A Study on Compression Characteristic of Wet Vapor Refrigerant

Similar documents
Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Sub-Critical Operation of the CO2 Expander/ Compressor

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Compressor Capacity Control: A New Direction

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Purdue e-pubs. Purdue University

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional Test Results

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Numerical Evaluation of Performance Curves of a High Frequency Microcompressor

Heat Transfer of R-22 and Alternatives in a Plate- Type Evaporator

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Performance of CO2 Cycles with a Two-Stage Compressor

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Performance of an Improved Household Refrigerator/Freezer

High Efficiency R-134a Compressor for Domestic Refrigerator

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Efficiency of Non-Azeotropic Refrigerant Cycle

Optimization of Compressors used in Air Conditioning Units

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Two-Step Capacity Modulation of a Single Cylinder Compressor

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Compressor Capacity Control

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Low GWP Refrigerants for Air Conditioning Applications

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

R32 Compressor for Air conditioning and Refrigeration applications in China

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Leakage of Mildly Flammable Refrigerants into a Room

Simulation of the Working Process of an Oil Flooded Helical Screw Compressor with Liquid Refrigerant Injection

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Higher Efficiency, Lower Sound, and Lower Cost Air Conditioning Compressors: Part 1 Efficiency

Study of R161 Refrigerant for Residential Airconditioning

Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances

Experimental Study on the Performance of Twisted Capillary Tube

Characterization of Thermal Processes in Scroll Compressors

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

An Analysis of a New Type Refrigeration Cycle (MICLOSS)

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Development of HFC-134a Compressor for Domestic Refrigerator

Mini Vapour Cycle System For High Density Electronic Cooling Applications

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Dynamic Simulation of Liquid Chillers

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Air-Cooled Heat Exchanger Performance for R410A

An Experimental-Numerical Procedure to Characterize Compressor Performance under Cycling Operating Conditions of Refrigerators

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

Performance Measurement of R32 Vapor Injection Heat Pump System

An Experimental and Theoretical Study on System Performance of Refrigeration Cycle Using Alternative Refrigerants

Transcription:

Purdue University Purdue e-pubs nternational Compressor Engineering Conference School of Mechanical Engineering 1996 A Study on Compression Characteristic of Wet Vapor Refrigerant A. K. Dutta Shizuoka University T. Yanagisawa Shizuoka University M. Fukuta Shizuoka University Follow this and additional works at: http://docs.lib.purdue.edu/icec Dutta, A. K.; Yanagisawa, T.; and Fukuta, M., "A Study on Compression Characteristic of Wet Vapor Refrigerant" (1996). nternational Compressor Engineering Conference. Paper 1112. http://docs.lib.purdue.edu/icec/1112 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

A STUDY ON COMPRESSON CHARACTERSTC OF WET VAPOR REFRGERANT Asit Kumar DUTTA Tadashi YANAGSAWA, and Mitsuhiro FUKUTA Department of Energy and Mechanical Engineering, Shizuoka University 3-5-1, Johoku, Hamamatsu, 432, JAPAN ABSTRACT n this study a compression characteristic of vapor -liquid two phase refrigerant mixture is analyzed theoretically by using the mathematical models of vapor-liquid mixture condition in which the droplet size of the liquid, homogeneous mix.'wre of vapor and liquid_ and the slugging concept of the liquid are considered. nfluences of the parameters. such as quality of wet vapor and the cylinder wall heat transfer. on the pressure as well as on the temperature are investigated. A model experiment has been done by using the components of the reciprocating compressor "'ithout connecting to the refrigeration cycle. Different condition of the liquid refrigerant such as liquid slug has been created by injecting liquid refrigerant into the cylinder prior to the compression start, and the first compression process has been considered for investigation. n this case, the result of the model considering slugging concept matches well vith the experimental result. Further. a refrigeration cycle experiment has been done by using a reciprocating compressor under liquid suctioning, and the cylinder pressure change at steady state operation vith different suction quality are recorded for investigation. n this case, the result of the model considering homogeneous vapor -liquid mixture or the smallest drop size ( l f.l 11V of liquid matches well with the experimental result. L NTRODUCTON n the refrigeration fields, wet compression is a common practice to decrease the discharge gas temperature. Beside this, several researches have been done concerning with slugging [1,2], leakage and the performances of the compressor during wet compression (3.4,5]. However, it remains the question of how the compression characteristics behave under wet compression. n this study, we have analyzed the compression pressure characteristic, temperature and pressure change under wet compression by considering 3- different models of vapor and liquid mix.'"tllre inside the compressor cylinder. Two different experiments have been done to check the validity of these models i.e. refrigeration cycle experiment with liquid suctioning, and the model experiment by injecting liquid refrigerant inside the compressor cylinder without connecting to the refrigeration cycle. 2. ANALYTCAL MODEL The model is presented schematically in Figure 1. n this figure, the compressor cylinder of volume (V) is considered as a control volume. The wet vapor refrigerant enters into the control volume and within the control volume owing to the small increment of piston as well as the heat from the outside, the temperature and pressure of the vapor increase and exchange heat to the existing liquid refrigerant. The process will be repeated throughout the whole compression period. Finally the refrigerant leaves the control volume. 2.1 Governing Equation From the physical laws of mass and energy conservation, the basic energy equations for vapor and liquid refrigerant are expressed as: (1) 235

~p ~ mf dt. =Gu(hr; -hr)+g,o(hr -hro)+q".r -G.(hg -hr)+mrvr dt +Q and volume equation for control volume is: (2) Where. G : refrigerant mass flow rate, v and h : specific volume and enthalpy, m: mass of refrigerant inside the control volume, P: pressure, Qwg and Qw r :heat flow from the wall to the vapor and liquid, P: pressure, Q: heat flow from the vapor to liquid. The subscripts e : evaporation. g and ~ : vapor and liquid, g1, go and f!i, P.o: incoming and outgoing vapor and liquid_ The properties of the refrigerant vapor are represented as: vg =ft(tg, P) and h 2 =h(tg, P), and the refrigerant liquid are -~--------------- represented as: V 1 =h(t 1 ) and h 1 =fit 1 ). Therefore, the main unknown variables in the -above equations are: Tg, T,. P. Ge and Q, provided the incoming and outgoing mass flow rate and the heat flow from the wall to the control volume are k:novv11_ Therefore. in order to solve those unknown variables, other Fig. 1 Analytical model two equations become necessary except the above stated three equations. and to do so, proper modeling of vaporliquid mixture should be needed. n this study, the following models are considered: () Droplet model (2) Homogeneous model and (3) Slugging model (1) Droplet Model: n this model it is assumed that, the vapor and liquid refrigerant within the control volume exist separately and have different temperatures. The heat flow (Q) from the vapor to the liquid inside the control volume can be calculated by considering the size of liquid drop, heat transfer coefficient [6] and temperature difference between liquid and vapor inside the control volume The main unknown variables are: Tg, T 1, P and G 0. The step-by-step solution procedure of the equations are obtained as follows: first to solve the equations without considering G., and compare T r with the saturation temperature corresponding to the cylinder pressure. (2) Homogeneous Model: n this model, it is assumed that, the vapor and liquid refrigerant inside the control volume possess the same temperature at any moment. Then, the energy equations ( 1) and (2) for vapor and liquid can be modified, and written together as follows: The main unknown variables are: T (T g=t r ), P, and G. Under wet compression pressure P is the function of T, and the other two variables are solved by the appropriate equations (3) Slu2'2ing Model: n this model, it is assumed that, the liquid refrigerant in the control volume is the same temperature as initial at any moment, and the gas is always the saturation gas under wet compression. Therefore, volume equation for the control volume is same as (3) except v r is replaced by vflm, and the energy equations (1) and (2) can be modified, and written together as follows: 236

(5) Where, h bm : specific enthalpy of the liquid refrigerant at the initial condition. The main unknown variables are: T g, P and Ge, and under wet compression pressure P is the function of temperature. Therefore, the remaining variables are solved easily by the appropriate equations. The heat transfer (Qw) from the wall surface to the control volmne can be expressed as follows: (6) where, Aw: heat transfer area, a : convective heat transfer coefficient which can be obtained from the Adair correlation [7] based on the reciprocating compressor. The property values which are used in that correlation, are considered in terms of the vapor quality within the saturated as well as the superheated zone corresponding to the average cylinder pressure. Flow meter Condenser Control valve gauge To simulate the compression process, the incoming and outgoing flow rate are calculated considering flow through the valve ports as the nozzle flov: [8]. The properties of the refrigerant HCFC22 can be obtained from the correlation equations [9]. The property subroutine was implemented in the simulation programs. Expansion valve Evaporator Fig. 2 Refrigeration cycle experiment 3. EXPERMENTAL METHODS 3.1 Cycle Experiment Refrigeration cycle is shown in Figure 2. An open type reciprocating compressor ( stroke volume 56.3 em' ) which is generally used in the automobile refrigeratio~ was connected to the refrigeration cycle. n order to control the suction quality, a bypass line Pressure Transducer /Thermocouple Additional was connected to the compressor suction line from the condenser outlet. The main portion of the condensed liquid refrigerant was passed through the evaporator, and the bypass portion was added at the suction line through a control valve. Pressure in the cylinder and the plenums of the compressor were measured by the piezo-electric and the strain gauge type pressure transducer respectively. The compressor was driven by an electric motor, and the compressor speed along with the rotation angle was measured by an optical sensor. Temperature at different points of the cycle were measured by the C-C thermocouples. Refrigerant flow rates through the evaporator and the bypass were measured by a rotameter and an oval type flow meter respectively. Refrigerant HCFC22 was used as a working fluid, and the cycle was operated under suction and discharge absolute pressure of0.59 MPa and 1.57 MPa respectively. CYlinder Block Rubber Ring Fig. a Model experiment Data were recorded at steady state operation, with different suction quality and compressor speed. Further, the vapor quality at the suction port was obtained by revising the vapor quality at mixing point since refrigerant takes 237

heat from the plenum wall. 3.2 Model Experiment of Wet Compression with Liquid Slug Model experiment has been done by using the component of the reciprocating compressor without connecting to the refrigeration cycle as shown in Figure 3. The upper part of the compressor. such as cylinder head, suction and discharge ports, valves etc., have been replaced by a metallic cylindrical cap, in which a sight glass, charging port, pressure gauge and a thenuocouple were installed ( the volume ratio of the top dead and the bottom dead center of the piston= 1. 8 ). To prevent the leakage through the piston ring, a groove has been created around the top surface of the piston and a n1bber o-ring vvas installed. The compressor was driven by an electric motor. and the ON-OFF operation of the compressor was controlled by the clutch attached to the compressor pulley. The compressor speed along with rotation angle \Vas measured by the magnetic sensor. Cylinder pressure was measured by the strain gauge pressure transducer and the output signal of that transducer was recorded by the computer. Liquid refrigerant injected to the compressor cylinder by the charging vessel and the charged mass of refrigerant was calculated as follows: the weight of the charging vessel was measured by the electronic measuring equipment before and after the charge. n the charging condition, the liquid slug was clearly found inside the cylinder through the sight glass fitted at the top of the cylinder. Compressor was started when the cylinder pressure reached to the sawration pressure corresponding to the room temperature. Experiment was done by varying the liquid refrigerant quality with different speed, and only the first compression pressure change was considered for investigation. Refrigerant HCFC22 was used as a working fluid for this experiment. Furthem1ore, the experiment was also done with superheated refrigerant vapor. and recorded the cylinder pressure change by the computer as same as before. ~ 1 2. sr----;:~~-=--=--::----=c::------., -Gas P.22.0u l ;ty(!05%) ---O~.J~] 1ty (90%) - - Ou a 1 t y 16 3%) Z -~~ 01..1a l, ty (42Y.) ~.5~~~==~~~~~--- 2000 rpm bperim~'tttal 0 8~-~9~0~-~1~8~0----~27~0,------~360 Crank AnglE' (degree) Fig. 4 Results of the cycle experiment --105'Yo - - - 63% 42% Experimental 0~----~----~----------~ 4r-----------------------, 3 --105% -.-.- 63'Yo 42% 4. RESULTS AND DSCUSSONS 4.1 Refri~eration Cycle Experiment Figure 4 shows the suction and discharge plenum pressure and cylinder pressure change at each suction quality, and it indicates that cylinder suction pressure is affected by the suction plenum pressure and valve losses. Therefore, to investigate the compression characteristic at different suction quality, the cylinder pressure change at each suction quality is normalized with the pressure at crank angle 180 degree and the compression and discharge pressure change are shown in the Figure 5. Further, the pressure change calculated by considering the homogeneous and slugging models \Vith same experimental condition are shown in the bottom two of the Figure 5. n the simulations, the measured discharge temperature at each suction quality is used as a wall temperature. By comparing model results with experimental one, it is clear that, the calculated results considering homogeneous model behave in the same way with the Homogent:eus Model 0~----------------------~ 4r------------------------, 3 --105o/o - - - 63% 42'Y Slu.gging Model ~~0,------------~2~70~--------~360 Crank Angle (degree) Fig.5 Cycle experimental and calculated results experimental results, i.e. at the latter half of the compression (crank angle 230'""'-"285 degree), the pressure rise become slower as compared with superheated vapor pressure rise and decreases with decreasing suction quality due 238

to the cooling effect of refrigerant liquid. While, at the begi1ming ofthe compression (crank angle 180"-'230 degree) the pressure rise of the wet vapor at each suction quality becomes slightly earlier (though it is not clear in the figure) as compared v.ith tl1e superheated vapor pressure rise since the temperature difference between wall and refrigerant inside the cylinder enhance the evaporation of liquid. Further, the results of the slugging model shows thar the pressure rise of the wet vapor become earlier with decreasing quality The results of droplet model are not shown here since with smallest drop size the results of the droplet model are almost same with the homogeneous model, while at largest drop size the heat transfer between vapor and liquid decreases which causes to increase the pressure rise as compared with the superheated vapor. G 100r---------------------~~ 8!J ~ 60 "E '-' 53-- <10 \ ~ Qualitv 105%- 95% 85% ---- 60% Depending on the same behavior of the homogeneous model and experimental results, it can be said that, during liquid suctioning at steady state operation. the liquid enters into the cylinder as a fine drop and perfectly exchanges heat with the vapor inside the cylinder. Further, the figure 6 shows the temperature and quality change of the refrigerant vapor with crank angle considering homogeneous model. The figure indicates tl1at the temperature of the vapor decreases in the process of compression due to the evaporation of the refrigerant liquid. The quality curve shows that at 86% quality the liquid refrigerant is evaporated in the process of compression, vvhile at 60% quality, the condensation occurs in tl1e process of compression since the liquid cool tl1e vapor up to its saturation temperature corresponding to the vapor pressure. and fi..trther cooling is the cause of condensation. i2~r-------------------~--~ 188 1---------_-/ Qualitv --105%. --- 85% -----60% 6(1 ----- - - - - --- - - -- --- 2000 rpm Homogeneous Model 40 0~--~9~(1~--~~~8~0----~27~0~--~360 Crank Angle (degree) Fig. G Temperature and quality change inside the cylinder Finally, the Figure 7 is a plot of calculated and experimental discharge vapor temperature, and it shows that, discharge temperature decreases with decreasing the suction vapor quality and below 90% quality, the discharge temperature becomes equal to the saturation temperature corresponding to the discharge pressure. Figure 7 further indicates that, the calculated result considering heat transfer from wall to refrigerant inside the cylinder matches well with the experinlental result. 4.2 Model Experiment of Wet Compression with Liguid Slu~ The model experimental results of variation of cylinder pressure with different starting quality are shown in the top of the Figure 8, and the calculated results from different models are shown in the bottom three of the same figure. Compared the experimental results with model results it can be seen tl1at, the trend in pressure rise of slugging model at each starting quality behave the same as the 100.--.-.--~~--r-~~ experinlental results, i.e. at 90% quality of the wet vapor, the trend in compression pressure rise becomes slower as compared with the superheated vapor (103%) pressure rise. While at 61% quality, the pressure rise becomes earlier and is almost the same as the superheated vapor pressure rise, because at low quality the volume of liquid refrigerant enhance the compression on the vapor. On the other hand, the trend in pressure rise 40 40 - Calculated with heat transfer 1 1 without heat transfer Experimental -.--..--... -~--- / J 2000 rpm 60 80 100 (%) Fig. 7 Discharge temperature change with suction quality of the homogeneous model at each starting quality becomes slower with decreasing quality due to the cooling effect of the refrigerant liquid. The results ofthe droplet model shows that at constant quality the compression pressure rise decreases with decreasing drop size since as tl1e drop size decreases the surface area ofthe drop increases. Further, at smallest drop size (l,u~ the result ofthe droplet model is almost same with the homogeneous model 239

5. CONCLUSONS The compression pressure characteristic of the wet vapor refrigerant was investigated experimentally and mathematically, and was drawn the following conclusions: l. The slugging condition created by the model experiment was analyzed by the slugging model, and the results indicated that under slugging condition the compression pressure rise became earlier with decrease in starting quality of vapor below 90%. "2 _ 5 c.. ~ --103%" - --- 61% 850 rpm 2. The cylinder process of the compressor under liquid suctioning at steady state operation, was analyzed by the homogeneous model or the droplet model of smallest drop size (l.u ni). The results indicated that the pressure rise of the \Vet vapor became earlier at the beginning of the compression as compared \v:ith the superheated vapor pressure rise. However at latter half of the compression it became slower with decreasing suction quality. 3. From the analytical results it became clear that, the evaporation of the liquid refrigerant in the compressor cylinder decreased not only the vapor temperature but also decreased the compression pressure rise under liquid suction:ing. Further, as compared with the results excluding the heat transfer, it can be said that heat transfer during wet compression must not be avoided. 6. REFERENCES 1) Sing, R., et al, ASHRAE Trans. Vol. 92, Part 1B,(l996), pp.250'""258. 2) Liu, Z., et al, Proc. 1994 nt. Comp. Engn. Conf. at purdue, (1994), pp. 433'""440. 3) Afjei, Th., et al., Proc. 1992 nt. Cornp. Engn. Conf. at purdue, (1994) pp. 541----550. 4) Ayub, S., et al., Proc. 1992 nt. Comp. Engn. Conf. at purdue, (1992), pp. 561----567. 5) Hirano, T., et al., Trans. JAR Vol. 10, No. 2 (1993), pp. 227'""- 238. (in Japanese) 6) Stosic, N., et al., Proc. 1988 nt. Comp. Engn. Conf. at purdue, (1988) pp. 354'""-361. 7) Adair, R. P., M. S. Thesis, Purdue university (1972) 8) Fukuta, M., et al., Trans. JSME (Series B), Vol. 61, No. 582, (1995) pp. 542...,548. (in Japanese) 9) Refrigeration and Air-conditioning hand book, 1992, JAR. (in Japanese) ";;". S c.. ~ c.. "' Volum~ Ratio (1.8) Exf)~rimf'ntal.s~----------~--------~ 2,---------------------~ --103% - --- 61% Slugging model.5~----------~--------~ --103% --- - 61% Homogen<?ous rnoml.sl-----------~--------~ 2r--------------------, --103% DropSizcl /.Lm --- - 61%.... ~1.5 90"/o Drop Size 50 1.1. m 61% - -. Droplet ModE> T a~0:-----2::-4:-::0:--_._--_.3 0-=0 J36 0 Crank Angle (degree) Fig. 8 Model experimental and calculated results 240