Glow-worm to address system issues and does not relate to the manufacture of the particular boilers. Contact details Registered businesses and engineers should contact Glow-worm using the following hyperlink, which will open up an online Part Request Form:- https://tinyurl.com/y8546gws Regulations, Standards and Codes of Practice guidelines for correct water treatment Technical Guidance Document J - Heat Producing Appliances https://www.housing.gov.ie/sites/default/files/migratedfiles/en/publications/developmentandhousing/buildingstandards/filedownload%2c37240 %2Cen.pdf

Standards available from BSI and NSAI BS 7593 (1) - Code of practice for treatment of water in domestic central heating systems IS 813 (2) - Domestic gas installations (Edition 3) and Amendment 1:2017 BS EN 14743 (3) - Water conditioning equipment inside buildings. Softeners. Requirements for performance, safety and testing BuildCert Chemical Inhibitor Approval Scheme (CIAS) http://www.beama.org.uk/download.cfm/docid/83dc22c1-2fcb-4d80- A663E9BD1277BDA5 BEAMA Code of Practice for Chemical Cleaning and Inhibiting of Domestic Hot Water Central Heating Systems. http://www.beama.org.uk/download.cfm/docid/e2280148-ab02-4e16-b7e1710be610870a Bibliography BS 7593 - Code of practice for treatment of water in domestic central heating systems (2) IS 813 - Domestic gas installations (Edition 3) and Amendment 1:2017 (3) BS EN 14743 - Water conditioning equipment inside buildings. Softeners. Requirements for performance, safety and testing