Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

Similar documents
Deluge & Preac tion Systems

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA. 319a. January 27, 2012

Model DDX Deluge Valve

TECHNICAL DATA OBSOLETE

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

TotalPac X Single interlock SUREFIRE system

TotalPac X Firecycle III Preaction Double interlock system

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

TOTALPAC2 Integrated Fire Protection System

Public Comment No. 2-NFPA [ Section No ]

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

BERMAD Fire Protection

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE

TotalPac 3 Firecyle III Deluge Remote controlled system

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

Instructions for Installation, Operation, Care and Maintenance

MODULE 2. Water-Based Suppression System Basics

Fire Protection Products Technical Data Book Table of Contents, August 2017

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

TECHNICAL DATA OBSOLETE

Deluge System. Pneumatic Release. Deluge System. Pneumatic Release

TECHNICAL DATA. model c-2

Corrosion in Fire Sprinkler Systems Increasing Your Liability, Increasing Your Costs, and Shortening System Life

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

MSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

Impact of Supervisory Gas Pressure on Dry Pipe Sprinkler System Water Delivery Time. Steve Wolin Director, Development and Compliance

Model: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance

Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description

Deluge/Preaction Systems Annotated Instructor s Guide

Deluge/Preaction Systems Annotated Instructor s Guide

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA TRIM DESCRIPTION DESCRIPTION VALVE OPERATION. 82 ASTM A 216 WBC.

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems

N2 BLAST Datasheet Preaction double interlock, Electric/Pneumatic c/w N 2 Blast Nitrogen generating system Self contained unit

Worldwide Contacts.

Box-in-Box Cold Storage Fire Protection Options

as required for residential sprinklers intended for use in dry pipe systems.

CONSTRUCTION REQUIREMENTS

Second Revision No. 11-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement

Tyco Fire Valves Pure Performance

FIRELOCK NXT AUTOMATIC VALVE SYSTEMS NOT JUST VALVES SIMPLICITY.

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole.

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT

Sprinkler System Installer Level 2

N2 BLAST Datasheet SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Self contained unit

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

Installation and Maintenance Requirements

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

N2 BLAST Datasheet Preaction double interlock, Electric/Pneulectric c/w N 2 Blast Nitrogen generating system Self contained unit

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

RESOLUTION MSC.44(65) (adopted on 11 May 1995) STANDARDS FOR FIXED SPRINKLER SYSTEMS FOR HIGH SPEED CRAFT

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Self-contained system

quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Application of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings

TotalPac 3 Single interlock Firecyle III Preaction Self-contained system

OPEN SPRINKLER SYSTEM

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

MSC Guidelines for Automatic Sprinkler Systems

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TN-25 Tunnel Fire Protection System. Safer. Smarter. Tyco.

Worldwide Contacts.

FireFlex DUAL Double Interlock, Self-contained system

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

TECHNICAL DATA. Viking Technical Data may be found on. The Viking Corporation s Web site at.

standard response elo upright sprinkler

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

DRY VERTICAL SIDEWALL SPRINKLERS TECHNICAL DATA

TECHNICAL DATA. 2. LISTINGS AND APPROVALS NOTE: Viking Dry Vertical Sidewall Sprinklers are NOT listed or approved. Sprinkler 103a.

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

Model AV Alarm Valve With and Without Model RC-1 Retard Chamber European Conformity Valve Trim General Description

Contren Learning Series Apprenticeship Training Program for Fire Sprinkler Fitters

CHAPTER THREE SPRINKLER SYSTEM AND FM-200 AGENT SYSTEM

micromatic standard sprinkler VK004 (K4.2) 3. technical data Page 1 of 6

FM-200 In-Cabinet Series

TotalPac 3 Wet pipe system c/w retard chamber

Sprinkler Solutions for Storage Applications

ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-10/(PGEN-10E)

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

Transcription:

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems STEVEN WOLIN, VICE PRESIDENT, PRODUCT TECHNOLOGY & COMPLIANCE ANTONIO LUIS, TECHNICAL SERVICES MANAGER RELIABLE AUTOMATIC SPRINKLER CO., INC.

Outline 1. Sprinkler System Types 2. Dry-pipe Valve Types 3. Deluge/Preaction Valve Types 4. Actuators 5. Corrosion 6. Air supplies 7. Accelerators

Sprinkler System Types Wet-pipe Dry-pipe Preaction Non-interlock Single-interlock Double-interlock Deluge

Sprinkler System Types Wet-pipe Dry-pipe Preaction Non-interlock Single-interlock Double-interlock Deluge NFPA 13: A sprinkler system employing automatic sprinklers attached to a piping system containing water and connected to a water supply so that water discharges immediately from sprinklers opened by heat from a fire.

Sprinkler System Types Wet-pipe Dry-pipe Preaction Non-interlock Single-interlock Double-interlock Deluge NFPA 13: A sprinkler system employing automatic sprinklers that are attached to a piping system containing air or nitrogen under pressure, the release of which (as from the opening of a sprinkler) permits the water pressure to open a valve known as a dry pipe valve, and the water then flows into the piping system and out the opened sprinklers.

Dry-pipe Sprinkler System Water Delivery Time Options 1. 60 second water delivery time to test connection 2. 500 gallon system exemption 3. 750 gallon system with quick-opening device exemption 4. Listed water delivery calculation 5. Water delivery test manifold 6. Other water delivery time listed by a nationally recognized testing laboratory Dry-pipe systems serving dwelling units must meet 15 second requirement.

Factors Influencing Water Delivery Time System volume System configuration Supervisory pressure Trip pressure Quick-opening device (accelerator) Water supply Sprinkler/test valve size

Dry-pipe Sprinkler System Allowable Sprinkler Types Upright sprinklers Horizontal sidewall sprinklers installed so water is not trapped Listed dry sprinklers In areas above 40 F only: Pendent or sidewall sprinklers on return bends On systems using potable water only, pendent or sidewall sprinklers on copper or CPVC specifically listed for dry pipe applications

Dry-pipe Sprinkler System Hydraulic Design 30% increase in area of sprinkler operation without changing density Gridded systems not permitted Reduced Hazen-Williams C Value for black steel pipe* 100 dry-pipe/preaction 120 for wet-pipe and deluge *Reduced Hazen-Williams C Value for dry-pipe and preaction systems also applies to galvanized pipe starting in 2013 edition of NFPA 13.

Sprinkler System Types Wet-pipe Dry-pipe Preaction Non-interlock Single-interlock Double-interlock NFPA 13: A sprinkler system employing automatic sprinklers that are attached to a piping system that contains air that might or might not be under pressure, with a supplemental detection system installed in the same areas as the sprinklers. Deluge

Preaction Sprinkler System Allowable Sprinkler Types Upright sprinklers Horizontal sidewall sprinklers installed so water is not trapped Listed dry sprinklers In areas above 4 C only: Pendent or sidewall sprinklers on return bends On systems using potable water only, pendent or sidewall sprinklers on copper or CPVC specifically listed for dry pipe applications

Sprinkler System Types Wet-pipe Dry-pipe Preaction Non-interlock Single-interlock Double-interlock Deluge NFPA 13: A non-interlock system, which admits water to sprinkler piping upon operation of detection devices or automatic sprinklers

Sprinkler System Types Wet-pipe Dry-pipe Preaction Non-interlock Single-interlock Double-interlock NFPA 13: A single interlock system, which admits water to sprinkler piping upon operation of detection devices Deluge Often used in data centers.

Non-interlock and Single-interlock Preaction Sprinkler Systems Maximum 1,000 sprinklers per preaction valve Supervisory gas required for single-interlock systems with more than 20 sprinklers By definition all non-interlock sprinkler systems have supervisory gas Minimum supervisory gas pressure of 7 psi required

Non-interlock and Single-interlock Preaction Sprinkler System Gridded systems not permitted for storage Miscellaneous storage may be protected with gridded systems Reduced Hazen-Williams C Value for black steel pipe* 100 dry-pipe/preaction 120 for wet-pipe and deluge *Reduced Hazen-Williams C Value for dry-pipe and preaction systems also applies to galvanized pipe starting in 2013 edition of NFPA 13.

Sprinkler System Types Wet-pipe Dry-pipe Preaction Non-interlock Single-interlock Double-interlock Deluge NFPA 13: A double interlock system, which admits water to sprinkler piping upon operation of both detection devices and automatic sprinklers

Double-interlock Preaction Sprinkler System Water Delivery Time 60 second water delivery time to test connection or Listed water delivery calculation or Water delivery test manifold A listed quick-opening device (accelerator) may be used to help meet the water delivery time requirements.

Double-interlock Preaction Sprinkler System - Hydraulic Design 30% increase in area of sprinkler operation without changing density Gridded systems not permitted Reduced Hazen-Williams C Value for black steel pipe* 100 dry-pipe/preaction 120 for wet-pipe and deluge *Reduced Hazen-Williams C Value for dry-pipe and preaction systems also applies to galvanized pipe starting in 2013 edition of NFPA 13.

Sprinkler System Types Wet-pipe Dry-pipe Preaction Non-interlock Single-interlock Double-interlock Deluge NFPA 13: A sprinkler system employing open sprinklers or nozzles that are attached to a piping system that is connected to a water supply through a valve that is opened by the operation of a detection system installed in the same areas as the sprinklers or the nozzles. When this valve opens, water flows into the piping system and discharges from all sprinklers or nozzles attached thereto.

Dry-pipe Valve Types DIFFERENTIAL MECHANICAL

Differential Dry-pipe Valves 100 year old technology

Differential Dry-pipe Valves

Differential Dry-pipe Valve Operation

Differential Dry-pipe Valves ADVANTAGES Simplicity DISADVANTAGES Size and weight Supervisory pressure Water delivery time

Mechanical Dry-pipe Valves Modern dry-pipe valves

Mechanical Dry-pipe Valve Operating Mechanism Ratio controlled by actuator instead of clapper Clapper latched in closed position by a combination of levers or pushrods Clapper size similar to inlet size

Mechanical Dry-pipe Valve Operation

Mechanical Dry-pipe Valve Operation in Real Time

Mechanical Dry-pipe Valves ADVANTAGES Size and weight DISADVANTAGES Complexity Low supervisory gas pressure Water delivery time

Supervisory Gas Pressure Water Supply Pressure (bar) Example Differential DPV Supervisory Pressure (bar) Example Mechanical DPV Supervisory Pressure (bar) Reduction in Supervisory Pressure with Mechanical vs Differential 7 1.7 1.0 40% 12 2.8 1.2 55% 17 3.8 1.5 60% 21 est. 4.5 1.7 est. 62%

Lower Supervisory Gas Pressure Means: Less leakage Smaller compressor Smaller nitrogen generator Faster water delivery

Deluge/Preaction Valve Types MECHANICAL DIAPHRAGM SOLENOID

Mechanical Deluge/Preaction Valves Clapper latched in closed position by a combination of levers or pushrods

Mechanical Operation

Mechanical Deluge/Preaction Valves Low friction loss (depending on design) Held closed by high-strength metal components Mechanically latches open Cannot reset itself Fast operation Available in a wide variety of sizes

Diaphragm Operation

Diaphragm Valve Operation

Diaphragm Deluge/Preaction Valves Capable of remote resetting Capable of pressure regulation Available in a wide variety of sizes

Solenoid Deluge Valve 40mm Solenoid Valve Alarm and Drain Section

Solenoid Deluge Valves Minimal required installation depth Only available in small sizes (40mm) Relatively high friction loss

Actuators

Actuators connect to deluge/preaction valves to maintain pressure in the control chamber until valve operation

Solenoid Valve Normally Closed Power open Used with valves that mechanically latch open Often used in data centers.

Solenoid Valve Latching Impulse Pulse power open Pulse power closed Solenoid valve latches in position until next power impulse changes state Used with on/off type valves

Wet Pilot Line Hydraulically connected (piped) to deluge/preaction valve

Dry Pilot Actuator Supervisory pressure holds actuator closed until pilot line detector/sprinkler opens

Double-interlock Electric/Electric Releasing Control Panel (RCP) monitors detection system and supervisory pressure switch Valve opens upon: RCP energizing solenoid to release system

Double-interlock Electric/Pneumatic RCP monitors detection system Dry pilot actuator monitors system pressure Valve opens upon both: RCP opening solenoid based on detection system operation; and Dry pilot actuator opening from loss of supervisory pressure Often used in refrigerated storage buildings.

Double-interlock Pneumatic/Pneumatic Actuator connected to: System to monitor supervisory pressure in system Dry pilot line to monitor supervisory pressure in dry pilot line Valve and actuator open upon both: Loss of supervisory pressure in system Loss of supervisory pressure in dry pilot line

Corrosion Images South-Tek Systems. Used with permission. 51

Dry and pre-action systems are involved in 59% of fire losses caused by corrosion-related obstructions to sprinkler flow (FM Global) 73% of dry and pre-action systems inspected had significant corrosion issues after 12.5 years (VdS Study) Corrosion leads to property damage, ongoing pipe repair and replacement, decreased c-factor and sprinkler head blockage potentially rendering the system inoperable in the event of a fire Images South-Tek Systems. Used with permission. 52

Corrosion Triangle Images South-Tek Systems. Used with permission. 53

Long Term Corrosion Study Image South-Tek Systems. Used with permission. Air v. 95% Nitrogen v. 98% Nitrogen Black Steel and Galvanized Pipe

Schedule 10 Black Steel (Results after 7.9 years of testing) As Received Cleaned Compressed Air Supervision 20.7 Years Service Life 95% Nitrogen Supervision 25.2 Years Service Life 98% Nitrogen Supervision 63.2 Years Service Life Images South-Tek Systems. Used with permission. 55

Schedule 10 Galvanized Steel (Results after 7.9 years of testing) As Received Cleaned Compressed Air Supervision 9.9 Years Service Life 95% Nitrogen Supervision 12.6 Years Service Life 98% Nitrogen Supervision 176 Years Service Life Images South-Tek Systems. Used with permission. 56

Corrosion Testing Conclusions As a result of 98% nitrogen in lieu of compressed air supervision: Extension of black steel pipe service life from 20 to 63 years Extension of galvanized steel service life from 10 to 176 years 57

Air (or Nitrogen) Supply

Air Supply Sources Compressor Plant air Nitrogen generator Bottles/cylinders

Air Supplies Pressure Maintenance Device A pressure maintenance device and air receiver (tank) are required by NFPA 13 Exception: Compressors supplying less than 160 lpm at 0.7 bar without an air receiver (tank) Compressor Air Receiver (tank) Pressure Maintenance Device

Air Supplies Pressure Maintenance Device Regulates supervisory pressure Check Valve Regulator Limits supervisory gas flow into sprinkler system Allows for quick filling Gauge Port To System Quick Fill Valve Strainer From Air Supply

Air Supply Tips 1. A tank mounted air compressor with a pressure maintenance device is the default in NFPA 13... for good reason 2. Gauges are required by NFPA 13 in each independent segment of air supply pipe 3. Quiet air compressors are becoming more common 4. Follow the additional air supply requirements in NFPA 13 Section 7.9 for refrigerated spaces (limit ice plugs) 5. Engineers and building owners should consider using >98% nitrogen (with a pressure maintenance device) for supervisory gas in dry-pipe and preaction sprinkler systems

If a dry-pipe or preaction sprinkler system in this building fills with water how is it drained?

Air supplies are important to help prevent unintended valve operation. Also, system side control valves help maintenance personnel test the system without introducing water to the refrigerated space.

Quick Opening Devices Accelerators Accelerators are intended to improve the trip time of dry-pipe and preaction valves Open on supervisory pressure decay Rate of pressure change (not differential) Divert supervisory gas into intermediate chamber (differential DPV) Vent actuator (mechanical DPV)

Quick Opening Devices Accelerators MECHANICAL ELECTRONIC Sensor and controller monitor supervisory pressure, open solenoid upon pressure decay Requires power supply and back-up power

Summary

There are three types of preaction sprinkler systems 1.Single-interlock 2.Double-interlock 3.Non-interlock

Significant components of a dry-pipe or preaction sprinkler system Dry-pipe valve or preaction valve with actuator Air/nitrogen supply Sprinklers

Operating mechanisms used for dry-pipe or preaction valves Differential clapper Mechanical clapper Diaphragm Solenoid

Components of the standard air supply required by NFPA 13 1.Compressor 2.Air receiver (tank) 3.Pressure maintenance device

Thanks for your attention!!!!