BRIZA 041/055 WALL / CEILING BRIZA 038/052 BUILT-IN WALL / CEILING Installation Instructions Briza 2 pipe & 4 pipe

Similar documents
BRIZA 12: Stand Alone / Built-In INSTALLATION INSTRUCTIONS: BRIZA12 - WALL AND CEILING

CLIMA CANAL HYBRID CLIMA CANAL. Low Water Temperature system LOW TEMPERATURE SYSTEM / HEATING AND COOLING LOW TEMPERATURE SYSTEM / HEATING

BRIZA EC 12 HYBRID. Low Water-Temperature system LOW TEMPERATURE SYSTEM / HEATING AND COOLING

BRIZA_038. EC MOTOR Briza Hybrid: High performance technology

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60

Quatro canal Super-powered climate control for 4-pipe systems

ST1. Mod. USE AND MAINTENANCE MANUAL

Instructions for installation and use English. More documents on: H B /09

QUATRO CANAL 2019.EX

SAFEGUARDING THE ENVIRONMENT IMPORTANT NOTES BEFORE USING THE OVEN OVEN ACCESSORIES CARE AND MAINTENANCE TROUBLESHOOTING GUIDE AFTER SALES SERVICE

Read this manual through carefully before installing/using the cleaner, paying special attention to the SAFETY INSTRUCTIONS

User Manual GV25 GV35 GV702. Company information: Original instructions GV12066 (1)

BRIZA Super slim and powerful heating, cooling

SAFEGUARDING THE ENVIRONMENT IMPORTANT NOTES BEFORE USING THE OVEN OVEN ACCESSORIES CARE AND MAINTENANCE TROUBLESHOOTING GUIDE AFTER SALES SERVICE

FREEDOM 2019.EX CZ - 21/11/18

FUN I / FUN U FUN I MCP / FUN U MCP FUN V / FUN V MCP

INSTRUCTIONS FOR USE. To make the most of your new oven, read the user's instructions carefully and keep them on hand for consultation in the future.

Type CODE Speed Heating Cooling

G-7s. Instruction Manual. G-Series Cooler COUNTERTOP COOLER. Part No.11IPA

Instructions for installation

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit

GB User and maintenance manual

HVG620 & HVG720 Gas Hob Manual for Installation, Use and Maintenance

WINDOW TYPE ROOM AIR CONDITIONER OPERATION AND INSTALLATION MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

51AKS I S O OWNER S MANUAL

THROUGH-WALL AIR-TO-AIR HEAT PUMP AND AIR CONDITIONER. Instruction Manual. Model AMB-12H

GCG-10. Instruction Manual. G-Series Cooler. Manual is for the following models: GCG-10-N33EB G-10-N33EB UPRIGHT COOLER

Flameproof Manual Call Points

Manual is for the following models: G-26 GCG-26 GCG-26-C31N* G-26-C31N* GCG-26-C231N* GCG-26-CA31N* *G,I,M,7,J plug. Instruction Manual.

CLIMA CANAL. Complete climate control and high power

E-COMBI EVO E-SYSTEM EVO

PORTABLE AIR CONDITIONER (LOCAL)

CLIMA CANAL Complete climate control and high power

G-10s. Instruction Manual. G-Series Cooler UPRIGHT COOLER. Part No.11IPA

QTS SELECTION TECHNICAL BOOKLET

CLIMA CANAL Lyngson as

Installation manual Mini Comfort 50 S/L 07/ V EN

GUH90 90 cm Canopy Hood

MHG201 Gas Hob Manual for Installation, Use and Maintenance

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Installation Operation Maintenance

PORTABLE AIR CONDITIONER (LOCAL)

GCG-9. Instruction Manual. G-Series Cooler. Manual is for the following models: GCG-9-N13EB G-9-N13EB GCG-9-B13EB UPRIGHT COOLER

VR60 GLASS FROSTERS INSTALLATION AND OPERATING MANUAL PLEASE LEAVE WITH OPERATOR. VR60 Glass Froster. Series 1

HEAT RECOVERY AIR HANDLING UNIT

OPERATING INSTRUCTIONS

FAITH (dmev) 230V / 24V DC SELV Flush Mounted Domestic Continuous Extract Fans

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Installation and Operating Instructions

Stainless Steel Chimney Extractor

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

Pedestal Range. Installation and user manual. Kiosk. Trafalgar. Tube. Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk

Table of Contents. Forward Quality Policy Design Parameters Section A Unit Operation Section B Unit Maintenance...

USER GUIDE. IMAX XTRA EL kW. For Installation Guide see reverse of book

G-10f/GCG-10f UPRIGHT COOLER

AIR CONDITIONER OWNER S MANUAL. Please read this manual carefully before operating your set and retain it for future reference.

Glass Chimney Hood. Installation & User Instructions Please keep for future reference

Welcome. Important Safeguards. Please read the Manual carefully before operating the machine ELECTRICAL CONNECTIONS:

Instruction Manual for Electric Ovens OO757X OO986X

06/2012. Mod: BMIV20/TP. Production code: 18G

K-Star International Group Inc. K-Star Electronic Appliance Inc. Toll Free:(800)

BRISE. Heating and cooling from a single radiator

40KMC KMQ

EH0554 Indoor Climate Control

MODEL 598A TWO-SPEED PLUS CENTRAL AIR CONDITIONER

User and maintenance manual

Operating instructions Page 12

LONGONI ENGINEERING SRL

Cooker Hood LA-72-CAN.

Double Door - Dual Zone Wine Cooler

INSTALLATION, USE AND MAINTENANCE MANUAL HIGH PRESSURE FAN COIL FOR PROFESSIONAL APPLICATIONS, BUILT-IN VERSION

isense & isense-ht 230V Flush Mounted Domestic Continuous Extract Fans

ST E /ST E / ST E / ST E ST E / ST E / ST E

IU-PSINV-HW12R IU-PSINV-HW16R IU-PSINV-HW18R IU-PSINV-HW25R

SAFETY INSTRUCTIONS IMPORTANT TO BE READ

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table)

Built-in single oven instruction manual C2233 / C2233BK. Contact Caple on or for spare parts

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual

OVENS AUS. Installation - Use - Maintenance. Oven models: 60cm Built in Ovens

30-pint Dehumidifier User Guide

AIR CONDITIONER OWNER S MANUAL. Please read this manual carefully before operating your set and retain it for future reference.

Sundirect Infrared Panel Heaters. Installation & Operation Instructions

OPERATING INSTRUCTIONS

Open Vented Condensing Boilers

Built-in Conventional Oven

Instructions for use

GCG-26c. Instruction Manual. G-Series Cooler

REG-183J REG-253J RADS-151J RADS-183J RADS-253J RAD-283J

TTV 1500 / TTV 3000 OPERATING MANUAL CONVEYING FAN TRT-BA-TTV TC EN

INSTRUCTION AND MAINTENANCE MANUAL DRYERS A5 - A6 - A7 - A7,5 - A8 - A9 - A10

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

XD-125 OWNER S MANUAL COMMERCIAL DEHUMIDIFIER

Installation and operating instructions. DK energy storage and DK energy buffer

INSTALLATION INSTRUCTIONS: these are intended for the qualified technician who must carry out the installation, hook-up and testing of the appliance.

Central Air Conditioning System

Owner s Information Manual

INSTALLATION GUIDE NZ AU C

INSTRUCTION AND MAINTENANCE MANUAL

AUTOMATIC MODULAR ICE FLAKER

Transcription:

BIZ 041/055 WLL / CEILING BIZ 038/052 BUILT-IN WLL / CEILING Installation Instructions Briza 2 pipe & 4 pipe Deze handleiding is beschikbaar in het NEDELNDS: http://theradiatorfactory.com/briza_benl Ce manuel est disponible en FNÇIS: http://theradiatorfactory.com/briza_befr http://theradiatorfactory.com/briza_fr Dieses Handbuch ist erhältlich in DEUTSCH: http://theradiatorfactory.com/briza_de This manual is available in ENGLISH: http://theradiatorfactory.com/briza_e http://theradiatorfactory.com/briza_e_imperial Please read this manual carefully before installing. Installation must only be carried out by skilled technicians. The unit must be installed according to national or local standards in force at the time of installation. lways use personal protective equipment. NBN EN60335-1 based on EN60335-1-2002 + a11:2004 + a1:2004 + a12:2006 + a2:2006 + a13:2008 + 14:2010 + 15:2011 NBN EN 60335-2-80 based on EN 60335-2- 80:2003 + 1:2004 + 2:2009 E / 27200.23700029-7 september 2016 3:49 PM - Jaga N.V. BIZ EC 1

User Device description: Jaga Briza EC are fan coils for the treatment of air in indoor environments. The units comply with the following Directives: 2006/42/EC Machinery Directive low voltage Directive 2006/95/EC electromagnetic compatibility Directive 2004/108/EC regulation n.327/2011/ue implementing Directive 2009/1/EC EP Declared conditions of use: The unit is not designed to be installed in rooms used for laundry purposes (IEC EN 60335-2-40). the unit is only to be installed in domestic or similar environments. it is prohibited to insert objects through the air inlet and outlet vents. IMPOTNT! the unit will function correctly only if the instructions for use are strictly followed, if the specified clearances are complied with during installation, as well as the use restrictions indicated in this manual. an installation that does not include the recommended free spaces, resulting in difficulty in maintenance and reduced performance pay the utmost attention to the signs and symbols located on the appliance. Identification of the unit: The units are equipped with a label sharing the serial number plate on the right side of the unit (on the left if the connections are on the right side of the unit). Functioning limits: Installation that does not meet the operating limits specified relieves Jaga N.V. from liability concerning damage to objects and persons. mains voltage 230 V 1 ph 50 Hz. maximum water inlet temperature: 3 90 c. maximum exchanger pressure: 6 bar. power supply voltage: 24 V ±10% Information regarding unintended use: The unit has been designed and constructed solely and exclusively to function as an air treatment terminal unit with ducting or panelling; any other use is strictly forbidden. Installing the Jaga Briza EC in an explosive environment is prohibited. Decommissioning: When the unit is not used for long periods of time, it must be disconnected from the mains by opening the mains switch of the system, set in place by the installer. If the unit is not used during the winter period, the water contained in the system may freeze. ll the water in the circuit must be drained on time. lternatively, a suitable quantity of anti-freeze liquid should be mixed with the water. estart after prolonged shutdown: Before starting up again: clean or replace the air filter. clean the exchanger. clean or unclog the drain of the condensate tray. bleed the water system. it is advisable to run the unit at maximum speed for several hours. Instruction for installation, handling and storage Packaging and components Follow these instructions to remove the packaging: check for any visible damage open the packaging check if the manual is in the package remove the packaging material and dispose it in the appropriate collection points or recycling facilities, in compliance with the local regulations SFEGUD THE ENVIONMENT Dispose of the packaging materials in compliance with the national or local legislation. DNGE! Do not leave the packaging within reach of children. Handling guidelines: DNGE! Movement of the unit must be performed with care, in order to avoid damage to the external structure and to the internal mechanical and electrical components. lso make sure that there are no obstacles or people along the route, in order to prevent the risk of impact, crushing or tipping the lifting device. lways use personal protective equipment. ll the operations listed below must be carried out in accordance with current health and safety regulations, with reference to the equipment used as well as the procedures followed. Before commencing handling operations, ensure that the lifting device has the required capacity for the unit in question. The units can be moved or lifted by hand or by means of a suitable truck. If the unit weighs more than 30 kg and is to be handled manually, this must be carried out by two persons: however, it is recommended to use a truck. If several units need to be moved at the same time, it is advisable to put the units in a container and lift them by means of a crane or similar vehicle. Storage conditions: Packaged units can be stored by stacking a maximum of four on top of each other and must be stored in a dry area. Technical spaces and positioning: IMPOTNT! Incorrect positioning or installation of the unit may amplify noise levels and vibrations generated during operation. 2 BIZ EC E / 27200.23700029-7 september 2016 3:49 PM - Jaga N.V.

Maintenance TTENTION! maintenance must only be carried out by qualified technicians, qualified to work on air-conditioning and refrigeration systems. Use suitable work gloves. do not insert sharp objects through the air flow or intake grilles Special note: Maintenance and cleaning of the grate: a dirty grate obstructs the flow of air to the ventilator, so clean the grate at regular intervals, depending on the usage and function of the room. The grate must not be dismantled for maintenance and can simply be cleaned with a vacuum cleaner Cleaning the appliance: always disconnect and lock out power before installing or servicing the fan!! cleaning at regular interval is important, (at least once a year), depending on the use and function of the room clean with a soft cloth dampened with water and a little dish soap. Do not use products based on solvents and detergents. Monthly: Checking the air filters The level of pollution of the filters must be checked at the beginning of the season when the unit will be used and generally every month. Every 6 months: Check the condition of the exchanger and condensate drain. If necessary: remove any debris from the finned surface to clear the air passage remove the dust using compressed air gently wash with water and brush gently dry using compressed air keep the condensate drain free from any obstructions that may prevent normal water flow outine maintenance Checking whether there is air in the water system. 1. start the system for a few minutes 2. stop the system 3. loosen the vent screw on the inlet collector and bleed it 4. repeat the operation several times until air is no longer released from the system. End of season Draining the water system (for all exchangers). It is advisable to drain the water from the system at the end of the season in order to prevent breakage due to freezing. Electrical circuit The following operations are recommended to perform maintenance on the electrical circuit: check the unit power consumption using a clip-on meter and compare the reading with the values shown in the documentation; inspect and check that the electrical contacts and relative terminals are tightened correctly. nti-freeze protection IMPOTNT! Mixing the water with glycol modifies the performance of the unit. Pay attention to the safety instructions on the package regarding glycol. If the unit is not used during the winter period, the water contained in the system may freeze. ll the water in the circuit must be drained on time. If draining the system is to complex, a suitable amount of antifreeze liquid can be mixed with the water. Warning: user safety This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance. lways use the mains switch to isolate the unit from the mains before carrying out any maintenance work on the unit, even if it is for inspection purposes only. Make sure that no one supplies power to the unit accidentally; lock the master switch in zero position. Please follow these instructions carefully in order to allow for an error-free installation and a carefree use. Entitlement to warranty is cancelled in case of: errors or damage resulting from not following the assembly, cleaning or user instructions supplied by the manufacturer, wrong, improper and/or irresponsible use or treatment of the device, wrong or incompetent repairs and defects due to external factors, self-applied changes to the device. equipment that is built in, in a way that it cannot be reached normally. If you have any questions or complaints, please contact your supplier or installer. The copyright of these instructions is the property of the company Jaga Inc. Page INDEX 2 User / Instruction for installation, handling and storage 3 Maintenance / Warning: use & safety 4 Composition 5 Mounting dimensions / coustic isolation 6 Dimensions / Dimensions hydraulic connections 7 Dimensions / Dimensions hydraulic connections 8 Installation instructions / Installation guidelines 9 Installation hydraulic and electrical connections 10 Connection to home automation / Option condensate drain tray 11 Option valve sets / Option room thermostats 12 Instructions for start-up / Instructions to dismantle the unit and dispose of hazardous substances E / 27200.23700029-7 september 2016 3:49 PM - Jaga N.V. BIZ EC 3

11 4 1 9 3 OPTION 2 12 8 6 10 7 5 Dynamic outlet grille 11 TTENTION! The direction of the air flow is determined by the shape of the grille fins. Fit the grille so that the airflow is sent into the room. Composition Briza Built-In Wall& Ceiling Composition Briza Wall & Ceiling surface 1 Dynamic Low-H 2 O heat exchanger 6 Mounting holes = Composition Briza Built-In + 2 Condensate drain model Built-In Ceiling 7 Tangential fan 10 Condensate drain pan wall model is included as standard 3 dditional drain pan for cooling, model only for Built-In ceiling 8 Frame made of reinforced galvanised steel plate 11 Dynamic outlet grille 4 Hydraulic connection 2-pipe 3/4 G (Eurocone) standard on the LHS 9 Electrical connection standard on the HS 12 Casing 5 Stainless steel grate 4 BIZ EC E / 27200.23700029-7 september 2016 3:49 PM - Jaga N.V.

Mounting dimentions Built-In Ceiling coustic isolation espect the free space around the unit as shown: max. 230 cm max. 230 cm Insulation against airborne noise Sound is reflected by hard materials. Soft, porous substances are best suited to absorbing airborne sound. Contact sound insulation Sound travels very easily in hard materials. Contact sound insulation will largely depend on this:. Quality of the placement< Contact points: make sure that sound- and/or mechanical vibrations cannot be transferred between different elements, e.g. between the built-in heaters and a metal carrier, through pipes, along air ducts etc. Hollow acoustic spaces: where air can travel, so can sound. Isolate the built-in heaters in hollow acoustic spaces. void cavities between insulation and pipes. These form small resonance boxes. void cavities along air ducts (the acoustic effect cannot be predicted for this). Mounting dimentions Built-In Wall TTENTION The unit must remain accessible for maintenance Free spaces and installation: IMPOTNT! Incorrect positioning or installation of the unit may amplify noise levels and vibrations generated during operation. 10 E / 27200.23700029-7 september 2016 3:49 PM - Jaga N.V. BIZ EC 5

Briza 041 Wall / Ceiling: Dimensions / Dimensions hydraulic connections Briza 038 2-pipe 4-pipe L 7.8 16.5 8.5 13 12.5 8 3.8 12.5 8 3.9 35.2 2.8 2.8 20.8 3 41 4.5 7.3 10 min. 10 2.3 Briza 055 Wall / Ceiling: Dimensions / Dimensions hydraulic connections Briza 052 2-pipe 4-pipe L 16.5 8.5 13 7.8 3.8 3.9 48.2 13 13 20.8 3 55 4.6 8.3 10 min. 10 2.3 Model T 1 T 2 T 3 T4 L (cm) 75 95 1 145 = supply = eturn Wall units standard delivery with condensate drain pan Ceiling units standard delivery without condensate drain pan 6 BIZ EC E / 27200.23700029-7 september 2016 3:49 PM - Jaga N.V.

Briza 038 Built-In Wall / Ceiling: Dimensions / Dimensions hydraulic connections Briza 038 2-pipe 4-pipe 7.8 L 12 7.5 8 3.8 7.5 8 3.9 2.8 2.8 35.2 38 20.8 3 4.5 7.3 10 min. 10 2.3 Briza 052 Built-In Wall / Ceiling: Dimensions / Dimensions hydraulic connections Briza 052 2-pipe 4-pipe 7.8 L 12 3.8 3.9 48.2 52 13 13 20.8 3 4.6 8.3 10 min. 10 2.3 Model T 1 T 2 T 3 T4 L (cm) 52 72 102 122 = supply = eturn Built-In Wall units standard delivery with condensate drain pan Built-In Ceiling units standard delivery without condensate drain pan drain pan option: only for Briza Built-In Ceiling E / 27200.23700029-7 september 2016 3:49 PM - Jaga N.V. BIZ EC 7

1 Installation instructions 2 Installation guidelines the installation must only be carried out by skilled technicians, qualified for working on air conditioning and cooling systems. Incorrect installation could cause the unit to run badly, with a consequent deterioration in performance. the unit must be installed according to national or local standards in force at the time of installation the unit must remain accessible for maintenance always use personal protective equipment 1 Disassemble the casing Disconnect the grille security a a emove the grille. Only for ceiling surface mounted: mark the fastening points on the wall or ceiling using those on the unit or according to the dimensions specified in this guide. the type of wall determines what type of screw or plug should be used OPTION b emove the screws above and below the unit. unscrew the grille security slide the clamp plates to the outer side of the grille c emove the casing. Further technical installation and connection (s) is identical for all Briza Built-In and Surface units. respect the free space around the unit as shown in the manual insulate the valves and connections and pipes with 10 mm thick anti-condensation material or install the auxiliary pans keep a slight tilt towards the condensate drain to help the water drain 8 BIZ EC E / 27200.23700029-7 september 2016 3:49 PM - Jaga N.V.

b Hydraulic connection c Electrical connection 3 Mount the casing a Position the casing ttach the screws above and below the unit TTENTION! It is very important for the water connections to be installed with care by qualified personnel. TTENTION! Position the drain pipes without mechanical stress on the drain connection of the unit. Hydraulic connections: Connect the unit to the hydraulic system with the indicated inlet/ outlet connections as shown on page 7. Make sure the connections are air tight with a sealant. all heat exchangers (including the additional one), are equipped with an air vent near the top connection, and a water drain near the lower connection. heat exchangers can be partially drained; it is recommended to bleed air inside the coil to be drained completely. Setting up the condensate drain: The condensation drainage system must be set up with an adequate inclination to make sure the water drain properly. When not using the condensate drain pan, the outlet duct must be connected directly to the condensation collection. In this case, the hydraulic and the valves must be used for cooling water surely be insulated against condensation. Stench trap (sifon): The condensate drain must be fitted with a stench trap: 50 mm 100 mm TTENTION! The electrical connection of the unit must be carried out by qualified personnel, in compliance with the regulations applicable in the country where the unit is installed. Non-conforming electrical connections releases Jaga N.V. from liability concerning damage to objects and persons. check that the voltage and frequency of the grid corresponds to the information on the registration plate of the device that the available installed power is sufficient for running the equipment if the unit is mounted on a metal surface, the earth connection must be installed in compliance with local regulations. The earth conductor must be longer than the other conductors so that it is the last one to release in the event the connection comes loose. that the supply cables are of adequate section for the maximum current required. MOTO [ 2 1 3 0 VDC 24 VDC 0..10 VDC [ SUPPLY b Place the grille TTENTION! The direction of the air flow is determined by the shape of the fins of the grille. lways set up or install a plug for cleaning in the lower part of the siphon in order to allow quick disassembly. Once installation is complete: bleed the air contained in the circuit make sure that there are no water leaks insulate the valves and connections and pipes with 10 mm thick anti-condensation material or install the auxiliary pans pour water into the condensate collection pan and check if the liquid is drained properly. Otherwise, check the inclination and look for possible blockages. Only for Briza Ceiling (with casing) slide the clamping plates to the inner side of the grate assure the grille security E / 27200.23700029-7 september 2016 3:49 PM - Jaga N.V. BIZ EC 9

0...10 V Connection to home automation Briza Clima Canal Quatro Canal 24 VDC + 24 VDC - 0..10 V Option: condensate drain tray Built-In Ceiling units: standard delivery without condensate drain tray drain pan option: only for Briza Built-In Ceiling 215 Option condensate drain tray for Briza Built-In Ceiling Option: condens water-level sensor switch features: Normally closed (NC) white polypropylene with silicone O-ring. condensation water level sensor E316052 Briza H38 0..10V Domotica + 0...10VDC - 0VDC CODE: 7990.050/51/52 Netvoeding / limentation Netzteil / Power supply 24 VDC 1 4 ++ -- DC LO DC ON L N 5 6 30 Ø 20 50 230 VC 295 Briza H52 128 95 2.8 Type switch Max. switching current Max. switching voltage Max. temperature Max. pressure 10 W (NC) 0. 100 VDC 80 C / 194 F PSIG Briza H38 Condensate drain tray L 215 Code: 5127.00010001 Briza H38 Liquid water level sensor for Briza H52 Condensate drain tray L 295 Code: 5127.00010002 Briza H52 condensate drain tray Code: 5127.00010003 10 BIZ EC E / 27200.23700029-7 september 2016 3:49 PM - Jaga N.V.

Option: valve sets Option: roomthermostats set 95 Valve sets 24 VDC (0...10VDC) CODY.SC5.10.3... < sleeve couplings valve Eurocone x 3/4 M24 90 lockshield Eurocone x 3/4 M24 90 thermal motor 0...10V (24V) set 96 2 lockshields Code CODY.LOB.00.3... < sleeve couplings 2 lockshield 3/4 M24 90 Jaga two-way valve + motor 230 VDC Code 7990.409: 180 -G 1/2 F/NG 230 Volt 2 Watt Code 7990.411: 180 -G 3/4 F/NG 230 Volt 2 Watt only for mounting on the distributor with position indicator (open / close) sleeve couplings to be provided by the installer 3/4 M24 * Sleeve couplings Code Precision metal tube 110 ø M24 x 10/1 112 ø M24 x 12/1 114 ø M24 x 14/1 115 ø M24 x 15/1 116 ø M24 x 16/1 118 ø M24 x 18/1 Synthetic tube 212 ø M24 x 12/2 214 ø M24 x 14/2 219 ø M24 x 16/1.5 216 ø M24 x 16/2 217 ø M24 x 17/2 218 ø M24 x 18/2 PE/LU tube 314 ø M24 x 14/2 316 ø M24 x 16/2 326 ø M24 x 16/2.2 318 ø M24 x 18/2 336 ø M24 x 16/2.2 only for TECE-tube STEEL TUBE FO C.H. 501 ø M24 x 1/2 503 ø M24 x 3/8" DG 160T room thermostat Code: 8751.050009 thermostat heating / cooling control outputs 0..10 V DC 0..10V DC control valves full modulating fan speed utomatic or manual heating / cooling changeover fan speed automatically or manually in 3 steps (3V - 6V - 8V) 24 VDC supply JT 100: room thermostat Code: 8751.050012 for 2- and 4-pipe fan coil units heating - cooling mode (4-pipe) auto switching heating cooling 3 programmable zones (5.1 + 1) 0-10V output optional external room-temperature sensor semi-recessed in wall mounting box JT 200: room thermostat Code: 8751.050013 for 2- and 4-pipe fan coil units heating - cooling mode (4-pipe) auto switching heating cooling 3 programmable zones (5.1 + 1) 0-10V output mounting on wall mounting box or directly on the wall key card / window contact Jaga JDPC.002 Only to order together with the device. Ex factory (contact Jaga for more info). With control panel only for 2 pipe wall mounted model with casing control with touch operation and sensors for water and room temperature, pre-configured power supply 24 VDC heating/cooling/standby with automatic switch (temporary manual adjustment is possible) 0-10 V input ventilator settings: standby heating: 3 speeds (operates at water temperature >32 C, can easily be modified) cooling: 3 speeds (operates at water temperature <18 C, can easily be modified) Without control panel for 2 pipe Built-In model control without operation and with sensors for water and room temperature, pre-configured power supply 24 VDC auto switch heating/cooling/standby 1 fan speed heating 1 fan speed cooling 0-10 V input (contact Jaga for more information) E / 27200.23700029-7 september 2016 3:49 PM - Jaga N.V. BIZ EC 11

Instructions for start-up Instructions to dismantle the unit and dispose of hazardous substances TTENTION! Start-up and Commissioning of the unit (where applicable) must be carried out by skilled personnel, qualified to work on this type of product. Before starting up, make sure the installation and electrical connections have been carried out in compliance with the instructions in this manual. lso make sure that there are no unauthorised persons in the vicinity of the unit during the above operations. Preliminary checks before start-up Before starting up the unit,check if: 1. the unit is positioned correctly 2. the supply and return pipes of the hydraulic unit are connected and insulated properly; 3. the pipes are clean and bled 4. the inclination of the unit towards the drain and the siphon are correct 5. the exchangers are clean 6. the wiring connections are correct 7. the screws that secure the conductors are clamped 8. the supply voltage is that required 9. the electric fan consumption is correct and does not exceed the maximum allowed value It is advisable to run the unit at maximum speed for several hours. SFEGUD THE ENVIONMENT Jaga N.V. has always cared about protecting the environment. When the unit is dismantled it is important to strictly following theseprocedures: the unit must be dismantled by a firm authorised for the disposal of scrap machinery/products The unit as a whole is composed of materials considered as secondary raw materials and the following conditions must be complied with: if the appliance contains antifreeze, this should not just be disposed, as it causes pollution it must be collected and disposed of properly the electronic components (electrolytic condensers) are considered special waste, and must be delivered to a body authorised to collect such items the pipe insulation made of polyurethane foam, polyethylene foam mesh and the sound-absorbing sponge that lines the panelling must be removed and processed as urban waste Please follow and keep these instructions! re conform to the CE Directive : NBN EN60335-1 based on EN60335-1-2002 + a11:2004 + a1:2004 + a12:2006 + a2:2006 + a13:2008 + 14:2010 + 15:2011 NBN EN 60335-2-80 based on EN 60335-2-80:2003 + 1:2004 + 2:2009 12 BIZ EC E / 27200.23700029-7 september 2016 3:49 PM - Jaga N.V.