INVERTER SPLIT - TYPE

Similar documents
ROOM AIR CONDITIONER INSTALLATION MANUAL

SPLIT-TYPE ROOM AIR CONDITIONER

INSTALLATION MANUAL COMFORT...BUILT TO LAST. 9,000, 12,000 and 18,000 BTU SINGLE-ZONE DUCTLESS MINI-SPLIT SYSTEM Heat Pump

Choosing the installation site. Installation. 07 Choosing the installation site

R410A SPLIT SERIES DC INVERTER

INVERTER SPLIT -TYPE ROOM AIR CONDITIONER

INVENTER SPLIT -TYPE ROOM AIR CONDITIONER

SPLIT -TYPE ROOM AIR CONDITIONER

Installation. All about the. of your. Split Type Room Air Conditioner. Refer to Page 2 for table of contents.

SINGLE - ZONE Ductless Split System Heat Pumps Installation, Operation & Maintenance Manual

SPLIT -TYPE ROOM AIR CONDITIONER

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

SPLIT -TYPE ROOM AIR CONDITIONER

SPLIT -TYPE ROOM AIR CONDITIONER

FLOOR-STANDING TYPE AIR CONDITIONER INSTALLATION MANUAL

Air Conditioner Service Manual KSWT SERIES INSTALLATION INSTRUCTION. Wall-mounted Split Type

Inverter Air Conditioner Installation Manual GIN 090/GIN 091 GIN 120/GIN 121 GIN 180/GIN 181 GIN 240/GIN 241

DUCTLESS MINI-SPLIT INSTALLATION MANUAL FOR MODELS: 1PAMSHQCW PAMSHQCW12-15 COMFORT...BUILT TO LAST 12,000 BTU / 15 SEER QUICK CONNECT

QUICK CONNECT INSTALLATION MANUAL DUCTLESS MINI-SPLIT SYSTEM FOR MODELS: 2PAMSHQC12 2PAMSHQC18 2PAMSHQC24 2PAMSHQC36

Installation Manual. WAS / WYS Series. For 9,000-36,000 BTU/hr Systems. Inverter+ and Inverter++ Models

INSTALLATION GUIDE MODEL: ACDC12(B)

Installation Manual. KS Series KS09 KS12 KS18 KS24 KS28. J3387_Kaden_Installer_Manual_ indd 1

R32. Installation Manual Split Type Wall Mounted Air Conditioner. This appliance shall be installed in accordance with: REFRIGERANT

MULTI TYPE ROOM AIR CONDITIONERS INSTALLATION INSTRUCTIONS

Inverter Air Conditioner Installation Manual

- INVERTER SPLIT TYPE ROOM AIR CONDITIONER

FLOOR-STANDING SPLIT TYPE ROOM AIR CONDITIONER

DUCTLESS MINI-SPLIT INSTALLATION MANUAL COMFORT...BUILT TO LAST

Installation Manual SPLIT-TYPE ROOM AIR CONDITIONER

INVERTER SPLIT - TYPE ROOM AIR CONDITIONER

Installation and Operation Manual. SVH Series. Inverter Single Zone Ductless Mini-Split SVH09SA-0 SVH09SA-1 SVH12SA-0 SVH12SA-1 SVH18SA-1 SVH24SA-1

DVC/DVH Series. Inverter Single Zone Ductless Mini-Split A-DVC/DVH 09SF A-DVC/DVH 12SF A-DVC/DVH 18SF A-DVC/DVH 24SF

Installation Instructions

Installation manual. Split Type Room Air Conditioner

Inverter Room Air Conditioner Installation Manual KSV26CRC, KSV26HRC, KSV35CRC, KSV35HRC, KSV53HRC, KSV62HRC, KSV70CRC, KSV70HRC, KSV80HRC

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

Installation Manual Forest Series All Model Numbers

Installation Manual ENE ACDC12. Solar Mini-Split Heat Pump System

Installation Manual. Aurora Series All Model Numbers SPLIT-TYPE ROOM AIR CONDITIONER CS

Inverter Air Conditioner Installation Manual

UltraV Series Outdoor Units

Installation Manual. KSIF Series All Model Numbers SPLIT-TYPE ROOM AIR CONDITIONER

Please read this manual carefully before installation and keep it for future reference. CONTENTS. Installation Manual. DIY Series

INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR CONDITIONER

Installation Manual. SYSPLIT WALL FLEXI Series SPLIT-TYPE ROOM AIR CONDITIONER

Installation Manual. Aurora Series All Model Numbers SPLIT-TYPE ROOM AIR CONDITIONER

Split Air Conditioner

AOYG18LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL. For authorized service personnel only. PART NO

Installation Instructions

INSTALLATION MANUAL SPLIT TYPE ROOM AIR CONDITIONER (PART NO )

Installation Instructions

Installation Manual INVERTER ONE-TWO/ONE-THREE /ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR CONDITIONER

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS

Installation Instructions

KFTC Series 18,000 to 48,000 Btu/h Cooling Only & Heat Pump INSTALLATION MANUAL

Installation Manual. Oasis Series All Model Numbers SPLIT-TYPE ROOM AIR CONDITIONER CS

Installation Instructions

R32 INSTALLATION MANUAL ENGLISH AIR CONDITIONER (SPLIT TYPE) Indoor unit RAS-10PKVPG-E RAS-13PKVPG-E RAS-16PKVPG-E

Fixed Speed Split Room Air Conditioner Installation Manual KSE26CRC, KSE26HRC, KSE35CRC, KSE35HRC, KSE53HRC, KSE62HRC, KSE70CRC, KSE70HRC, KSE88CRC

MXZ-4B80VA MXZ-5B100VA INSTALLATION MANUAL

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

OWNER S AND INSTALLATION MANUAL RAV-480FS2B/RAV-480AS2B RAV-600FS8B/RAV-600AS8B

INSTALLATION INSTRUCTIONS

1. BEFORE INSTALLATION

Service Manual. Air Conditional

Air Conditioner. user installation & manual manual. imagine the possibilities

Installation Manual. Forest Series All Model Numbers SPLIT-TYPE ROOM AIR CONDITIONER

Table of Contents. Installation Manual. Accessories Safety Precautions Installation Overview Installation Diagram.

Installation Manual. All Model Numbers SERIES SPLIT-TYPE ROOM AIR CONDITIONER

DLCMRA. INSTALLATION INSTRUCTIONS Multi zone Outdoor Unit Ductless System Sizes 18, 27, 36 and 48 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

Installation and Operation Manual. CMA12SB-0 Series. Horizontal/Side Discharge Condensing Units

1. BEFORE INSTALLATION

Installation Manual PMV Kit RBM-PMV0363E RBM-PMV0903E

Installation Instructions

DAIKIN AIR CONDITIONER

Installation Instructions

SPLIT WALL-MOUNTED AIR CONDITIONER

LG Room Air Conditioner INSTALLATION MANUAL

AIR CONDITIONER INSTALLATION MANUAL

1. BEFORE INSTALLATION

Ductless Split Air Conditioner

0RGHOV,QGRRU 8QLW MWM36Y3J 2XWGRRU 8QLW MRM36Y3J 11

Installation manual for room air conditioner

FLEX MULTI SPLIT DUAL ZONE & TRI-ZONE INSTALLATION INSTRUCTIONS

Split Air Conditioner

INSTALLATION INSTRUCTIONS

1. BEFORE INSTALLATION

INSTALLATION MANUAL. R22 Split Series. Models FTY25GXV1 FTY35GXV1. Installation manual R22 Split series

R32 AIR CONDITIONER HIGH WALL MOUNTED INSTALLATION MANUAL. English DC INVERTER IMPORTANT NOTE: Indoor unit high wall mounted HRD

[FLARE CONNECTION TYPE] ATTENTION

LG Room Air Conditioner

Wall Air Handler Ductless Split System Heat Pumps Installation, Operation & Maintenance Manual

1. BEFORE INSTALLATION

Installation Instructions

Split Air Conditioner. Model: WMI09MH16S WMI12MH16S WMI18MH16S

LG Room Air Conditioner

AS09HPAN AS12HPAN. Split-type Air Conditioner (Cooling and Heating)

FLOOR TYPE AIR CONDITIONERS

Installation Instructions

Transcription:

INVERTER SPLIT - TYPE ISSUE No 2 DATE 04/09/08 P/No 2020323A2868

CONTENTS SAFETY PRECAUTIONS Warning 2 Operating temperature 2 BEFORE INSTALLATION Tools needed for installation 3 Items required for installing the unit 3 Typical installation4 INSTALLATION Installation 5 REFRIGERANT PIPE CONNECTION Refrigerant pipe connection 10 ELECTRICAL WORK Connecting the cable to the indoor unit 17 Connecting the cable to the outdoor unit 18 CHECKING THE DRAINAGE AND FORMING THE PIPING Checking the drainage 19 Forming the piping 19 AIR PURGING Air purging 20 Satety and leakage check 22 TEST RUNNING Test running 22 Read This Manual Inside you will find many helpful hints on how to install and test the air conditioner properly! CAUTION Contact an authorised service technician for repair or maintenance of this unit Contact an authorised installer for installation of this unit The air conditioner is not intended for use by young children or infirmed persons without supervision Young children should be supervised to ensure that they do not play with the air conditioner If the power cord is to be replaced, replacement work shall be performed by authorised personnel only Installation work must be performed in accordance with the national wiring Standards by authorised personnel only Take care not to catch fingers on the fan when adjusting vertical louvres This air conditioner may use R22, R407C or R410A refrigerant (Confirmed before installation) IMPORTANNT NOTES 1

SAFETY PRECAUTIONS! OPERATING TEMPERATURE 50 27 34-15 2

BEFORE INSTALLATION Tools needed for installation 65 Items required for installing the unit Clip Anchor Seal (See page 10 for details) (See page 10 for details) Insulation materials Cable Tie (5~10) 160mm 3

BEFORE INSTALLATION Typical installation Self-tapping Screw A 3 2 Clip Anchor 15cm above 1 Installation Plate 12cm above 12cm above Air Filter Mole than 17m Less than 23m 6 Connecting pipe Assembly A 10cm above Air Outlet 60cm above 20cm above B 100cm above 60cm above C Loop the connective cable (If applicable) 4

INSTALLATION Installation Read completely then follow step by step Indoor unit Fig1 Outdoor unit 2 2 Fig2 Rooftop installatiom 5

INSTALLATION Piping length elevation 8 20 15 8 20 15 18 8 20 15 21 5/8 3/8 160mm 953mm 10 25 40 24 5/8 3/8 160mm 953mm 10 25 40 28 5/8 3/8 160mm 953mm 10 25 40 Capacity is based on standard length and maximum allowance length is on the basis of reliability Oil trap should be installed every 5~7 metres When the connecting pipe is longer than 5 metres, additional refrigerant should be added into the unit according to the above table through the service port on the LO valve on outdoor unit Fig3 Indoor unit installation 1 Fit the Installation Plate 1) Fit the installation plate horizontally on structural parts of the wall with spaces around the installation plate 2) If the wall is made of brick, concrete or the like, drill eight (8) 5mm diameter holes in the wall Insert Clip anchor for appropriate mounting screws 3) Fit the installation plate on the wall with eight (8) type A screws Correct orientation of Installation Plate Fig4 Note Fit the Installation Plate and drill holes in the wall according to the wall structure and corresponding mounting points on the installation plate (Dimensions are in mm unless otherwise stated) 6

50 50 INSTALLATION Indoor unit outline 150mm or more to ceiling Installation plate 120mm or more to wall 45 90 B 120mm or more to wall Left rear side refrigerant pipe hole 65 40 A 40 7,000 & 9,000Btu/h model (A 710, B 250) 12000Btu/h model (A 790, B 265) Indoor unit outline 150mm or more to ceiling Installation plate Right rear side refrigerant pipe hole 65 120mm or more to wall 305 45 90 120mm or more to wall Left rear side refrigerant pipe hole 65 45 850 45 Right rear side refrigerant pipe hole 65 18,000Btu/h model Hooked Part 150mm or more from the ceiling 998 Fig s 5 380 380 67 120mm or more from the wall 322 65 130 130 22 65 120mm or more from the wall 178 Indoor Unit Outline 21,000 & 24,000 Btu/h models Above 150 from the ceiling Fig5 Hooked Part Hooker Part 1250 815 257 Above 120 from the wall 95 95 325 Above 120 from the wall 55 Pipe hole 58 55 Indoor unit outline 55 Pipe hole 28,000Btu/h model Wall 2 Drill a hole in the wall 1 Determine hole positions according to the diagram detailed in Fig5 Drill one (1) hole ( 65mm) slanting slightly to outdoor side 2 Always use wall hole conduit when drilling metal grid, metal plate or the like Indoor Outdoor 5-7mm Fig6 7

43 INSTALLATION 3 Connecting Pipe and Drainage Installation 1 Run the drain hose sloping downward Do not install the drain hose as illustrated below Do not block water flow with a rise Do not put the end of the drain hose into water Connecting pipe Fig7 2 When connecting an extension drain hose, insulate the connecting part of the extension drain hose with a shield pipe, do not let the drain hose become slack 1 For the left-hand and right-hand piping, remove the pipe cover from the side panel 2 For the rear-right-hand and rear-left-hand piping, install the piping as shown Bend the connecting pipe to be laid at a height of 43mm or less from the wall 3 Fix the end of the connecting pipe (Refer to Tightening Connection in REFRIGERANT PIPING CONNECTION) Right-hand piping Rear-right piping Indoor unit outline Connecting pipe Side Part cover Left-hand piping Rear-left piping Fig9 Fig8 4 Indoor unit installation 1 Pass the piping through the hole in the wall 2 Put the upper claw at the back of the indoor unit on the upper hook of the installation plate, move the indoor unit from side to side to see that it is securely hooked 3 Piping can easily be made by lifting the indoor unit with a cushioning material between the indoor unit and the wall Remove cushioning material after finish piping 4 Push the lower part of the indoor unit up on the wall, Then move the indoor unit from side to side, up and down to check if it is hooked securely Fig10 Upper Hook Lower Hook Cushioning material 8

INSTALLATION 5 Piping and wrapping Bundle the tubing, connecting cable, and drain hose with tape securely and evenly as shown in Fig11 Because the condensed water from rear of the indoor unit is gathered in ponding box and is piped out of room Do not put anything else in this box Drain hose Indoor unit Connecting cable Fig11 Ponding box Pipe room Connecting pipe Wrapping belt CAUTION Connect the indoor unit first, then the outdoor unit Do not allow the piping to be exposed out from the back of the indoor unit Be careful not to let the drain hose become slack Heat insulate the connecting piping Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause drain pan to overflow inside the unit Never cross connect or inter wind the power wire with any other wiring Run the drain hose sloped downward to drain out the condensed water smoothly Outdoor unit installation Outdoor unit installation precautions Install the outdoor unit on a rigid base to prevent noise and vibration Select the air outlet direction so that discharged air is not blocked In the case where the installation location is exposed to strong winds, make sure the fan operates properly by putting the unit lengthwise along the wall or by using a shield to minimise wind exposure Especially in windy areas, install the unit to minimise exposure to wind For suspended installations, the installation bracket should follow with technique requirement in the installation bracket diagram The installation wall should be solid brick, concrete or of same construction, or reinforced to minimise movement or vibration The connection between the wall bracket and the air conditioner should be firm, stable and reliable Ensure there lare no obstacles which block flow air Strong wind Fig12 9

B REFRIGERANT PIPE CONNECTION Securing of outdoor unit Anchor the outdoor unit with a bolt and nut 10 or 8 tightly and horizontally on a concrete or rigid mount Model A(mm) B(mm) Air inlet A Air inlet 18000Btu/h 530 290 21000Btu/h 24000Btu/h 560 335 590 333 Fig13 Air outlet Drain joint installation If a drain elbow is used, the unit should be placed on a stand which is taller than 3cm If the unit is used in an area where temperature O falls below 0 C for 2 or 3 days in succession, it is recommended not to use a drain elbow, as the drain water may freeze and the fan will not rotate Fit the seal into the drain elbow, then insert the drain joint into the base pan hole of the outdoor unit, rotate 90 to secure Connect the drain joint with an extension drain hose (Locally purchased), in instances where you need to drain condensed water away from the unit Seal Drain joint Base pan hole of outdoor unit Fig14 Seal Drain pipe Refrigerant pipe connection 1 Flaring work Main cause for refrigerant leakage is due to defects in the flaring work Carry out correct flaring work using the following procedure A Cut the pipes and the cable 1 Use the piping kit accessory (if applicable) or pipes purchased locally 2 Measure the distance between the indoor and the outdoor unit 3 Cut the pipes a little longer than the measured distance 4 Cut the cable 15m longer than the pipe length 90 C Oblique Roughness Burr Fig15 Pipe Reamer B Burr removal 1 Completely remove all burrs from the cut cross section of pipe/tube 2 Face the end of the copper pipe/tube in a downward direction as you remove burrs in order to avoid burrs dropping into the tubing Face down Fig16 10

REFRIGERANT PIPE CONNECTION C Putting flare nut on Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal (Note It is not possible to put them on after flaring work) Copper tube Flare nut D Flaring work Carry out flaring work using flaring tool as shown below Firmly hold copper pipe in a die according to the dimension shown in the table below Outer diam (mm) Max A(mm) Min 635 13 07 953 16 10 127 18 10 160 24 22 Bar "A" Fig17 Bar Copper pipe Clamp handle Fig18 Handle Yoke Cone Red arrow mark Tightening Connection Align the center of the pipes Sufficiently tighten the flare nut with fingers, and then tighten it with a spanner and torque wrench as shown Caution Excessive torque can break nut depending on installation conditions Indoor unit tubing Flare nut Pipings Outer diam 635 953 Fig19 Tightening Additional tightening torque (Kgm) torque (Kgm) 16 20 30 35 127 160 50 55 75 80 11

REFRIGERANT PIPE CONNECTION E Check Smooth all round Improper flaring Even length all round Connetion of pipes - Indoor Tubing retainer For Rear Right Piping Rear right Front Rear left Connecting cable Drain hose Piping 12

REFRIGERANT PIPE CONNECTION Insert the piping, drain hose and the connecting cable into the piping hole Tubing retainer Connecting cable 13

REFRIGERANT PIPE CONNECTION For Rear Left Piping Tubing retainer 14

REFRIGERANT PIPE CONNECTION 15

REFRIGERANT PIPE CONNECTION Tubing retainer Connecting cable Connection of pipes - outdoor 75 8 16

ELECTRICAL WORK Connect the cable to the indoor unit Terminal block of indoor unit L N S 1 2(N) S all models according to diagram Cord clamp To outdoor unit 9000Btu/h model 12000Btu/h model 18000Btu/h model Front Panel To outdoor unit 21000Btu/h model 24000Btu/h model 28000Btu/h model Code wire 10mm 40mm The supply voltage must be consistent with Electrical box the rate voltage of the air conditioner cover Connect the cable to the indoor unit NOTE Before performing any electrical work, turn off the main power to the system 10A 10 18 16A 15 21 16A 15 6 24 16A 15 28 20A 25 17

ELECTRICAL WORK Connect the cable to the outdoor unit 7 Wire connector of outdoor unit L N S 10mm 40mm Wire -holding board 18

CHECKING THE DRAINAGE AND FORMING THE PIPING Checking the drainage Downward slope Do not raise Accumulated drain water Air Tip of drain hose dipped in water Less than 50mm gap Water leakage Water leakage Water leakage Ditch Forming the piping B 19

AIR PURGING C Air purging Air and moisture in the refrigerant system have undesirable effects as indicated below Pressure in the system rises Operating current rises Cooling or heating efficiency drops Moisture in the refrigerant circuit may freeze and block capillary tubing Water may lead to corrosion of parts in the refrigeration system Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system Air purging with vacuum pump Preparation Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed Remove the service valve caps from both the gas and the liquid side on the outdoor unit Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage Pipe length and refrigerant amount Connecting pipe length Less than 5m Air purging method Use vacuum pump Additional amount of refrigerant to be charged More than 5m Use vacuum pump 9K - 18K Models (Pipe length-5) x 15g/m 21K - 28K Models (Pipe length-5) x 40g/m 20

AIR PURGING When relocate the unit to another place, perform evacuation using vacuum pump Make sure the refrigerant added into the air conditioner is in liquid form in any case (Not applicable to units that use freon R22 ) Caution in handling the packed valve Open the valve stem until it hits against the stopper Do not try to open it further Securely tighten the valve stem cap with a spanner or the like Valve stem cap tightening torque (See Tightening torque table on page 16 ) Outdoor unit A B Packed valve Refrigerant Fig22 Gas side Liquid side Indoor unit C D Half union Flare nut Stopper Cap Valve body Valve stem Fig23 When Using the Vacuum Pump (For method of using a manifold valve, refer to its operation manual) 1 Completely tighten the flare nuts, A, B, C, D, connect the manifold valve charge hose to a charge port of the low-pressure valve on the gas pipe side 2 Connect the charge hose connection to the vacuum pump 3 Fully open the handle Lo of the manifold valve 4 Operate the vacuum pump to evacuate After starting evacuation, slightly loose the flare nut of the Lo valve on the gas pipe side and check that the air is entering (Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus) 5 After the evacuation is complete, fully close the Manifold valve Compound meter Pressure gauge handle Lo of the manifold valve and stop the operation of the vacuum pump -76cmHg Make evacuation for 15 minutes or more and Handle Lo Handle Hi check that the compound meter indicates 5 Charge hose Charge hose -76cmHg (-1 x 10 Pa) o 6 Turn the stem of the packed valve B about 45 counterclockwise for 6~7 seconds after the gas coming out, then tighten the flare nut again Make sure the pressure display in the pressure indicator Low pressure valve is a little higher than the atmosphere pressure Fig24 7 Remove the charge hose from the Low pressure charge hose 8 Fully open the packed valve stems B and A 9 Securely tighten the cap of the packed valve Vacuum pump 21

TEST RUNNING Safety and leakage check Electrical safety check Perform the electric safe check after completing installation 1 Grounding work After finishing grounding work, measure the grounding resistance by visual detection and grounding resistance tester 2 Electrical leakage check (performing during test running) During test operation after finishing installation, the service person can use the electroprobe and multimeter to perform the electrical leakage check Turn off the unit immediately if leakage happens Check and find out the solution ways till the unit operate properly Gas leak check 1 Soap water method Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of th piping If bubbles come out, the pipes have leakage 2 Leak detector Use the leak detector to check for leakage CAUTION Indoor unit check point Cover Outdoor unit check point D B C A A Lo packed valve B Hi packed valve C and D are ends of indoor unit connection Fig25 Test running Perform test operation after completing gas leak check at the flare nut connections and electrical safety check Check that all tubing and wiring have been properly connected Check that the gas and liquid side service valves are fully open Connect the power, press the ON/OFF button on the remote controller to turn the unit on Use the MODE button to select COOL, HEAT, AUTO and FAN to check if all the functions work well O When the ambient temperature is too low (lower than 17 C), the unit cannot be controlled by the remote controller to run at cooling mode, manual operation can be taken Manual operation is used only when the remote controller is disable or maintenance is necessary Hold the panel sides and lift the panel up to an angle until it remains fixed is a clicking sound Press the Manual control button to select the AUTO or COOL, the unit will operate under Forced AUTO or COOL mode (see User Manual for details) The test operation should last about 30 minutes Manual control button AUTO/COOL 22

Rated Capacity Test (Cooling mode) Under Cooling Mode, set the air conditioner at High Fan Speed and set the temperature to 17 C, then press the TURBO button 6 times within 10 seconds (be sure the indoor unit buzzes 6 times) The system will enter Rated Capacity Test mode The buzzer will keep on sounding for 2 seconds when the fan speed reaches rating speed and the compressor rotates at rating speed The air conditioner can enter the Rated Capacity Test mode only when all the above conditions are met This mode will automatically de-activate after 5 hours During the Rated Capacity Test mode, if common protection, ambient temperature limitation for start-up and rotation frequency or de-frost protection occurs, the test must be stopped Rated Capacity Test (Heating mode) Under Heating Mode, set the air conditioner at High Fan Speed and set the temperature to 30 C, then press the TURBO button 6 times within 10 seconds (be sure the indoor unit buzzes 6 times) The system will enter Rated Capacity Test mode The buzzer will keep on sounding for 2 seconds when the fan speed reaches rating speed and the compressor rotates at rating speed The air conditioner can enter the Rated Capacity Test mode only when all the above conditions are met This mode will automatically de-activate after 5 hours During the Rated Capacity Test mode, if common protection, ambient temperature limitation for start-up and rotation frequency or de-frost protection occurs, the test must be stopped 23