Institute of Industrial Science, University of Tokyo Bulletin of ERS, No. 45 (2012) FAILURE OF CEILINGS IN AN AIRPORT BUILDING DURING THE 2011 OFF THE

Similar documents
S. Motoyui 1 and Y. Sato 2

Development of Seismic-induced Fire Risk Assessment Method for a Building

Fire propagation over combustible exterior facades exposed to intensified flame in Japan

Available at: Last Modified: December 2012

HEAT REMOVAL TESTS FOR THE HIGH PERFORMANCE VAULT STORAGE SYSTEM OF SPENT NUCLEAR FUEL

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

Osaka City New Supply of Office Buildings & Office Stock Pyramid 2015

EVACUATION SIMULATION FOR BUILDING DAMAGE CAUSED. Shiori KUBO Rei FUJITA Hidenori YOSHIDA Lalith WIJERATHNE Muneo HORI

eature Enhancement of Functions of Tokaido Shinkansen Earthquake Disaster Prevention System Tadayoshi Arashika and Shigeru Nakajima

Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement

Indoor Climate Control Effect of AAC Panel Heat Capacity Experimental rooms and simulations with three structural materials

Health Monitoring System Using FBG-Based Sensors for a 12-Story Building with Column Dampers.

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

HOT IN HERE: OFFICE OCCUPANT THERMAL COMFORT IN LAWRENCE HALL

Overview of fiber optic sensing system: BOTDR and its applications

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation

VALIDATION OF FINITE ELEMENT MODELS OF INJURY RISK IN VEHICLE-ROADSIDE BARRIER CRASHES

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Tokyo-wan Aqualine - Experience of Traffic and Safety

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

Disaster Mitigation of Debris Flows, Slope Failures and Landslides 759

CASE STUDY ANALYSIS OF CENTRIFUGAL FAN HIGH AMPLITUDE VIBRATION. Ken Singleton

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CEE:3371 Principles of Hydraulics and Hydrology Project #2 Flow Measurement with a Weir

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

Feasibility Study of Use of Elevators in Fire Evacuation in a High-rise Building

Section Plaster Accessories

Innovative Services Give Dayton Contractor A Big Edge

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Chapter 17, Initiating Devices

GENIE CLIP TYPE RST. Resilient Sound Isolation Clip INSTALLATION INSTRUCTIONS

However, uncertainty exists on the proper approaches to fastening claddings over exterior insulation.

An Innovative Device for Vacuum and Air Venting

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model

Analysis of Triangle Heating Technique using High Frequency Induction Heating in Forming Process of Steel Plate

Seismic Countermeasures for Environmental Radiation Monitoring System

OPTIMISATION OF NOZZLE ARRANGEMENTS ON DESCALING HEADERS. Jürgen W. Frick Lechler GmbH D Metzingen / Germany

Duke University Medical School. Duke School of Nursing

Consolidated Contractors Company IPLOCA Health & Safety Meeting. Preview Radar System

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

HOME CINEMA SPEAKER PACKAGE

EVAPORATION NEEDS ENERGY

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS DU/DUH DUAL OUTPUT RANGE INFRARED TUBE HEATERS

Person Detection Techniques for an Internet of Things(IoT)-Based Emergency Evacuation System

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

A Study on Cooling Rate with Blade and Sound Fire Extinguisher

Nature as a Classroom As an agriculture student majoring in Forest Science, concentrating originally on crop and soil sciences, I devoted my time

SICK AG WHITEPAPER 3 TECHNOLOGIES FOR PCB DETECTION

Reaction of Non Combustible Materials with Fire to Safe Guard Lives and Property in Building Environment

Protecting Multi-level Residential Buildings By GERALD A. O ROURKE, CPP

State of the Road Tunnel Safety Technology in Japan. Hideto Mashimo 1

Intelligent Speed Dome Installation Manual. Version 1.0.0

Static cooling ceiling system SKS-4/3 DS 4094 E /1. Technical Selection

Port of Portland Conveying Equipment Guidelines

Series RFII 5.6 K-factor. Flush II Concealed Pendent Sprinklers

DESCRIPTION OF THE LAUNDRY ROOM AND THE WASHER-DRYER INSTALLATION

ICSV14. Cairns Australia 9-12 July, Noise reduction of handheld vacuum cleaners according to geometric optimization of air passages

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen

L O S S C O N T R O L

4.0 EROSION AND SEDIMENT PROCESS. 4.1 Mechanics of Erosion

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

INTERIOR FINISHES AND FIRE PROTECTION SYSTEMS

Development of Post-Accident Monitoring System for Severe Accidents

SNAP, CRACKLE, & POP: THE BWR POWER UPRATE EXPERIMENT

A Design of IADSS with the Earthquake Detecting Function


Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development

DECOMMISSIONING OF THE REACTOR VESSEL OF THE COMPACT SODIUM COOLED NUCLEAR REACTOR FACILITY (KNK)

The World's Longest-distance * Detection

Fire/Arson Investigation Unit Fire Investigation Report

Preliminary Summary Report of Serious or Near Serious CAL FIRE Injuries, Illnesses and Accidents GREEN SHEET. Firefighter Burn Injury.

Fire at detention centre Schiphol

NON-DESTRUCTIVE MONITORING AND ACTIVE PREVENTION OF CORROSION IN SUSPENSION BRIDGE MAIN CABLES

PART V: WORKING WITH LASERS

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

VICTORIA BC V8R 1C4. # of Occupants (At time of fire): 30 # of Injured: 0 # of Deaths: 0 Total Dollar Loss Estimate:

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

SECTION GAS-FIRED RADIANT HEATERS

Indoor Thermal Environment of Residential Buildings in Three Cities of China

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

E. Luminaire: Complete lighting fixture, including ballast housing if provided.

CATHARINE BLAINE. Teacher Guide. CONTENTS Stormwater in the Schoolyard Lesson 3

INSTALLATION INSTRUCTIONS

MINIATURE HEAT TRANSPORT SYSTEMS WITH LOOP HEAT PIPES

SECTION INTERIOR LIGHTING

Development of a Slope Stability Program for Transmission Towers

EXPERIMENTAL PERFORMANCE INVESTIGATION OF SWIRLING FLOW ENHANCEMENT ON FLUIDIZED BED DRYER

INSTALLATION INSTRUCTIONS

Indoor Air of a Double-Storey Residential House in Malaysia

Case Studies of Master Planning for Sustainable Urban Underground Space Utilization

A Study on Anti-Loosening Characteristics of Different 3/8 BSW Threaded Fasteners

Eliminating Condensation and Resulting Corrosion. Sulphur Tail Gas and De-Gas Lines

Case study about initial action by disaster prevention staffs at a fire

GEOTEXTILE DEFORMATION ANALYSIS OF GEOSYNTHETIC CLAY LINERS WITH FEM

The Effect of Pedestrian Traffic on the Dynamic Behavior of Footbridges M. Studničková

AMOUNT OF MOISTURE PRODUCED INSIDE BATHROOM AND APPURTENANT CHANGING ROOM

Transcription:

Institute of Industrial Science, University of Tokyo Bulletin of ERS, No. 45 (2012) FAILURE OF CEILINGS IN AN AIRPORT BUILDING DURING THE 2011 OFF THE PACIFIC COAST OF TOHOKU EARTHQUAKE AND ESTIMATION OF ITS IMPACT Yasushi OBA 1, Yosuke NAKASO 2 and Ken ichi KAWAGUCHI 3 ABSTRACT: This is an investigation report on the failure of ceilings at the entrance hall of an airport building with well space during the 2011 off the Pacific Coast of Tohoku Earthquake. Although nobody was injured by the accident, the height of the ceilings was so high that the estimation of the extent of possible damage to human body is worth to understand the risk of such failure. The impact estimation was carried out by using a broadcasting video record taken accidentally during the earthquake and the results of ceiling dropping test to a dummy head. Key Words: the 2011 off the Pacific Coast of Tohoku Earthquake, Suspended ceiling, Impact estimation INTRODUCTION This is an investigation report on the failure of ceilings at entrance hall with well space of an airport building during the 2011 off the Pacific Coast of Tohoku Earthquake. Luckily, nobody was injured by the accident, however the height of the ceilings was so high and it is worth to estimate impact of the failure and possible danger to human body for better understanding of the risk of such failure. The impact estimation was carried out by reference to the news video taken during the accident and by comparing to the experimental results of dummy head test. The building has restored its function in a short period, ensuring the safety after the inspection and removal of the ceiling. INVESTIGATION REPORT Overview of damage Details of the building and its damage, the building s site plan, and acceleration observed 12 km away from the airport are shown respectively in Tables 1 and 2 and Figures 1 and 2. The seismic intensity of 6-Lower on the JMA scale was observed near the location. This report focuses on failure of ceilings in large well space (area: 25.8 11.2 m, ceiling height: 8.3 m) served as an entrance hall and a lobby. At the well space, ceilings were separated into five rows among which lightings are located. The northernmost row (11.2 m 3.0 m) fell in whole during the main shock. (Figures 3 to 6) 1 Predoctoral fellow, Institute of Industrial Science, The University of Tokyo 2 Graduate student, Department of Architecture, The University of Tokyo 3 Professor, Institute of Industrial Science, The University of Tokyo -55-

Table 1. Details of building Structure Scale Open Steel 2 stories (partially 3 stories) Long side 120 m (north to south), Short side 42 m Total floor area 7,800 m 2 March 11, 2010 (1st anniversary) Table 2. Details of damage to ceilings Space Lobby at the 1st fl. Gallery at the 2nd fl. Shop at the 2nd fl. Details of damage Failure of ceilings (Figure 5, row) Failure of ceilings at stepped part (Figure 5, row~) Deformation of ceilings like hanging (Figure 5, row) Failure of indirect lightings and ceilings over 11 m long Hanging of duct vents Table 3. Details of fallen ceiling Ceiling furrings Light gage steel furring (details in text) Ceiling panels Plaster board (underlayer) of 9.5 mm thick + Decorated acoustic rock wool board of 15 mm thick Ceiling height / Suspension length 8.3 m / 1.6 m max 287gal max 302gal max 230gal Figure 1. Site plan of airport Figure 2. Observed acceleration N Figure 3. Internal view of lobby Figure 4. Failure of ceiling -56-

Figure 5. Reflected ceiling plan of lobby Figure 6. Section of lobby Details of fallen ceilingreference to Table 3 As illustrated in Figures 7 and 9, a gap was observed between arrangement of ceiling and one of inserts on roof side and the ceiling was put to one side against arrangement of hanger bolts along the direction of ceiling width (there was no hanger bolt around the bottom of ceiling plan in Figure 7). Therefore, there was no hanger bolt to hang panels and furrings on the southern part of the ceiling and they cantilevered. Channels and hanger braces seemed to be reinforcement for that was set only at the southern part of the ceiling (right side in Figure 9). These hanger braces was set at each ceiling runners but they had little effect to reduce horizontal motion of the ceiling because of absence of hangar bolt at the end. Braces, which composed triangles with hanger braces, was set only at three points. The arrangement of hanger bolts along the longitudinal direction was uniform, except in west end with air conditioning ducts, but three pairs of braces was set to southern side (braces seen in Figure 8 was set only at most southern row of hanger bolts in Figure 7). Upper ends of braces was fastened to hanger bolts around their roots with metal fittings, on the other hand, lower ends was fastened to furrings and hanger bolts mainly by spot welding (it seemed). Longitudinal end of the ceiling butted against stepped parts of surrounding ceiling without clearance. Finishing panels at the parts also fell off by collision. Figure 7. Reflected plan of fallen ceiling Figure 8. Longitudinal section of ceiling (b-b) Figure 9. Lateral section of ceiling (a-a) Discussion on cause of the failure Almost all furring channel (Figure 7) and many deformed clips fell (Figure 10), therefore, it is suggested that direct cause of the failure was coming off of clips. First, there was strong possibility -57-

that eccentricity caused by the arrangement of braces mentioned above caused larger deformation on northern side of the ceiling than on the other parts. Actually large deformation was found only at northern edge cover, which was set at both of southern and northern longitudinal edges, at contact point with stepped ceiling (Figure 11). All ceiling runners were fastened to the edge covers in southern and northern edges with fitting members like pin. Therefore, it seems that assembly of the edge covers and the ceiling runners as a whole could move like parallel crank and the degree of freedom of the motion was constrained by ceiling panels through clips and screws. For that reason it is suggested that large force caused by the eccentricity acted on the clips. On the day, a TV interview for NHK (Japan Broadcasting Corporation) about the airport s first anniversary was assigned. The camera crew happened to video during the failure of ceiling on TV camera, and the video was broadcasted as news. It is confirmed that the failure began at northeastern corner of the ceiling in the video and it corresponded with the phenomena as discussed above (Figure 12). Figure 10. Fallen clips Figure 11. Deformation at northeastern corner Figure 12. Ceiling just before failure (from NHK TV news) Estimation of impact of failure The accident occurred at highly public and important building such as airport terminal. Furthermore, although similar accidents had been reported, in Kushiro airport for example, the experiences had not been used effectively. Therefore, there are many points to be inspected seriously. These points considered, in this report we estimate influence on human bodies that impact of the failure of the ceiling might have for understanding of the risk of the accident. Method of estimation We estimate falling velocity of the ceiling from TV news video mentioned above and comparing it to test result of falling velocity just before impact of similar material in Ref. 3 we estimate impact and degree of injury in case that a man stands just under ceiling and is hit directly by it. Estimation of falling velocity from video First, for preparation to make the estimation we discuss precision of falling velocity estimated from video by reference to results of former tests. In Refs. 1~3, ceilings of various materials were dropped onto dummy head in free fall from a height of 1~20m in the range and the impacts were measured in its moment. In the test that underlayered ceiling with furring channels was dropped from a height of 8 m we compare velocity measured by speed gun with one estimated from video. -58-

Table 4. Velocity measured by speed gun in test 35cm 20cm Height from GL [m] Falling velocity [m/s] 1.34 9.16 1.26 9.24 1.16 9.10 1.07 9.30 0.98 9.10 Figure 13. Video of test (dt=0.034sec) Falling velocity estimated from video We attempt to estimate falling velocity from video of the test. It is estimated about 10m/s in Figure 13. 0.35 / 0.034 10 [m/s] Falling velocity measured by speed gun The estimation above is made at 0.95 m~1.35 m height from GL. Velocity measured by speed gun at the height is about 9 m/s (Table 4). Therefore, in the case of fall from the height of 8m it is suggested that the falling velocity can be estimated with error of about a tenth. Differences between the accident and the test Conditions are different between the actual accident and the test in Ref. 3. The most different condition is the size of ceiling at its fall. In the accident suspended ceiling the size of 11.2 m 3.0 m fell almost together (total weight of the ceiling with furring channels was about 4.0 kn). On the other hand, in the test boards about the size of one sheet on the market (mainly 910 mm square) were dropped with their bodies horizontally. However, based on observation of modes of the ceiling s failure in the test, in the case that fragile materials such as rock wool board and plaster board impact onto human head with their planes horizontal and with a certain velocity it is found that failure caused at impact point is very local and like punching. Therefore, it can be suggested that in the case that ceilings impact onto human head with their planes horizontal the failure phenomenon concerned with the impact occurs within small area (about a sheet of board). For that reason it is supposed that in the case that falling velocity just before impact is equal to one in the test the size of ceiling has little influence and impact nearly equal to one in the test is caused. The inclination of the ceiling during fall in the news video seemed different locally inside the ceiling the size of 11.2 3.0 m. However, the part of the ceiling that fell to the floor first, focused in the following, seemed falling with its plane roughly horizontal at the height of 170 cm above the floor. From specimens of various materials tested in Refs. 1~3, the underlayered one (8 mm thick calcium silicate board and 12 mm thick acoustic rock wool board) with furring channels is most similar to the fallen ceiling in the accident (Tables 5 and 6). The ceiling dropped in the test is 910 mm 910 mm in size and weights 105 N. Its data is used in the following. Table 5. Materials of fallen ceiling in the airport Material name Unit weight Size (mm) Weight (N) Plaster board 60 [N/m 2 ] 11200 3000 9.5 Acoustic rock wool board 51 [N/m 2 ] 11200 3000 15 Single-sized furring channel 3.3 [N/m] 49400 4027 Double-sized furring channel 4.2 [N/m] 32000-59-

Table 6. Materials of ceiling in the dropping test Specimen Material Size (mm) Weight (N) Calcium silicate board 910 910 8 Underlayered ceiling Rock wool board 300 600 12 with furring channels Single-sized furring channel 17 25 0.8 105 Double-sized furring channel 17 50 0.8 Discussion of velocity just before impact It is assumed that a man of 170 cm tall stands just under the ceiling in the accident. Estimated from the TV video, falling velocity of the ceiling at the height of 170 cm above the floor is approximately 8.5 m/s. Since the ceiling height is 8.3 m, the velocity may be equal to one in condition that falling height is 6.6 m. Here the estimated velocity is verified with relation between falling height and velocity tested in Ref. 3 (Figure 17). The falling velocity of underlayered ceiling with furring channels to falling height of 6.6 m is 8.7 m/s. It agrees approximately with 8.5 m/s estimated above. Therefore, in this case it is assumed that the velocity just before impact of the ceiling falling in a body and one of ceiling the size of 910 mm 910 mm in the test are approximately equivalent for same falling height. 25cm Figure 14. Video of falling ceiling (NHK) Figure 15. Video at 0.029 s after Figure 14 (NHK) 14 velocity(m/s) 12 10 8 6 Falling velocity to falling height of 6.6m 4 2 height(m) 0 0 2 4 6 8 10 12 14 16 18 20 Figure 16. The first landed part of ceiling Figure 17. Velocity of the underlayered ceiling -60-

Comparison of impacts to human head For the reasons mentioned above, it is assumed that impact of the actual fallen ceiling is approximately equal to one of underlayered ceiling with furring channels in the test (similar material is substituted because of absence of completely same one). The figure of relation between falling height and impact on dummy head by the reference is shown below. 7,000 F(N) 6,000 5,000 4,000 3,000 2,000 Impact on man 170cm tall Performance of helmet 4900N Cervical vertebrae of the aged 20~39 4090N Cervical vertebrae of the aged 40~59 3130N Skull fracture 2450N 1,000 height(m) 0 0 2 4 6 8 10 12 14 16 18 20 Figure 18. Impact of the underlayered ceiling According to this, the impact on human head is estimated at 5100 N. In the figure thick solid line indicates the limit of skull (temporoparietal bones) fracture by Nahum. Thick broken lines indicate the limits of cervical fracture for men aged 20~39 and 40~59. Thin broken line indicates the limit used in performance regulation of helmets. It is confirmed that the impact estimated from the test data exceeds the limit of skull fracture. As mentioned above, if a man had stood just under the falling ceiling there might have been possibility that the impact led to critical injury such as brain contusion and injury of cervical vertebrae. CONCLUSIONS Airports are used by large numbers of people usually and should function as important base in disasters. For these buildings the situation that they lose safety and function by failure of ceilings should be avoided the most. It is well known that damage by earthquake at Kushiro airport terminal in September 2003 has been a good lesson as a precedent. In the accident as reported here luckily nobody was injured, but the seriousness of danger of ceilings with high ceiling height such as the lobby is proved in the estimation of impact in this report. Care to safety is required at architectural planning and design including select of the ceiling material. ACKNOWLEDGMENT We are grateful to kind cooperation of people in charge of the airport. This research is supported by grant from the Ministry of Land, Infrastructure, Transport and Tourism. Furthermore, we are grateful to the National Research Institute for Earth Science and Disaster Prevention for publishing strong-motion data. REFERENCES [1] Uchida, T., Kawaguchi, K. and Katayama, S. (2009) Fundamental research on the safety of non-structural components, using human tolerance index, in large enclosures criteria: Part1: Human tolerance indexes. Summaries of technical papers of annual meeting Architectural Institute of Japan, A-1, 1081-1082. -61-

[2] Katayama, S., Kawaguchi, K. and Uchida, T. (2009) Fundamental research on the safety of non-structural components in large enclosures using human tolerance index: Part2: Results of the experiments. Summaries of technical papers of annual meeting Architectural Institute of Japan, A-1, 1083-1084. [3] Uchida, T., Kawaguchi, K., Ogi, Y. and Ohya, S. (2010) Fundamental research on the safety of non-structural components in large enclosures using human tolerance index: Part3: Results of the experiments 2. Summaries of technical papers of annual meeting Architectural Institute of Japan, B-1, 881-882. -62-