VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

Similar documents
Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Worldwide Contacts.

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, Dual-Purpose Water Supply, Domestic and Fire Sprinkler System General Description

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Model AV Alarm Valve With and Without Model RC-1 Retard Chamber European Conformity Valve Trim General Description

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

TECHNICAL DATA. 319a. January 27, 2012

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

as required for residential sprinklers intended for use in dry pipe systems.

Technical Data. Sizes 2 in. (DN50) to 16 in. (DN400) Approvals UL and ULC Listed FM Approved

TECHNICAL DATA OBSOLETE

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

TOTALPAC2 Integrated Fire Protection System

special request FACTORY ASSEMBLED UPRIGHT WITH SCREW FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) WRENCH FLATS *

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

Worldwide Contacts. Technical Data

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Technical Data. Sizes 2 12 Inch (DN50 DN300)

Model CV-1F Grooved End Swing Check Valves. General Description. Technical Data. Installation. Page 1 of 6 FEBRUARY 2016 TFP1550. Worldwide Contacts

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

Technical Data. Installation

Series TY-FRL 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Sprinkler Identification Number. Page 1 of 6 AUGUST 2018 TFP288. Worldwide Contacts.

WRENCH FLATS NPT 1/2" 7/16" (11,1 mm) NOMINAL MAKE-IN. 1-1/2" (38,1 mm) 2-3/16" (55,6 mm) WRENCH NPT. (12,7 mm) NOMINAL MAKE-IN.

Technical Data. Outlet Connections (Ref. Figure 2) ISO 7-Rc 3/8 1/2 inch NPT 3/4 inch NPT. Nominal Assembly Lengths Ref. Table A

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

O-RING UPRIGHT SHIELD WRENCH FLATS WRENCH FLATS FIGURE 1 SERIES TY-B UPRIGHT (TY3153) AND PENDENT (TY3251) SPRINKLERS

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

AQUAMIST Mist Control Center (MCC) Pump Skid Unit. General Description. Technical Data. Page 1 of 8 JANUARY 2016 TFP2270. Worldwide Contacts

RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

TECHNICAL DATA OBSOLETE

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

Worldwide Contacts.

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Technical Data. Sizes: ANSI Inches (DN) 2-1/2 (DN65), 3 (DN80), 4 (DN100), 5 (DN125), 6 (DN150), 8 (DN200), 10 (DN250)

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Horizontal Sidewall Wet Pipe and Dry Pipe Systems General Description

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

* Temperature rating is FIGURE K-FACTOR QUICK RESPONSE SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS

Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

Model CV-1FR Riser Check Valves 2 to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data. Page 1 of 6 OCTOBER 2010 TFP950

Instructions for Installation, Operation, Care and Maintenance

Series TY-FRB 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General Description

Submittal Packages Detailed with Items and Reviewers

Page 1 of 8 DECEMBER 2018 TFP408. Worldwide Contacts.

RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 5.6 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole.

Sprinkler Identification Numbers

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Specification/ Data Sheet

FIGURE 1 MODEL RFIII ECLH CONCEALED HSW SPRINKLER ASSEMBLY AND FEATURES. 5/16" (7,9 mm) MIN. 9/16" (14,3 mm) MAX.

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

ESCUTCHEON PLATE SEATING 3/4" NPT SURFACE. 1-1/2" (38,1 mm) CROSS SECTION PENDENT RECESSED PENDENT

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

G3/8" DIN ISO 228 THREAD SHOULDER AND DUST CAP MATING SURFACE. STYLE H ESCUTCHEON (SEPARATELY ORDERED) 85 mm DIA. (3-3/8")

Sprinkler Identification Numbers. TY3351 Horizontal TY3451 Vertical. Technical Data

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

TotalPac X Firecycle III Preaction Double interlock system

Care and Maintenance

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16" (42,7 mm) CROSS SECTION

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General Description

Deluge & Preac tion Systems

TotalPac X Single interlock SUREFIRE system

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

TECHNICAL DATA. Wet 26a. February 22, 2009

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response)

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

Transcription:

Worldwide Contacts www.tyco-fire.com VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description The TYCO VIZOR Electronic Dry Pipe Accelerator (EDPA) is a quick-opening device intended to reduce the operating time of the dry pipe valves listed in Table A following operation of one or more automatic sprinklers. Unlike traditional mechanically operated quick-opening devices, the VIZOR Accelerator is a microprocessor-based, electronic, quick-opening device. The VIZOR Accelerator automatically adjusts to both small and slow changes in system air pressure, but trips when there is a steady drop in system air pressure upon sprinkler operation. The VIZOR Accelerator features the following: Direct mounting to the riser Installation consistent with the installation of mechanical devices Easy test-and-reset function, as compared to mechanical accelerators Operation of a dry pipe valve within four seconds over a wide range of system volumes, system initial air pressures, and sprinkler K-factors Built-in low-pressure and high-pressure alarm supervision Electronically self-supervising technology, similar to that used in typical alarm panels for alarm and detection systems Battery back-up in the event of primary power failure The VIZOR Electronic Dry Pipe Accelerator utilizes a unique, patented system air pressure monitoring design that continuously samples the system air pressure. IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. When the VIZOR Accelerator detects a sustained drop in air pressure, the VIZOR Accelerator energizes its internal solenoid valve. The energized solenoid valve then opens to permit system air pressure into the intermediate chamber of the dry pipe valve. The pressurized intermediate chamber neutralizes the differential pressure holding the dry pipe valve closed and permits the dry pipe valve to trip and flow water into the system piping. NOTICE The VIZOR Electronic Dry Pipe Accelerator described herein must be installed and maintained in compliance with this document and with the applicable standards of the NATIONAL FIRE PROTEC- TION ASSOCIATION, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of this device. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. Contact the installing contractor or product manufacturer with any questions. Technical Data NOTICE Quick operation of the TYCO VIZOR Electronic Dry Pipe Accelerator does not ensure that the fire protection system will meet the water delivery time requirement of the authority having jurisdiction (following opening of the Inspector s Test Connection). The sprinkler system designer has to be aware that water delivery time is primarily determined by the configuration and volume of the piping network, system air pressure at the time of accelerator trip, number and orifice size of open sprinklers, and water supply characteristics. It is essential for the designer to verify the impact of these site-specific factors on water delivery time. Approvals Listings and approvals are under the name of Potter Electric Signal Company Electric Dry Pipe Accelerator (EDPA). Refer to Table A for Listings and Approvals for use of the VIZOR Accelerator with specific dry pipe valves. UL and ULC Listed The VIZOR Accelerator is UL and ULC Listed per UL14 for a maximum system capacity of 190 gallons (397 liters) for a single nominal 5. K-factor sprinkler and a maximum working water pressure of 300 psi (20,7 bar). FM Approved The VIZOR Accelerator is FM Approved for TYCO Model DPV-1 Valves and can be used with the following discontinued models: Central Models AG and AF, GEM Models F302 and F3021, and Star Models A and A1. Page 1 of 12 AUGUST 201

Page 2 of 12 Manufacturer Valve Model Valve Size ANSI Inches (DN) UL Listed FM Approved TYCO Model DPV-1 4 and (DN100/150) X X Central Models AG and AF 3, 4, and (DN0/100/150) X See note. Gem Models F302 and F3021 4 and (DN100/150) X See note. Star Models A and A1 4 and (DN100/150) X See note. Note: For retrofit applications, the FM Approved Model DPV-1 application of EDPA Electronic Accelerator Systems can be used for the specified discontinued valves. TABLE A LABORATORY LISTINGS AND APPROVALS FOR DRY PIPE VALVE COMPATIBILITY Switch Setting Low Air Threshold psi (bar) Nominal Pressure psi (bar) High Air Threshold psi (bar) 0 7 (0,4) 10 (0,9) 15 (1,04) 1 7 (0,4) 15 (1,04) 20 (1,3) 2 15 (1,04) 20 (1,3) 25 (1,72) 3 15 (1,04) 25 (1,72) 30 (2,07) 4 20 (1,3) 30 (2,07) 35 (2,41) 5 25 (1,72) 35 (2,41) 40 (2,7) 30 (2,07) 40 (2,7) 45 (3,10) 7 35 (2,41) 45 (3,10) 50 (3,45) 45 (3,10) 55 (3,79) 0 (4,14) 9 55 (3,79) 5 (4,4) 70 (4,3) TABLE B HIGH/LOW PRESSURE SETTINGS Maximum Water Pressure 300 psi (20,7 bar) Air Pressure 10 to 5 psi (0,9 to 4,4 bar) Pressure Decay For Trip 0.1 psi/sec. (0,007 bar/s) High/Low Pressure Settings Refer to Table B VIZOR Environmental Specifications VIZOR Accelerator NEMA 2, Indoor use 40 F to 120 F (4 C to 49 C) Battery Cabinet NEMA 1, Indoor use 32 F to 120 F (0 C to 49 C) Power Requirements Maximum 0.75 A @ 120/220 AC Batteries (Ordered Separately) Standard 24-hour battery back-up provided by two 12-volt (1.3 AH) Batteries Optional 90-hour battery back-up provided by two 12-volt (5 AH) Batteries Battery Current Draw Standby: 43 ma; Alarm: 440 ma Dry Contact Rating Trouble: 5 A @ 30 VDC High/Low: 5 A @ 30 VDC Installation Dimensions Refer to Figure NOTICE When the VIZOR Accelerator is installed in accordance with these instructions, the equipment s design provides reasonable protection against limited radio frequency sources. Intentionally subjecting the equipment to radio frequency sources could result in unintended operation of the dry pipe system. VIZOR Accelerator Indicators and Controls Refer to Figures 1 and 2. AC Power (Green LED): On steady when AC power is present Trouble/Supervisory (Amber LED): On steady for Trouble, 1 flash per second (slow) for low pressure, 4 flashes per second (fast) for high pressure Battery Trouble (Amber LED): On steady for low battery Tripped (Red LED): Flashes for 30 seconds to indicate the solenoid is open and the VIZOR Accelerator is tripped; lights steady after 30 seconds indicating the solenoid is closed

Page 3 of 12 S1 SET S2 RESET HAZARDOUS VOLTAGE MAY BE PRESENT. DISCONNECT POWER BEFORE SERVICING. AC POWER TROUBLE / SUPERVISORY OFF SILENCE TROUBLE / SUPERVISORY LED INDICATOR CODES ON STEADY: SYSTEM TROUBLE SLOW FLASH: LOW PRESSURE FAST FLASH: HIGH PRESSURE BATTERY TROUBLE TRIPPED OPERATING INSTRUCTIONS Normal operation: Place S1 to SET after system reaches normal air pressure. Disable for testing or maintenance: Place S1 to OFF. Reset after a trip: Place S1 to OFF. After system reaches normal operating pressure, press S2 to RESET and place S1 to SET. Note: The accelerator will be in a trouble condition when S1 is placed to OFF. Press S2 to SILENCE to silence the trouble buzzer. FIGURE 1 FRONT VIEW WITH COVER CLOSED S1 (Two-Position Switch): Up to SET to place the VIZOR Accelerator in service when air pressure matches rotary switch setting; down to OFF to take the VIZOR Accelerator out of service S2 (Two-Position Momentary Switch): Up to RESET to reset the VIZOR Accelerator after activation; down to SILENCE to silence the buzzer Buzzer: Indicates any trouble or supervisory condition by sounding an audible alarm Trouble Dry Contacts (Normally Open): Activate on any trouble condition such as low batteries or when S1 is pushed into the OFF position; activate on a loss of AC power after 0 minutes High/Low Dry Contacts (Normally Open): Activate when system pressure is outside of the normal setting of the rotary switch Operation The TYCO VIZOR Electronic Dry Pipe Accelerator provides a microprocessor-based, electronic, dry pipe valve accelerator designed to monitor the air pressure in a dry pipe system and reduce the time it takes for the dry pipe valve to operate following the opening of one or more sprinklers. The VIZOR Accelerator can be used in new installations or to replace mechanical type accelerators in existing systems. The VIZOR Accelerator operates upon detection of a steady drop in air pressure of 0.1 psi per second (0,007 bar/s) or greater, or if the pressure drops to 5.5 psi (0,3 bar). The VIZOR Accelerator typically responds to an open sprinkler in approximately 2 seconds. In order to minimize false trips and high/low air trouble conditions, the use of a tank mounted air compressor or plant air in conjunction with the TYCO AMD-1 Air Maintenance Device is strongly recommended, The compressor, or plant air, should be set to maintain a minimum of 10 psi greater than the required system air pressure. Note: Although the VIZOR Accelerator is designed to respond to an open sprinkler in approximately 2 seconds, operation of the dry pipe valve is expected within 4 seconds. The difference of 2 seconds is a conservative estimation for the dry pipe valve to physically trip. Upon detection of a drop in air pressure, the VIZOR Accelerator opens an internal solenoid valve allowing system air pressure into the intermediate chamber of the dry pipe valve. The pressurized intermediate chamber neutralizes the differential pressure holding the dry pipe valve closed and permits the valve to open. The solenoid valve automatically closes after 30 seconds. The VIZOR Accelerator contains two sets of normally open, dry contacts. The High/Low Supervisory Contacts close if the normal system air pressure in the system increases or decreases beyond a given point (refer to Table B). The ten-position rotary switch (refer to Figure 2) provides ten preset pressure settings. The factory setting is position #4 for a normal system air pressure of 30 psi. The Trouble Dry Contacts close during any one of the following conditions: Low-battery condition (up to a 1-minute delay is normal) AC power loss (after a 0-minute delay) SET/OFF switch in the OFF position An internal buzzer sounds during any off-normal condition. Installation The TYCO VIZOR Electronic Dry Pipe Accelerator must be installed in accordance with this section. NOTICE When working on the VIZOR Accelerator or the dry pipe valve, S1 should be in the OFF position; otherwise, the dry valve can inadvertently trip. Make all pipe fitting connections to the VIZOR Accelerator inlet and outlet ports by using the wrench flats on the

Page 4 of 12 200 (1059) 200 (941) K 11.2 2400 (904) K=.0 MAXIMUM SYSTEM CAPACITY, GALLONS (LITRES) 2200 (327) 2000 (7570) 100 (13) 100 (05) 1400 (5299) K=5. K=4.2 1200 (4542) 1000 (375) 00 (302) 10 20 30 40 50 0 (0,7) (1,4) (2,1) (2,) (3,4) (4,1) MINIMUM SYSTEM AIR PRESSURE, PSI (BAR) Notes 1. Quick operation of the TYCO VIZOR Electronic Dry Pipe Accelerator does not ensure that the fire protection system will meet the water delivery time requirement of the authority having jurisdiction (following opening of the Inspector s Test Connection). The sprinkler system designer has to be aware that water delivery time is primarily determined by the configuration and volume of the piping network, system air pressure at time of Accelerator trip, number and orifice size of open sprinklers, and water supply characteristics. It is essential for the designer to verify the impact of these site-specific factors on water delivery time. 2. The sensitivity criteria for the VIZOR Accelerator is a function of its pressure decay for trip rating of 0.1 psi (0,007 bar) per second, as well as the system volume, the K-factor of the sprinklers being utilized, and the minimum initial air pressure. The larger the system volume combined with smaller sprinkler K-factor or lower initial air pressure results in a slower air decay rate upon the first sprinkler operation. Conversely, a smaller system volume combined with a larger sprinkler K-factor or higher initial air pressure results in a faster air decay rate. 3. When the sprinkler system has been designed within the criteria provided by Graph A, operation of the VIZOR Accelerator and subsequent operation of the associated dry pipe or preaction valve can be expected within four seconds. In the case of the double interlock preaction system, operation is based on the electric detection system operating before a first sprinkler operation. 4. The minimum system air pressure must be the greater of that required for the dry pipe / preaction valve as a function of the maximum expected water supply pressure or per Graph A when using the VIZOR Accelerator. 5. When considering multiple sprinkler operations as in the case of using a dry system water delivery design per NFPA 13, use the 11.2 K-factor and larger curve as referenced in Example 3 below. Examples 1. For a system volume of 1500 gallons (50 liters) and the use of sprinklers having a K-factor of 5., the minimum system air pressure must be 1.5 psi (1,3 bar). 2. For a system volume of 2000 gallons (7570 liters) and the use of sprinklers having a K-factor of.0, the minimum system air pressure must be 1.0 psi (1,1 bar). 3. With the use of a dry system water delivery design per NFPA 13, wherein the operation of two 5. K-factor sprinklers might be anticipated (and the effective K-factor is then 11.2), the 11.2 K-factor and larger curve can be utilized. Consequently, for a system volume of 2400 gallons (904 liters), the minimum system air pressure must be 11.5 psi (0, bar). GRAPH A TYCO SENSITIVITY CRITERIA BASED ON FM APPROVAL

Page 5 of 12 VIZOR Accelerator. DO NOT tighten connections by grasping the VIZOR Accelerator housing. Failure to do so may result in damage to the components within the device. Install all required conduits and make all connections with AC power off. The VIZOR Accelerator must be hard-wired to complete the installation. During installation, the buzzer may sound. Silence the buzzer at any time by momentarily pushing S2 to the SILENCE position. The VIZOR Accelerator must be installed according to applicable NFPA codes (for example, NFPA 13, 70, and 72) as well as all local installation codes. Step 1. Install the VIZOR Accelerator as shown in Figures and 7. Apply pipe-thread sealant sparingly to male threads only. Step 2. Following Figure 2 and Table B, set the Ten-Position Rotary Switch to the required setting using the provided screw driver. Step 3. As shown in Figure 2, tape the 12V, 1.3 AH Batteries together. Connect the Harness wires (Leads in Figure 2) to the Batteries, slide the Battery Assembly into the Housing, and plug the Harness Connector into the VIZOR Accelerator circuit board. For the optional 90-hour batteries, mount the Remote Battery Enclosure horizontally and within 10 feet of the VIZOR Accelerator. Splice the battery cable (Figure 5), connect the cable to the Batteries, then plug the Battery Assembly into the VIZOR Accelerator Harness. Lastly, plug the Harness Connector into the VIZOR Accelerator circuit board. Step 4. Close and lock the cover. Step 5. Push S1 to the OFF position. Step. In order to minimize an inadvertent primary (A/C) power loss and to facilitate maintenance, it is recommended that a dedicated circuit be hard-wired to the VIZOR Accelerator. The following notifications occur: The Green AC LED lights, the Amber Trouble / Supervisory LED lights, the Red Tripped LED lights, and the buzzer sounds. Assuming the batteries are charged, the Amber Battery Trouble LED remains unlit. Step 7. Optionally conduct trip tests of the VIZOR Accelerator and the dry pipe valve in accordance with the Care and Maintenance section. Step. Optionally, and/or if required by local jurisdiction, hard-wire monitoring circuits to the Trouble and High/ Low supervisory contacts using 14 to 1 AWG wire. Step 9. Push S1 to the SET position. Step 10. Verify proper operation of the VIZOR Accelerator using the No Flow Trip Test for Accelerator Only procedure described in the Care and Maintenance section. Setting Procedure As soon as possible after an operation, reset and restore to service the Dry Pipe Valve (listed in Table A) and the TYCO VIZOR Electronic Dry Pipe Accelerator in accordance with the following procedure. NOTICE Completely drain the system before proceeding. After setting a fire protection system, notify the proper authorities and advise those responsible for monitoring proprietary and/or central station alarms. Step 1. Push S1 to the OFF position. Step 2. Silence the internal audible alarm at any time by momentarily pushing S2 to the Silence position. Step 3. Locate all of the system s low point drain valves to help facilitate resetting of the system. Refer to the appropriate dry valve data sheet for valve resetting procedures. Step 4. Clean the strainer by removing the clean-out plug and strainer basket. Step 5. Follow the resetting procedure for the installed dry pipe valve. When the procedure calls for the system piping to be pressurized with air, start to pressurize the system and then proceed to Step. Step. When the system reaches an air pressure of approximately 10 psi and while the system is in the process of reaching its intended pressure, blow-down each drain valve. Be sure to include the low body drains at the dry pipe valve and the Inspector s Test Connection. To blow-down, open each drain valve individually, and when water stops draining, close the drain valve. This blow-down procedure assures that complete draining of the system can be more easily accomplished. Step 7. When the system reaches the normal intended air pressure, wait approximately 30 seconds to allow for stabilization of the air pressure within the piping. Momentarily push button S2 on the VIZOR to the RESET position to clear the red tripped LED, and then push button S1 the SET position. Step. Open the Inspector s Test Connection (ITC), verify that the VIZOR has tripped. A momentary burst of air from the dry pipe valve s automatic drain valve indicates that the VIZOR Accelerator has tripped. Verify that the timeto-trip for the accelerator is essentially the same as in previous tests. This procedure also clears scale and debris from the pipe and fittings that are connected to the VIZOR Accelerator. Step 9. Push S1 to the OFF position, allow the system to automatically return to its intended pressure via its automatic air supply. After waiting approximately 30 seconds, momentarily push S2 to the RESET position, and then push S1 to the SET position. Step 10. Partially open the Main Control Valve. Slowly close the system s Main Drain Valve as soon as water discharges from the drain connection. Step 11. Depress the plunger on the dry pipe valve s automatic drain valve to verify that it is open and that no water discharges. The absence of water discharge from the automatic drain valve is an indication of a properly set water seat within the dry pipe valve. If water is discharging, refer to the Care and Maintenance section within the technical data sheet for the dry pipe valve to determine/correct the cause of the leakage problem. If there are no leaks, fully open the system s Main Control Valve. The system is now set for service.

7 9 05 12 345 7 9 05 Page of 12 120/220 VAC POWER CONNECTION BATTERIES WITH WIRING HARNESS 120 VAC POWER C NO L N TROUBLE TEN-POSITION ROTARY SWITCH FOR HIGH/LOW PRESSURE SETTINGS HI/LOW AIR C NO SOLENOID + - 123 4 12 3 4 SOLENOID VALVE FACTORY WIRED BAT BUZZER ASSEMBLE BATTERIES IN FIELD WITH ELECTRICAL TAPE WHITE LEAD WHITE LEAD BLACK LEAD ASSEMBLE BATTERIES THEN... INSTALL BATTERY ASSEMBLY THEN... ENCLOSURE BATTERY WIRING HARNESS CONNECT HARNESS 7 90 BATTERY RED LEAD HARNESS CONNECTOR MOUNTED BATTERY HARNESS CONNECTOR COVER HIGH/LOW PRESSURE ROTARY SWITCH SETTING DATA ROTARY SWITCH CIRCUIT BOARD FIGURE 2 FRONT VIEW WITH COVER OPEN

Page 7 of 12 CIRCUIT BOARD PRESSURE TRANSDUCER SOLENOID VALVE FRONT COVER INLET CROSS-SECTION OUTLET -5/" (1 mm) 1/2" CONDUIT KNOCKOUTS (4 TOTAL) -7/1" (214 mm) -3/4" (171 mm) FRONT COVER 1-13/1" (4 mm) 1-5/" (41 mm) 5-3/" (137 mm) 1 GA. STEEL ENCLOSURE REAR LEFT SIDE FIGURE 3 ASSEMBLY

Page of 12 NO. 1 2 3 4 5 DESCRIPTION QTY. Electronic Dry Pipe Accelerator, Vizor...... 1 Battery, 1.3 AH........ 2 1/2" Swing Check Valve. 1 1/2" Y-Strainer........ 1 1/2" Union........... 2 1/2" 90 Elbow........ 4 P/N 52-312-3-000 92-312-1-004 4-049-1-004 52-353-1-005 CH CH NO. 7 9 10 11 12 13 DESCRIPTION QTY. P/N 1/2" x Close Nipple.... 2 CH 1/2" x 1-1/2" Nipple.... 3 CH 1/2" x 4" Nipple....... 1 CH 1/2" x 7" Nipple....... 1 CH 1/2" x 9-1/2" Nipple.... 1 CH Select Nipple per Table. 1 CH Select Nipple per Table. 1 CH Nipple Number 12 13 Select Appropriate Nipple Sizes Per Riser Size 4 Inch (DN100) 1/2" x -1/2" 1/2" x 9" Inch (DN150) 1/2" x 5-1/2" 1/2" x 11" NOTES: 1. All Fittings and Nipples are galvanized (Standard Order) 2. CH: Common Hardware 1,2 VIZOR ELECTRONIC DRY PIPE 1,2 VIZOR ELECTRONIC DRY PIPE 7 TRIM CONNECTION TO DRY SYSTEM 4 9 5 7 11 10 5 13 3 12 MODEL DPV-1 DRY PIPE VALVE WITH TRIM 7 TRIM CONNECTION TO DRY SYSTEM 4 9 5 7 11 10 5 13 3 12 MODEL DPV-1 DRY PIPE VALVE WITH TRIM TRIM CONNECTION TO INTERMEDIATE CHAMBER TRIM CONNECTION TO INTERMEDIATE CHAMBER 4 INCH (DN100) INCH (DN150) FIGURE 4 TRIM ARRANGEMENT (52-312-3-001) LOCATE NEMA 1 BATTERY CABINET (P/N 52-312-3-002) 10'-0" (3 m) MAXIMUM FROM SPLICE SEPARATELY ORDERED INLINE FUSE HOLDER (P/N 92-312-1-00) AND 5 AMP FUSE (P/N 92-312-1-005) INTO POSITIVE RED HARNESS LEAD AND LOCATE WITHIN CABINET WHITE LEADS SPLICE (2) 1 GA. WIRES SUPPLIED BY INSTALLER INTO HARNESS BLACK LEAD CONNECT MODIFIED HARNESS TO CIRCUIT BOARD STORE (2) 12 V, 5 AH BATTERIES (P/N 92-312-1-003) IN CABINET AND ATTACH LEADS FIGURE 5 REMOTE 90 - HOUR STANDBY BATTERY FOR FM INSTALLATIONS LOCATE AT RISER MODIFY BATTERY HARNESS SUPPLIED WITH WITH SEPARATELY ORDERED PARTS AS INDICATED AND WITH MATERIALS SUPPLIED BY INSTALLER

Page 9 of 12 12" (300 mm) 12-3/4" (324 mm) 14" (355 mm) 27-1/2" (700 mm) LEFT SIDE FRONT 4 INCH (DN100) 11-1/2" (290 mm) 13-7/" (352 mm) 14-3/4" (375 mm) 29" (737 mm) LEFT SIDE FRONT INCH (DN150) FIGURE INSTALLATION DIMENSIONS FOR TYCO MODEL DPV-1

Page 10 of 12 NOTES: 1. 2. 3. Installation notations are typical for all Dry Pipe Valve models shown. Some items provided with VIZOR Accelerator Trim (P/N 52-312-3-001) may be used for retrofit. Field fabrication using additional materials will be required to facilitate connection to existing valve trim and riser connections. Placement of accelerator relative to existing riser assembly will vary. Controls and indicators on accelerator cover must be accessible, and hinged cover must be operable as shown. VIZOR ELECTRONIC DRY PIPE COVER COVER MUST BE ACCESSIBLE AND OPERABLE FIELD FABRICATE TO SUIT FROM 1/2" NPS PIPE AND FITTINGS FLOW SYSTEM RISER CONNECTION FLOW FLOW EXISTING VALVE TRIM TRIM CONNECTION TO INTERMEDIATE CHAMBER RIGHT SIDE VIEW RIGHT SIDE VIEW LEFT SIDE VIEW Refer to Data Sheets: Central 3 Inch Model AF, 10-3.2 (7-9), and 4 & Inch Model AF/AG, 10-4.0 (7-9) or 10-5.0 (7-9), Star Model A-1 2-2.1.31 (2-00) 4 Inch 2-2.1.41 (2-00) Inch Refer to Data Sheets: Star Model A 2-2.1.30 (-97) 4 Inch 2-2.1.40 (-97) Inch Refer to Data Sheet: Gem 4 & Inch Model F302/F3021 TD107 (11-97) FIGURE 7 INSTALLATIONS FOR DRY PIPE VALVES MANUFACTURED BY CENTRAL, GEM, AND STAR

Page 11 of 12 Care and Maintenance The TYCO VIZOR Electronic Dry Pipe Accelerator must be inspected and maintained in accordance with the NFPA. The following test procedures must be performed in addition to any specific requirements of the NFPA. Any impairment must be immediately corrected. Before closing a fire protection system main control valve on the system that it controls, obtain permission from the proper authorities to shut down the affected fire protection system and notify all personnel who may be affected by this action. In accordance with the requirements of NFPA 25 and 72, one of the trip tests described in this section must be performed quarterly. Battery tests also described here must be performed semi-annually and annually. The VIZOR Accelerator uses electronic components to monitor the system air pressure. Keep all radio transmitters or RF sources at least one foot from the VIZOR Accelerator. Failure to do so could result in an unintended operation of the dry pipe system. Notify the proper authorities and all personnel who may be affected before temporarily disabling the VIZOR Accelerator or performing an alarm test. The VIZOR Accelerator must be in a normal condition for 0 seconds before conducting a trip test. Failure to wait 0 seconds after air pressure has reached the normal level will result in a failed test. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (e.g., NFPA 25 and 72), in addition to the standards of any authority having jurisdiction. Contact the installing contractor or product manufacturer with any questions. Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection Service. Full Flow Trip Test: Valve and Accelerator Step 1. Open the Inspector s Test Connection. Verify that the VIZOR Accelerator trip-time is essentially the same as in previously performed tests. Also, make sure that the following notifications occur (Ref. Figure 1): Red Tripped LED lights Amber Trouble/Supervisory LED flashes 4 times per second (fast) Buzzer sounds High/Low Contacts transfer Step 2. Verify that the dry pipe valve tripped and that the time for water delivery to the Inspector s Test Connection is essentially the same as in previous tests. Step 3. After verification of water delivery to the Inspector s Test Connection, close the system s Main Control Valve and reset the system. Partial Flow Trip Test: Valve and Accelerator Step 1. Close the system s Main Control Valve and then open the system s Main Drain Valve to relieve the supply pressure to the dry pipe valve. Step 2. Partially open the system s Main Control Valve at least to the point at which water can be heard flowing though the system s Main Drain Valve, and then slowly close the system s Main Drain Valve. Step 3. Additional turns may be necessary to ensure latching of the appropriate dry pipe valve; refer to the appropriate technical data sheet. Step 4. Open the Inspector s Test Connection. Verify that the time-to-trip for the VIZOR Accelerator is essentially the same as in previous tests. A momentary burst of air from the dry pipe valve s automatic drain valve indicates that the VIZOR Accelerator has tripped. Also, verify that the following notifications occur (Ref. Figure 1): Red Tripped LED lights Amber Trouble/Supervisory LED flashes once per second (slow) Buzzer sounds High/Low Contacts transfer Step 5. Verify that the dry pipe valve tripped and waterflow alarms operate. Step. Immediately after verification of the dry pipe valve trip, close the system s Main Control Valve and reset the system. No Flow Trip Test: Accelerator Only Step 1. Close the system s Main Control Valve and then open the system s Main Drain Valve to relieve the supply pressure to the dry pipe valve. Step 2. Open the Inspector s Test Connection. Verify that the time-to-trip for the VIZOR Accelerator is essentially the same as in previous tests. A momentary burst of air from the dry pipe valve s automatic drain valve indicates that the VIZOR Accelerator has tripped. Also, make sure that the following notifications occur (Ref. Figure 1): Red Tripped LED lights Amber Trouble/Supervisory LED flashes once per second (slow) Buzzer sounds High/Low Contacts transfer Step 3. Reset the system. Battery Tests Perform the following tests to verify that the batteries are connected and working and to verify battery levels. Battery Connections Perform this test semi-annually. 1. Open the Battery Housing and unplug the Batteries from the VIZOR Accelerator circuit board. 2. Verify that the VIZOR Accelerator registers battery trouble and sounds the internal audible alarm. 3. Press S2 to the Silence position. 4. Plug the Batteries back into the VIZOR Accelerator circuit board and close the Housing. 5. Verify battery trouble clears. Battery Levels Perform a battery load test annually. An alarm-and-detection technician can perform this test.

Page 12 of 12 Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name. VIZOR Electronic Dry Pipe Accelerator (with Trim) Specify: VIZOR Electronic Dry Pipe Accelerator for use with the 4 or inch TYCO Model DPV-1 Dry Pipe Valve trim, P/N 52-312-3-001 Required batteries are ordered separately; see below. VIZOR Electronic Dry Pipe Accelerator (without Trim) Specify: VIZOR Electronic Dry Pipe Accelerator, P/N 52-312-3-000 Required batteries are ordered separately; see below. Separately Ordered Parts For the 24-Hour Battery, specify a quantity of 2 and P/N: 24-Hour Battery, 12 V, 1.3 AH...253 For the 90-Hour Battery, specify a quantity of 2, battery size, fuse, fuse holder, and cabinet with P/Ns: 90-Hour Battery 12 V, 5 AH...254 Fuse, 5 A........................... 257 Fuse Holder......................... 255 90-Hour Battery Cabinet, in. x 4 in. x in. (203 mm x 102 mm x 203 mm)....52-312-3-002 1400 Pennbrook Parkway, Lansdale, PA 1944 Telephone +1-215-32-0700 201 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association