Unity CV2GIP Decentralised Mechanical Extract Ventilation (dmev) Installation Instructions

Similar documents
Centair CMEV.4 / CMEV.4e / CMEV.4eHT Mechanical Extract Ventilation (MEV) System Installation Instructions

Unity CV2GIP / CV2SVGIP Decentralised Mechanical Extract Ventilation (dmev) User / Homeowner Guide

Centair CMEV.4 / CMEV.4e / CMEV.4eHT Mechanical Extract Ventilation (MEV) System User / Homeowner Guide

D100, D125 & D150. Installation Instructions

Fusion HRV2 Mechanical Ventilation with Heat Recovery User / Homeowner Guide

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit

MEV SPIDER INSTALLATION GUIDE FOR ENGINEER / INSTALLER

HOTLINE:

isense & isense-ht 230V Flush Mounted Domestic Continuous Extract Fans

WHHR Midi & Midi Lite

Code of Practice - Ventilation- Mechanical Extract Ventilation (MEV) + Mechanical Ventilation with Heat Recovery (MHVR)

"WHHR125DC" Whole House Heat Recovery Unit with Low Energy DC Motor. Installation, Operating and Maintenance Instructions domestic and commercial use

FAITH (dmev) 230V / 24V DC SELV Flush Mounted Domestic Continuous Extract Fans

HRX-aQ Range. Mechanical Ventilation with Heat Recovery appliances. Installation and Operating Instructions

Zehnder Comfosystems. ComfoAir 180 Datasheet

Green Line HRX. Mechanical Ventilation with Heat Recovery appliance. Installation and Operating Instructions

MODEL: DV72 R & L. Mechanical Ventilation with Heat Recovery Installation Instructions and User Manual

CI/SfB (57.7) 3rd Edition WINNER2011. Winners of the Energy Efficiency Initiative 2011 Award with our Lo-Carbon Continuous Ventilation Product Range.

Thank you for choosing EnviroVent

Purge Ventilation Unit. Product Manual. ventilation systems TP625

Residential Carbon Friendly Ventilation SAP Q Eligible. ventilation

Lo-Carbon MULTIVENT MVDC-MS & MVDC-MS H VENTILATION SYSTEMS V~50Hz. Installation and Wiring Instructions IP22. Stock Ref.

Lo-Carbon SELV Tempra

INTEGRA PLUS ABC. 230V~ 50Hz. Stock Ref. N. Installation and Wiring Instructions IPX2

Lo-Carbon Quadra SELV

Centrif Duo & Centrif Duo Plus

Vireo HR155WM / HR155CM / HR185WM Mechanical Ventilation with Heat Recovery User / Homeowner Guide

CI/SfB (57.7) 1st Edition. Lo-Carbon Response/SELV dmev Unit. A new generation of Lo-Carbon continuous running fans

Green Line HRX. Mechanical Ventilation with Heat Recovery appliance. Installation and Operating Instructions

Installation and Maintenance

CI/SfB (57.7) 1st edition

Installation and Maintenance

Titon CME1 Q Plus Mechanical Extract Ventilation Unit

Installation and Maintenance

Installation and Maintenance Instructions for the Installer. Please refer to the User Manual for instructions on how to operate the system

Lo-Carbon Quadra Centrifugal Fan

VENTILATION. Mechanical Ventilation with Heat Recovery appliance. Installation and Operating Instructions. Models: HRX2-S, HRX2-B, HRX2-FP, HRX2-BFP

CMX-S. Company name: Contact: Tel: Central Mechanical Extract Ventilation (cmev) appliance. Installation and Operating Instructions

energisava 200 WALL & FLOOR MOUNTED VERSION INSTALLATION GUIDE FOR ENGINEER / INSTALLER

Installation and Maintenance

Installation and Maintenance

Titon HRV1 Q Plus HRV1.5 Q Plus HRV2 Q Plus Heat Recovery Ventilation Units

Vent-Axia Svara Multifunctional app controlled fan. Important Information 2 Installation and Wiring Instructions 3-11 Accessories 12 Pin Code 12

Installation and Maintenance

Intake air from outside. Supply air to house. Extract air. from house. Extract air from house. Exhaust air from house to outside

Thank you for choosing EnviroVent

EKF. EC kitchen extract fan range. Installation and Wiring Instructions. Stock Ref. N EKF355E1 EKF400E1 EKF450E1 EKF450E3 EKF500E3 EKF560E3

IF IN DOUBT, INSTALLATION SHOULD BE MADE BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH CURRENT WIRING REGULATIONS.

Installation and Maintenance

energisava 200 CEILING MOUNTED VERSION INSTALLATION GUIDE FOR ENGINEER / INSTALLER

Decentralised Mechanical Extract Ventilation 2 Speed Axial Extract Fan Installation Guide. Fig. 2 Fan components.

MRXBOX95B-LOFT. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting. Installation and Maintenance

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

Green Line CMX. Central Mechanical Extract Ventilation (cmev) appliance. Installation and Operating Instructions. Model: CMX

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS.

Trimbox Mixed Flow Fans. Product Manual. ventilation systems TP220T TP221T TP222T TP223T

01 Safety. IMPORTANT Be sure to have read and understood these instructions before beginning the installation process.

Turbo Inline Fan, White - Non Illuminated Art no.33500

Internal/External Wall/Window Fan Range GX6. Installation and maintenance instructions Retain for future use

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Installation & Commissioning

QUALITY SPACE HEATERS

ECO dmev Decentralised MEV

FLAT2000L/R. Low Energy Positive Input Ventilation Unit. Installation and Maintenance. Alternative inlet position. 2.1 Spigot Inserts.

SUNWARM AIR SOLAR PRE-HEAT VENTILATION SYSTEM

White - Non Illuminated Art no White - Cool White LED Art no.32600

Warnings, Safety Information and Guidance

FMH Range Hoods. Installation, Operation & Maintenance Instructions

MRXBOX95-WH1. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Intake air from outside

WHHR125DC - Aera. Whole House Mechanical Ventilation with Heat Recovery - MVHR

PLEASE READ ALL SECTIONS OF THIS GUIDE BEFORE COMMENCING YOUR INSTALLATION AND IN CONJUNCTION WITH YOUR DRAWINGS.

Intake air from outside. Supply air to house. Extract air. from house. Extract air from house. Exhaust air from house to outside

airooncentre.co.uk irconcentre.co.uk Xpelair Low Energy Wall/Window Fan Range GX6 EC2 GXC6 EC2 Quick Order Hotline or

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Installation & Commissioning

FM900. Installation, Operation and Maintenance Instructions. Built-In Extractor

ECo 2 Wall INSTALLATION GUIDE FOR ENGINEER / INSTALLER

Installation & Operating Instructions

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Installation & Commissioning

Model: Kair Whole House Ventilator Model Number: KHRVWH2000

VA 150 A, VA 150 P WINDOW EXTRACT FAN. Installation and Wiring Instructions V/1/50Hz

EVX101 Extractor Installation, Use and Maintenance

COOKER HOOD USER HANDBOOK FOR INSTALLATION AND OPERATION MODELS CRC95

MRXBOX95-WH1. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Bracket

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N

EVP61/91/101/121. Extractor. Installation, use and maintenance.

230V & SELV INSTALLATION GUIDE FOR ENGINEER / INSTALLER IPX4 IPX5

Wiring the fan correctly...

CI/SfB (57.7) 2nd edition. Lo-Carbon Quadra

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N

Wiring the fan correctly...

Integra. Integra Plus EC MVHR. Installation & Commissioning. Stock Ref. N EC Integra Plus EC PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.

MRXBOX95-WALL. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Extract air.

Lo-Carbon SOLO Plus SELV Centrifugal Bathroom/Toilet Fan

ELIX 1003 IPX4. Energy Efficient Centrifugal Fan with EC Motor Installation and Operating Instructions

Installation Manual for BR500

Installation Manual for isodrive 650 Motor

Sentinel. Kinetic MVHR Range. Installation & Commissioning. Stock Ref. N PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.

HEX390 Heat Exchanger

Lo-Carbon T-series Window & Roof Models

VENT TREX. Product Guide

Transcription:

Unity CV2GIP Decentralised Mechanical Extract Ventilation (dmev) Installation Instructions Commissioning Data: To be completed by the Commissioning Engineer. Refer to User / Homeowner Guide also supplied.

Contents 1.0 General Description / Physical Specification Page 1.0 General Description / Physical Specification 3 2.0 Installation Instructions 5 2.1 General Preparation 5 2.2 Positioning / Application 5 2.3 Wall Mounting 6 2.4 Ceiling Mounting 7 2.5 Ducting Guidelines 8 2.6 Electrical 9 2.7 Wiring 9 2.8 On Site Commissioning / Set Up 11 3.0 Guarantee 16 1.1 1.1.1 1.1.2 1.1.3 1.1.4 1.1.5 1.1.6 Overview Greenwoods Unity CV2GIP is a continuously running (dmev) extract fan, designed to offer a simplistic approach to meet Building Regulations and provide an energy efficient domestic ventilation solution to improve indoor air quality in dwellings. The concept revolves around one product, which has been designed to be flexible in application (ceiling and wall installations) and to meet the performance requirements of all wet rooms within a dwelling. The Unity CV2GIP features new Greenwood TimerSMART TM and Greenwood HumidiSMART TM technology (fully automatic integral delay / over-run timer and humidity functions) which monitor the homeowners environment. For enabling / disabling features see section 2.8 On Site Commissioning. A boost speed facility is provided to increase the ventilation rate during peak times, helping to provide a comfortable indoor environment. Either a switch-live light switch or an alternative boost switch (not supplied) should be wired to provide this operation (see section - 2.6 Electrical). This product features on SAP Appendix Q, part of the process will require the Installation Checklist for dmev products to be completed and submitted to building control, available at www.sap-appendixq.org.uk, along with all other relevant paperwork. Record sheets for commissioning information are provided; please refer to section 4 of the User / Homeowner Guide also supplied with the product. Packaging Includes 1 x Unity CV2GIP Unit 1 x Loose item set 1 x Installation Instructions 1 x User / Homeowner Guide Ancillary Items Required: 100mm round ducting or Flat duct (110 x 54mm) or (204 x 60mm). 100mm grille & appropriate boost switch (GS2). 2 3

2.0 Installation Instructions 1.1.7 The appliance is not intended for use by young children or infirm persons unless they have been adequately supervised by a responsible person to ensure that they can use the appliance safely. Young children should be supervised to ensure that they do not play with the appliance. 2.1 2.1.1 General Preparation The Unity CV2GIP fan is supplied with a 100mm nominal spigot for connection of ducts for installation. 1.1.8 1.1.9 Siting Notes: Where an open-flued oil or gas-fuelled appliance is installed in the kitchen, extract ventilation can cause the spillage of flue gases. Care must be taken to ensure ventilation is reduced appropriately, as set out in the Building Regulations. Kitchens with solid-fuel appliances should not have extract fans fitted. When installing wall mounted fans, ensure that there are no buried cables or pipes in the way. It is recommended that this fan is mounted 1.8m above floor level. 2.1.2 2.1.3 2.1.4 100mm diameter rigid duct should be used to provide the best performance levels required for compliance with Building Regulations. Greenwood Airvac Technical Services can be contacted on +44 (0) 1903 777135 should you have any questions in respect of this. Installation of the unit should be in accordance with the current editions of Building Regulations and BS7671: IEE Wiring Regulations. Electrical installation must only be carried out by a qualified Electrician. 1.2 Physical Specification 62 mm 68 mm 48 mm 2.2 Positioning / Application 2.2.1 The unit can be installed on a wall or ceiling mounted and ducted. 2.2.2 The unit must be securely mounted using all four fixing holes provided (see Figure 1). Ø 99 mm Ø 178 mm Ø 199 mm 129.5 mm Using No.8 screws provided, ensure that all four fixing points on the back plate are securely fitted Front Side Figure 1: Back Plate Screw Fixtures 4 5

Unity CV2 InstallAW 18.1.11 19/1/11 03:46 Page 6 2.3 Wall Mounting 2.4 Ceiling Mounting 2.3.1 Determine the most ideal location for the unit for this installation, also taking account of the electrical services. 2.4.1 Determine the most ideal location for the unit for this installation, also taking account of the electrical services. 2.3.2 Ensure there is adequate access for installation and eventual replacement. Note: The electronics cover has been designed to retain and hold screws, for ease, when positioning/mounting the product to a surface. 2.4.2 Ensure there is adequate access for installation and eventual replacement. Note: The electronics cover has been designed to retain and hold screws, for ease, when positioning/mounting the product to a surface. 1 2 3 1 2 3 Ø = 117mm To remove outer front cover, rotate to the left until retaining clips are released. Then loosen the 3 fixing screws (see Note above). 4 Fill in any gaps with mortar or foam and make good internal and external walls. Make sure that ducting remains circular. 7 6 Carefully close the electronics cover, ensuring that the outer rubber seal edges are positioned correctly back into the fan body. Carefully open the electronics cover until retention hinge is fully extended. 5 To ensure the control panel is in the correct configuration, please mount the fan with orientattion symbol arrows facing upwards. 8 Cut the duct to width of the plasterboard or tiled wall with slight fall to exterior. (Make provisions for cable). 6 Using the four No 8 screws, secure fan body to the wall. The electrical cable passes through as appropriate. Wire fan (See wiring details). 9 Screw the protective wall grille over the Tighten the 3 fixing screws. To attach the outer front cover, rotate to the right, utilising the guidance external duct opening. rail, until firmly secured by the retaining clips. X = 65 Ø = 105mm To remove outer front cover, rotate to the left until retaining clips are released. Then loosen the 3 fixing screws (see Note above). 4 The unit must be securely mounted using all four fixing holes provided (see section 2.2). Wire fan (See wiring details). 7 Carefully open the electronics cover until retention hinge is fully extended. 5 Place flexible or rigid ducting over the spigot of the fan. Fit ducting to spigot using appropriate method. Refer to section 2.5. 8 Diagram depicting typical installation ducted Tighten the 3 fixing screws. To attach the outer front cover, rotate to the right, utilising the guidance through roof soffit. rail, until firmly secured by the retaining clips. Cut an opening through the ceiling for the fan and electrical cable. 6 Carefully close the electronics cover, ensuring that the outer rubber seal edges are positioned correctly back into the fan body. 9 Diagram depicting typical installation ducted through roof to external wall. 7

2.5 Ducting Guidelines 2.6 Electrical 2.5.1 2.5.2 A 100mm nominal diameter spigot is provided for connection to ducting. Ductwork should be securely connected to fan spigot. Failure to do this will cause unnecessary air leakage and may impair performance. All duct connections require sealing. Where ducts are installed against a solid structure this can be difficult to achieve. In such locations preassembly of duct sections should be considered. This will require that connections are permanent to ensure the seal is maintained during installation. 2.6.1 2.6.2 2.6.3 2.6.4 WARNING: All wiring must conform to BS7671: IEE Wiring Regulations. WARNING: The appliance must be isolated from the mains supply before removing the electronics cover. The installation must be carried out by a qualified electrician. The Unity CV2GIP is suitable for a 220-240V ~ 50Hz single phase supply fused at 3A. 2.5.3 If applicable, Fire dampers MUST BE FITTED in accordance with Part B of the Building Regulations. 2.6.5 A double-pole switch having a minimum contact separation of 3mm must be used to provide isolation for the unit. 2.5.4 2.5.5 Rigid Ducting - Install using the least number of fittings to minimise resistance to airflow. Where access to ducts will not be possible after construction is complete, i.e. within floor and wall voids, consideration should be given to permanent connection and sealing with an appropriate non-hardening sealant, and not using duct tape to achieve connection and sealing. Flexible Ducting - Ensure ducting lengths are kept to minimum and ducting is pulled taut so that it is smooth and straight. Where bends are necessary, and where ducting is run in restricted areas, ensure the ducting is not crushed. Connection of lengths of flexible duct must use a rigid connector and jubilee clips or similar to ensure a long term seal is achieved. Connection of lengths of flexible duct should not be taped-only. 2.6.6 2.6.7 The recommended alternative switch-live switch for use is the - Greenwood Airvac; GS2 switch. GS2 Remote Switch Positions Trickle (I) Boost (II) Function Fan running at trickle speed Fan running at boost speed The fan must not be mounted above or closer than 1m to the cooker where it could be affected by excessive heat or moisture. II I 2.5.6 The fan exhaust must terminate to external air and be protected by a suitable wall or roof terminal. Roof terminal to have a minimum equivalent free area of 7,500mm 2. 8 9

2.6.8 Wiring Details 2.8 On Site Commissioning / Set Up Strip cable to correct lengths as shown in Figure 2 - Diagram 2.a. Insert cable through cable entry point (A), and then clamp cable using the cable clamp (B). Push the wires into the terminal block (C) as per wiring diagram (see section 2.7). Tighten screws of the terminal connection. 2.8.1 2.8.2 This section covers set up, configuration of the unit for installation and altering pre-set factory settings. Control Panel Note: A facility to park the earth cable has been provided (D); as the fan is double insulated no connection to earth is required. (D) (C) (B) (A) (C) Room Selection Buttons 2.6.9 Figure 2 - Wiring Details Fan Specifications 220-240V ~ 50Hz / 1Ph IPX4 5 Watts max. Cable sizes (max): Fixed flat wiring 2 core 1mm 2, 3 core 1/1.5mm 2 Diagram 2.a. Trickle Airflow Commissioning Speed Adjustment Greenwood HumidiSMART TM On / Off Boost Airflow Commissioning Greenwood TimerSMART TM On / Off 2.7 Wiring Diagram 220-240V ~ 50Hz / 1Ph 10 11

2.8.3 Room Installation Selection 2.8.5 To Commission Kitchen Fan Airflow Rates Once the wiring connections have been checked, switch the mains supply on. On first power up, both Bathroom and Kitchen Room selection button lights should flash to indicate that an appropriate installation setting needs to be selected. Whilst both room selection lights are flashing, press the Kitchen button. The Kitchen light should show as solid. The Boost speed light should now start to flash. Note: If no button is selected, lights should flash for 15 minutes and should then divert to Bathroom Default settings and lock out the commissioning section of the controls. Note: To reactivate commissioning mode see Section 2.8.9. Boost Factory Setting: 13 l/s (Through wall) To adjust the airflow, press the [-/+] buttons to the required level and verify with an airflow measuring device, then press the Boost button [ ] to confirm and the boost light should show as solid. 2.8.4 To Commission Bathroom Fan Airflow Rates (Includes WC) Whilst both room selection lights are flashing, press the Bathroom button. The Bathroom light should show as solid. The Boost speed light should now start to flash. The Trickle speed light should now start to flash. Trickle Factory Setting: 8 l/s (Through Wall) To adjust the airflow, press the [-/+] buttons to the required level and verify with an airflow measuring device, then press the Trickle button [ ] to confirm and the trickle light should show as solid. Boost Factory Setting: 8 l/s (Through Wall) To adjust the airflow, press the [-/+] buttons to the required level and verify with an airflow measuring device, then press the Boost button [ ] to confirm and the boost light should show as solid. Note: Selection lights should remain on for approximately 10 seconds to enable the setup and status of the fan to be observed and checked, upon which time the commissioning section of the controls should lock. Note: For WC reduce Boost airflow to 6 l/s. Note: To reactivate commissioning mode, see Section 2.8.9. The Trickle speed light should now start to flash. Trickle Factory Setting: 5 l/s (Through Wall) To adjust the airflow, press the [-/+] buttons to the required level and verify with an airflow measuring device, then press the Trickle button [ ] to confirm and the trickle light should show as solid. Note: Selection lights should remain on for approximately 10 seconds to enable the setup and status of the fan to be observed and checked, upon which time the commissioning section of the controls should lock. Note: To reactivate commissioning mode, see Section 2.8.9. 12 13

2.8.6 To Activate Greenwood HumidiSMART TM 2.9 Performance Graph Press [ ] to activate the Greenwood HumidiSMART TM, the light should come on to indicate that the function is active. 2.9.1 Airflow Characteristics Factory set to OFF Option s ON / OFF 2.8.7 To Activate Greenwood TimerSMART TM Press [ ] to activate the Greenwood TimerSMART TM, the light should come on to indicate that the function is active. Factory set to OFF Option s ON / OFF 2.8.8 To Reactivate Commissioning Mode Press any button to activate the panel. The current fan set up / status should be shown via the panel lights. To enter the commissioning mode press and hold [-/+] buttons simultaneously for approximately 3 seconds until the Bathroom & Kitchen lights flash - room and airflow settings from previous commissioning should be recalled. See section 2.8 for commissioning details. Note: To master reset press and hold [-/+] buttons simultaneously for approximately 10 seconds until all lights flash to indicate the fan has been reset to factory settings and then revert to both room selection lights at Note: The Unity CV2GIP will automatically compensate for fluctuations in back pressure, start of commissioning mode. to meet Building Regulation requirements 14 15

3.0 The Guarantee Period 3.1.1 3.1.2 3.1.3 This Greenwood product (Unity CV2GIP) has a 2 Year Guarantee. This does not affect your statutory rights. Full details available on request from +44 (0) 870 900 1880 or www.greenwood.co.uk / info@greenwood.co.uk All information is believed correct at time of going to press. E&OE. All goods are sold according to Greenwood Air Management Ltd s Standard Conditions of Sale which are available on request. All dimensions referred to are in millimetres unless otherwise shown. Greenwood Air Management Ltd reserves the right to change specifications and prices without prior notice. Copyright Greenwood Air Management Ltd 2010. Greenwood Air Management Ltd Greenwood House, Brookside Avenue, Rustington, West Sussex, BN16 3LF 16 Main Line Tel: +44 (0) 1903 771021 Technical Services: +44 (0) 1903 777135 Main Line Fax: +44 (0) 1903 782398 Web: www.greenwood.co.uk Email: info@greenwood.co.uk 05.10.920 Issue 1 (MCR 600) January 2011