Assessing the Condensate-Drainage Behavior of Dehumidifying Heat Exchangers

Similar documents
Off-Cycle Condensate Drainage Behavior of Compact Heat Exchangers: Assessment and Enhancement

The Effects of Hydrophilicity on Water Drainage and Condensate Retention on Air-Conditioning Evaporators

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Effect of Inclination Angle on the Air-Side Performance of Aluminum Parallel Flow Heat Exchangers Under Wet Conditions

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Purdue e-pubs. Purdue University

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Open-Cell Metal Foams for Use in Dehumidifying Heat Exchangers

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

Heat Transfer of R-22 and Alternatives in a Plate- Type Evaporator

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Effect of the Use Pattern on Performance of Heat Pump Water Heater

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Efficiency of Non-Azeotropic Refrigerant Cycle

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

2.2. General view of Microchannel Heat Exchangers

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Mini Vapour Cycle System For High Density Electronic Cooling Applications

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

2. HEAT EXCHANGERS MESA

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Experimental Study on the Performance of Twisted Capillary Tube

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners

MAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Low GWP Refrigerants for Air Conditioning Applications

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Performance of CO2 Cycles with a Two-Stage Compressor

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

Compressor Capacity Control

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

Compression of Fins pipe and simple Heat pipe Using CFD

Air-Cooled Heat Exchanger Performance for R410A

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Sub-Critical Operation of the CO2 Expander/ Compressor

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Global Journal of Engineering Science and Research Management

Study of R161 Refrigerant for Residential Airconditioning

Fifteen Years of Dehumidification Results from Heat Pump Water Heaters

NOVEL COMPACT SORPTION GENERATORS FOR HEAT PUMP APPLICATIONS

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

MINIATURE HEAT TRANSPORT SYSTEMS WITH LOOP HEAT PIPES

Refrigerant Mass and Oil Migration During Start-up Transient

Control Method Of Circulating Refrigerant Amount For Heat Pump System

EXPLORING POSSIBILITIES WITH THE DEVELOPMENT OF THE LOOP HEAT PIPE TECHNOLOGY. Roger R. Riehl

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING SYSTEM

Heat sinks for electronic cooling applications

PASSIVE HEAT EXCHANGER ANTI-FOULING FOR SOLAR DHW SYSTEMS

Experimental Comparison of Natural Convection Heat Transfer from a Blackened V-Fin Array

Design Optimization of Variable Geometry Microchannel Heat Exchangers

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Enhancement of Heat Exchanger Performance by the Extended Surfaces-Fins

Optimizing Chemistry and Coater Settings for Faster Drying

Physical Mechanism of Convection. Conduction and convection are similar in that both mechanisms require the presence of a material medium.

Exercise 2-4. Heat Exchangers (Optional Exercise) EXERCISE OBJECTIVE DISCUSSION OUTLINE. Description of a brazed plate heat exchanger DISCUSSION

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Simultaneous Heat and Mass Transfer in a Wetted Heat Exchanger, Part I: Experiments

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Effect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators

Evaluation of Mechanical Dehumidification Concepts (Part 2)

R32 Compressor for Air conditioning and Refrigeration applications in China

Numerical Evaluation of Performance Curves of a High Frequency Microcompressor

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 4 Assessing the Condensate-Drainage Behavior of Dehumidifying Heat Exchangers Arindom Joardar University of Illinois at Urbana-Champaign Zhong Ping Gu University of Illinois at Urbana-Champaign Anthony M. Jacobi University of Illinois at Urbana-Champaign Follow this and additional works at: http://docs.lib.purdue.edu/iracc Joardar, Arindom; Gu, Zhong Ping; and Jacobi, Anthony M., "Assessing the Condensate-Drainage Behavior of Dehumidifying Heat Exchangers" (4). International Refrigeration and Air Conditioning Conference. Paper 639. http://docs.lib.purdue.edu/iracc/639 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

R087, Page 1 ASSESSING THE CONDENSATE-DRAINAGE BEHAVIOR OF DEHUMIDIFYING HEAT EXCHANGERS A. JOARDAR, ZHONGPING GU and A. M. JACOBI Department of Mechanical and Industrial Engineering, University of Illinois at Urbana-Champaign, 1206 West Green Street Urbana, IL, 61802, USA Tele: (2170 649-3162 Fax: (217) 244-6534 E-mail: a-jacobi@ uiuc.edu ABSTRACT Contemporary compact heat exchangers often employ very high fin densities. In many air-conditioning applications such as automotive cooling, the heat exchanger operates to dehumidify the conditioned air. It has been observed that the amount of condensate retained on the air-side surface significantly increases with increased fin density. Retained condensate not only affects the thermal-hydraulic performance, but it also has adverse implications on the quality of conditioned air. Conventional wind tunnel experiments to assess performance are expensive. A method for characterizing water drainage from heat exchanger surfaces, the so-called dynamic dip test, is described. The dynamic dip test is explored as a fast and efficient method for comparative and screening studies for applications where off-cycle drainage is important. Results from more than 30 automotive-style heat exchangers are presented, and condensate drainage characteristics are explored to assess surface tension effects in inter-fin and louver gaps of highfin-density, compact heat exchangers. 1. INTRODUCTION In a quest for high thermal performance, contemporary compact heat exchangers often employ very high fin densities. In many air-conditioning applications, particularly automotive systems, the aircooling heat exchanger operates to dehumidify the conditioned air for passenger comfort. It has been observed that the amount of condensate retained on the air side surface during dehumidification process, significantly increases with increased fin density. This retention is due at least in part to the capillarity effects in the narrow fin and louver spaces. Retained condensate not only affects the thermal-hydraulic performance of heat exchangers used in such applications, but also has adverse implications on quality of conditioned air. The retained water increases the pressure drop across the heat exchanger by restricting the flow of air. Apart from pressure drop penalty, the retained condensate could cause fouling of surface and provide medium for biological activity leading to unpleasant odours with conditioned air. With growing concerns about the impact of quality of conditioned air on human health, air-quality issues cannot be ignored in surface design. While there has been some research on condensate retention and its thermal-hydraulic effects under steady-state conditions, there is very little work available in the open literature addressing condensate drainage in off cycle operation. 1.1 Literature Review In 1999, Osada and co-workers [1] performed heat transfer and visualization experiments on single fin columns of flat tube evaporators. They investigated the effects of surface wettability, louver geometry, and inclination angle on condensate drainage. They concluded that fin geometry near the exit face of the heat exchanger is important due to accumulation of driven water which must drain either through louver slits or down the exit face. The louver length was also found to influence drainage

R087, Page 2 behaviour increasing the distance from the tube to beginning of louver cut can increase condensate retention effects. Mclaughlin and Webb [2] studied the impact of fin geometry on drainage using a tabletop test cell for experiments with single-fin column. Their results suggest louver pitch to be the single most important parameter determining drainage characteristics of louvered fin evaporators. They state that a critical louver pitch between 1.1 and 1.3 exists for a louver angle of 30 o at which condensate retention increased by 26%. Kaiser et al., [3] studied the condensate drainage behaviour in automotive heat exchangers. They compared the dip test method to real time retention results obtained from wind tunnel experiments. The coils retaining the most and least condensate in a steady state wind tunnel experiment, likewise held the most and least in a dip test. They concluded that dynamic dip testing could be powerful tool for assessing the condensate retention behaviour of heat exchangers. Zhong and Jacobi [4] introduced a new experimental technique of dynamic dip-testing to study off-cycle condensate drainage behaviour. A preliminary model based on gravity, surface tension and viscosity effects was developed to predict the drainage behaviour of round-tube-and-fin heat exchangers. 1.2 Objectives The objective of this work is to characterize the drainage behaviour of compact heat exchangers used for automotive systems. In order to quantitatively assess the drainage behaviour of heat exchangers, the so called dynamic dip test was performed. The procedure involves immersing the coil in a tank of water, dropping the water level quickly, and measuring the mass of retained water as a function of time. The mass retained after 30 minutes was deemed as steady state retention. This parameter was used to characterize drainage performance and assess drainage enhancing methods. 2. EXPERIMENTAL APPARATUS AND PROCEDURE 2.1 Experimental Apparatus A schematic diagram of the dynamic dip-test apparatus is shown in Figure 1. The setup consisted of a large water reservoir, a smaller submerged air tank to control the water level using pressurized air, and a supporting structure for mounting and weighing the heat exchanger. The volume of the large reservoir was about 1 m 3 and the smaller displacement tank was 0.4 m 3. A pipe of mm diameter was used as an air passage. The heat exchanger was suspended from an electronic balance using a fixed acrylic frame and simple mounting hardware. The mounting arrangement depended on the particular orientation to be tested. For testing in vertical orientation, heavy wire was looped under the top tank or manifold and interlocked with the frame to provide a stable rigid support that did not interfere with drainage. In the case of testing in an inclined orientation, a special mounting bracket was used to provide rigid, nonintrusive support for the specimen. A computer-based data acquisition system with a recording interval of 1 second was used for monitoring and recording data. The system was comprised of a Sartorius precision balance with a built in serial RS232 port and a personal computer. Winwedge TM software was used for data recording in a text file. The balance was calibrated to an accuracy of ±0.1 grams. 2.2 Experimental Conditions and Procedures 1. Before an experiment, the displacement tank was filled with water, and a test coil was suspended over the water reservoir. The balance was levelled using the built-in spirit level. In order to initiate an experiment, the balance was turned on and zeroed, and a final heat exchanger alignment was checked with a spirit level for vertical orientation and with plumb/protractor for inclined coils. 2. The air vent was then closed, and the pressurized air supply was used to fill the displacement tank, causing the water level to rise and submerge the test specimen. Once the specimen was submerged, the air supply was closed. Due to the buoyancy effects the scale showed a negative reading at this point. 3. The water in the tank was agitated, and a fine brush was used to remove bubbles from the heat exchanger surface. The air vent was then suddenly opened to allow water into displacement tank. The water level in the main reservoir dropped rapidly and faster than about 0.2 m/sec.

R087, Page 3 After the air release there was an increase in scale reading to a maximum due to decreasing buoyancy force; the maximum occurred when the water level dropped below the coil bottom. This maximum was taken as time, t=0 (i.e. this moment is the start of the drainage process for the purposes of presenting the data). This procedure provides the equivalent to a dip. 4. As water drained from the specimen, the amount of water retained on the surface was recorded by the data acquisition system. Data recording was terminated manually after 0 seconds. Repeated experiments were conducted starting with both dry and wet heat exchangers to check for hysteresis. 5. The recorded data were then normalized in a spreadsheet by dividing by the total wetted surface area and nominal core volume of the heat exchanger and plotted against time. PRESSURIZED AIR LINE IBMCompatible ELECTRONIC SCALE AIR VENT Tape drive WATER AIR PUMP HEAT EXCHANGER WATER Figure 1. Schematic diagram of dip-test apparatus. 3. DYNAMIC DIP TESTING RESULTS The heat exchanger specimens used in this work were flat-tube louvered-fin heat exchangers common to automotive applications. The coils were all aluminium. The evaporator consisted of flat tubes brazed to columns of fins, with a header (manifold) at the top (and bottom in some cases) of the core this geometry is sometimes referred to as a brazed-plate-and-serpentine-fin heat exchanger The comparative study involved testing of more than 30 compact heat exchangers for the purposes of performance evaluation and to seek improvement methods for reducing condensate retention. In particular, the effects of increased fin density, surface coating or treatment, and coil geometry at the drainage exit region on the steady-state retention were investigated. Efforts were also made to identify the causes of water retention. It was found that as the fin density of a coil increases, surface tension effects become increasingly dominant, and inter louver bridges form, leading to enhanced retention. In this section results from dip testing will be presented for all the heat exchangers tested as part of this work. Multiple experiments were conducted starting with dry and wet surface to assess the repeatability of the data. In general, for the same coil the experimental results were found to be highly repeatable. Most of the results presented here pertain to vertical orientation of the coil and are normalized both with respect to total heat transfer surface area and nominal core volume. A summary of the geometrical description of various test-specimen coils is given in in Table 1. The various exchangers will be referred to by their numbers as appearing in the table.

R087, Page 4 coil External Dimensions (HxWxD) (mm^3) Number of Tanks Table 1 Specimen geometrical data Fin Dimensions Thickness (mm) Fin Pitch (mm) Coated Tube No. Tube Dimensions Width (mm) 1 240 x 254 x 58 Single 0.09 1.59 NA 23 1.88 58 2 215 x 241 x 89 Double 0.09 2.12 NA 21 3.05 89 3 220 x 264 x 75 Single NA 1.81 NA 22 NA 75 4 229 x 259 x 73 Double NA 1.95 NA 20 NA 73 5 229 x 259 x 73 Double NA 1.95 NA 20 NA 73 6 215 x 241 x 89 Double 0.09 2.12 NA 21 3.05 89 7 240 x 235 x 58 Single 0.09 1.59 NA 21 1.88 58 8 235 x 232 x 58 Single 0.09 1.69 NA 21 1.88 58 9 238 x 229 x 58 Single 0.09 1.81 NA 21 1.88 58 10 235 x 232 x 58 Single 0.09 1.59 NA 21 1.88 58 11 215 x 240 x 89 Double 0.09 2.12 No 21 3.05 89 12 215 x 240 x 89 Double 0.09 2.12 Yes 21 3.05 89 13 213 x 230 x 90 Double 0.09 2.12 NA 19 3.05 90 14 205 x 215 x 80 Single 0.09 2.31 NA 17 2.79 80 15 217 x 205 x 90 Double 0.09 2.12 NA 18 NA 90 Depth (mm) Dynamic dip test results in the form of mass per unit heat transfer area as a function of time are shown in Figure 2 for coils 1 to 4. The general behaviour of the data shows a monotonic decrease in retained water. However, it is interesting to note the significant variation in the rate of decrease. Coils 1 and 2 are at two extremes of the spectrum of drainage pattern. Coil 1 has high fin density and is single-tank coil, in contrast to the double-tank configuration and lower fin density of coil 2. Coils 3 and 4 are somewhat intermediate cases from a geometric viewpoint. At the end of 0 seconds, Coil 1 held 137.8 g/m 2 and coil 2 held 97.95 g/ m 2. Apparently, the drainage behaviour and retention in coils of the type 1 and 3 are dominated by surface tension forces and to a lesser degree by viscous forces. More than 80% of the water that will eventually leave the coils drains during first seconds. On the other hand, coils of type 2 continue to drain even after the initial seconds at a good rate, and it seems that gravitational and viscous forces are important in dictating the drainage pattern in these cases. Another interesting feature is the early drainage behaviour over the first 15 seconds. Coil 1 has a sharp transition to a steady state after initial free-fall type drainage, in contrast to the slow transition for Coil 2. Once again, Coils 3 and 4 are intermediate in behaviour. It is difficult to ascertain the exact causes for these patterns, but they may be due to geometrical differences between the coils. The effect of coil tilt on drainage behaviour is shown in Figure 2 (b). The figure demonstrates that tilting does not profoundly affect nature of drainage pattern but the amount of retained water at any given time is less when the coil is tilted. This reduction varies quite significantly from coil to coil. At the end of 0 seconds, the reduction achieved by 10 o tilting was 25%, 11.7% and 23.3% for Coils 1, 3 and 4. For Coil 2 the reduction was 55.6%. The dramatic improvement seen for Coil 2 can be understood in the light of the fact that it is far less compact in comparison to the other coils and hence the resistance to drainage due to surface tension effects is less. Figure 3 presents the dip test results for coils 5 and 6. Coil 5 performs better than 6 in the vertical orientation but coil 6 outperforms 5 in an inclined position. As mentioned above, in an inclined position the drainage from coil 6 was greater because it was less compact than 5. The reasons for the superiority of coil 5 in the vertical position are not clear, except perhaps for the surface coating. Coil 5 was dimensionally identical to Coil 4. The results were also plotted after normalizing with core nominal volume and conclusions remained unchanged.

R087, Page 5 Hxgr 1 Hxgr2 Hxgr 3 Hxgr 4 Hxgr 1 Hxgr 2 Hxgr 3 Hxgr 4 0 0 0 0 (a) 0 0 0 0 (b) Figure 2. Dynamic dip test results for drainage as a function of time, showing distinct patterns. (a) Vertical orientation (b) Inclined (10 o ) position. Hxgr 5 Hxgr 6 Hxgr 5 Hxgr 6 (Gms / m 2 ) 0 600 800 0 1 1 (a) 0 0 600 800 0 1 1 (b) Figure 3. Comparison of dip test results for coils 5 and 6. Coil 5 performs better in vertical position and coil 6 out performs 5 in tilted orientation. (a) Vertical (b) Tilted by 10 o. The effect of fin density and fin geometry on drainage was investigated using coils 7 to 10 which were of very similar in overall size and construction. Coil 7 was very similar to Coil 1, with 1.59 mm fin pitch and a triangular fin shape when viewed from either face of the heat exchanger. The fin shapes for coils 8 to 10 were rectangular, with a fin pitch of 1.69, 1.85 and 1.59 mm, respectively. The dip test results are presented in Figure 4(a). As expected, for similar coils an increase in fin density results in increased retention. However, over 0 seconds the differences are smaller and were within 8% of each other. Therefore, it appears an increase in fin pitch did not have a significant effect on long-time, steady state retention. On the other hand, the impact of fin geometry was dramatic. Coil 7 with triangular fins (viewed from the face) held 52.2% more water compared to its rectangular counterpart, Coil 10. The results clearly demonstrate the importance of surface tension effects on drainage behaviour and retention. Visual inspection of Coil 7 during experiments revealed accumulation of water between fin surfaces in the vicinity of the fin base. Apparently water was drawn up to the fin base and held there by capillarity effects. For the rectangular shape, much greater fin density is necessary for capillarity effects to become important.

R087, Page 6 Hxgr 7 (?,16 fpi) Hxgr 8 ( 15 fpi) Hxgr 9 ( 14 fpi) Hxgr 10 (16 fpi) 0 600 800 0 1 1 Figure 4 Dip testing results for coils 7 to 10 show the effect of fin density and geometry on drainage behaviour. The fin geometry of Coil 7 triangular and others are rectangular when viewed from air exit side. Hx 11 (No Coating) Hx 12 (Coated) 0 600 800 0 1 1 Figure 5 The effect of surface coating on drainage behaviour. Coils 11 and 12 were identical except for the surface coating. Figure 5 demonstrates the effect of surface coating for enhanced wetability. Coils 11 and 12 were identical in every respect, except for the coating on Coil 12. The surface coating improved the drainage performance by 11.2 % over 0 seconds duration. The drainage pattern remained almost identical for both the coils. The dip test data for coils 13 to 15 are presented in Figure 6(a). The results are normalized both with respect to total heat transfer surface area and nominal core volume. Test specimen 14 was a single header, louvered-fin heat exchanger, and the other two were double-header-type coils. The results suggest that in general coils with two headers on either end of the coil are inherently better drainers than single-header heat exchangers. Normalization of data either by area or volume did not introduce any differences in these conclusions. The exact causes for such wide difference in performance between Coil 14 and that of 13 and 15 could not be established in the absence of louver geometry data. However it was observed that single header coils suffer from the disadvantage of having a closed bottom for structural integrity. It is intuitively clear that the bottom area through which drainage takes place should be relatively open and clear to

R087, Page 7 facilitate free passage of water. The end-plates could block the passage of condensate and cause increased retention. In order to investigate such a possibility, dip-testing experiments were conducted on the same coil with and without these end plates. Figure 6(b) presents the real-time drainage plots and it is observed that the heat exchanger without bottom plates held 15% less compared to the same coil with bottom plates. The tests were repeated twice under fully dry conditions to check for repeatability. H xgr 13 H xgr 14 H xgr 15 With End Pla tes No End Plates 1 No End Plates 2 0 600 800 0 1 1 (a) 0 600 800 0 1 1 (b) Figure 6 (a) The dip testing results for coils 13 to 15. Coil 14 was single tank type as opposed to double tanks for coils 13 and 15. (b). The effect of bottom end-plates on condensate retention. The coil without bottom retains 15% less water compared to the original. In order to ascertain how representative the dip test results are to a particular class of heat exchangers, an investigation was conducted by choosing a batch of 5 random coils and comparing their steady state retention. The 4 different classes of heat exchanger chosen were coil 6, 13, and 14 with and without coating. For each coil, multiple experiments were performed starting from dry and wet conditions to assure repeatability for that particular specimen. The results for only coil 6 and 14 (without coating) are presented here in Figures 7(a) and (b). The standard deviations were 5.2%, 6.52%, 5.56% and 10.52%, respectively which is not significant except for the last case. It is difficult to draw conclusions regarding the observed deviations, but it is apparent the results presented in this work are repeatable. 4 4 Hxgr 6 C oil 1 C oil 2 C oil 3 C oil 4 C oil 5 Hxgr 14 C oil 1 C oil 2 C oil 3 C oil 4 C oil 5 0 600 800 0 1 1 (a) 0 600 800 0 1 1 (b) Figure 7 Dip test results for 5 identical heat exchangers. (a) Coil 6: Mean - 53.14, Std Deviation- 5.2%. (b) Coil 14 (without coating): Mean 140.28, Std Deviation-10.52%.

R087, Page 8 4. CONCLUSIONS? Two distinct drainage patterns were observed. One exists for compact heat exchangers which make a rapid transition to the steady state condition after the free-fall regime. Another type shows a more gradual transition and in some coils no distinct steady state regime exists.? In comparing different coils under vertical and inclined orientations, the results depend on whether gravitational or surface tension dominate, but in general inclination reduces steady state retention by roughly 20%.? It is believed that surface tension effects play a dominant role in water retention for high fin density coils.? Fin shape seems to have a dramatic influence on water retention. Coils with rectangular fin arrangements (i.e., the serpentine was rectangular) and corrugated louver edges were found to have 52.2% lower retention compared to the same coils with triangular, straight edge louver fins.? Apart from fin geometry, the louver geometry can also play an important role in condensate retention. However, in the absence of relevant data no firm conclusions can be drawn from our testing, but the literature suggests louver geometry is important.? Another factor contributing to retention was the construction and geometry at the bottom of the coil. In general, coils with two headers performed better than single-header heat exchangers, due to a more open bottom. It is important that the bottom area through which drainage takes place remain open and clear to facilitate free passage of water.? For the single header Coil 15, about a 15% improvement in drainage could be achieved by cutting out the bottom plates. However, it is imp ossible to isolate this performance to the bottom plates; it might be related to other geometry changes (damaged fins). REFERENCES Kaiser, J., Y. Zhong, A. M. Jacobi, C. Zhang and H. Hu, 3, Condensate Retention and Dynamic Drainage from the Air-Side Surface of Automotive-Style Heat Exchanger, Proc.Int. Conf. Compact Heat Exchangers and Enhancement Tech. for the Process Industries 3, p. 361-366. McLaughlin, W.J. and Webb, R.L., 0, Condensate Drainage and Retention in Louver Fin Automotive Evaporator, Proc. SAE Int. Cong., Detroit, MI: SAE paper 00HX-34. Min, J. and R. L. Webb, 2, Long-Term Wetting and Corrosion Characteristics of Hot Water Treated Aluminum and Copper Fin Stocks, Int. J. Refrig., vol. 25: p. 1054-1061. Osada, H., Aoki, H., Ohara, T. and Kuroyanagi, I., 1999, Experimental Analysis for Enhancing Automotive Evaporator Fin Performance, Proc. Int. Conf. Compact Heat Exchangers and Enhancement Tech. for the Process Industries-1999, p. 439-445. Zhong, Y. and A.M. Jacobi., 3, Dynamic Dip-Testing to Assess the Condensate-Drainage Behaviour of De-Humidifying Heat Exchangers. Proc. 2 nd Int. Conf. on Heat Trans., Fluid Mech. and Thermodynamics, vol. 1, p. 560-567.