DOMESTIC HOT WATER Follow operational sequence

Similar documents
Quickheat 30 weather compensated boiler control

Energy-Efficient, Environmentally-Friendly Heating Solutions. Baxi Luna HT Residential Troubleshooting Guide

12.0 Servicing. Electrode Position Fig Annual Servicing Inspection (Cont) 4 ±0.5

Service manual. Riva Plus HE. M296.28SR/C System boiler. Wall hung, fanflue, roomsealed, high efficiency gas boiler

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Ultra Low NOx PowerVent with Honeywell Electronic Control California Only

Service manual GARDA HE MK2. M96A.24SM/B Combi boiler M96A.28SM/B Combi boiler

HEAT ONLY & COMBI BOILER

Service manual RIVA ADVANCE HE M110.24SM/C M110.32SM/C Wall hung, fan flue, room sealed, high efficiency gas boiler

SERVICE MANUAL RIVA COMPACT M90E.24S M90E.28S M90E.32S Wall hung, fan flue, room sealed gas boiler

A/23 MFFI - A/27 MFFI

Service manual. Riva Plus HE. M296.28SM/C Combi boiler. Wall hung, fanflue, roomsealed, high efficiency gas boiler

Servicing Instructions Type C Boilers G.C.N: LEAVE THESE INSTRUCTIONS ADJACENT TO THE GAS METER

Mikrofill Ethos Condensing combination boiler

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

CONTENTS PRODUCT GAS TYPE CONVERSION ADJUSTMENTS FAULT & FAILURE. Product Notation Safety Systems Technical Data Main Components Operating Functions

Service manual RIVA COMPACT HE M96.24SM/C M96.28SM/C M96.32SM/C M96.24SR/C2 M96.28SR/C

Service manual. Riva Plus HE ERP. Wall hung, fanflue, roomsealed, high efficiency gas boiler. Leave this manual adjacent to the gas meter

Q - Series Boiler. Troubleshooting Manual

Settings and Maintenance of the CombinAir

With a power output ranging from 13kW to 24kW, they provide the flexible answer for the majority of traditional installation scenarios.

USERS GUIDE. LOGIC+ Combi 24, 30, 35

BOSCH CONDENS 5000W ZSB18-2A

Service & Trouble Shooting Manual

SUPPLY TO CENTRAL HEATING SYSTEM SUPPLY TO DHW TANK RETURN FROM CENTRAL HEATING SYSTEM RETURN FROM DHW TANK

Baxi Maxflow Combi WM

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04

Baxi Maxflow Combi FS

User's Instructions. Alpha CB50

New Power Vented Rheem FVIR Tanks

NIKE Star 24 3 E. Instantaneous wall-hung with open chamber boilers. NIKE Star 24 3 E

AXIAL HEATER TROUBLE SHOOTING GUIDE. Models: AX24 N/PV, AX24 N/PV LT, AX24 LP AX26 N/PV, AX26 N/PV LT, AX26 LP AX28 N/PV, AX28 N/PV NT, AX28 LP

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL

ENVI Boiler Controller

User's Instructions. Alpha CD24C/32C. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

USERS GUIDE 24, 30. For installation guide see reverse of book

95M-200. Gas-Fired Direct Vent Modulating Hot Water Boiler. Control Manual And Troubleshooting Guide. P/N , Rev.

Technical

AUS. Format 34I-34E BF

Technical Documentation

USER'S INFORMATION MANUAL

Technical

Logic+ Combi

USER'S INFORMATION MANUAL

User's Instructions. Alpha CD25X/28X. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers

Service manual RIVA ADVANCE HE M110B.24SM/C M110B.32SM/C M110B.24SR/C

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

GB24 & GB30. User Manual

User Manual for model

BG2000S PRE-MIX GAS BURNER

Installation and Servicing Instructions. Alpha CB50

1. COMMISSIONING OF THE BOILER en DESCRIPTION FUNCTION BUTTON DESCRIPTION SYMBOL DISPLAY

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model MICROGENUS PLUS. R EN - Edition 02-01/04/2007

Figure 10 or Figure 6

USER'S INFORMATION MANUAL

Open Vented Condensing Boilers

24-28 kw Conventional Combi Gas Boiler. Lawa / LawaPlus

Alpha CD13R,18R and 24R

USER'S INFORMATION MANUAL

Service booklet for the Engineer for Gas Condensing Boilers

MAINTENANCE AND SERVICE GUIDE

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

Service manual. Riva Plus HE ERP RIVA PLUS HE 24C ERP COMBI BOILER RIVA PLUS HE 28C ERP COMBI BOILER

PLEASE LEAVE THIS INSTRUCTION WITH THE USER. Ecomfort 30 HE. User instructions

USER'S INFORMATION MANUAL

USER GUIDE. IMAX XTRA EL kW. For Installation Guide see reverse of book

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 11/10/08

Installation and Servicing Instructions. Alpha 240/280. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired Combination Boilers

SERVICE MANUAL RIVA PLUS M90D.24S M90D.28S M90D.24SR M90D.28SR

PLEASE LEAVE THIS INSTRUCTION WITH THE USER ECOMFORT PLUS 25 HE. User instructions

Control manual and troubleshooting guide

Great Britain en. Installation, user and service manual. Control panel HMI Gas 310/610 ECO PRO

CONVERSION TO PROPANE MANUAL M-Series Condensing Boiler. Wall-Mounted, Gas-Fired Boiler

prestige Control Application Supplement - Type 5 MCBA WARNING

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model CLAS. R EN - Edition 01-01/02/2007

for Gas Condensing Boilers

The guarantee on this appliance is valid for 12 months from the first day of installation.

Service manual GARDA HE GARDA HE SILVER M96.24SM/B M96.28SM/B M96.24SM/D M96.28SM/D

Installation and Servicing Instructions

SERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS

Technical

Installation and Servicing Instructions. Alpha CD24C/32C

MAINTENANCE AND SERVICE GUIDE

MAINTENANCE AND SERVICE GUIDE

Grant UK VortexBlue. 21, 26 and 36kW Blue Flame Oil Boiler Range. Supplementary Installation, Servicing and User Instructions

Installation & Maintenance Manual

SPECIFICATIONS - NIKE

24 VAC Intermittent Pilot Gas Ignition Control

WHE 2.24 / WHE 2.24 FF

TO DO IF YOU SMELL GAS

STM Department TRAINING MODULE. : instantaneous. Version 1.0, Jan 2006

FORMAT DGT HE. User instructions. Please read the Important Notice within this guide regarding your boiler warranty

FEATURES AND BENEFITS. Up to 109.8% part load efficiency

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28

BAXI LUNA 310 Fi TECHNICAL INFORMATION

FEB-24E UK SUPERCOMPACT COMBINATION BOILER USER MANUAL

Baxi Megaflo System HE IE Range. User s Operating Instructions & Important Warranty Information. Gas Fired Wall Mounted Condensing Boiler

Transcription:

DOMESTIC HOT WATER Follow operational sequence Turn Winter/Summer selector to Summer position. The display is switch on. Go to section A Error 110 flashing Error 131 flashing Turn the selector to reset If the error 110 is still flashing Go to section J Error 20, 28 or 50 flashing Go to section E Error 119 flashing Go to section C Turn DHW thermostat to max. Open DHW tap fully. DHW flow sensor operated (red neon on the sensor illuminated) Is mains water filter and assembly clean. Is the magnetic detector well assembled DHW flow rate more than 2 l/min. Go to section G 3 way valve is addressed towards DHW circuit Go to section K Pump runs Go to section B Error 125 flashing Fan runs Error 160 flashing Go to section D Fan runs at correct speed Error 160 flashing Go to section L Fault finding PRIME HT PROMAX COMBI HE PLUS pag. 1/8

DOMESTIC HOT WATER Follow operational sequence (continue) Spark at ignition electrodes for up to 5 seconds and for 3 attempts Go to section H Turn the selector to reset Burner lights Go to section F Burner does not stay alight after 5 sec. Go to section I Burner output modulates to maintain the temperature set Reduce DHW flow rate Burner modulates Clean DHW NTC sensor and DHW heat exchanger Error 130 flashing Go to section M Close DHW tap DHW flow sensor senses no flow. Burner goes out Fan stops after 10 seconds Pump runs for 30 seconds Operation sequence successful Fault finding PRIME HT PROMAX COMBI HE PLUS pag. 2/8

CENTRAL HEATING - Follow operational sequence Turn Winter/Summer selector to Winter position. The display is switch on. Go to section A Error 110 flashing Turn the selector to reset If the error 110 is still flashing Go to section J Error 20, 28 or 50 flashing Go to section E Error 119 flashing Go to section C Turn Central Heating thermostat to max. Pump runs Ensure controls are set to demand and verify the contacts are closed External controls calling for heat and internal clock calling for heat Go to section B Error 125 flashing 3 way valve is addressed towards CH circuit Go to section K Fan runs Error 160 flashing Go to section D Fan runs at correct speed Error 160 flashing Go to section L Fault finding PRIME HT PROMAX COMBI HE PLUS pag. 3/8

CENTRAL HEATING - Follow operational sequence (continue) Spark at ignition electrodes for up to 5 seconds and for 3 attempts Go to section H Turn the selector to reset Burner lights Go to section F Burner does not stay alight after 5 sec. Go to section I Burner output modulates to maintain the temperature set Check the CH NTC sensor Go to section E Error 130 flashing Go to section M Burner goes out Fan stops after 10 seconds Pump continues to run for 3 minutes (room thermostat open) Operation sequence successful Fault finding PRIME HT PROMAX COMBI HE PLUS pag. 4/8

FAULT FINDING SOLUTION SECTIONS A Check line voltage at: Main terminals L and N Check electrical supply Main terminal fuse Replace fuse 3. PCB X1 connector terminals 1,2 Check wiring Boiler working display illuminated B Check line voltage at: Pump If pump jammed, release Replace pump PCB X3 connector terminals 3,4 Change pump supple cable C Central Heating system pressure < 0,5 bar Re-pressurise system Check connection water pressure switch terminal COM and PCB connector X400 terminals 3,4 Replace water pressure switch Check the tap of the automatic air vent is opened Open the automatic air D Fan connections correct at fan. PCB X2 connector is 230 V AC across terminals 3,4 Fan jammed or faulty winding Replace fan Fault finding PRIME HT PROMAX COMBI HE PLUS pag. 5/8

E Temperature sensors faulty. Cold resistance 10 kω @ 25 C (DHW and CH sensors) 20 kω @ 25 C (FLUE sensor) (resistance reduces with increase in temp.) Replace sensor F Check and correct the connexion of the silicon tube between the fan and the gas valve Gas at burner Ensure gas is on and purged PCB X3 connector is 230 V AC across terminals 1,2 Replace gas valve G Check and correct: the position of the electronic sensor on the hydraulic group of the gas boiler the connexion between the PCB X400 connector terminals 3,6,7 and the electronic sensor Check the voltage between (Vcc red wire) and GND (blue wire) is more than 5 VDC Replace the electronic sensor H Check and correct: Ignition electrode and lead Electrode connection 3. Spark gap and position Voltage at main PCB X2 connector is 230 V AC across terminals 2,5 Check wiring Replace igniter Fault finding PRIME HT PROMAX COMBI HE PLUS pag. 6/8

I Check the gas supply pressure: For Natural Gas > 10-11 mbar Check and correct: the mechanical set of the gas valve (CO2 values - see instruction) Flame sensing electrode and lead connections 3. Flame sensing electrode position Flame current should be more than 0,5 μa Replace flame sensing electrode J Overheat thermostat operated or faulty, i.e. continuity across thermostat terminals Allow to cool. Continuity across thermostat terminals more than 1,5 ohm Replace the thermostat K Check line voltage at: Motor 3 way valve Replace motor 3 way valve PCB X3 connector terminals 5,6 central heating function 5,7 DHW function Change motor supple cable L Fan connections correct at fan. PCB X401 connector terminals 5,6,7,8 Check if the setting of the pcb is correct. (See the list of parameters Instruction for Replace fan Service) Fault finding PRIME HT PROMAX COMBI HE PLUS pag. 7/8

M Temperature sensors faulty. Cold resistance 10 kω @ 25 C (CH sensor) 20 kω @ 25 C (FLUE sensor) (resistance reduces with increase in temp.) Replace sensor If pump is running the exchanger could be obstructed Replace exchanger Fault finding PRIME HT PROMAX COMBI HE PLUS pag. 8/8