Burner Management System

Similar documents
Burner Management System

Burner Management System

Basic unit with integrated air-fuel ratio control for forced draft burners

Basic unit with integrated fuel-air ratio control for forced draft burners LMV Building Technologies Division

Basic Unit with integrated Fuel / Air Ratio Control for Forced Draft Burners LMV Building Technologies

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products

Oil Burner Controls LMO24... LMO44...

Oil Burner Controls LMO24... LMO44...

LGA... Gas Burner Controls. Building Technologies Division

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

Burner controls. Building Technologies HVAC Products

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

C Note! LGI16... Burner Controls. Building Technologies

Oil Burner Controls LOA3... Building Technologies HVAC Products

Gas Burner Controls. Building Technologies HVAC Products

Flame detector. Building Technologies Division Infrastructure & Cities Sector

Flame detector. The QRA4.U is for use with the following types of burner control:

Burner Controls. Building Technologies HVAC Products

Infrared Flame Detectors

Flame detector. The QRA4.U is for use with the following types of burner control:

UV Flame Supervision System

LAE10 LFE10. Use. Series 02

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies HVAC Products

Product Range Overview

QRA10... QRA53... QRA55...

Use. Burner controls for use with forced draught gas or gas / oil burners of small to medium capacity in intermittent operation.

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products

Use. The burner controls are certified to EN 230 and EN 298.

Oil Burner Controls LOA3... Building Technologies Division

LME75... Burner controls. Building Technologies

QRA10... QRA53... QRA55...

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies Landis & Staefa Division

QRA10... QRA53... QRA55...

Infrared Flame Detectors

Power Flame Incorporated

Program module for burner control LME71.000

Blue-flame Detectors

Heating Element. Building Technologies HVAC Products

Building Technologies Division

LFL Series Burner Flame Safeguard Control

RAR... Photocell Detectors. Building Technologies Division

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification

QRA10... QRA53... QRA55...

Building Technologies

Control Products & Systems OEM

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

Burner control unit BCU 370

PRELIMINARY EDITION

Burner control unit BCU 370

Building Technologies Division

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature

Eclipse Trilogy Flame Safeguard Modulating Sequences

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products

EUROBOX SERIES TYPES CM...N SM...N MM...N

for relative humidity and temperature

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

EUROBOX SERIES TYPES CM... SM... MM...

for relative humidity and temperature

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

Forced draught gas burner

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Automation System TROVIS 5400 Boiler Controller TROVIS 5474

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

Room Air Quality Sensors

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

Duct Temperature Sensors

Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature

EUROFLAT SERIES TYPES C... S... M...

Duct Air Quality Sensors

Power Flame Incorporated

Interface and EOL Modules 8

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

QFM21... Duct sensors. Symaro. for relative humidity and temperature

DKG 972. Gas Burner Safety Control. For 2-stage atmospheric gas burners

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

Rules for Intruder Alarm Systems

Distributed By: M&M Control Service, Inc Building Technologies

Monitoring Devices 11/1

Protective system controls, automatic burner control units, burner control units. Industrial & Commercial Thermal. 6 Edition 06.

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

for relative humidity and temperature with calibration certificates

DATASHEET. Burner control unit FDA 601x

Room air quality sensors

YP7999A1000 ControLinks Fuel Air Ratio Control Panel

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

Flame detector FD 2011 / FD 2012

Transcription:

7 541 Burner Management System MV27.1... Burner control with integrated air / fuel ratio control for forced draft burners. The MV27.1 are designed for intermittent operation. The MV27.1... and this Data Sheet are intended for use by OEMs which integrate the burner management system in their products! Use The MV27.1... burner management system is a microprocessor-based unit with matching system components for the control and supervision of forced draft burners of medium to high capacity. 22.06.2006 HVAC Products

Warning notes For additional safety notes, refer to the Basic Documentation of the MV27.1... system (P7541)! To avoid injury to persons, damage to property or the environment, the following warning notes should be observed! The MV27.1... is a safety device! Do not open, interfere with or modify the unit. Siemens will not assume responsibility for any damage resulting from unauthorized interference! All activities (mounting, installation and service work, etc.) must be performed by qualified staff Before making any wiring changes in the connection area of the MV27.1, completely isolate the unit from the mains supply (all-polar disconnection) Ensure protection against electric shock hazard by providing adequate protection for the burner control s connection terals Each time work has been carried out (mounting, installation, service work, etc.), check to ensure that wiring and parameters is in an orderly state Fall or shock can adversely affect the safety functions. Such units must not be put into operation, even if they do not exhibit any damage For display of the flame on the AZ2, following general conditions apply: - Display is subject to various component tolerances so that deviations of ± 10 % can occur - Note that for physical reasons there is no linear relationship between flame display and detector signal values Mounting notes Ensure that the relevant national safety regulations are complied with Mounting 217 10 103.5 Additional mounting surfaces 122 6.5 7541z298e/0606 M5 x 4 Outer contour of housing 0.3 (103.5) Installation notes Always run high-voltage ignition cables separately while observing the greatest possible distance to the unit and to other cables Do not mix up live and neutral conductors 2/17

Electrical connection of the flame detectors It is important to achieve practically disturbance- and loss-free signal transmission: Never run the detector cable together with other cables ine capacitance reduces the magnitude of the flame signal Use a separate cable Observe the maximum permissible detector cable lengths The ionization probe is not protected against electric shock hazard. It is mainspowered and must be protected against accidental contact ocate the ignition electrode and the ionization probe such that the ignition spark cannot arc over to the ionization probe (risk of electrical overloads) Standards and certificates Conformity to EEC directives - Electromagnetic compatibility EMC (immunity) - Directive for gas appliances - ow-voltage directive 89 / 336 / EEC 90 / 396 / EEC 73 / 23 / EEC ISO 9001: 2000 Cert. 00739 ISO 14001: 2004 Cert. 38233 Identification code to EN 298 chapter 4 F T / M C B B Service notes If fuses are blown, the unit must be returned to Siemens Disposal notes The unit contains electrical and electronic components and must not be disposed of together with domestic waste. ocal and currently valid legislation must be observed. 3/17

Mechanical design The MV27.1... is a microprocessor-based system with matching system components for the control and supervision of forced draft burners of medium to high capacity. The following system components are integrated in the MV27.1 basic unit: Burner control with gas valve proving system Electronic air / fuel ratio control with a maximum of 2 actuators Modbus interface Example: Modulating gas burner The system components (display and operating unit, actuators) are connected directly to the MV27.1 basic unit. All safety-related digital inputs and outputs of the system are monitored by a contact feedback network (CFN). For intermittent operation in connection with the MV27.1..., an ionization probe or optical flame detector type QRB or QRC is used. The burner management system is operated and parameterized with the help of the AZ2 display and operating unit or a PC tool. The AZ2... features an CD and menu-driven operation, offering straightforward operation and targeted diagnostics. To simplify diagnostics, the display shows the operating states, the type of fault and the point in time the fault occurred. The different parameter setting levels for the burner / boiler manufacturer and the heating engineer are protected by passwords. Basic settings that the plant operator can make on site do not demand a password. There is also a communication interface COM from which higher level systems such as building automation (GA). Using the BCI and OCI410 interfaces, a PC with ACS410 software can be connected. Among other features, the software affords convenient readout of settings and operating states, parameterization of the MV27.1..., and trend logging. The burner / boiler manufacturer can choose from a number of different fuel trains and has a wide variety of parameter setting choices (program times, configuration of inputs and outputs, etc.) to ensure optimum adaptation to the relevant application. The SQM3... and SQN1 actuators are driven by stepper motors and offer highresolution positioning. The characteristics and settings of the actuators are defined by the MV27.1... basic unit. 4/17

Type summary Microprocessor-based burner control for single-fuel burners of any capacity, electronic air / fuel ratio control, up to 2 actuators, integrated gas valve proving system. Type reference Mains voltage Parameter set Type of flame detector MV27.100A2 AC 230 V Europe QRA2 / QRA4 (USA) / QRA10 / QRB / QRC / ION TSA Gas Oil 3 s 5 s Technical data MV27.1 basic unit Teral loading «Inputs» Mains voltage AC 230 V -15 % / +10 % Mains frequency 50 / 60 Hz ±6 % Power consumption < 30 W (typically) Safety class I, with parts according to II and III to DIN EN 60 730-1 Degree of protection IP00 Note: The burner or boiler manufacturer must ensure degree of protection IP40 to DIN EN 529 for burner controls by adequate installation of the MV2 Perm. mains primary fuse max. 16 AT (externally) Unit fuse F1 (internally) 6.3 AT (DIN EN 60 127 2 / 5) Mains supply: Input current depending on the operating state of the unit Undervoltage Safety shutdown from operating approx. AC 186 V position at mains voltage Restart on rise in mains voltage approx. AC 195 V Status inputs: Status inputs (with the exception of the safety loop) of the contact feedback network (CFN) are used for system supervision and require mains-related input voltage Input safety loop refer to «Teral loading outputs» Input currents and input voltages - UeMax UN +10 % - UeMin UN -15 % - IeMax 1.5 ma peak - IeMin 0.7 ma peak Contact material recommendation gold-plated silver contacts for external signal sources (P,, max, etc.) Transition / settling behavior / bounce - Perm. bounce time of contacts when switching on / off UN AC 230 V Voltage detection - On AC 180...253 V - Off < AC 80 V max. 50 ms (after the bounce time, the contact must stay closed or open) 5/17

Technical data (cont d) Teral loading «Outputs» Total contact loading: Noal voltage AC 230 V, 50 / 60 Hz Unit input current (safety loop) from: max. 5 A - Fan motor contactor - Ignition transformer - Valves - Oil pump / magnetic clutch Individual contact loading: Fan motor contactor Noal voltage AC 230 V, 50 / 60 Hz Noal current 2 A Power factor cosϕ > 0.4 Alarm output Noal voltage AC 230 V, 50 / 60 Hz Noal current 1 A factor cosϕ > 0.4 Ignition transformer Noal voltage AC 230 V, 50 / 60 Hz Noal current 2 A Power factor cosϕ > 0.2 Fuel valves Noal voltage AC 230 V, 50 / 60 Hz Noal current 2 A Power factor cosϕ > 0.4 Operation display Noal voltage AC 230 V, 50 / 60 Hz Noal current 0.5 A Power factor cosϕ > 0.4 Cable lengths Mains line AC 230 V max. 100 m (100 pf / m) Display, BCI max. 3 m (100 pf / m) for used outside the burner cover or the control panel in assessment: max. 10 m (100 pf / m) for used outside the burner cover oad controller R max. 20 m (100 pf / m) External lockout reset button max. 20 m (100 pf / m) Other lines max. 3 m (100 pf / m) Specification as per EN 60730-1 Type of shutdown or interruption of each circuit Shutdown with microswitch 1-pole Mode of operation type 2 B 6/17

Technical data (cont d) Cross-sectional areas The cross-sectional areas of the mains power lines (, N, and ) and, if required, the safety loop (safety limit thermostat, water shortage, etc.) must be sized for noal currents according to the selected external primary fuse. The cross-sectional areas of the other cables must be sized in accordance with the internal unit fuse (max. 6.3 AT). Min. cross-sectional area 0.75 mm² (single- or multi-core to VDE 0100) Cable insulation must meet the relevant temperature requirements and environmental conditions. Fuses used in the MV27.1... basic unit - F1 6.3 AT DIN EN 60 127 2 / 5 Connecting cable display BCI Environmental conditions Standard signal cable standard length 0.3 m and 2 m ocation under the burner cover or in the control panel Delivery Specification H 72385 0000 0 Supplier Hütter http://www.huetter.co.at/telefonkabel.htm Storage DIN EN 60 721-3-1 Climatic conditions class 1K3 Mechanical conditions class 1M2 Temperature range -20...+60 C Humidity < 95 % r.h. Transport DIN EN 60 721-3-2 Climatic conditions class 2K2 Mechanical conditions class 2M2 Temperature range -30...+60 C Humidity < 95 % r.h. Operation DIN EN 60 721-3-3 Climatic conditions class 3K3 Mechanical conditions class 3M3 Temperature range -20...+60 C Humidity < 95 % r.h. Condensation, formation of ice and ingress of water are not permitted! 7/17

Technical data (cont d) Flame detectors Ionization probe No-load voltage at ION teral (X10 05 teral 2) approx. UNetz Caution! Protect the ionization probe against electric shock hazard! Short-circuit current max. AC 1 ma Required detector current. DC 4 µa, flame display approx. 30 % Possible detector current max. DC 16 40 µa, flame display approx. 100 % Max. perm. length of detector cable 3 m (wire ground 100 pf / m) (laid separately) Note: With increasing detector cable capacitance (cable length), the voltage at the ionization probe, and thus the current, drops. ong cable lengths plus very highly resistive flames might necessitate low-capacitance detector cables (e.g. ignition cable). In spite of technical measures taken in the circuitry aimed at compensating potential adverse effects of the ignition spark on the ionization current, it must be made certain that the imum detector current required will already be reached during the ignition phase. If this is not the case, the connections on the primary side of the ignition transformer must be changed and / or the electrodes relocated. Photoresistive detectors QRB No-load voltage at QRB... teral (X10 05 teral 3) Max. perm. length of QRB... detector cable (laid separately) approx. DC 5 V 3 m (wire wire 100 pf / m) Note: A detector resistance of RF < 500 Ω is identified as a short-circuit and leads to safety shutdown in operation as if the flame had been lost. For this reason, before considering the use of a highly sensitive photoresistive detector (QRB1B... or QRB3S), it should be checked whether this type of flame detector is really required! Increased line capacitance between QRB... connection and mains live wire has an adverse effect on sensitivity and increases the risk of damaged flame detectors due to overvoltage. Always run detector cables separately! Threshold value flame supervision QRB with MV2 Start prevention (extraneous light) with RQRB Operation with RQRB Short-circuit detection with RQRB < 400 kω intensity > 10 % < 230 kω intensity > 16 % < 0.5 kω 8/17

Technical data (cont d) Flame detectors QRA2 / QRA4 (U.S.) / QRA10 Blue-flame detectors QRC Caution! If flame detectors type QRA2 / QRA4 are used for flame supervision with the MV2, it must be ensured that the detector is permanently connected to power (conforg to EN 230), thus enabling the system to detect flame detector failures during startup. Aquivalent threshold value: Operation approx. 20 µa (measured with DC 15 V / 4.5 kω series resistor) For system-specific reasons, the display of flame intensity is limited to a maximum of approximately 55 %. 9/17

Block diagram inputs / outputs Burner flange Motor Alarm Motor continuous SV Z V3 P P N N N T 3 2 1 3 2 1 2 1 Siemens marking umberg code umberg code Siemens marking GP T GP 3 2 1 3 2 1 3 2 1 3 2 1 X5-01 X9-04 X7-02 X4-02 X6-03 X3-05 X3-03 03K54 03K30 03K10 03K66 03K57 03K80 02K15 02K02 04K01 02K13 04K80 03K34 05K30 X3-02 X5-03 X8-04 X8-02 X7-01 X3-04 1 2 1 2 3 4 1 2 1 2 3 4 1 2 3 1 2 3 4 5 N N N 2 3 On/off pa Safety loop V2 V1 B4 Reset P GP max P max 3 2 1 X5-02 03K31 02K43 X10-06 5 1 2 + QRA... 05K37 X10-05 1 2 3 4 QRB... ION RXD0 TXD0 U Display 1 2 3 4 X56 02K37 X75 1 2 Signal input Voltage umberg code Siemens marking 3521 04/ RAST2.5 X92 4 3 2 1 3521 06 / RAST2.5 X54 6 5 4 3 2 1 3521 06 / RAST2.5 X53 6 5 4 3 2 1 AK 1550/5-3.5-gr X74 5 4 3 2 1 Name PTR Siemens marking RXD1 TXD1 U Bus ACT0 Input B ACT0 Input A ACT0 Output B ACT0 Output A U ACT ACT1 Input B ACT1 Input A ACT1 Output B ACT1 Output A U ACT Analog output external 24 V external input b Display / BCI Fuel counter COM Actuator Fuel Actuator Air oad output AK 1550/5-3.5-gr X64 5 4 3 2 1 7541a14e/0606 Reserve 10/17

Inputs / outputs (cont d) X3-03 X3-05 X6-03 X4-02 X7-02 X9-04 X5-01 X5-02 FUSE 1 T6.3 IEC 60127-2/V X75 X10-05 X10-06 X3-02 X5-03 X8-04 X8-02 X7-01 X3-04 N BCI X56 VSD X74 1 7541z297/0506 COM X92 1 FUE X54 1 AIR X53 1 X64 1 11/17

Connection diagram MV2... X8-02.2 Wiring point for series valves MV2... X8-02.3 X8-02.1 Fuel valve V1 X7-01.2 X7-01.3 Fuel valve V2 X7-02.2 X7-02.3 Fuel valve V3 X6-03.2 X6-03.3 Fuel valve SV X4-02.2 X4-02.3 Ignition Power signal for air pressure switch (P) X3-02.2 P X3-02.1 Air pressure switch (P) 1' X8-04.1 Reset / manual locking On/Off X5-03.1 Controller (on / off) 3 X5-03.2 Controller closing / stage 3 Power signal for controller X5-03.4 X5-01.3 P 2 X5-03.3 X5-01.2 Controller opening / stage 2 Pressure switch- Power signal for pressure switch X5-02.3 X9-04.3 P P max T (CPI) X5-02.2 X9-04.2 Pressure switch-max Pressure switch-dk-fas / T or valve closing contact (CPI) X10-06.2 QRA... (+) Flame QRA... + QRB... / 1) only QRC... X10-06.1 X10-05.1 X10-05.4 QRA... (-) Protective earth () ION 1) X10-05.5 Power signal () X10-05.3 QRB... / QRC... signal voltage X10-05.2 Ionization probe (ION) X8-04.2 Indication oil / gas Fan X3-05.3 Continuous fan operation 1-3 3 X3-05.1 Fan motor contactor Fan X3-05.2 Alarm X3-03.1 End switch burner flange (component of safety loop) X3-03.2 Power signal for end switch burner flange STB AUX Water shortage X3-04.1 X3-04.2 Safety loop Power signal for safety loop X3-04.3 Protective earth () N X3-04.4 Power supply neutral conductor (N) 1 F 6.3AT 1' X3-04.5 Power supply phase conductor () 7541a15e/0606 12/17

Connection diagram (cont d) oad output DC 24 V external DC 0 / 1...10 V Signal reference MV2... X74.1 X74.3 X74.2 VDS + 24 V + Mains supply input 0...10 V - MV2... Fuel counter input Power supply for fuel counter Input fuel counter X75.2 X75.1 + - Fuel actuator Functional earth for shield connection SQM3... SHIED X54.1 X54.3 X54.4 X54.5 X54.6 UAC_SA ACT0_OUT_A ACT0_OUT_B ACT0_IN_A ACT0_IN_B AZ2... / OCI... U Display Display X56.1 DC 5 V X54.2 TXD0 X56.2 TXD0 FE RXD0 X56.3 RXD0 Air actuator Functional earth for shield connection X53.1 X53.3 X53.4 X53.5 SQM3... SHIED UAC_SA ACT1_OUT_A ACT1_OUT_B ACT1_IN_A GA U Display X56.4 GA X92.1 Signal reference DC 5 V X53.6 ACT1_IN_B TXD1 X92.2 TXD1 X53.2 RXD1 X92.3 RXD1 FE X92.4 Signal reference 7541a37e/0606 13/17

Fuel train applications (examples) Direct gas ignition Program G Direct ignition SV V1 V2 DK max SA 7541s01e/0505 Gas pilot ignition 1 Program Gp1 Gas pilot SV V1 DK V2 max SA PV 7541s02e/0505 Gas pilot ignition 2 Program Gp2 Gas pilot SV V1 V2 DK max SA PV 7541s03e/0505 Fuel valve control program Direct trafo G PV *) V1 V2 TSA1 TSA2 Operation Gas (always modulating) Pilot ignition 1 Gp1 PV V1 V2 Pilot ignition 2 Gp2 PV V1 V2 egend for fuel trains: *) Not used 1) Series connection of two 115 V- valves (each requiring approx. 25 VA control power) 2) Preheating device V Fuel valve DK Gas valve proving Pressure switch HE Heating element HO Heavy fuel oil O ight fuel oil SA Actuator No Normally Open SV Shutoff valve (outside the building) PV Pilot valve 7541f01e/0505 14/17

Fuel train applications (examples) Direct ignition with light fuel oil, multistage Program O V1 7541s04/0305 1-stage burner V2 Program O V1 2-stage burner 7541s05/0305 V3 V2 Program O V1 3-stage burner 7541s06/0305 15/17

Fuel train applications (examples) Direct ignition with light fuel oil, modulating Program O V1 1) max M 1) Modulating burner (without shutdown facility for adjustable head) 7541s07e/0505 Program O V1 1) max M Modulating burner (with shutdown facility for adjustable head) 7541s08e/0505 Fuel valve control program ight fuel oil (Trafo direct ignition) O V1 V2 V3 TSA1 TSA2 Operation V3 V2 K position 7541f02e/0606 MIN MAX stage operation 16/17

Dimensions Dimensions in mm MV27.1... 230 202 192 141 82,5 22,8 10,2 118,5 122 135 16,5 39,3 R100 217 202 172 128,5 82,5 27,2 12,5 23,5 60 19,5 19,7 100,8 118,5 76,6 53,6 25,5 7541m08/0506 2006 Siemens HVAC Products GmbH Subject to change! 17/17