Actionpac LNS3 Intelligent Damper Control and Monitoring System

Similar documents
Actionpac 60/120 (LNS Standard)

V3 Intelligent Damper Control and Monitoring System

October 2013 Bespoke Intelligent Damper Control and Monitoring System

Safegard V4 Bespoke Intelligent Damper Control and Monitoring System

Catalogue. ActionpacEMSStandard. Electro Mechanical Control & Monitoring System.

Fire and Smoke Control Systems

Actionair. Hot/Shield PTC. BROCHURE UPDATED* High Operating Temperature Smoke Management and Fire Dampers

Installation Datasheet

Advanced Air. Hard Wired Damper Control Panels. Systems 10, 11, & 12. Hard-Wired Systems. Bespoke Systems Available. Value Engineered Solutions

DCS-100. intelligent damper control & monitoring system

Lonworks Damper Interface Catalogue

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

Smoke Vent Control Panel PCB4 V4 Installation Manual

TransShield ACS Fully Automated Intumescent Fire and Sliding Plate Smoke Damper

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

Reliably Advanced Extinguishing Control

Advanced FireAlarm Panel 1-4Loop

TransShield ACS Fully Automated Intumescent Fire and Sliding Plate Smoke Damper

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range

An introduction to... Sigma

incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications

Reliably Advanced Extinguishing Control

ID3000 intelligent. fire alarm panel

ID2000. intelligent fire alarm panel

UNIJET CAR PARK VENTILATION SYSTEM

SHEVTEC Extended Travel Distance. System for Chettles Yard, Nottingham

Different types of Fire Alarm System

ID3000 intelligent. fire alarm panel

Flostop TS D7E and A8E. Operation Manual

5, SE GÅNGHESTER,

ID50series. intelligent fire alarm panels

FIRElux Emergency Lighting

SUPREMATouch. Modular Fire & Gas Detection System

The EN54 Part 2, 4 and 13 Fire System

Networked Access Control Panel. Installation Guide

Wireless Fire & Security Solutions. Fire Product Showcase

NEW. Innovative heating controls. Commercial boiler control systems. Control 8000 & MX25

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

Fire Damper Interface (24V)

X-Stream Air Natural Ventilation kits are predominantly designed for self-installation. Suitable for ventilating existing and new build applications.

EMERGENCY ASSISTANCE ALARMS

Typical Operating & Maintenance Manual for SOLA-BOOST X-Air Project Name

Control Panels and Fire Detection Equipment

Fire detection and alarm

SUPREMATouch. Modular Fire & Gas Detection System

SUNWARM AIR SOLAR PRE-HEAT VENTILATION SYSTEM

KSUF CONTROL AND MONITORING UNIT. Description. Installation Designed for wall installation.

Fire Damper Interface (230V)

technical specification smoke venting systems

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

All by design. ASSA ABLOY Door Controls

C-Bus Four Channel Analogue Output Unit Installation Instructions

FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

BMS Commissionability Review. October Four Seasons Hotel Park Lane PROJECT:

Installation and user manual for the BiWire / Conventional Repeater Panel

Bionics Instrument. Alarm Handling. Gas Alarm Systems

DESIGN PHILOSOPHY FOR FIRE ALARM & DETECTION SYSTEM

Flopurge TS. Operation Manual

Advanced Air. Fire & Smoke Damper Control Panels. Systems 10, 11 & 42. Fully Addressable or Hard-Wired Systems. Bespoke Systems Available

APPLICATION DATA SHEET

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DISABLED TOILET / EMERGENCY ASSISTANCE ALARMS

Fact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems

30 top tips to tackle HVAC challenges No.21 - Fireman s override

Touchpoint Plus. A whole new control experience

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

ORION Mini-Rep INSTALLATION MANUAL

Building Services Brochure

Top tip No. 21 Fireman s override

5000 Series Rack Panels

The EN54 Part 2 & 4 Fire System

Smoke Damper Interface (230V)

HART XL High Sensitivity Smoke Detection

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

Scanlight Next generation dimmable addressable lighting control

MINERVA MX. 800 Series Ancillary Equipment

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32

Innovative protection that combines power and flexibility

Installation and Operating Instructions

Uniclass L7535: N3253 EPIC L13:Y42. CI/SfB (57) X (K5) Residential Smoke Ventilation

The EN54 Part 2 and 4 Fire System

5000 INSTALLATION GUIDE

LC2200 Level Controller Installation and Maintenance Instructions

Loadstar AC/DC Systems

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

Esmi Sense FDP Fire detection panel with ALC2 loop controller

Intelligent 2 & 4 Loop Fire Alarm Control Panels

Specification Data. General:

FIREMASTER ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES LEADING THE WAY IN FIRE PROTECTION

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

Smoke Control in Apartment Buildings. Smoke Control

intelligent fire alarm ID60series panels

Wireless Fire & Security Solutions. Fire Product Showcase

MINERVA MZX125 Digital Addressable Fire Detection System

LC3000 Level Controller Installation and Maintenance Instructions

DIVA8MG2. Compact PAVA System Master Unit. DIVA8 System

PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM

Transcription:

November 2005 Actionpac LNS 3 NEW AND ENHANCED Intelligent Damper Control and Monitoring System Range and Features Panel PC Driven system. User friendly, no need for operating and maintenance manual. Full diagnostic for system and device integration from Panel PC. Flexible system architecture, enables sophisticated as well as simple fire engineering configurations. Network unidirectional 2 core cable, utilising daisy chain method of wiring to all devices reducing wiring costs. Centralised or localised wiring to input and output devices, reducing wiring costs. Graphic User Interface operates on a windows platform making it universally accepted. Localised supplies to all devices. Will control and monitor many variants of Actionair motorised Dampers.

Smoke the silent killer Introduction Consultants in the field of fire engineering have long recognised the damage and danger to human life that can be caused by smoke spreading through buildings, even when the fire is confined to a small area. Smoke/fire protection can save human lives as well as keeping damage to property and contents to an absolute minimum. Control measures for smoke/fire protection in old and new buildings comprise a wide variety of systems and items of equipment, that must be carefully integrated in order to ensure maximum safety. One of the most important tasks is performed by the automatic smoke and fire dampers that are incorporated into HVAC systems. In an emergency they must close immediately to contain the smoke and fire and prevent their spread through the ducting, or open immediately to allow smoke extraction to take place. The system represents a new generation of smoke/fire damper control. The system has been designed with the user in mind, providing an advanced tool that simplifies installation and commissioning of smoke/fire dampers and peripheral devices. The Panel PC operates on a Windows platform making it universally accepted and utilises solid state technology for optimum reliability. It s server architecture delivers new benefits such as reduced commissioning time, simplified operation and scope for future growth. The Intelligent Smoke and Fire Damper typical Control System application. The system is designed to protect life and property from damage caused by smoke and fire, by providing the means to: Compartmentalise fire zones. Reduce the spread of smoke and fire. Keep escape routes and fire-fighting access open. Allow pressurisation and smoke extract by combined operation of dampers and fans. S Denotes Automatic Smoke and Fire Damper in smoke containing Mode on the first floor whilst offering pressurisation to immediate floors (above and below) and stairwell. + + + + Actionpac Ground Level Entrance + + + 2

Specification Control Panel The System consists of a Panel PC,UPS and preloaded software. The system communicates with the damper interfaces to provide intelligent control and monitoring of motorised dampers. The data network cabling enables substantial reduction in costs when compared with conventional systems. Digital inputs and outputs (DX-8) can be accommodated on the network cable or located within the panel enclosure. The Panel PC is supplied with software and operates on a Windows platform, making it extremely user friendly. The server architecture delivers new benefits, such as reduced commissioning time, ease of configuration, simplified operation and system growth. Full diagnostics for system and device integration from the Panel PC, along with automatic scheduled damper testing facility to meet new European damper test standards. Digital Input / Output Device DX-8 This device accepts eight volt free contact inputs into the system. Typical inputs would be from fire alarm panels, fireman s override switches,manual call points and smoke detectors. This device also provides eight relay outputs to be driven from the system. Typical outputs would be to fans and BMS systems. Large strategy (cause and effect) lists can be driven from these input / output devices and they can be placed anywhere on the network to reduce cabling costs, or located within the Panel PC enclosure. Mimic Panels Bespoke LED mimic panels are available to clients specification. Firefighter s Override Panels (FOP) Bespoke key switch or push button firefighter's override panels are available to clients specification. Damper Interfaces All the damper interfaces accept local auxiliary inputs (normally smoke detectors) which can drive cause and effect schedules. Smoke Fire Damper Interface () This device,which is a registered LonMark FSDAC product, can be used with the system or in smaller distributed systems as it is supplied complete with software. The controls and monitors motorised smoke/fire dampers. The device ensures correct operation and status of the damper and provides an alarm at the PC Panel in the event of local power supply failure. Smoke Damper Interface (SDI) This device controls and monitors motorised smoke dampers. Fire Damper Interface (FDI) Monitors damper position and provides facility for energising an electromagnet. Damper failsafes closed via spring mechanism and must be manually reset. 3

Wiring Detail Control Mode Smoke Fire Damper interface CONTROL MODE DRIVE L N 90 0 1 2 S1 S2 S3 ISOLATE S4 S5 ISOLATE S6 IN OUT TF 72 C L N POWER IN NETWORK Control Options System will control and monitor any motorised damper and offer monitoring of any manual reset. Cable Specifications ELECTRICAL THERMAL RELEASE Typical operation Power On Damper resets Power Off Spring release External mechanical position indicator with pointer. Release Time 20 secs. Reset Time 60 secs. 24V A.C.or D.C. Connect 24V via a safety isolating transformer. 220 240V A.C.50 / 60Hz To isolate from main power supply, the system must incorporate a device which disconnects the phase at least 3mm contact gap. Cable Type Max device to device Max total cable Conductor size Belden 8471NH 400m 500m 1.3mm 2 Pirelli FP200 Gold 400m 500m 1.5mm 2 Pirelli FP PLUS 400m 500m 1.5mm 2 Firetuf 400m 500m 1.5mm 2 Firetuf Plus 400m 500m 1.5mm 2 These cable specifications are fundamental to the stable and reliable operation of your smoke/fire control and monitoring system. Failure to adhere to these specifications will result in unstable and unreliable network communications and will void all warranties. SMOKE FIRE DAMPER INTERFACE (SHOULD BE POSITIONED < 1 METRE FROM THE DAMPER CONTROL MODE TO ALLOW FOR DIRECT CONNECTION OF THE FLYING LEADS, 3 + 5 METERS FLYING LEADS AVAILABLE ON REQUEST Power Consumption 24V A.C. or D.C. 220V - 240V A.C. Maximum power consumption for combined plus 24V or 230V actuator is <13W. 1. Maximum number of devices per cable segment is 64. If >64 and / or >500m cable segment, use a network extender kit. 2. If wired as a loop,the network is polarity sensitive. In all other instances, the network is polarity insensitive. 3. Each cable segment must be wired in a daisy chain i.e. in and out and no stubs will be allowed. 4. Belden 8471NH is not fire rated. 4

Typical Network Schematic General Schematic of Actionpac LNS Damper Control System Panel PC Data Network B.M.S. Vent Panel Smoke Fire Damper Interface One per Control Mode Damper Control Mode* OUTPUTS DX - 8 INPUTS Device located in Panel on Network DX - 8 Digital Input / Output Device Interface to Fire System BMS Inputs *If more than one Damper to be controlled by an, SDI or FDI please refer to Actionair Sales Office. Supply to each Damper Interface from nearest local distribution board. To additional devices as required Fire Alarm Inputs Fireman s Switch Inputs Benefits Completely flexible to meet practically any building s damper requirements 3 levels of alarm priority Panel PC driven system with real-time graphic displays Panel PC utilises solid state technology for optimum reliability Operates on windows TM platform user friendly Full configuration and diagnostics from Panel PC Allows for exact location of devices in text Multiple wiring configurations to include Radial or Loop Topology Damper operational count provided Flexibility to accommodate any last minute changes to strateg, zones, damper additions, damper locations etc. Guaranteed input response times of <10 seconds on a 512 damper system to meet the new draft BS EN 12101-9. Automatic scheduled Damper testing 5

Panel Specification Enclosure Specifications Standard enclosure sizes and weights are dependent on number of panel routers and DX8's required. Max load (Watts) Enclosure Size (mm) 500 600 x 600 x 300 500 800 x 800 x 300 500 1000 x 800 x 300 500 1200 x 800 x 300 Colour RAL 7032 Hinged Left Power cables Bottom entry right hand side Network cables Top entry I/O cables Top entry Customer Service Actionair provides quality products backed by a dedicated team committed to providing the very best in customer service. Offering experienced technical backup, comprehensive sales and administrative customer support, product commissioning and maintenance service. Protection Max ambient temperature Minimum clearance for vents IP 20 (230 Volt terminals shrouded) 30 C (Panel must be in a ventilated environment) 150mm System Commissioning Actionair offers a comprehensive after sales service to include precommissioning checks and a complete commissioning service for all our products. 6

Control Mode 5 PTC and Control Mode 6 PTC Control Mode 5 PTC and Control Mode 6 PTC 60 seconds MAX Reset/ 20 seconds Release operation. These new series of control modes achieve 60 seconds to drive to the end position, with a 20 second spring return time. This brings Actionair dampers in line with imminent European standardisation for fire and smoke control. As with all PTC modes, this series uses the snaplock interface. Fire rated dampers are primarily designed to be fitted into a wall or floor, and the interface displaces the mode from the line of the wall. Dampers may be installed and finally the mode removed from storage for easy fitting, thus preventing damage to the mode before it is required. End switches and LSF cable are provided as standard on all modes. Versions are available to allow fail-safe close for fire safety (Smoke/Shield) or fail-safe open for smoke extract (Vent/Shield) and may be combined with protective enclosures (Hot/Shield) to provide enhanced operation for 1 hour at 300 C or 2 hours at 300 C. The Electro Thermal Release (ETR) supplied for fire damper use has integral fail-safe devices to ensure that it is installed into the ductwork correctly. ETR units are not supplied with Hot/Shield, because these are designed to operate at temperatures in excess of 72 C, should a fire cause any temperature rise. End switches are provided with each mode, so that damper Reset and Release positions may be monitored. The mode is permanently attached to the mechanism driving the damper blades. ETR Indication light As standard, a green LED lamp is built into the ETR housing. This gives the user a simple and clear visual check that the Actuator is receiving power, the ETR is correctly fitted, and the thermal fuse is intact. Smoke/Shield and Vent/Shield M5 PTC 24V 7W (10VA), end switches SPDT 250V 6(3)A XNNN00015 Smoke/Shield Thermal Release / Power Off Fail-safe Close* M6 PTC 230V 8W (12.5VA), end switches SPDT 250V 6(3)A XNNN00016 Smoke/Shield Thermal Release / Power Off Fail-safe Close* M5 PTC Vent 24V 7W (10VA), end switches SPDT 250V 6(3)A XNNN00019 Vent/Shield Thermal Release / Power Off Fail-safe Open* M6 PTC Vent 230V 8W (12.5VA), end switches SPDT 250V 6(3)A XNNN00020 Vent/Shield Thermal Release / Power Off Fail-safe Open* M5 PTC NON ETR 24V 7W (10VA), end switches SPDT 250V 6(3)A XNNN00017 Smoke/Shield Power Off Fail-safe Close M6 PTC NON ETR 230V 8W (12.5VA), end switches SPDT 250V 6(3)A XNNN00018 Smoke/Shield Power Off Fail-safe Close M5 PTC Vent NON ETR 24V 7W (10VA), end switches SPDT 250V 6(3)A XNNN00021 Vent/Shield Power Off Fail-safe Open M6 PTC Vent NON ETR 230V 8W (12.5VA), end switches SPDT 250V 6(3)A XNNN00022 Vent/Shield Power Off Fail-safe Open *Smoke/Shield and Vent/Shield Control Modes M5 PTC and M6 PTC are supplied as standard with the Electrical Thermal Release (ETR). The units Fail-safe by means of the unique and patented ETR device which operates at 72 C, or if the power supply is off/interrupted. Complying with BS 5588 Part 9 1999. Non ETR versions Fail-safe when the power is off/interrupted. Hot/Shield and Hot/Vent/Shield HM5 PTC 24V 7W (10VA), end switches SPDT 250V 6(3)A XNNN00281 Hot/Shield Power Off Fail-safe Close HM6 PTC 230V 8W (12.5VA), end switches SPDT 250V 6(3)A XNNN00282 Hot/Shield Power Off Fail-safe Close HM5 PTC Vent 24V 7W (10VA), end switches SPDT 250V 6(3)A XNNN00283 Hot/Vent/Shield Power Off Fail-safe Open HM6 PTC Vent 230V 8W (12.5VA), end switches SPDT 250V 6(3)A XNNN00284 Hot/Vent/Shield Power Off Fail-safe Open HM5-2H PTC 24V 7W (10VA), end switches SPDT 250V 6(3)A XNNN00285 Hot/Shield Power Off Fail-safe Close HM6-2H PTC 230V 8W (12.5VA), end switches SPDT 250V 6(3)A XNNN00286 Hot/Shield Power Off Fail-safe Close HM5-2H PTC Vent 24V 7W (10VA), end switches SPDT 250V 6(3)A XNNN00287 Hot/Vent/Shield Power Off Fail-safe Open HM6-2H PTC Vent 230V 8W (12.5VA), end switches SPDT 250V 6(3)A XNNN00288 Hot/Vent/Shield Power Off Fail-safe Open Hot/Shield and Hot/Vent/Shield Control Modes HM5 PTC and HM6 PTC (operational for 1 hour @ 300 C) and HM5 2H PTC and HM6 2H PTC (operational for 2 hours @ 300 C) are not supplied with the Electrical Thermal Release (ETR). They Fail-safe when the power is off/interrupted). 7

Actionpac Electro Mechanical Smoke and Fire Damper Hard Wired Control Panels EMS Standard EMB Bespoke Actionpac Electro Mechanical Smoke and Fire Damper Control System. Automatic damper operation utilising Relay Logic and LED indication of damper status. Damper Panels: Customised Central Control Panel. Remote Repeater Panel. Fire Damper Monitor Panel. Specialist Panels available: Fan Control Panel. Fireman s Control Panel. Mimic Panel. Example Actionpac EMB Panel Please Note: is recommended when greater numbers of Smoke/Shield Dampers are to be controlled / monitored. Sometimes, depending on project requirements, it may also be advantageous to utilise on smaller numbers of Smoke/Fire Dampers. Please refer to Actionair Sales Office. Example Actionpac EMS Panel Actionair, South Street, Whitstable, Kent CT5 3DU England Tel: (01227) 276100 Fax: (01227) 264262 International Code: +441227 Email: sales@actionair.co.uk Website: Part of Ruskin Air Management Limited no compromise... Quality System Certificate No 017 Assessed to ISO 9001:2000 PRODUCED BY: www.graphicpartnership.com