ECONOPLATE H1-heat only HEAT INTERFACE UNIT. Installation, Commissioning and Servicing Instructions for vented systems.

Similar documents
ECONOPLATE H1-heat only HEAT INTERFACE UNIT. Installation, Commissioning and Servicing Instructions for unvented systems.

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

MEGAFLO HE Iss 1

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

POWERFLOW Series. Unvented Electric Storage Water Heaters. Installation & Operating Instructions Manual

INSTALLATION AND SERVICING

Unvented Electric Water Heater 10/15 litre Undersink

SATK50-60 series CONTENTS. Recess Mounted Heat Interface Unit - SATK series INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE

UNDERCOUNTER SERVICE MANUAL. Ecoboiler UC4L 2.4kW Ecoboiler UC10L 2.8kW Ecoboiler UC10L 5.6kW Ecosmart UC4L 2.

Alpha CombiMax 350 and 600

Installation and Servicing Instructions. Alpha FlowSmart

Unvented Direct & Indirect Hot Water Cylinders (400L L)

Unvented Direct & Indirect Hot Water Cylinders (400L L)

HEATRAE SADIA. Installation and User Instructions for the UTC Undersink Vented Water Heater

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

Wall-mounted compact indirect heat interface unit SATK30 series Safety instructions Dimensions Technical specifications Installation Commissioning

T-RECESSED RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Installation and User Instructions HS10U, HS15U.

Stokvis R600 LMS IP Water Heater Gas-Fired Floor Standing Condensing

Electronically controlled instantaneous water heater. MCX: 27300, and models. Installation instructions

SERVICE MANUAL. Ecoboiler Model range: T20 ( ) T30 ( )

Powerflow Unvented water heater

Alpha FlowSmart 25 and 50

Installation and User Guide Please leave this guide with the end user (for future reference)

MW & EW 10 & 15 Litre Unvented Water Heaters HANDBOOK. IMPORTANT: This booklet should be given to the customer after installation and demonstration.

AquaFlo II. Issue 3 December Please read these instructions carefully before commencing installation of the AquaFlo unvented water heater

Installation & Technical Guide. Domestic & Commercial.

NON-SUBMERSIBLE WATER PUMP

Multipoint Technical Data

AQUARIUS 45 MARINE SERVICE MANUAL

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

MEGAFLO Eco Plus Solar Unvented Hot Water Cylinders 400L -570L

FRANKE MINERVA 3-IN-1 HOT WATER TAP HEATING TANK INSTALLATION GUIDE

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03. Technical Data Electrical Details Connection Details Dimensions Standing Losses

Installation and Wiring Instructions

Ecoboiler T20 & T30 SERVICE MANUAL. Marco Beverage Systems Ltd. 63d Heather Road, Sandyford Industrial Estate, Dublin 18, Republic of Ireland

ZIP Varipoint III. Installation, Maintenance and User Instructions. Models VP303, VP503 VP803, VP953 direct unvented water heaters. Issued August 2008

PHV-RECESSED RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

INSTALLATION MANUAL. Domestic hot water tank with option kit for air to water heat pump system EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 EKUHWB

CALEFFI. SATK wall-mounted heat interface unit Fitted for connection to DHW storage. SATK40 series 01216/14 GB

Installation and Commissioning Instructions FMU3 Floor Mixing Unit with Grundfos UPM3 Pump

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

PANDORA HEAT BANKS OXFORD BROOKES, HARCOURT HILL. Operation and Maintenance. THERMAL INTEGRATION LTD. Tel: Internet:

EcoSmart boiler SERVICE MANUAL

heat interface units A BOILER WITHOUT A FLAME

OWNERS INSTRUCTION MANUAL

USER GUIDE. IMAX XTRA EL kW. For Installation Guide see reverse of book

Concealed Twin & Triple Thermostatic Shower Valve with Diverter. Installation & Operating Guide

Twin & Triple Exposed Thermostatic Shower Valve Installation & Operating Guide

Instructions for Use Installation and Servicing

Logic+ Combi

THERMOSTATIC SHOWER VALVE

PremierPlus Unvented Hot Water Cylinder Installation and User Manual

Megaflo Eco Plus Unvented Indirect Hot Water Cylinders 800L L

OWNER S GUIDE SEQUENTIAL THERMOSTATIC SHOWER VALVE. 150mm Inlet Pipe Centres. Shower Control. Handles and. may differ depending.

Zircon Installation Manual

SATK wall-mounted Heat Interface Unit (HIU) Instantaneous domestic hot water production

Installation and Servicing Instructions. Alpha GasSaver GS-1

HW3 Handwash Installation and Operating Instructions

AQUAIR S SERIES. of Water to Air Space Heaters INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONSS. Aquair S-10 Aquair S-16 Aquair S-20

Broag Pressurisation equipment

ZIP AquaFlo II. Models: Direct, Indirect and Solar Compatible. Unvented cylinder water heaters

Installation, Operating and Maintenance Guide

UNVENTED MAINS PRESSURE SOLAR WATER HEATERS 100 TO 300 LITRE CAPACITY DIRECT AND INDIRECT MODELS INSTALLATION AND SERVICING INSTRUCTIONS

Electronic Instantaneous Water Heaters Models: ES3, ES4 & ES6

Mira Sport Max with Airboost

BG2000S PRE-MIX GAS BURNER

Installation, operating and servicing instructions

Unvented water heater

PHV2000NT CHILLED WATER HEAT PUMP, SENSIBLE/DRY COOLING UNIT INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Alpha SolarSmart 100

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40

Unvented Direct & Indirect Hot Water Cylinders

INSTALLATION MANUAL. RD SERIES Digital Electric Water Heater Wall-hung Unvented

1 Dimensions Installation Mains/boosted cold water inlet Connection to the system Drain Dimension for fixing 6

Installation and User Instructions Aquaheat Unvented Water Heaters Models: AH30H

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

Heat 45 & 55. User Instructions FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

PLEASE LEAVE THIS INSTRUCTION WITH THE USER. Ecomfort 30 HE. User instructions

Mains Pressure Hot Water from an existing vented copper cylinder... Allows the cold water tank to be removed, freeing loft space.

Commissioning Pack. Heating and Hot Water Heat Pumps. IMPORTANT DOCUMENTS To Be Kept At All Times. With Equipment. Accredited Ecodan Installer:

CARVER CASCADE 2 & CASCADE 2 GE CARAVAN WATER HEATER INSTALLATION INSTRUCTIONS LEAVE THESE INSTRUCTIONS WITH THE USER

UNVENTED MAINS PRESSURE SOLAR WATER HEATERS 210, 250 AND 300 LITRE CAPACITY INDIRECT MODELS INSTALLATION AND SERVICING INSTRUCTIONS

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

Installation, Operating and Servicing Instructions

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Direct, Indirect, Solar & Heat Pump Un-Plumbed & Pre-Plumbed Unvented Cylinder Installation & Maintenance Manual

Installation, operation and Maintenance Manual

AIR CURTAIN HX RECESSED RANGE

Quantum. Installation, User and Service Manual. Hot Spring

UNIQ HEAT BATTERIES REFERENCE MANUAL_V2.2. Version: 2018_07_19_v2.2

ELECTRIC FIRE PUMP CONTROLLER

Installation and Servicing Instructions. Alpha SolarSmart 90

STREAMLINE OVERSINK. Fitting Instructions and User Guide _iss_05.indd 1 15/09/ :46:30

KYROS INSTALLATION MANUAL KYROS. Digital Electric Water Heater Wall-hung Unvented

Installation Instructions For Monsoon Extra Universal Single Duty Pump

This manual must be kept with the appliance

Transcription:

ECONOPLATE H1-heat only HEAT INTERFACE UNIT Installation, Commissioning and Servicing Instructions for vented systems. Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING, OPERATING OR SERVICING EQUIPMENT. THE ECONOPLATE H1 UNIT IS INTENDED FOR USE IN LOW TEMPERATURE DISTRICT HEATING SCHEMES. STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL Tel: 020 8783 3050 / 08707707747 Fax: 020 8783 3051 / 08707707767 E-Mail: info@stokvisboilers.com Website: www.stokvisboilers.com ECONOPLATE H1-heatonlyvented SERIES-V1-IO&M-15072014

CONTENTS Item Page 1. Warnings 1 2. General Requirements 2 3. Unit Description 2 4. Technical Data 3 5. Installation 4 6. Operation of Unit 8 7. Commissioning 8 8. Fault Finding 9 9. Servicing 10 10. Internal Components 11 11. Schematics 12 12. Appendices 13 THIS HEAT INTERFACE UNIT COMPLIES WITH THE ESSENTIAL REQUIREMENTS OF THE LOW VOLTAGE DIRECTIVE 2006/95/EC AND THE ELECTROMAGNETIC COMPATIBILITY DIRECTIVE 2004/108/EC. 1. WARNINGS Inside the Unit there is 230V, so Unit MUST be isolated before being worked on and must only be serviced by a competent and authorised person. Water within the Unit can reach temperatures of up to 85 C so great care must be taken when changing, adjusting or servicing Components within. 1

2. GENERAL REQUIREMENTS Related Documents The Pressure Systems Safety Regulations 2000 It is the law that pressure system appliances are installed, maintained and serviced by competent persons in accordance with the above regulations. Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety, to ensure that this law is complied with. The installation of this Unit should be in accordance with the relevant requirements of the Pressure System Regulations, Building Regulations and IEE Regulations. 3. UNIT DESCRIPTION This Heat Interface Unit is designed to be used on low temperature hot water supply of up to 85 C. The Unit is configured to provide indirect heating to a heating system, via a heat exchanger, and has been amended specifically for use on a vented heating system. The indirect heating can be fed to a hot water cylinder to heat up cold water. The Unit is housed within a powder coated steel cabinet with a removable front cover. Inside there is manufactured pipework assembled together with an electronic valve that is controlled by an electronic controller which takes care of the heating demand. This unit does have components within it to enable it to be converted for use on an unvented system at a later stage. 2

4. TECHNICAL DATA Figure 1 Basic Overall Dimensions including spacer hanging bracket Technical Data General Data Maximum Pressure District 6 bar Maximum Pressure Heating 3 bar Maximum District Temperature 85 C Maximum District Flow Rate 18l/min Weight Empty 20 kg Dimensions 469 x 630 x 276 Electrical Supply Power Consumption 230V 3 Amp 105W 3

Temperature Range Heating Water Temperature Range 60 C to 80 C Water Connections District Inlet/Outlet Heating Inlet/Outlet 3/4 BSP Male 3/4" BSP Male Heating Performance Heat Output @ Δt 11K Heating Circuit XS Head from Integral Pump @ Δt 11K 22kW 22kPa Min System Features Heating Ramp-Up Time of 3 Minutes. Pump Anti-Lock Feature Runs Pump for 5 Seconds every 24 Hours. 5. INSTALLATION Figure 2 Connection Locations 4

Note when working with the unit, supply services when connected could reach 85 C, and once electrically connected the unit has 230V present within. You will need access from above and below the Unit to install the relevant Pipework to and from the Unit. A spacer plate has been provided enabling pipework to be run behind the Unit. Secure the spacer plate to the wall securing via 4 points provided [see below]. Mount the Unit on to the Bracket, securing it to the bracket with the screws provided. Figure 3 Spacer Plate 5

Pipework Connections The District and heating pipework must be connected to the appropriate points labelled on the figure below. An isolation/connection kit for the district in and out has been provided, enabling isolation from the primary flow and return pipes. You must not isolate the heating circuit from either the cold feed pipe or expansion tank. You need to ensure that both sides of the systems you are connecting to are clean or have been properly flushed out. Figure 4 Pipework Connections District Inlet and Outlet ¾ Male BSP These are situated at the top of the unit with inlet on the left [Connection 1, Figure 5] and outlet on the right [Connection 2, Figure 5]. When connecting the district supply to and from the unit, ensure to provide air eliminator at upper most point of pipework. Heating Inlet and Outlet ¾ Male BSP These are situated at the bottom of the unit with heating flow on the left [Connection 4, Figure 5] and heating return on the right [Connection 3, Figure 5]. Connect these to your heating distribution system ensuring it has been appropriately flushed beforehand. 6

Safety Relief Discharge ½ Female BSP This is provided on the heating circuit, and although not in use in vented mode, MUST still be safely piped away via a suitable tundish according to local bylaws. A hole is provided in the casing to allow pipework to leave the unit. Water Inlet capped off This connection is here should the system ever be converted to unvented. It has been capped off both ends to indicate it is not in use, and so nothing should be connected to this point. Electrical Connection All wiring to the Unit must be in accordance with the I.E.E. regulations, and any local regulations which apply. Note: If in any doubt, a qualified Electrician should be consulted. Figure 5 Terminal Block Wiring 7

A 12 way terminal block has been provided inside the station to which connections are to be made [see Figure 5 above]. Mains 230V needs to be provided to terminals 1 to 3 via cable gland in the top of the unit. The fuse needs to be rated at 3 Amps. This will provide power to both the Station and the Heat Meter within. There is 230V supply for the pump over terminals 7 to 9, and you need to connect your pump power cable to these terminals accordingly via cable gland in top of unit. The Unit will then provide power to the pump when it is in heating mode. In order to turn the Unit into heating mode, a switched live is to be provided over terminals 11 and 12. Whenever power is applied over these two terminals, the Unit will go into heating mode, and will continue to heat until power to these terminals is switched off. 6. UNIT OPERATION Whenever power is applied to the Unit, the Stepper Motor resets itself in order to return to its starting setting. Once it is in the correct position the Unit is ready for its operation. When the switched live is activated by a requirement from your system, the Unit will activate Heating mode after approx 5 seconds. The system Pump will be switched on, and the Control Valve will start to operate via the Stepper Motor and will gradually increase the temperature of the Heating water to the pre-set temperature over a period of up to 3 Minutes. The Unit will continue to provide heating water at the set temperature, until power over the switched live stops and the Unit will go into standby mode. 7. COMISSIONING Note when working with the unit, supply services when connected could reach 85 C, and once electrically connected the unit has 230V present within. The Unit set point has been set to 73 C ±0.5 C, and will provide heating water to ±1.0 C of the set point. If the set point needs to be changed then you need to access Poti P2 at the top of the electronic box. The set point can be adjusted by rotating the Poti. The Unit can provide the heating water between 60 C and 80 C over the range of the adjustment [assuming there is sufficient district primary]. Anti clockwise reduces the temperature and clockwise to increase the temperature. 8

Heat Meter Booklet is provided along with these Instructions. System Safety Relief Valve A 3-Bar system Safety Pressure Relief Valve is provided within the Unit which MUST be piped away via a Tundish according to local Guidelines. 8. FAULT FINDING Firstly check the electronic box to check it is not in fault mode indicated by red light. If the Unit still does not operate, then the next step is to check all wiring is correctly connected to the right component, especially if Connectors have been taken off at any stage [see Appendices Table 1]. If the above does not rectify the problem and the Unit still does not operate satisfactorily, then below are some suggestions of potential issues. Alternatively consult Supplier for assistance. Guide Fault Possible Causes Action District water not entering the Unit. Blocked Strainer. Unscrew the Strainer Cap Bolt and take the Strainer out, ensuring you have isolated Unit and waited for water to cool down. Clean or replace accordingly. No Heating. Heating light not coming on controller Control Valve not operating. Check voltage is going to switched live. Check operation of relay and replace if not working Check that 24V is being supplied to DC Coil. If above does not resolve issue, replace Stepper Motor. 9

Pump not operating. Check that Impeller has not seized. Check you have 240V going to Pump. If above does not resolve issue, replace Pump. District water temperature too low. Check District supply conditions. Heat Exchanger potentially fouled 9. SERVICING SCHEDULE Note when working with the unit, supply services when connected could reach 85 C, and once electrically connected the unit has 230V present within. It is recommended that this Unit is serviced once every 12 months. Servicing the Strainer Isolate the Unit from District supply. Open the screw cap from the Strainer and take the Filter Cartridge out. Note: The water in the Strainer could be anything up to 85 C. 10

10. INTERNAL COMPONENTS Figure 9 Internal Components 11

11. UNIT SCHEMATIC 12

12. APPENDICES Table 1 Electronic Box Wiring Denotation Description Individual Wiring Connector Remote Controller/Temperature Sensor 2 Black Wired to Relay via NO contacts Mixing Valve Stepper Motor Blue, Black, Brown and Green White Connector Mains Cable Blue, Brown and Green/Yellow Wired to Terminal Block Earth Cable Green/Yellow Non insulated Crimp Ring Pump Blue, Brown and Green/Yellow Wired to Terminal Block CH Temperature Sensor 2 Red Black Connector CH Safety Thermostat/Pressure Switch 2 Black Not used connected together Table 2 Electronic Box Dip Switches SWITCH FUNCTION ON OFF 1 High temp / Low temp central Low temp High temp heating 2 H1 Heating only Heating only [needs DIP Not required switch 4 on as well] 3 N/A N/A Correct 4 Single plate / Twin plate Twin Single 5 DHW preheating Enabled Disabled 6 DHW sensor Flow meter Flow switch N.B Switch 3 should always be in the off position, otherwise unit will not work. If in doubt do not make any changes. Table 3 Matrix LED ANOTATION COLOUR LIGHT OFF LIGHT ON LIGHT FLASHING ON Green Power Off Power On N / A HEAT Yellow No Heat Demand In Heat Mode N / A FAULT Red No Fault CH Saftey wire faulty Sensor fault replace failed NTC temperature sensor 13

Table 4 Pump Data 14