SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

Similar documents
SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS

Item Referenced and Amendments Building 1 Building 2 Analysis, Review and Remarks. Page 1 of 15

SAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly.

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

Denver Fire Department Fire Prevention Division

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

Business License Pre-inspection Checklist

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

SEMICONDUCTOR FABRICATION FACILITIES

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION GUIDELINE RESIDENTIAL CARE FACILITIES 2007 CBC/CFC (R-3.1)

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

Residential-based Care Facility R-4 Guideline

Business Fire Inspection. City of Guadalupe

Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.

Residential Care Facilities Having 6 or Fewer Clients Classified in the California Building Code as R-3.1 Occupancies

New Construction Fire Inspection Process

Osceola County Department of Fire Rescue and Emergency Medical Services

APPLICATION CERTIFICATE OF OCCUPANCY $50.00 FEE (non-refundable)

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY

Clackamas Fire District #1 Self Inspection Program. Oregon Fire Code (OFC)

PLAN REVIEW SUBMITTAL GUIDE

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES

REGULATIONS FOR OUTDOOR GATHERINGS AND EVENTS TENTS & MEMBRANE STRUCTURES

SEMICONDUCTOR FABRICATION FACILITIES

CHAPTER 7 ALTERATIONS LEVEL

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

GENERAL AREAS OF INSPECTION

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

INSPECTOR I SKILLS ADMINISTRATION

SEMICONDUCTOR FABRICATION FACILITIES

Residential Based Care Facility Guidelines

Common Fire Code Violation Checklist. Listed are some of the most commonly found fire code violations and should not be considered as all inclusive.

SEMICONDUCTOR FABRICATION FACILITIES

For additional information regarding R-3.1 residential care facilities please contact (951)

NFPA 45 NFPA 211 NFPA 1600

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

2012 B.C. Building Code Compliance Review (Division B Part 3)

Fire Sprinkler Plan Submittal Form

Winnipeg Fire Department Fire Prevention Branch

ENGINEERING/PLAN REVIEW - FEE SCHEDULE Exhibit A

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

MULTI-LEVEL & COVERED BOOTH CONDITIONS

Laboratories and Hazardous Materials. Company Overview

School Fire Safety Checklist

CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE

Checklist For Building Inspection & Fire Safety

To expedite the plan review and inspection processes, please refer to the information below.

PROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:.

TABLE OF CONTENTS. Part I Administrative... 1 CHAPTER 1 SCOPE AND ADMINISTRATION... 1

Plan Review Check List Fire Alarm System

Large Family Daycare Guideline

C I T Y O F B A N N I N G BANNING FIRE SERVICES 3900 W. WILSON STREET (951) PHONE (951) FAX

The Cannabis Industry: Fire Department Requirements

ERRATA TO THE 2000 INTERNATIONAL FIRE CODE. Fourth Printing, January 2002 Updated March 29, 2002

South Davis Metro Fire Agency

Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO

Tents and Temporary Membrane Structures Permit Procedure

OUTLINE FOR FIRE PREVENTION ACTIVITY

CITY OF PASADENA FIRE DEPARTMENT

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

New Facilities. Minimum Requirements

Camden County Fire Rescue Office of the Fire Marshal 125 N. Gross Road, Kingsland, GA

West Norriton Township

4. Distances to property line, buildings, other tents, parked vehicles and engines;

INITIAL FIRE SAFETY ASSESSMENT

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

Family Foster Home Fire Safety Evaluation Checklist Instructions

PART 2. Basic Code Requirements - Semiconductor & Microelectronic Facilities using HPM s

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

BUILDING/FIRE CODE REFERENCES 2006 EDITION

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

Agency for Health Care Administration

SECTION INSPECTION AND TESTING OF WORK

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

Tents and Temporary Membrane Structures Packet

FIRE PLAN CHECK CORRECTION List for Commercial Occupancies

HEALTH/LIFE SAFETY ANNUAL INSPECTION CHECKLIST (ROE)

Is the address of your property clearly visible and marked in large numbers that can be easily seen from the street?

INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)

Wausau Fire Department Inspection Violation Code Listing (Modified) All Applicable Records

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

CHIMNEYS AND VENTS CHAPTER 8

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal

SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET

TENTS AND TEMPORARY MEMBRANE STRUCTURES PERMIT PROCEDURE

General Industry Safety and Health Checklist Guidelines. Building and Premises. Loss Control Bulletin

(h) Pesticide Application.

GUIDELINES FOR INSPECTING GROUND BASED SPARKLING DEVICE (GBSD) RETAIL SALES FACILITIES

Transcription:

July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST TENANT IMPROVEMENTS Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments; I-Incomplete; D-Denied This Checklist outlines general requirements. Information contained herein applies to typical instances and may not address all circumstances. FILE REVIEW: 1. Review Permits Plus, Office Link, and the project folder for any previous fire department conditions. 2. Permit fees entered in Permits Plus. 3 rd or greater checks require an hourly fee for the review 3 Phase 1 Environmental Site Assessment approved. 4. Specific Conditions of Planning Permit apply. 5. Approved Alternate Materials or Methods of Construction apply. COVER SHEET: (THE FOLLOWING INFORMATION IS SHOWN AND IS ACCURATE) 6. Project Address 7. Owner contact information 8. Designer s contact information 9. Applicable Codes 10. Occupancy Type 11. Construction Type 12. Tenant Improvement Area COVER SHEET: (THE FOLLOWING INFORMATION IS LISTED AS DEFERRED SUBMITTAL) 13. Automatic sprinkler system to be modified per reference standard 14. Automatic fire alarm system to be modified per reference standard 15. Fire pump and/or standpipe system to be provided per reference standard

16. Special Extinguishing System to be provided per reference standard 17. Emergency Evacuation plans to be provided in E, B, E, H, I R and some M s (CFC 404) 18. Vegetation Management Plan to be provided (building is in WUI Fire Area) 19. In-Building Public Radio System to be provided if building >25,000 sf or >3 stories (SRCC 18-44: 511) 20. Hazardous Materials to be used or stored as part of this project 21. High Piled Storage to be part of this project SITE PLAN: (May not apply if T.I. is strictly interior to an existing building) 22. Drawn to scale and/or dimensions of Fire Service features noted 23. Apparatus access to within 150 feet hose-pull distance of all first floor exterior walls (CFC 503.3.1.1) 24. Apparatus access vertical clearance minimum 13 feet 6 inches (CFC 503.2.1) 25. Apparatus access minimum 20 feet wide for buildings to 30 feet tall (CFC 503.2.1) 26. Two apparatus access roads provided for buildings over 30 feet tall (SRCC 18-44: D104.1) 27. Two apparatus access roads provided for buildings over 62,000 sf (CFC D104.2) 28. Two apparatus access roads provided for more than 50 dwelling units (CFC D106.1) 29. Apparatus access minimum 26 feet wide for buildings over 30 feet tall (CFC D105.2) 30. Apparatus access 15 to 30 feet from building for buildings over 30 feet tall (CFC D105.3) 31. Apparatus access paved (CFC 503.2.3) 32. Apparatus turn-around per COSR Standard 203F is provided (CFC 503.2.5) 33. Apparatus access bridge or elevated surface per AASHTO Standards (SRCC 18-44: 503.2.6) 34. Apparatus access gates have Knox lock or Knox override if powered 35. Apparatus access gates 20 feet into site from public roadway 36. Fire lane curb markings and/or signage provided (FPB Standard) 37. Site Map with building addresses provided at multi-building site entrances (FPB Standard) 38. Fire hydrants every 300 ft on public roads and apparatus access roads (SRCC 18-44: 508.5.1) 39. Fire hydrants at least 40 feet from building (NFPA 24) 40. Sprinkler system FDC on street address side of building 41. Sprinkler system FDC within 50 ft of fire hydrant (SRCC 18-44.C105.1) 2 Page 2 of 7

42. Guard posts provided where hydrants, tanks, generators, gas meters subject to vehicle impact (CFC 508.6) 43. All exterior doors have paved access walkway to required apparatus access road (CFC 504.1) 44. Twenty foot wide pedestrian access from main exit to public way in A and E Occupancies 45. Level ladder staging area provided at all emergency egress windows (FPB Standard ) 46. Fire Department key box provided at main building or site entrance (CFC 506) FLOOR PLANS: 47. Allowable height and area shall be per CBC Section 503 and Table 503 48. Mixed uses shall be separated as required by CBC Section 508 49. Exterior wall fire resistiveness shall be per CBC Section 704 50. Openings in rated exterior walls shall have protections as specified in CBC Section 715 FLOOR & ROOF: 51. Verify roof rating and surface comply with CBC Chapter 15 52. TJI/Composite Wood Joists. Composite wood joists in sprinklered buildings. Maximum 16 in depth or comply with one of the exceptions (drywall on underside, sprinkler within, fill joists with noncombustible insulation). 53. TJI/Composite Wood Joists. Open joists require fire stopping of channels into 300 ft/2 areas. Closes joists (ceiling on the underside) require fire-stopping into 160 ft/3 areas. 54. Draft stops shall be installed in attics per CBC 717.4. See exceptions for fire sprinklered attics 55. Skylights, if provided, are not installed within the area, based upon distance to property line, to be protected 56. Smoke and heat vents and draft curtains shall be provided, when required, by CBC Section 910. 57. Roof access shall be provided and new buildings four or more stories shall provide a stairway (CFC 504) GENERAL REQUIREMENTS, EXITING, DOOR SCHEDULE: 58. Two exits if >50 occupants or above/below ground floor (CFC 1015.1, CFC 1019) 59. Doors swing in direction of exit travel if serving >50 occupants (CFC 1008.1.2) 60. Panic hardware on doors of A, E occupancies with >50 occupants (CFC 1008.1.9) 61. No knowledge, single-action hardware on all exit doors, including gates (CFC 1008.1.8.3) 62. Manually operated flush or bolt locks are not permitted on egress doors (CFC 1008.1.8.4) 3 Page 3 of 7

63. The number of doors for each room or area complies with CFC 1015, Table 1015.1, and 1019 64. Exits do not pass through laboratories, store rooms, kitchens, hazardous use areas (CFC 1014.2) 65. Exits separated min 1/3 diagonal of space if sprinklered or 1/2 diagonal if not sprinklered (CFC 1015.2) 66. Common Path of Egress Travel Distance per CFC 1027.17.2 67. Exit Access Travel Distance per CFC Table 1027.17.2 68. Egress Widths per CFC Table 1005.1 69 Occupant load calculations are provided for the rooms and assembly areas, and occupant load signs are processed for assembly areas (CFC 1004). 70. Maximum Occupant Load signage if >50 occupants in A Occupancies (CFC 1004.3) 71. Illuminated exit signs clearly delineate path of egress all spaces >50 occupants. Signs at directional changes in hallways, visible from any direction of egress travel and where necessary. (CFC 1011.1) 72. Exit signs are flush or perpendicular to mounting surface so they are in the field of view 73. Signage detail is provided for the landing areas of vertical stairways more than 3 stories. Signage states location East, West, etc., terminus-roof access or not, floor number and floors served by stairs. Signs to be 5 foot above floor landing (CFC 1020.1.6) 74. Type 1 hood with 1-hour exhaust duct installed at all commercial cooking appliances (CFC 609) 75. One 2A:10B-C fire extinguisher is provided per 3,000 sf, max 75 ft travel distance 76. Type, size, mounting height, and travel distance are appropriate for the hazard and are detailed on the plans, CFC 906. 77. Signage at HVAC, sprinkler, electrical, and fire alarm control location required (CFC 510) 78. SFM regulated occupancies: >2 stories or without straight-run stairs have at least one elevator sized for medical gurney - min 80 in x 54 in cab interior (CFC 807) INTERIOR ELEVATIONS AND FINISH SCHEDULE: 79. Wall and Ceiling finish material Classes per CFC Table 803.3 80. SFM regulated occupancies: decorative materials treated for flame spread and smoke production EXTERIOR ELEVATIONS: 81. 12 inch illuminated address characters on street elevation (FPB Standard ) 82. Doors swing in direction of exit travel if serving >50 occupants (CFC 1008.1.2) MECHANICAL PLANS: 83. Air-handling units >2,000 cfm have smoke detector in supply duct for automatic shutdown 4 Page 4 of 7

84. Fire Dampers are shown and detailed. Activation method is specified and listing is for passive or dynamic. 85. If handling hazardous materials, provide 1 cfm per ft/2. ELECTRICAL PLANS: 86. Path of egress from all spaces to the public way is illuminated to 1 foot candle (CFC 1006.2) 87. Egress illumination has 90 minute backup power per CFC 1006.3 88. Emergency alarm required in accordance with CFC 908 89. If to be equipped with a fire alarm system, reference the Fire Alarm Power Supply Standard specifically to address the need for a separate disconnect, locking of the disconnect, color and signage. 90. If to be equipped with a fire pump, reference the Fire Pump Standard to ensure the special electrical conductor protections are provided at the time of building construction 91. Provision for elevator shunt-trip, if required, are noted on the electrical drawings 92. If commercial cooking equipment, provisions are made for shunt-trip on appliance power circuit ALTERNATE OR CLEAN AGENT GAS: 93. Room use or type of hazard and/or process is detailed on the plans. 94. Equipment and devices data sheets, voltage and battery calculations are provided. 95. Concentration and discharge calculations are provided. USE AND PROCESS SPECIFICS: Group R Occupancies 94. Smoke detectors are located in sleeping rooms, hallway and adjacent room if vaulted ceiling, also at the top of stairs and lower level, 907.3.2. Assembly Use 95. Occupant loads certificates for assembly rooms are created, 1004.3. 96. Exit door hardware; panic hardware is on all exit doors except main entry, no other security bolt hardware allowed with panic hardware, 1008.1.9. 97. Data sheets for fire-resistive decorative materials are provided, 804, 806, and 807. Battery Rooms 98. Spill control method and materials are detailed, CFC 608.5. 99. When ventilation is required, calculations are provided to verify ventilation rate maintains the room atmosphere to 1 percent by volume of hydrogen or a minimum ventilation rate of 1 cfm/ft2 of floor area, 608.6.1. 5 Page 5 of 7

100. Door signed stating room contains lead-acid batteries, energized electrical circuits, and corrosive liquids are detailed on the plans, 608.7. 101. Battery systems are seismically braced and room smoke detection is provided, 608.8 and 608.9. Fuel-Dispensing Station 102. Details for dispensing unit or island, and emergency shut-off location are provided, and tank construction is in accordance with CFC Chapter 22 and 34. Hazardous Materials 103. Hazardous Materials, CFC 27 always applies then the chapter specifics. 104. Spill control and secondary containment, CFC 2704.2, 2705.1.3, 2705.2.1.3, 2705.2.1.4, 3404.3.7.3, 3404.3.7.8.2, 3404.4.3, 3405.3.7.5.3 and 3405.3.7.5.6.3. 105. Spill control and secondary containment shall be liquid tight, i.e. compatible floor coating, 2704.2.1(1) and (2), 2704.2.2.1 (1) and (2). 106. Cryogenics, CFC 32. 107. Compressed Gases, CFC 30. 108. Flammable Combustible Liquids, CFC 34. 109. Highly Toxic and Toxic Materials, CFC 37. 110. Oxidizers, CFC 40. 111. Unstable and Water Reactive materials, CFC 43 and 44. HPM Workstations, Gas Cabinets Exhausted Enclosures, Silane Gas, and Ozone Systems 112. Complies with CFC Chapters 18, 27, and 37. High-piled Storage 113. Speculation buildings with potential to house high-pile storage but not designed for high-piled storage is requiring demarcation lines (12 ft. above floor level) and verbiage on walls ( No storage permitted above this line by the authority of the Fire Marshal s Office. ) and letter from owner agreeing that building is not designed for nor will it be used for high-piled storage, 2304.3. 114. The 14 items in CFC 2301 are detailed or provided, 2301.1. 115. Aisle width and rack locations are on the plans, 2301.1. 116. Exterior fire access doors are on the plans, 2301.1. 117. Detection and suppression systems are provided, 2301.1. 118. Smoke removal system or heat vents or curtain boards are detailed on the plans, 2301.1. 119. Need product hazard classifications, quantities, location, etc, consult additional information in the High Pile Standard. 2301.1. 6 Page 6 of 7

LPG Tanks 120. Location on a site plan is provided, CFC 38 and NFPA 58. Consult the LPG Install Standard Medical Gases 121. Quantity, location and room construction are provided and detailed, CFC 30 and consult the Medical Gas Standard. 122. Paint Booth, Powder Coating, Electrostatic Spray Operations 123. Manufacture data sheets for the booth and equipment are provided, CFC 15 and consult the Spray Booth Standard. 124. Construction and ventilation details for spray booths, areas or rooms are provided. Welding Operations 125. Location is detailed, signage detailed, type of gases, storage location and quantity of gases, CFC 26. 7 Page 7 of 7