freedom residential concealed pendent Sprinkler vk458 (K7.4)

Similar documents
FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK457 (K4.9) TECHNICAL DATA

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK468 (K4.9) TECHNICAL DATA

TECHNICAL DATA. The Viking Corporation s Web site at Overall Length (Sprinkler Body): 2-5/16 (59 mm)

TECHNICAL DATA OBSOLETE

freedom residential concealed pendent sprinkler VK488 (K3.0)

freedom residential horizontal sidewall sprinkler Vk450 (k4.2)

freedom residential concealed pendent lead free sprinkler

FREEDOM RESIDENTIAL CONCEALED PENDENT LEAD FREE SPRINKLER VK4570 (K4.9) TECHNICAL DATA

standard response sprinklers (vk102 & vk202) 3. technical data Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Sprinkler 11j

TECHNICAL DATA. * Metric K-factor measurement shown is in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0.

standard response/qr extended coverage concealed pendent sprinklers vk614 & vk616

freedom residential concealed pendent sprinkler vk474 (K5.8)

TECHNICAL DATA OBSOLETE

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK494 (K4.9) TECHNICAL DATA

TECHNICAL DATA OBSOLETE

mirage Quick response concealed pendent sprinkler vk464 (K8.0)

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

TECHNICAL DATA. Viking Technical Data may be found on Minimum Operating Pressure: Refer to the Approval Chart.

mirage Quick response concealed pendent sprinkler vk465 (K4.2)

TECHNICAL DATA. Viking Technical Data may be found on Maximum Working Pressure: 175 psi (12 Bar).

STANDARD/quick. Sprinkler 42o. August 8, 2011

TECHNICAL DATA. Viking Technical Data may be found on UNS-C84400 for Sprinkler VK202.

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK468 (K4.9) TECHNICAL DATA

mirage standard response concealed pendent sprinkler vk492 (K5.6)

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK498 (K5.8) TECHNICAL DATA

TECHNICAL DATA. Page 1 of 5

STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLER VK352-D (K8.0) TECHNICAL DATA

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

Form No. F_ Rev 14.1 Page 1 of 6 TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE CONCEALED HSW SPRINKLER VK630 (K8.0) TECHNICAL DATA

quick response sprinkler vk194 Sprinkler 104j January 1, 2011

standard/quick response sprinklers (vk302 & vk352) 3. technical data Specifications: Available since Sprinkler 41g May 1, 2009

QUICK RESPONSE DRY CONCEALED PENDENT SPRINKLER VK194 TECHNICAL DATA

FREEDOM RESIDENTIAL CONCEALED HORIZONTAL SIDEWALL SPRINKLER VK480 TECHNICAL DATA

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK486 (K4.0) TECHNICAL DATA

freedom residential flush pendent sprinkler vk476 (K4.9)

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK460 (K5.8) TECHNICAL DATA

TECHNICAL DATA. Cover Plate Assembly must be ordered separately:

freedom residential pendent sprinkler vk466 (K5.2)

FREEDOM RESIDENTIAL PENDENT LEAD FREE SPRINKLER VK4700 (K3.0) TECHNICAL DATA

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK470 (K3.0) TECHNICAL DATA

Page 1 of 7. Replaces Form No. F_ Rev 16.3 (Added 16X22 and 18X20 coverage areas)

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK479 (K3.0) TECHNICAL DATA

December 14, 2015 Page 1 of 7 TECHNICAL DATA

TECHNICAL DATA vk470 (K3.0)

sprinkler vk538 (K11.2)

freedom residential horizontal sidewall lead free sprinkler VK4840 (k4.2)

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

Standard Spray concealed horizontal sidewall sprinkler VK481

HORIZON MIRAGE QUICK RESPONSE LARGE ORIFICE CONCEALED PENDENT SPRINKLER VK406 TECHNICAL DATA

Quick response concealed horizontal sidewall sprinkler VK481

Page 1 of 7. Form No. F_ Rev Replaces Form No. F_ Rev 17.1 (added 205deg version)

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

MIRAGE EC/QREC OH-ELO CONCEALED PENDENT SPRINKLER VK538 (K11.2) TECHNICAL DATA

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 TECHNICAL DATA

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

freedom residential Upright sprinkler vk467 (k4.9)

microfast quick response extended coverage hsw sprinkler vk606

standard/quick response extended coverage light and ordinary hazard elo sprinklers

STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK602 TECHNICAL DATA

TECHNICAL DATA OBSOLETE

HORIZON QUICK RESPONSE FLUSH PENDENT SPRINKLERS TECHNICAL DATA

standard response/ quick response extended coverage

microfast sr/qr extended coverage pendent sprinkler

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data

quick response Sprinkler 105a October 25, 2010

standard response dry horizontal sidewall sprinklers

TECHNICAL DATA. Page 1 of 6

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA

quick response extended coverage horizontal sidewall sprinkler vk630 (k8.0)

quick response horizontal sidewall sprinkler vk360 (K8.0)

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

MicrofastHP EC/QREC FUSIBLE ELEMENT HSW HIGH PRESSURE SPRINKLER VK613 (K5.6) TECHNICAL DATA

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD ELO PENDENT SPRINKLER VK608

qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

micromatic standard response stainless steel sprinklers

TECHNICAL DATA. Refer to Approval Chart 1 and FM Design Criteria for FM Approval requirements that must be followed.

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

standard response large orifice dry

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

STANDARD/QUICK RESPONSE EXTENDED COVERAGE DRY HORIZONTAL SIDEWALL SPRINKLER TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE FUSIBLE ELEMENT PENDENT SPRINKLER VK601 (K5.6) TECHNICAL DATA

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

MICROFAST AND MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

standard response elo upright and pendent sprinklers (storage-density/area)

micromatic standard sprinkler VK003 (K2.8) 3. technical data Page 1 of 7

MICROFAST SR/QR EXTENDED COVERAGE HSW SPRINKLER VK605 (K5.6) TECHNICAL DATA

standard response fusible link sidewall sprinkler VK112 (K5.6)

TECHNICAL DATA. The Viking Corporation s Web site at Frame Casting: Brass UNS-C84400

quick response ordinary hazard dry hsw sprinklers (8.0K) (VK275, VK277, & VK279)

Transcription:

Sprinkler 142u 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Sprinkler VK458 is a small highsensitivity glass bulb residential sprinkler for use with a domed cover assembly. The orifice design, with a K-Factor of 7.4 (107 metric*), allows the sprinkler s efficient use of available water supplies for the hydraulically designed fire-protection system. The glass bulb operating element and special deflector characteristics meet the challenges of residential sprinkler standards. Concealed sprinkler VK458 is pre-assembled with a threaded adapter for installation with the domed cover that provides up to ½ (12.7 mm) of vertical adjustment. The cover plate is available with several decorative finishes to meet design requirements. The two-piece design allows installation and testing of the sprinkler prior to installation of the cover plate. The push-on, thread-off design of the concealed cover plate assembly allows easy installation of the cover plate after the system has been tested and the ceiling finish has been applied. The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler. 2. LISTINGS AND APPROVALS culus Listed: Category VKKW NYC Approved: MEA 89-92-E, Volume 36 NSF Certified: NSF/ANSI Standard 61, Drinking Water System Components Refer to the Approval Chart on page 142w and Design Criteria on page 142x for culus Listing requirements that must be followed. 3. technical data Specifications: Available since 2005. Minimum Operating Pressure: Refer to the Approval Chart. Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar). Thread size: 3/4 (20 mm) NPT Nominal K-Factor: 7.4 U.S. (107 metric*) * Metric K-factor measurement shown is in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. Glass-bulb fluid temperature rated to -65 F (-55 C) Overall Length (Sprinkler Body): 2-5/16 (59 mm) Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass Deflector: Brass UNS-C26000, Brass UNS-C23000, or Phosphor Bronze UNS- C51000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Compression Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating Cover Assembly Materials: Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800 Spring: Beryllium Nickel Solder: Eutectic Ordering Information: (Also refer to the current Viking price list.) Viking Residential Concealed Pendent Sprinkler VK458 and Cover Plate Assembly must be ordered separately: Viking Technical Data may be found on The Viking Corporation s Web site at http://www.vikinggroupinc.com. The Web site may include a more recent edition of this Technical Data Page. Sprinkler: Base Part No. 13230ABX (includes sprinkler and adapter pre-assembled, with a protective plastic cap covering the unit) Note: When ordering this sprinkler using the SIN, add suffix -D. For example, concealed sprinkler VK458 = VK458-D. Form No. F_092305 Replaces page 142u-z, dated January 13, 2012. (Revised sprinkler materials and updated Figures.)

Sprinkler 142v Cover Plate Assembly: Base Part No. 12207 Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover temperature rating to the base part number: Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B, Brushed Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/I, Painted Black = M-/B Temperature Suffix: 135 F (57 C) = A For example, cover 12207 with a Polished Chrome finish and a 135 F (57 C) temperature rating = 12207FA. Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the Sprinkler Accessories section of the Viking data book.) Sprinkler Wrench: Part No. 13577W/B** (available since 2006) **A ½ ratchet is required (not available from Viking). Sprinkler Cabinet: Part No. 01731A (available since 1971) NOTE: Not for use with the Viking Residential Sprinkler Extension. 4. Installation Refer to appropriate NFPA Installation Standards. For NFPA 13D horizontal ceiling criteria and slopes, refer to TIA 1028R for slope ceiling criteria exceptions. 5. Operation During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. inspections, tests and maintenance Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. availability The Viking Model VK458 Sprinkler is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. Guarantee For details of warranty, refer to Viking s current list price schedule or contact Viking directly. Figure 1: Concealed Sprinkler VK458 with Protective Shell Sprinkler Temperature Classification TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Nominal Temperature Rating 1 Maximum Ambient Ceiling Temperature 2 Temperature Rating of the Cover Assembly (Required) Cover Plate Base Part Number 3 Ordinary 155 F (68 C) 100 F (38 C) 135 F (57 C) 12207 Red Bulb Color Cover Plate Finishes: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black 1 The sprinkler temperature rating is stamped on the deflector. Footnotes 2 Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.

Sprinkler 142w Sprinkler Base Part Number 1 SIN Approval Chart Residential Concealed Pendent Sprinkler VK458 For systems designed to NFPA 13D 6 or NFPA 13R. For systems designed to NFPA 13, refer to the design criteria on page 142x. Overall Length NPT Thread Size Nominal K-Factor Maximum Water (Sprinkler Body) Working Pressure Inches mm U.S. metric 2 Inches mm 13230ABX VK458 3/4 20 7.4 107 175 psi (12 bar) 2-5/16 59 Maximum Areas of Coverage 4 Minimum Water Supply Requirements 4 (Refer also to Design Criteria on page 142x.) Listings and Approvals 3 culus 5 NYC 8 NSF 9 Installed below smooth, flat, horizontal ceilings, including ceilings with slopes up to and including 2/12 (9.5 ). 12 ft. x 12 ft. (3.7 m x 3.7 m) 20 gpm @ 7.3 psi (75.7 L/min @ 0.50 bar) AX1 AX1 AX1 14 ft. x 14 ft. (4.3 m x 4.3 m) 20 gpm @ 7.3 psi (75.7 L/min @ 0.50 bar) AX1 AX1 AX1 16 ft. x 16 ft. (4.9 m x 4.9 m) 20 gpm @ 7.3 psi (75.7 L/min @ 0.50 bar) AX1 AX1 AX1 18 ft. x 18 ft. (5.5 m x 5.5 m) 23 gpm @ 9.7 psi (87.1L/min @ 0.67 bar) AX1 AX1 AX1 20 ft. x 20 ft. (6.1 m x 6.1 m) 28 gpm @ 14.3 psi (106 L/min @ 0.99 bar) AX1 AX1 AX1 Installed below ceilings with slopes 7 up to and including an 8/12 (33.7 ) pitch. Refer to Figure 5 on page 142z. Maximum Areas of Coverage 4 Minimum Water Supply Requirements 4 (Refer also to Design Criteria on page 142x.) Listings and Approvals 3 UL NYC 8 NSF 9 16 ft. x 16 ft. (4.9 m x 4.9 m) 22 gpm @ 8.8 psi (83.3 L/min @ 0.61 bar) AX1 AX1 AX1 18 ft. x 18 ft. (5.5 m x 5.5 m) 28 gpm @ 14.3 psi (106 L/min @ 0.99 bar) AX1 AX1 AX1 20 ft. x 20 ft. (6.1 m x 6.1 m) 28 gpm @ 14.3 psi (106 L/min @ 0.99 bar) AX1 AX1 AX1 Sprinkler Temperature Ratings A - 155 F (68 C) Cover Temperature Rating X - 135 F (57 C) Footnotes 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. Cover Plate Finishes 1 - Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black 10 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. 3 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 4 For areas of coverage smaller than shown, use the Minimum Water Supply Requirement for the next larger area listed. Flows and pressures listed are per sprinkler. 5 Listed by Underwriter s Laboratories for use in the U.S. and Canada. 6 Refer to TIA 1028R slope ceiling criteria exceptions. 7 Areas under sloped ceilings must be measured along the ceiling slope. Actual floor coverage in the horizontal plane under sloped ceilings will be less than the listed area of coverage. 8 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 36. 9 Tested and Certified by NSF (National Sanitation Foundation) to NSF/ANSI Standard 61, Drinking Water System Components. 10 Other paint colors are available on request with the same listings as the standard finish colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 4.

Sprinkler 142x culus Listing Requirements: DESIGN CRITERIA (Also refer to the Approval Chart on page 142w.) When using Viking Residential Concealed Pendent Sprinkler VK458 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of coverage and minimum water supply requirements shown in the Approval Chart on page 142w. For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: The flow rates given in the Approval Chart on data page 142w for NFPA 13D and NFPA13R applications for each listed area of coverage, or Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the design area in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13. Minimum distance between residential sprinklers: 8 ft. (2.4 m). DEFLECTOR POSITION: Install Residential Concealed Pendent Sprinkler VK458 with the deflector 3/8 (9.5 mm) to 7/8 (22.2 mm) below the ceiling. Refer to Figure 3. NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also also refer to pages RES1-17 for general care, installation, and maintenance information. viking Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities Having Jurisdiction. Figure 2: Sprinkler Installation and Correct Use of Sprinkler Wrench

Sprinker 142y Figure 3: Sprinkler Dimensions and Cover Installation Figure 4: Identification of Custom Paint Color for Concealed Covers

Sprinkler 142z See Note 1 below. Maximum ceiling slope = 8/12 (33.7 ). Refer to the Approval Chart for listed areas of coverage. Notes: 1. Listed areas of coverage correspond to areas measured along ceiling slope. (For sloped ceiling installations, actual floor coverage in the horizontal plane under sloped ceilings will be less than the listed area.) 2. Actual installations may require multiple sprinklers. A single sprinkler installation has been shown for clarity. 3. For cathedral ceiling applications, install sprinklers in a symmetrical mirror-image of Figure 5. Figure 5: Installation Instructions - Sloped Ceilings Form No. F_092305 Replaces page 142u-z, dated January 13, 2012. (Revised sprinkler materials and updated Figures.)