EXPERIMENTAL STUDY ON THE LOOP HEAT PIPE OPERATING UNDER HORIZONTAL ORIENTATION

Similar documents
EXPLORING POSSIBILITIES WITH THE DEVELOPMENT OF THE LOOP HEAT PIPE TECHNOLOGY. Roger R. Riehl

EVALUATING LOOP HEAT PIPE PERFORMANCE IMPROVEMENT USING CIRCUMFERENTIAL GROOVES. Nadjara dos Santos, Roger R. Riehl

MINIATURE HEAT TRANSPORT SYSTEMS WITH LOOP HEAT PIPES

Design of Miniature Loop Heat Pipe

Temperature Oscillation of mlhp with Flat Evaporator

Experimental study of hybrid loop heat pipe using pump assistance for high heat flux system

Development of the Micro Capillary Pumped Loop for Electronic Cooling

Thermal Performance of a Loop Thermosyphon

COOLING OF DESKTOP COMPUTER USING HEAT PIPES

Experimental Investigation on the Effection of Flow Regulator in a Multiple Evaporators/Condensers Loop Heat Pipe with Plastic Porous Structure

Experimental Study on Waste Heat Recovery from the Pyrolysis Stack using Heat Pipe

IJIRST International Journal for Innovative Research in Science & Technology Volume 1 Issue 12 May 2015 ISSN (online):

Loop Heat Pipe Wick Fabrication via Additive Manufacturing

Experimental Analysis on Effect of Design Parameters on the Performance of Single Loop Pulsating Heat Pipe

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES

How Wicks and Orientation

Heat Transfer in Evacuated Tubular Solar Collectors

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

0Effect of Fin on the Performance Characteristics of Close and Open Loop Pulsating Heat Pipe

THERMAL ANALYSIS AND FLOW VISUALIZATION OF A FLAT LOOP HEAT PIPE

15. Heat Pipes in Electronics (1)

Thermal Performances of Loop Heat Pipe with Hybrid Wick Structures in Evaporator

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

SCIENCE CHINA Technological Sciences

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

INVESTIGATION OF HEAT TRANSFER IN EVAPORATOR OF

VISUAL STUDY ON TWO-PHASE FLOW IN A HORIZONTAL CLOSED-LOOP OSCILLATING HEAT PIPE , Thailand , Thailand

FABRICATING A HEAT PIPE STRUCTURE WITHIN A RADIATING PLATE FOR ELECTRONICS FAN-LESS COOLING

DEVELOPMENT OF HEAT PIPE LOOP TECHNOLOGY FOR MILITARY VEHICLE ELECTRONICS COOLING

High Temperature Water-Titanium Heat Pipes for Spacecraft Fission Power

HEAT PIPES

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

DESIGN AND ANLYSIS OF MODIFIED HYBRID SOLAR SYSTEM USING NANO FLUIDS

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Passive cooling of telecommunication outdoor cabinets for mobile base station

Effect of Inclination Angle in Heat Pipe Performance Using Copper Nanofluid

Numerical study of heat pipe application in heat recovery systems

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

American International Journal of Research in Science, Technology, Engineering & Mathematics

Effect of Inclination Angle on Performance Limit of a Closed-End Oscillating Heat Pipe

Global Journal of Engineering Science and Research Management

Local Heat Transfer Characteristics of the R1234ze(E) Two Phase Flow Inside a Plate Heat Exchanger

Experimentation of Heat Pipe Used In Nano-Fluids

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

COOLING SYSTEM FOR HERMETIC COMPRESSOR BASED ON THE LOOP THERMOSYPHON

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

The Way We Were and Are Going on Cooling High Power Processors in the Industries

Development of Small-diameter Tube Heat Exchanger: Circuit Design and Performance Simulation

Performance Analysis of Heat Pipe using Different Screen Mesh Sizes Manikandan.K * 1, Senthilkumar.R 2,

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Heat transport capability and compensation chamber influence in loop heat pipes performance

Pool boiling heat transfer enhancement on porous surface tube

SOLAR WATER DISTILLATION BY USING WATER IN THE INNER GLASS EVACUATED TUBES

Thermal Control of High-Powered Desktop and Laptop Microprocessors Using Two-Phase and Single-Phase Loop Cooling Systems

Adsorption refrigeration system using waste heat

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

Internal flow Patterns of the Horizontal Heat Mode Closed-Loop Oscillating Heat Pipe with Check Valves (HHMCLOHP/CV)

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

EXPERIMENTAL STUDY OF DUAL EVAPORATOR LHP WITH TWO COMPENSATION CHAMBERS

Sodium Heat Pipes for Spacecraft Fission Power Generation

APPLICATION OF MINI HEAT PIPES FOR THERMAL MANAGEMENT OF OPTO-ELECTRONIC INSTRUMENTS

Experimental Study on Thermal Behavior of a Stainless Steel-Di Water Flat Plate Heat Pipe

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Performance Study of Solar Heat Pipe with Different Working Fluids and Fill Ratios

Experimental Investigation of Two Phase Closed Thermosyphon Using Propylene Glycol As A Working Fluid

Reducing the Temperature of Machining Tool by using Heat Pipe

Effect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

Compression of Fins pipe and simple Heat pipe Using CFD

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

LAMINATION AND CHARACTERIZATION OF A POLYETHYLENETEREPHTHALATE FLEXIBLE MICRO HEAT PIPE

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

NOVEL COMPACT SORPTION GENERATORS FOR HEAT PUMP APPLICATIONS

Research Article / Araştırma Makalesi EXPERIMENTAL INVESTIGATION OF R600A REFRIGERANT FLOW INSIDE ADIABATIC CAPILLARY TUBE

PERFORMANCE OF WATER FILLED THERMOSYPHONS BETWEEN OC

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Heat sinks for electronic cooling applications

Experimental study on a hybrid loop heat pipe

Characterization of a Heat Sink with Embedded Heat Pipe with Variable Heat Dissipating Source Placement for Power Electronics Applications

Operation of a Two-Phase Reverse Loop Thermosyphon

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

Measurement of internal pressure and thermal performance in a closed-loop oscillating heat-pipe with check valves (CLOHP/CV)

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

Small Scale Pilot Plant Thermal Dryer for Sewage Sludge Dewatering System A Preliminary Study

Flow Boiling of R245fa in a Microgap with Integrated Staggered Pin Fins

EXPERIMENTAL AND THEORTICAL STUDY OF THE THERMAL PERFORMANCE OF HEAT PIPE HEAT EXCHANGER

Operating Characteristics of Multiple Evaporators and Multiple Condensers Loop Heat Pipe with Polytetrafluoroethylene Wicks

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Development of a Dilution Refrigerator for Low-Temperature Microgravity Experiments

DEEPAK PALIWAL, S.P.S.RAJPUT

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

This is a repository copy of Development of cryogenic loop heat pipes: A review and comparative analysis.

Transcription:

Proceedings of the International Conference on Mechanical Engineering and Renewable Energy 2017 (ICMERE2017) 18 20 December, 2017, Chittagong, Bangladesh ICMERE2017-PI-350 EXPERIMENTAL STUDY ON THE LOOP HEAT PIPE OPERATING UNDER HORIZONTAL ORIENTATION A.R. Tuhin 1, Phuoc Hien Huynh 2, Kyaw Zin Htoo 2, Keishi Kariya 3 and Akio Miyara 3 1 Exchange student, Graduate School of Science and Engineering, Saga University, 1 Honjo-machi, Saga,840-8502, Japan and Student, Department of Mechanical Engineering, Chittagong University of Engineering & Technology, Bangladesh. 2 Graduate School of Science and Engineering, Saga University, 1 Honjo-machi, Saga,840-8502, Japan. 3 Department of Mechanical Engineering, Saga University, 1 Honjo-machi, Saga, 840-8502, Japan. metuhin12@gmail.com *, hphien@hcmut.edu.vn, kyawzinhtoo1992@gmail.com, kariya@me.saga-u.ac.jp and miyara@me.saga-u.ac.jp Abstract Nowadays, Loop heat pipe (LHP), a passive two-phase heat transfer device, has been paid more attention for applying in the modern cooling electronics system. In this study, a LHP with flat-rectangular evaporator is fabricated and investigated thermal performance under horizontal orientation in two different cases that vary in length of vapor, liquid, and condenser lines. Water is selected as working fluid while sintered stainless steel wick is capillary structure of the LHP. The results show that the LHP with shorter lines operates better than the longer one and can keep the heater surface temperature smaller than 85 o C when the heat load is at 80 W. Keywords: Loop heat pipe, Electronics cooling, Capillary force, Phase change. 1. INTRODUCTION Heat pipe (HP) has been applying successfully and become the state of commercialization in the electronics cooling field. However, during the past decades, the electronics such as the processors, microprocessors changed enormously with the miniaturized tendency. For instance, it is predicted that the number of element per 1 cm 2 can reach 20 billion in 2020 [1]. It is sure that this tendency will offers the new challenges such as heat transport capacity, operation heat flux to the present HP cooling systems. At this moment, LHP, a novel catalogue of HP, can be considered as one of promising solutions that can face with the above challenge. Although both LHP and HP operates base upon phase changing processes and utilizes the capillary or gravity force to maintain the circulation of working fluid, there are some different points between normal HP and LHP. Firstly, in LHP evaporating vapor and condensed liquid flows in two separated pipes, so it can avoid the occurrence of entrainment or flooding limitation that prevents condensed liquid from returning evaporator. Another point is the location of the wick. While the wick body covers almost the length of normal HP, it exists only inside LHP s evaporator with the thickness smaller than 1cm. Obviously, the pressure drop through the wick can be reduced, so LHP can transport heat through the further distance than conventional HP. In addition, fine pore wick such as sintered wick is often selected in the LHP to create higher capillary force for operating under various orientations such as horizontal, adverse as well as favorable gravity condition. In summary, comparing to normal HP, LHP has more flexible characteristics, higher heat transport capacity and further heat transfer distance ability. Even though there are numerous studies on LHP, but almost all of them focused on the cylindrical LHP which is suitable for extraterrestrial applications. On the contrary, in the electronics cooling field on the earth, the flat-shaped evaporator possesses more benefits such as lighter weight, simple assembly, smaller thermal contact resistance due to the absence of thermal adapter between the HP and electronic devices. Despite the above advantages, the number of research on these LHPs has just begun to expand for ten years ago due to the complexity fabrication. For instance, in 2007 Randeep Singh et al [2] conducted a research on investigating the performance of miniature LHP with flat disk shape evaporator. Under the horizontal condition, their LHP can keep evaporator temperature below 100±5 o C when working in the 5 W to 70 W range of heat load. Besides, they also conducted another study for investigating the effect of wick characteristics on the LHP s performance [3]. Evaporator with copper wick performs better than one with nickel wick; however, it also causes the larger heat leak from evaporator to compensation chambers. Moreover, for reducing the thickness of LHP, there are some research groups such as S. Wang et al [4], S. Becker et al [5], Yu. Maydanik et al [6], etc who conducted study on LHP with flat-oval evaporator. This group of LHP is classified into the ELR (Evaporator with Longitudinal Replenishment) branches which compensation chamber is located aside active zone. Almost ELR LHP is thinner than 10mm; however, it requires complex fabrication procedure as well as easy to be deformed at high pressure operation.

In this study, a LHP with flat rectangular evaporator is fabricated and investigated heat transfer characteristic under horizontal condition. Sintered stainless steel wick is used in this experiment. Water is selected as working fluid due to low pressure operation and good compatibility characteristics with copper. As shown in Fig. 1, a system of fins or crossing grooves is fabricated on the evaporator surface to sure not only heat transfer from heater to the wick but also creating the paths for vapor flow out sufficiently. Thermal performance of LHP is investigated when LHP works at different heat load in the two cases which connection lines, which include vapor and liquid line, and condenser are different in length. Fig.2: Schematic diagram of experiment Fig.1: Evaporator with sintered stainless-steel wick 2. EXPERIMENT DESCRIPTION 2.1 Experimental setup and apparatuses Figure.2 demonstrates the experimental schematic diagram. The LHP is profiled as a loop that includes evaporator, vapor line, condenser, and liquid line connecting respectively together. The evaporator is heated by the copper heating block which four cartridge heaters are inserted inside. To cut down thermal contact resistance, a thin layer of thermal conductivity grease is filled between top surface of heating block and bottom surface of evaporator. The YAMABISHI MVS 520 Volt slider is used for converting the AC into DC source and adjusting amount of heat power input while magnitude is monitored on the YOKOGAWA WT230 digital power meter. In this experiment, condenser is cooled by water which circulate between condenser and ADVANTEC LV 400 constant temperature circulator. As shown in Fig. 3, three 0.5mm diameter K type T 1, T 2, T 3 are installed into the heating block to calculate the heat flux and temperature at the top surface of heating block T s1. On the other hand, temperature from 1mm diameter K type thermocouple T 4 can be used to estimate the temperature at bottom surface of evaporator. In addition, temperatures at evaporator outlet, condenser outlet as well as compensation chamber inlet are measured by three K type thermocouples T eo, T co and T cci inserted directly on the path of working fluid. The mass flow rate and the temperature difference of cooling water when flowing through condenser are measured by the MASSMAX MMM7150K mass flow meters and two K type thermocouples T wa-i, T wa-o respectively. Another thermocouple T a measures the surrounding air temperature. Except for T a, thermocouples are calibrated to sure that error is smaller than ±0.05 C. All measuring data is collected automatically by using Keithley 2071 Data Acquisition System which interfaces with PC by Exelink software. Table 1 shows LHP s parameters in detail. Fig.3: Positions of thermocouples inside heating block and base body of evaporator Table 1: Main parameters of LHP in experiment Evaporator Material Copper 80 Width, mm 70 Height, mm 25 Active area, mm 2 60 x 45 Fin geometry Cross area, mm 2 2 x 2 Height, mm 1.5 Fin pitch, mm 4 Wick Structure Material Stainless steel Pore radius, μm 63 Porosity, % 36 48 Bulk volume, mm 3 50 x 41 x 5 Vapor line 700 450 Condenser 600 300 Liquid line Working fluid 1300 3.2/1.7 Water 950 3.2/1.7 2.2 Experimental condition The insulation of the heating block, evaporator, vapor

T [ C] T [ C] line and condenser section are conducted carefully to eliminate the heat loss from heater as well as influence of environment on the result. During experiment period, room temperature is kept stably around 25 o C. The constant temperature circulator maintains the inlet temperature T wa-i and mass flow rate of cooling water at value of 28.5 o C, 30 kg/h respectively. The heat power input is increased until the T 4 reaches 100 o C. Besides, to guarantee vacuum condition as well as proper amount of working fluid charged in LHP, the charging system consisting liquid tank, glass level indicator and stop valve as shown in Fig.4 was established, and the charging procedure was conducted carefully as following steps. Fig.4: Connection between charging system (red rectangular) and LHP Firstly, both of LHP and charging system was vacuumed to remove all non-condensing gases. Then, water was charged into charging system while LHP was disconnected by the stop valve. During this process, vacuum condition of charging system was lost; hence, it is necessary to vacuum the charging system again. Finally, the open the stop valve connecting between charging system and the LHP for water flowing into the LHP. The amount of charging water was determined from glass level indicator. Moreover, before charged into charging system, the purified water was also boiled to reduce the concentration of dissolve gases inside its volume. 2.3 Data reduction Heat flux and heat flow rate flowing through the heating surface to active area of evaporator q = k T 1 T 2 = k T 2 T 1 Heater surface temperature T s1 = k T 1 T 3 2 (1) Q = qa (2) T s1 = T 1 3 q k (3) This temperature is considered as electronics temperature. With different electronic devices, the limits of this temperature are different. From [7], this value is often recommended to be at 85 o C for reliable and effective operation of electronics such as microprocessors, processers. Total thermal resistance R t R t = T s1 T wa i Q (4) 3. RESULT AND DISCUSSION 3.1 Heat transfer capacity From the experimental results, difference in length of connection lines and condenser varies the heat transfer capacity of LHP. With the condition that T 4, temperature at the base body of evaporator, is lower than 100 o C, the LHP with the shorter lines can work until heat load reaches 95 W while the longer one can transfer only 50 W from heater to the heat sink. The LHP can operate if the capillary condition described in Eq (5) is satisfied. The component Δp v is the pressure drop relating to vapor phase that happens in vapor grooves, vapor line, and condenser. The Δp l is the pressure drop when liquid flows through liquid line and wick structure. Opposite to conventional HP, in LHP the Δp v is more dominated than the Δp l. This explains why the vapor line and condenser become longer, despite the better cooling condition at condenser, it also contributes to the increment of total pressure drop, causes the capillary limitation happens and reduces heat transfer capacity of LHP. p c = 2σ r > p v + p l (5) 3.2 Ts1 and temperatures at different positions inside LHP change with heat load Q 110 90 70 50 30 10 30 35 40 Q [W] 45 50 55 T_s1 T s1 [ C] T_eo T eo [ C] T_co T co [ C] T_cci T cci [ C] Fig.5: Temperatures vs heat load in the case of long LHP 100 90 80 70 60 50 40 30 20 20 30 40 50 60 70 80 90 100 Q [W] T_s1 T s1 [ C] T_eo T eo [ C] T_co T co [ C] T_cci T cci [ C] Fig.6: Temperature vs heat load in the case of short LHP

Rt[K/W] Figure. 5 and Fig. 6 demonstrate value of T s1 as well as T eo, T co, T cci of the long and short LHPs when working at different heat load conditions. Both of long and short LHPs, T eo is a little lower than T s1 while T co and T cci are nearly equal together. This result shows that the circulation exists in both cases, or there is no reverse flow of vapor from compensation chamber to condenser that will cause the sudden increment of T cci. In the case of long LHP, values of T s1 are almost higher 85 o C although heat load is lower than 55 W. Besides, the changing tendency of this temperature is not regular with heat load. On the other hand, the short LHP can keep T s1 lower than 85 o C when heat load is at around 80 W. Besides, in the range of heat load that is larger than 50 W, the relation between T s1 and heat load become nearly proportional together which is similar to the constant conduction heat transfer mechanism. 3.3 Total thermal resistance vs heat load For understanding more clearly performance of both long and short LHPs, the values of total thermal resistance R t dependence of heat loads are demonstrated in Fig. 7. In this experiment, the R t of long LHP are higher than 1.2 K/W while the short LHP can operate with the smallest R t at 0.7 K/W with heat load at 75 W. For the long LHP, within the range of heat load from 35 W to 55 W, R t has the reducing trend with heat load while for the short LHP, operation characteristics can be divided into two modes that are variable thermal resistance and constant thermal resistance. This explains why in the case of short LHP, when working at heat load higher than 50 W, the relation between T s1 and heat load is nearly linear. The higher values of R t under low heat load conditions can be explained basing upon the small evaporating rate and flooding condition of evaporator; as a result, evaporating vapor flows out vapor groove to condenser difficultly, and supplying heat power has the trend that transfer through the wick body more easily, cause value of R t to become higher. 2 1.8 1.6 1.4 1.2 1 0.8 0.6 20 40 60 80 Q [W] 100 R_t R t (Short) [K/W] [K/W] R_t R t (Long) [K/W] [K/W] Fig.7: R t of long and short LHP with heat load 4. CONCLUSION In this study, the LHP with flat rectangular evaporator is fabricated and investigated thermal performance under horizontal orientation when changing the length of connection lines and condenser. Temperature distribution inside the LHP demonstrates that circulation happens in both of long and short LHP. However, longer connection and condenser line causes the heat transfer capacity of long LHP lower than short LHP because of increasing of pressure loss though cooling capacity of longer condenser is higher. the surface of heater T s1 is higher than 85 o C and total thermal resistance are almost more than 1.2 K/W. The short LHP can operate stably in the range of heat load from 25 W to 95 W when temperature at the base of evaporator is lower than 100 o C under horizontal condition. In addition, this LHP can keep T s1 below 85 o C, which can be regarded as limitation temperature for the reliable and effective operation of electronics, when operating at heat load around 80 W. The operation characteristics of LHP can be classified into two modes that are variable thermal resistance and constant thermal resistance. 5. REFERENCES [1] S. M. Sohel Murshed and C. A. Nieto de Castro, A critical review of traditional and emerging techniques and fluids for electronics cooling, Renew. Sustain. Energy Rev., vol. 78, no. March 2016, pp. 821 833, 2017. [2] R. Singh, A. Akbarzadeh, and M. Mochizuki, Operational characteristics of a miniature loop heat pipe with flat evaporator, Int. J. Therm. Sci., vol. 47, pp. 1504 1515, 2008. [3] R. Singh, Effect of Wick Characteristics on the Thermal Performance of the Miniature Loop Heat Pipe, vol. 131. August 2009, pp. 1 10, 2009. [4] S. Wang, J. Huo, X. Zhang, and Z. Lin, Experimental study on operating parameters of miniature loop heat pipe with fl at evaporator, Appl. Therm. Eng., vol. 40, pp. 318 325, 2012. [5] S. Becker, S. Vershinin, V. Sartre, E. Laurien, J. Bonjour, and Y. F. Maydanik, Steady state operation of a copper e water LHP with a fl atoval evaporator, Appl. Therm. Eng., vol. 31, no. 5, pp. 686 695, 2011. [6] Y. Maydanik, S. Vershinin, M. Chernysheva, and S. Yushakova, Investigation of a compact copper e water loop heap pipe with a fl at evaporator, Appl. Therm. Eng., vol. 31, no. 16, pp. 3533 3541, 2011. [7] K. Ebrahimi, G. F. Jones, and A. S. Fleischer, A review of data center cooling technology, operating conditions and the corresponding lowgrade waste heat recovery opportunities, Renew. Sustain. Energy Rev., vol. 31, pp. 622 638, 2014. 6. NOMENCLATURE Symbol Meaning Unit OD/ID Pipe outer, inner diameter k Copper thermal conductivity (W/m K)

A q Q R t σ r T 1, T 2, T 3 T 4 T a T co T cci T eo T s1 Heated area Heat flux Heat load Total thermal resistance Distance among thermocouples Surface tension Pore radius Heater temperature Evaporator base temperature Room temperature condenser outlet compensation chamber inlet evaporator outlet heater surface (m 2 ) (W/m 2 ) (W) (K/W) (N/m)