INSTALLATION INSTRUCTIONS EXIT CHECK DELAYED EGRESS EMLOCK 1511S / 1511T

Similar documents
INSTALLATION INSTRUCTIONS 101-DE/101-KDE

Exit Check Integrated Delayed Egress Locks

Code Compliance. Selected Exit Check models are available to comply with one or more codes listed below. See Operation on page 3.

Exit Check Integrated Delayed Egress Locks

EXIT CHECK DELAYED EGRESS LOCKS

Delayed Egress Locks 38 SECURITY DOOR CONTROLS

Exit Check Integrated Delayed Egress Locks

Delayed Egress System DORMA EMDE

White Papers: Delayed Egress Hardware

ACCESS & EGRESS LOCKING DEVICES SOLUTIONS. 1.2 Delayed Egress Locks. The lock behind the system. SDCSecurity.com

Accessories DESK TOP CONTROLS MODELS SPECIFICATIONS MODELS SPECIFICATIONS UNDER DESK TOP MOUNTING MINI DESK TOP CONSOLE

Multi-Mode Annunciators

Accessories. Desk Controls. Break Glass Emergency Door Release SECURITY DOOR CONTROLS

Accessories. Desk Top Controls

Egress Devices for Code Compliant Access-Controlled Egress Doors

705 Emmett Street Bristol, CT DynaLock MODEL 3101C-TJ101 DELAY EGRESS SYSTEM WIRING INSTRUCTIONS

SP-1000X. Panic Device Power Controller Installation Guide. Rev

DE5300 Delayed Egress System. General Information

Remote Chexit Module (RCM) System. General Information

Accessories. Desk Controls. Break Glass Emergency Door Release SECURITY DOOR CONTROLS

Exit Switches 410 & 420 SERIES MODELS SPECIFICATIONS HOW TO ORDER 1 SPECIFY MODEL 2 SPECIFY FINISHES 3 SPECIFY OPTIONS

Exit Switches SECURITY DOOR CONTROLS. 400 Series 410 & 420 Series. Finishes. Finishes. Options. Options. Specifications.

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

Optional cable and connectors SELECTRIC TM PRO

MODEL KP-200 VANDAL RESISTANT & WEATHERPROOF FLUSH MOUNT DIGITAL KEYPAD DESIGNED FOR ACCESS CONTROL APPLICATIONS

Addendum for STI-6406 with Dual Access Control

INSTALLATION INSTRUCTIONS EA SERIES DOOR PROP/EXIT ALARM

Pilfergard Door Alarms

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

RELEASE DEVICE CONTROLS

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)

CM-RQE70 PIR REQUEST TO EXIT DETECTOR

SOFTWARE VERSION 2.20 CONTROL PANEL RESET:

Is the Key! Premium Grade Access Control Hardware

OPTICAL TURNSTILE SYSTEM

Exit Stopper. STI-6400 Series

AL600ULADA. NAC Power Extender. Installation Guide

Modular Fillerplate Subassembly P/N: X Endcap P/N: Strike *, P/N: " Narrow Stile Plastic Template. Mortise.

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

Power Transfer Devices. Access Control Accessories. How To Order. How to Order

AL800ULADA. NAC Power Extender. Installation Guide

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

MODEL B2 INSTALLATION MANUAL

CM-RQE70A PIR REQUEST TO EXIT DETECTOR

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

400 SERIES REMOTE AMPLIFIER SIREN W/ HANDHELD REMOTE ETSA461HPP - 100W ETSA462HPP - 200W

400 SERIES REMOTE SIREN WITH REMOTE ROTARY CONTROL PANEL ETSA481RSR - 100W ETSA482RSR - 200W

Crypto-Lock. Model CC-8521B Updated 7/17. Access Control System. MONITEQ, Inc. INSTRUCTION MANUAL

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

EVO192 v3.0 Fire and Burglary What s New

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

ETSA380MF SHOWN WARNING. shall be used ONLY on approved vehicles. It is the sole responsibility of the user of these devices to ensure compliance.

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

Section 1: General Description. Section 2: Features. Section 3: Operation. CM-RQE70 PIR REQUEST TO EXIT DETECTOR Installation Instructions.

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

SuperBus Hardwire Output Module (HOM) Document Number: Rev. D March 1999

STANDARD FEATURES SPECIFICATIONS

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

DS160/161 Request To Exit PIR sensors Installation Instructions

380 SERIES REMOTE SIREN ETSA380R

20 Light Remote Annunciator

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

ACCESS & EGRESS REMOTE CONTROLS SOLUTIONS. The lock behind the system. SDCSecurity.com

DS160/DS161 Request To Exit PIR sensors Installation Instructions

631RF Amp Power Supply

D1255RB/D1256RB/D1257RB

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

TS93 EMF SERIES. INSPK NO Rev.03/10

400 SERIES REMOTE AMPLIFIER SIREN W/ HANDHELD REMOTE ETSA461HPP - 100W ETSA462HPP - 200W

Series. Access Power Controllers. Installation Guide

Exit Stopper. STI-6400 Series

22-F fire exit rim device for all types of 4 x 8 (1219mm x 2438mm) single doors and 8 x 8 (2438mm

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

PoE SOLUTIONS Power over Ethernet Capable Locking Hardware SOLUTIONS

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

A1UL PERS. Personal Emergency Response System. For Technical Support Please Contact Your Service Provider Or Distributor

EM 3000-EW AH INSTALLATION EARLY WARNING ELECTROMAGNETIC LOCK A. INTRODUCTION B. DELAY EGRESS FUNCTIONS

FMR Installation Instructions. Addressable Fire System Controller

Installation Guide for models:

ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

ACM4 Series UL Listed Sub-Assembly Access Power Controllers

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

HARDwired Installation/ Owner s Manual

System components portfolio overview. Power supplies, electromagnetic locks, electric strikes and system accessories

KP-100A BACKLIT DIGITAL KEYPAD FOR ELECTRIC LOCK AND SECURITY SYSTEM INSTALLATIONS

Duct smoke housings, 4-wire D341/D341P and D342/D342P

SPLIT-DECODED CONTROLLER

RCR-REX Request-to-Exit Dual Technology Motion Sensor Installation Guide

Installation, Operating and Maintenance Manual

MANUAL RESET ALARM RELEASE

300 SERIES MINI MAGNETIC LOCK 1000 SERIES INDUSTRIAL MAGNETIC LOCK 1100 SERIES ARCHITECTURAL MAGNETIC LOCK 1100 SERIES MORTISE MAGLOCK & DOOR PULL

Application Note. Using XPoint Wireless Devices with Emergency Lighting. 1 of 16

Transcription:

801 Avenida Acaso, Camarillo, Ca. 93012 (805) 4940622 www.sdcsecurity.com Email: service@sdcsecurity.com INSTALLATI INSTRUCTIS EXIT CHECK DELAYED EGRESS EMLOCK 1511S / 1511T KEEP PUSHING. THIS DOOR WILL OPEN IN 15 SECDS. ALARM WILL SOUND. California Building Code Compliant Application When unauthorized egress is initiated, the Exit Check delays egress through the door for a period of 15 or 30 seconds. An integral digital countdown display and voice commands inform the person intending to exit of the seconds remaining to unlock. Meanwhile, the person exiting must wait allowing personnel or security respond. The door unlocks after the 15 or 30 second delay period has elapsed, permitting egress. A signal from the fire/life safety system will release the lock immediately for uninhibited egress in an emergency. Exit Check applications include: Restricting the egress of patients for their own safety. Restricting the egress of commercial center patrons for security application needs. Controlling pedestrian traffic in transportation facilities, including airport jetways and tarmacs Standard Features 1650 lbs. Holding Force 15 or 30 Second Exit Delay when activated. 1 or 2 Second Nuisance Delay 75dB Alarm Tone with Digital Display & Voice Instruction Choice of Activation Trigger: Door Movement Exit Device w/ REX Switch Touch Sense Bar w/rex Switch Auto Up Occurs when power is restored and/or the fire panel is restored. (When Allowed by Code) Manual Up This is a UBC & California Building Code Compliant Feature Only after power restoration and fire panel reset may the lock be reset manually at the opening. Lock can be reset with the builtin reset key switch or, a key switch or keypad adjacent to the door. Optional Features D = DPS Door Position Switch B = BAS Bond Alert Sensor A = ATS Anti Tamper Switch E = Energy Saver Option (1200 lb. Holding Force) Building & Fire Life Safety Code Compliant IBC International Building Code IFC International Fire Code NFPA 101 Life Safety Code NFPA 1, UFC, Uniform Fire Code UBC Uniform Building Code CBC California Building Code SBC Standard Building Code BOCA National Building Code compliant Chicago Building Code compliant Vandal resistant Proximity Sensor Trigger Auto Sensing 12/24VDC input power Connection for Tandem Option (Pairs of Doors) P:\INSTALLATI INST\Delayed Egress\INST1511ST\INST1511ST.vsd Rev G7 0219 Page 1 Only the 1511S and the 1511T have been UL listed as Special Locking Arrangements to UL Standard 294, and NFPA 101. GWXT, GWXT7 Auxiliary Locks UL,cUL Listed FWAX Special Locking Arrangements UL Listed California State Fire Marshal Listed CSFM #37740324:103

1511S Operational Description The door is closed and secured by latching hardware. The model 1511S Exit Check locks the door in the secured position, and the display shows the unlock delay time. Activation / Alarmed Release : Activation of the 1511S Exit Check s 15 or 30 second unlock cycle is started by releasing the door latch and applying up to 15 lbs. of pressure to the door causing slight door movement. A short nuisance delay period is then initiated, a preactivation warning tone is sounded and the integral display will start counting down. To prevent false alarms, relatching the door during the nuisance delay period will silence the preactivation warning tone, reset the countdown display and keep the door locked. Once the nuisance delay period has been exceeded, the Exit Check continues with an irreversible door release cycle. The integral digital countdown display and voice commands continue to inform the person intending to exit of the seconds remaining until unlock and an alarm output is activated to alert personnel of an unauthorized exit. After the 15 or 30 second delay cycle has expired, the Exit Check will release the door allowing free egress. Reset / Relock: The Exit Check can be manually reset by authorized personnel by closing the door and activating the integral reset key switch or by momentarily activating a switch connected to the remote reset terminals. Request to Exit / Authorized Bypass: Momentarily actuating the integral key switch to the bypass position or momentarily activating a switch connected to the REX terminals will initiate the request to exit cycle and unlock the 1511S Exit Check allowing free egress. After the request to exit cycle has expired, the Exit Check will automatically relock. Leaving the integral key switch in the bypass position or placing a maintained closure across REX terminals will reset the request to exit cycle and keep the 1511S unlocked for extended periods of time. Releasing the remote contact or returning the integral key switch to the center position will restart the request to exit cycle and will relock the door after the request to exit time has expired. (NFPA101) The 1511S operation complies with the following building and fire codes: NFPA 101; NFPA 1UFC; UBC; IBC; IFC; SBC; CBC (California Building Code). Listings: UL Listed: Special Locking Arrangements and Auxiliary Locks; California State Fire Marshal (CSFM) Listed. Option Code NA ND NH Delay Release Time 15 sec or 30 sec 15 sec 30 sec Nusiance Time 1 sec or 2 sec 0 sec or 1 sec 0 sec or 1 sec Reset after Alarm Manual Manual Manual Lock Status on Up Locked or Unlocked Locked or Unlocked Locked or Unlocked NC (CBC Compliant) 15 sec 0 sec or 1 sec Manual Unlocked Per BOCA compliance, the Exit Check is manually reset by authorized personnel after an alarm by closing the door and actuating the integral reset key switch or by momentarily closing a contact connected to the remote reset terminals. In addition, reset will be automatically initiated once the door has been opened, then closed and remains closed for 30 consecutive seconds. (BOCA/Chicago) The 1511S operation complies with BOCA National Building Code and the Chicago Building Code: UL Listed, Special Locking Arrangements and Auxiliary Locks. Option Code BD BH BC (CHICAGO) Delay Release Time 15 sec 30 sec 15 sec Nusiance Time 0 sec or 1 sec 0 sec or 1 sec 0 sec Reset after Alarm Auto/Manual Auto/MAnual Auto/Manual Lock Status on Up Locked or Unlocked Locked or Unlocked Locked or Unlocked P:\INSTALLATI INST\Delayed Egress\INST1511ST\INST1511ST.vsd Rev G7 0219 Page 2

PLACE AGAINST LOCK JAMB FOR R.H. DOORS 1/2 DIA FOR WIRE First install mounting plate at two slot locations only and make proper adjustments before marking remaining five mounting hole locations. Mark location five places: #10 self dril/tap screws provided for up to 1/8 thick metal applications. FOLD DOTED LINE Note: Machine screws provided for applications with heavier gauge material Drill (#21) and tap for #1032 screw. PLACE AGAINST LOCK JAMB FOR L.H. DOORS 1/4 DIA GUIDE PIN HOLE 9/16 DEEP Specifications Interior Applications Only Input Voltage Requirements: Dual Voltage (Auto Sensing) 12/24 VDC (/ 10%) (Use with a UL 294 Standard Supply) Consumption: Standard Model (1650 lbs.) 1511S 820/500 ma@ 12/24 VDC 1511T 1500/850 ma @ 12/24 VDC Energy Saver (1200 lbs., E Option) 1511S 452/274 ma@ 12/24 VDC 1511T 660/486 ma @ 12/24 VDC Size: 11"L x 23/4"H x 25/8"D Lock Status Relay Rating: 1 Amp @ 30V resistive Alarm Output Rating: 1 Amp @ 30V resistive DPS Rating: 250 ma @ 30V resistive BAS Rating: 250 ma @ 30V resistive ATS Rating: 1 Amp @ 30V resistive Operating Condition: 049 deg C, 85% RH (noncondensing) Included in Package PLACE AGAINST DOOR Center punch on mark TEMPLATE TEMP1511 ARMATURE SCREW PACK 1580S101C EMLOCK SCREW PACK C1500 1511S EMLOCK HOUSING ASSY. & MOUNTING PLATE 1511S ARMATURE 1511S12T 1511S TRIGGER & ARMATURE BASE 1511S11 Suggested Optional Equipment Digital Entry 918 Digital Keypad Two relay outputs: Relay 1 Reset; Relay 2 Choice of momentary or sustained bypass. Remote Speaker 101SP Indoor Surface Mount; 85dB@3ft.; Compact Design (4 in. sq.); Plugin connector included for easy installation Supply 600 Series Supply Field 12 or 24VDC modular Supplies with Fire/Life Safety Emergency Release. Tricolored LED, separate PTC protected outputs, battery charger, and Class 2 Outputs. 602RF 1 Amp 631RF 1.5 Amp 632RF 2 Amp 634RF 4 Amp 636RF 6 Amp Station Controls, Annunciator Panels, and Consoles 728 Single station two function key switch control for alarm reset and access or sustained bypass. 1011A The single station annunciator is equipped with a tricolored LED and audible alarm. 101PAM Visual & audible annunciation, timed access, sustained bypass and audible mute. 728L Single station two function key switch control for alarm reset and access with a tricolored LED showing door condition. 1014AM Provides visual & audible annunciation with audible mute for one, two, three or four openings. TCC Desk Top : Stations 4, 8, & 12 SDC Annunciator Consoles provide remote annunciation of multiple openings. Stations are specified in sets of four. Control switches are capable of both sustained bypass and timed unlocking. 702R Single station one function key switch control for alarm reset. 1011AK Visual & audible annunciation and a two function key switch for alarm reset and access or sustained bypass. P:\INSTALLATI INST\Delayed Egress\INST1511ST\INST1511ST.vsd Rev G7 0219 Page 3 PSB560 Requesttoexit pressure sense nonlatching bar that will activate the Exit Check when slight pressure is applied to the bar. For doors without latching.

First install mounting plate at two slot locations only and make proper adjustments before marking remaining five mounting hole locations. Mark location five places: #10 self dril/tap screws provided for up to 1/8 thick metal applications. FOLD DOTED LINE Note: Machine screws provided for applications with heavier gauge material Drill (#21) and tap for #1032 screw. Door and Frame Preparation Instructions STEP 1. Locate the paper template and fold along the dotted line. Place the folded edge of the template against the door stop and door at the header while against the vertical stop, opposite the hinge side of the door. Tape in place at this position. STEP 2. As indicated on the paper template, punch the designated hole locations on the frame and armature mounting holes on the door. (NOTE: PRIOR TO DRILLING, INSPECT TO SEE IF ANY OF THE HOLES CANNOT BE DRILLED DUE TO THE FRAME OR DOOR CFIGURATI. A FILLER PLATE OR ANGLE BRACKET MAY BE REQUIRED. SEE PAGE 4.) 21/2" 25/8" 11" 23/4 1/2 DIA FOR WIRE PLACE AGAINST HEADER PLACE AGAINST PLACE AGAINST LOCK JAMB FOR L.H. DOORS LOCK JAMB FOR R.H. DOORS 1/4 DIA GUIDE PIN HOLE 9/16 DEEP STEP 3. Drill and tap the two 1511S mounting holes as indicated on the paper template. (NOTE: READ NOTE TEMPLATE WITH REGARD TO SELECTING THE PROPER HOLE SIZE FOR ARMATURE MOUNTING BOLT.) PAPER TEMPLATE HINGE SIDE OF FRAME (OPPOSITE FROM LOCK) PLACE AGAINST DOOR Center punch on mark Door and Frame Reference IMPORTANT! IT IS HIGHLY REMENDED THAT YOU FIRST INSTALL THE MOUNTING PLATE AT TWO SLOT LOCATIS LY. THIS WILL ALLOW YOU TO MAKE PROPER ADJUSTMENTS OF THE LOCK S POSITI PRIOR TO MARKING, DRILLING AND TAPPING THE FOUR PERMANENT MOUNTING PLATE HOLES. SLOT LOCATIS 1/2 DIA FOR WIRE First install mounting plate at two slot locations only and make proper adjustments before marking remaining five mounting hole locations. PLACE AGAINST LOCK JAMB FOR R.H. DOORS FOLD DOTED LINE Mark location five places: #10 self dril/tap screws provided for up to 1/8 thick metal applications. Note: Machine screws provided for applications with heavier gauge material Drill (#21) and tap for #1032 screw. PLACE AGAINST LOCK JAMB FOR L.H. DOORS 1/4 DIA GUIDE PIN HOLE 9/16 DEEP PLACE AGAINST DOOR Center punch on mark TEMP1511 NOTES: #10 self drill/tap screws provided for up to 1/8" thick metal applications For applications with heavier gauge material, drill (#21) and tap for #1032 machine screws. P:\INSTALLATI INST\Delayed Egress\INST1511ST\INST1511ST.vsd Rev G7 0219 Page 4

ARMATURE MOUNTING INSTRUCTIS STEP 1. Mount armature to door. (See figures 2A, 2B & 2C.) STEP 2. Install the mounting plate (filler plate and/or angle bracket if needed see figures 1A, 1B & 1C) to header with only the two screws at the slotted hole locations at this time. Snug the screws down lightly (do not torque) so the mounting plate & lock can be repositioned later. STEP 3. Temporarily install the lock to the mounting plate with the 1/420 socket head screws encased in the lock. STEP 4. With the lock mounted, close the door so the armature holder just comes into contact with the face of the lock. If the door is not completely closed when the lock & armature touch, open the door and reposition the lock away from the door as described in step 2. (THIS IS TO PREVENT THE DOOR FROM USING THE LOCK AS THE DOOR STOP.) STEP 5. Remove the lock from the mounting plate, mark & punch all remaining screw and wiring holes. Drill & tap holes as indicated on the paper template and install all screws. STEP 6. Reinstall the lock to the mounting plate. At this point, if there is no need to remove the lock for painting or any other reason, install the antitamper plugs over the socket head mounting screws, using a soft hammer to avoid damage to the lock case. SEX NUT Figure 2A SOLID DOOR Drill exactly 3/8" diameter through the door. From sexnut side of door, drill ½ diameter hole 13/8" deep. Mount armature to door with hardware provided per Figure 2A. Figure 2B HOLLOW METAL DOOR From sexnut side of door, drill exactly 1/2" hole through one metal thickness only. From armature side of door, drill 5/8" hole to insert reinforcement tube. Press in sexnut & reinforcement tube all the way and mount armature to door using hardware provided per Figure 2B. DOOR 1/2 REINFORCEMENT TUBE 1 ¾ HOLLOW METAL DOOR REINFORCEMENT BY OTHERS 1 3/8" 5/8" DRILL 1/2" DRILL DOOR ARMATURE 5/16 18 ARMATURE MOUNTING SCREW ARMATURE HOLDER ARMATURE ARMATURE 5/16 18 ARMATURE MOUNTING SCREW ARMATURE HOLDER 5/16 18 ARMATURE MOUNTING SCREW LETTER F DRILL & TAP 5/1618 ARMATURE HOLDER REGULAR, FILLER PLATE & ANGLE BRACKET DETAILS Figure 2C REINFORCED ALUMINUM OR HOLLOW METAL DOOR Use letter F drill and tap for 5/1618 machine screw. Mount armature to door with hardware provided per Figure 2C. FILLER PLATE ANGLE BRACKET Figure 1A REGULAR Figure 1B WITH FILLER PLATE Figure 1C WITH ANGLE BRACKET P:\INSTALLATI INST\Delayed Egress\INST1511ST\INST1511ST.vsd Rev G7 0219 Page 5

Typical System Wiring Single Door (Model 1511S) Display Modes 2 conductors To Smoke Detection System Supply AC Mains To Fire Panel 2 conductors 15 00 Door armed and locked. Alarm countdown has ended, door is unlocked and alarm sounding until reset. 8 or 10 conductors 3 or 5 conductors Door unlocked and alarm is shunted (REX or Bypass) Door has been opened after REX, Bypass or Alarm. Key Switch or Access Control (Optional) 101SP Remote Speaker [EXT SPKR] J2 [ PWR ] [ FP ] [ LOCK ] J6 [GRN RLY] [RED RLY] [RM TRIG] [RESET] [ DPS ] [ BAS ] C NC NO C NC NO C NC NO C NO C NO C NO C NO C NC NO C NC [REX] [IBO] REMOVE J6 LY IF A FIRE PANEL OR SMOKE DETECTI SYSTEM IS CNECTED TO [FP] INPUT (Pg. 9) 400URMB Remote Buzzer RED BLK GRN ORG BLU WHT 600 Series Supply 918 Digital Keypad AUX RELAY MAIN RELAY NO C NO C Remote Bypass/Reset P:\INSTALLATI INST\Delayed Egress\INST1511ST\INST1511ST.vsd Rev G7 0219 Page 6

Typical System Wiring Pair of Doors (Model 1511T) Display Modes 2 conductors To Smoke Detection System 8 or 10 conductors Supply AC Mains To Fire Panel 2 conductors 4 conductors (1511T only) 15 Door armed and locked. 00 Alarm countdown has ended, door is unlocked and alarm sounding until reset. Door unlocked and alarm is shunted (REX or Bypass) 3 or 5 conductors Key Switch or Access Control (Optional) Door has been opened after REX, Bypass or Alarm. [EXT SPKR] [ PWR ] [ FP ] [ LOCK ] [GRN RLY] [RED RLY] [RM TRIG] [RESET] [REX] [IBO] [ DPS ] [ BAS ] J6 J2 C NC NO C NC NO C NC NO C NO C NO C NO C NO C NC NO C NC REMOVE J6 LY IF A FIRE PANEL OR SMOKE DETECTI SYSTEM IS CNECTED TO [FP] INPUT (Pg. 9) C NO 918 Digital Keypad 600 Series Supply RED GRN BLK BLK WHT BLK BLU L3 OPTI 728U or 728UL3 Key Switch Reset Station RLY1 J1 R9 C4 BAS DPS R7 Z1 C1 D2 J4 [ ATS ] [ BAS ] [ DPS ] D1 [TRIG OUT ] [ LOCK ] IN [ PWR ] TB8 TB7 TB6 TB5 TB4 TB3 TB2 TB1 NO C NC NO C NC NO C NC NO C Z4 SLAVE P:\INSTALLATI INST\Delayed Egress\INST1511ST\INST1511ST.vsd Rev G7 0219 Page 7

Wiring to Infant & Patient Protection Systems System Operation 1. Close and hold REX input. The 1511S will be in the Bypass mode and will be unlocked. 2. Whenever the IBO input is closed and held, the 1511S will instantly relock and rearm. Egress is possible as the normal 15/30 sec delayed unlock. 2 conductors To Smoke Detection System To Patient Protection System 3 conductors Supply AC Mains To Fire Panel 2 conductors 3 or 5 conductors 3. Releasing the IBO input will return the 1511S to the Bypass mode. 8 or 10 conductors 4. Releasing the REX input will rearm the system. 5. Upon powerup, you must manually reset the lock to activate the IBO input. Key Switch or Access Control (Optional) Connection to a Infant/Patient Monitoring Systems has not been investigated by UL. 101SP REMOTE SPEAKER [EXT SPKR] J2 [ PWR ] [ FP ] [ LOCK ] J6 [GRN RLY] [RED RLY] [RM TRIG] [RESET] [ DPS ] [ BAS ] C NC NO C NC NO C NC NO C NO C NO C NO C NO C NC NO C NC [REX] [IBO] REMOVE J6 LY IF A FIRE PANEL OR SMOKE DETECTI SYSTEM IS CNECTED TO [FP] INPUT (Pg. 9) 918 Digital Keypad C NO 600 Series Supply 728U or 728UL3 Key Switch Reset Station P:\INSTALLATI INST\Delayed Egress\INST1511ST\INST1511ST.vsd Rev G7 0219 Page 8 BLK GRN RED RED BLU BLK WHT L3 OPTI Keep Closed To Unlock Close To Override Unlock Patient Protection System

Wiring Details & Functions (ALL OPTIS SHOWN) JUMPER [EXT SPKR] J2 [ PWR ] [ FP ] [ LOCK ] [GRN RLY] [RED RLY] [RM TRIG] [RESET] [REX] J6 [IBO] [ DPS ] [ BAS ] C NC NO C NC NO C NC NO C NO C NO C NO C NO C NC NO C NC REGULATED POWER SUPPLY 12VDC OR 24VDC REMOTE SPEAKER Dry, FIRE ALARM INPUT Dry, SMOKE DETECTI SYSTEM INPUT JUMPER J6 LOCK SECURE RLY ALARM RLY MITOR RELAY OUTPUTS EXTERNAL TRIGGER OR SDC REX PUSH BAR REQUEST TO EXIT KEY OR ACCESS CTROL SYSTEM REMOTE RESET INSTANT BYPASS OVERRIDE [PWR] [FP] [LOCK] TERMINAL BOARD CNECTIS POWER IN POWER IN AUX LOCK AUX LOCK 12 VDC OR 24 VDC TO CLOSED FIRE/SMOKE DETECTOR CTACT SLAVE/TANDEM LOCK POWER TERMINALS MITOR RELAY OUTPUT CFIGURATIS LOCK STATUS RELAY STATE SECURE ALARMED & LOCKED GRN RLY = RED RLY = OFF GRN RLY = RED RLY = [DPS] [BAS] [ATS] MITORING OPTIS Com Com Com DOOR POSITI (DPS) BD ALERT (BAS) ANTITAMPER (ATS) [GRN RLY] LOCK SECURE OUTPUT ALARMED & UNLOCKED GRN RLY = OFF RED RLY = [RED RLY] [RM TRIG] [RESET] ALARM OUTPUT EXTERNAL TRIGGER INPUT EXTERNAL RESET INPUT JUMPER SETTINGS JUMPER J6 (Fire Alarm Input) Factory Installed. Remove J6 only if a dry, normally closed contact from a fire alarm OR smoke detector system is connected to the Fire Panel [FP] terminals. [REX] [IBO] REQUEST TO EXIT INPUT INSTANT BYPASS OVERRIDE INPUT JUMPER (DOOR PROP) INSTALLED: The ExitCheck will enter the alarm mode if the door is held open past the request to exit period. REMOVED: The ExitCheck will remain unlocked if the door is held open past the request to exit period. No alarm will sound. The ExitCheck will relock and rearm upon closure of the door. P:\INSTALLATI INST\Delayed Egress\INST1511ST\INST1511ST.vsd Rev G7 0219 Page 9

DIP SETTINGS * * RELEASE NUISANCE REQ TO EXIT TRIG TYPE POWERUP TEVOICE MESSAGE 1 2 3 4 5 6 7 8 LOCATIS OFF POSITIS POSITIS Jumper Installed Jumper Removed (Door Prop Alarm Active) (Door Prop Alarm Inactive) Note See program option chart on page 11 for the details of the code compliant functions RELEASE TIME* The Release time can be selectable for 15 or 30 seconds. The Nuisance Delay time period is included in the door release cycle and it will not increase or decrease the total time to unlock once the ExitCheck TM is activated. WARNING! CTACT AUTHORITY HAVING JURISDICTI FOR APPROVAL PRIOR TO SELECTING RELEASE TIME OR PWRUP SETTINGS NUISANCE DELAY* The Nuisance delay time feature, intended to avoid accidental triggering, is selectable for 1 or 2 seconds. Releasing the door latch and pushing on the door will activate the internal trigger sensor. Activating the trigger beyond the nuisance delay time will start the irreversible Exit Delay cycle time. The Nuisance Delay time period is included in the lock release cycle and it will not increase or decrease the total time to unlock once the ExitCheck TM is activated. Releasing the door before the end of the Nuisance delay time will turn the warning alarm and reset the ExitCheck TM to secure mode. REQUEST TO EXIT PERIOD The Request to Exit (REX) time is selectable for 1, 15, 20, or 30 seconds. The REX time is the period of time the lock will remain bypassed, after a remote normally open contact switch is momentarily activated. When activated with an access control system, the REX time cycle begins immediately after the access control open time expires. The ExitCheck will automatically relock if the door is opened, and then closed during the REX time cycle. TRIGGER TYPE The trigger type is selectable for REMOTE or INTERNAL. Selecting INTERNAL mode uses the internal trigger sensor to activate the Exit Delay cycle. Selecting REMOTE mode disables the internal trigger. Activation of the Exit Delay cycle is triggered by an external exit device equipped with a normally open contact switch. POWERUP STATE* The powerup option, indicating the state of the ExitCheck TM upon restoration of system power, is can be selected to be UNLOCKED or LOCKED. In the LOCKED mode, the ExitCheck TM will attempt to reset to secure mode. In the UNLOCKED mode, the ExitCheck TM will remain unlocked and the digital display will indicate two horizontal bars. Turning the reset switch momentarily to the reset position will relock and rearm the door. This feature enables the ExitCheck TM to comply with code requirements in jurisdictions that require manual reset/relock upon loss and restoration of system power. ALARM TYPE The alarm type is selectable to TE LY or VOICE. When secure, the ExitCheck TM digital display will indicate a 15 second delay time. Upon activation of the irreversible Exit Delay cycle, the digital display begins counting down to zero. In VOICE mode, the countdown will be accompanied by a warning beeping tone and verbal exit instructions. When the digital display indicates zero, the ExitCheck TM releases. The speaker output changes to a continuous warning tone and the verbal instruction announces Exit Now. In TE LY mode, the countdown will be accompanied by a warning beeping tone only, which changes to a continuous tone once the Exit Delay cycle expires. MESSAGE TYPE The message type is selectable to MSG1 or MSG2. MSG1: (Female Voice) Exit in 12 seconds, facility staff has been notified...exit in 5 seconds...exit now... MSG2: (Male Voice) Exit in 12 seconds, security has been alerted...exit in 5 seconds...exit now Both messages repeat Exit now until the lock is reset. P:\INSTALLATI INST\Delayed Egress\INST1511ST\INST1511ST.vsd Rev G7 0219 Page 10

Dip Switch Settings By Model Option Code RELEASE NUISANCE REQ TO EXIT TRIG TYPE POWERUP TEVOICE MESSAGE 1 2 3 4 5 6 7 8 OFF POSITIS POSITIS Jumper Installed Jumper Removed (Door Prop Alarm Active) (Door Prop Alarm Inactive) LOCATIS RELEASE TIME NUSIANCE DELAY REQUEST TO EXIT PERIOD 15 sec 1 sec 1 sec NA 30 sec 2 sec 15 sec 20 sec All options are selectable 30 sec TRIGGER TYPE Switch Internal Remote 5 POWER UP STATE 6 Unlocked Locked ALARM TYPE MESSAGE TYPE Switch Switch 7 Switch 8 Tone Only Tone/Voice Msg #2 Msg #1 15 sec 1 sec 1 sec ND 15 sec 2 sec 15 sec 20 sec NFPA Compliant 30 sec NC 15 sec 1 sec 1 sec 15 sec 2 sec 15 sec NFPA/OSHPD compliant. Up Unlocked and Manual Reset are fixed. 20 sec 30 sec BD 15 sec 0 sec 1 sec 15 sec 1 sec 15 sec BOCA compliant. Automatic alarm reset after 30 continuous seconds of door closure 20 sec 30 sec 15 sec 0 sec 1 sec BC 15 sec 0 sec 15 sec BOCA/Chicago compliant. 0 sec nuisance. 20 sec Automatic alarm reset after 30 continuous 30 sec seconds of door closure 30 sec 1 sec 1 sec NH 30 sec 2 sec 15 sec 20 sec NFPA compliant. 30 sec BH 30 sec 0 sec 1 sec 30 sec 1 sec 15 sec BOCA compliant. Automatic alarm reset after 30 continuous seconds of door closure 20 sec 30 sec Switch 5 Switch 6 Switch 7 Switch 8 Internal Unlocked Tone Only Msg #2 Remote Locked Tone/Voice Msg #1 Switch 5 Switch 6 Switch 7 Switch 8 Internal Unlocked Tone Only Msg #2 Remote Unlocked Tone/Voice Msg #1 Switch 5 Switch 6 Switch 7 Switch 8 Internal Unlocked Tone Only Msg #2 Remote Locked Tone/Voice Msg #1 Switch 5 Switch 6 Switch 7 Switch 8 Internal Unlocked Tone Only Msg #2 Remote Locked Tone/Voice Msg #1 Switch 5 Switch 6 Switch 7 Switch 8 Internal Unlocked Tone Only Msg #2 Remote Locked Tone/Voice Msg #1 Switch 5 Switch 6 Switch 7 Switch 8 Internal Unlocked Tone Only Msg #2 Remote Locked Tone/Voice Msg #1 P:\INSTALLATI INST\Delayed Egress\INST1511ST\INST1511ST.vsd Rev G7 0219 Page 11

Lock Adjustment and Operation STEP 1. After the lock has been mounted to the door and frame per the provided template, feed the wiring through the access hole and out to the controller board. Reinstall the lock front cover onto the lock. Ensure that the trigger sensor is aligned with the hole in the cover. The sensor is preset at the factory to slightly project through the cover. WARNING: DO NOT ATTEMPT TO ADJUST THE TRIGGER SENSOR LENGTH. AS THIS WILL RESULT IN DAMAGE TO THE SENSOR AND VOID THE WARRANTY. STEP 2. Make all wiring connections to the lock. Observe the polarity of the input power terminals. The lock senses the power supply voltage and automatically configures itself for 12vdc or 24vdc operation. Correct power supply voltage must be used for proper lock operation. WARNING: INPUT TERMINALS FOR RESET, REX AND REMOTE TRIGGER MUST LY BE CNECTED TO A NORMALLY OPEN MOMENTARY DRY CTACT (I.E. 918 DIGITAL KEYPAD OR 728 KEY ). CNECTI TO A VOLTAGE OR A WET OUTPUT MAY DAMAGE THE LOCK AND VOID THE WARRANTY. STEP 3. Slowly swing the door closed and visually observe the position of the armature trigger as it approaches the trigger sensor on the lock. If the provided mounting template was used during the lock and armature installation, the trigger & sensor should align with one another both horizontally and vertically. The LED on the back of the trigger sensor will light when the armature trigger is detected. IMPORTANT: CORRECT OPERATI OF THIS LOCK DEPENDS THE TRIGGER SENSOR BEING ABLE TO DETECT THE ARMATURE TRIGGER WHEN THE DOOR IS CLOSED. A PROXIMITY ADJUSTMENT CAN BE MADE TO THE TRIGGER FOR FINE TUNING. THIS IS EXPLAINED IN STEP 4. STEP 4. The small black spot located on the locks front access cover facing the door is the trigger sensor. The TRIGGER SENSOR LED as well as the DIGITAL DISPLAY are beneficial in the testing process. the TRIGGER SENSOR LED located on the back of the sensor can be used to check the sensors operation and verify proper alignment and adjustment of the circular TRIGGER located on the armature assembly. The trigger sensor LED can be viewed through the terminal block side of the lock with the cover removed. You can find this near the speaker. The DIGITAL DISPLAY can be used for diagnostics when the lock is in bypass mode. It uses the TRIGGER SENSOR to sense door position so can also be used to check TRIGGER SENSOR operation. a) Double Dash Marks ( ) indicate that the TRIGGER SENSOR sees the TRIGGER and that the door is closed. b) Six Dash Marks ( ) indicate that the TRIGGER SENSOR does not see the TRIGGER. The door is either open or the trigger is improperly adjusted. Set the lock to BYPASS mode by turning the built in key on the lock counterclockwise. With the lock in the bypass mode, swing the door open. The TRIGGER SENSOR LED should be and the digital display should show Six Dash Marks. Prop your door open, place and hold a metal object (such as a coin) against the TRIGGER SENSOR on the face of the and verify that the TRIGGER SENSOR LED turns and that the DIGITAL DISPLAY changes to Double Dash Marks Remove the metal object and verify that the TRIGGER SENSOR LED turns OFF and the DIGITAL DISPLAY changes back to Six Dash Marks. This verifies that the trigger sensor is working. Close the door and verify that the TRIGGER SENSOR LED turns. If the LED does not turn and the DIGITAL DISPLAY does not change, adjust the TRIGGER on the armature assembly by turning the allen head screw in the center of the TRIGGER counterclockwise which will extend the trigger outward toward the lock face. Proper adjustment will allow the TRIGGER to touch the face of the TRIGGER SENSOR and be slightly depressed with the door fully closed. Reset the lock by turning the built in key switch momentarily clockwise. The lock should lock and the digital display should show the delay time. Now, push the door. With slight door movement (1/8" to 1/4 ) the delay process should start with the display counting down and the alarm sounding. If the delay process does not start once the door has moved, the circular target has been adjusted too far out and needs to be adjusted back in slightly. A properly adjusted target will pull away from the face of the sensor with 1/8" to 1/4 of door movement and start the delay process. STEP 5. Activation of the 1511S can be made by door movement or an external trigger. When using the door movement method, activation is achieved through the way the armature hardware is designed. When someone unlatches the door and applies up to 15 lbs. pressure, the lock will hold onto the armature while simultaneously letting the door & trigger armature move away from the lock & trigger sensor. Sensitivity in the detection of the trigger movement can be adjusted for optimum sensitivity & performance. This adjustment can be made as indicated in step 4. The center of the trigger or target is spring loaded and can be screwed in and out of the armature thus either decreasing or increasing the space between itself and the sensor. The spring feature of the target is to prevent damage from direct contact with the trigger sensor. Depending on the accuracy of the alignment, the trigger does not have to physically touch the sensor to operate correctly. P:\INSTALLATI INST\Delayed Egress\INST1511ST\INST1511ST.vsd Rev G7 0219 Page 12 1511S LOCK C BODY 1511S ARMATURE C TRIGGER SENSOR HORIZTAL ALIGNMENT TRIGGER ADJUSTABLE DISC VERTICAL ALIGNMENT

Systems Applications Reference Activation by applying pressure to doors with latching hardware: SOUNDS. DOOR CAN BE OPENED IN 15 SECDS. TCC / RCC 928 728 728L 702RU 1011AK 1011A 1014AM 101PAM Wall Mount Reset Station (Optional) Remote Annuciators and Control Panels (Optional) A pair of doors requires the 1511T Pushing either door triggers the delayed release of both doors. Activation by a remote trigger for doors with or without latching hardware: PT2 PT3 PT2 PT3 MS16 Latch Trigger PTH4 Hinge Switch Kit Sense Bar Trigger NonLatching PSB560, MSB550 Latching Exit Device with Builtin Switch Kit Trigger Latch Monitoring Strike Trigger For Mortise Exit Devices P:\INSTALLATI INST\Delayed Egress\INST1511ST\INST1511ST.vsd Rev G7 0219 Page 13