RECORD SUBMITTAL COVER SHEET PROJECT TITLE: AXCELLERATE PHARMA EQUIPMENT DESCRIPTION: CARRIER AQUASNAP AIR-COOLED CHILLER CH-1 OWNER: AXCELLERATE PHARMA MECHANICAL ENGINEER: ARDEN DATE: JUNE 27, 2014 SUBMITTED BY: CARRIER CORPORATION ALLAN IMBAULT JOB #4140H6512 CARRIER BUILDING SYSTEMS & SERVICES 95 SHAWMUT ROAD UNIT #3 CANTON, MA 02021 781-774-6300 781-774-6399 APPROVED: TITLE: DATE:
GENERAL NOTES 30RAP060 1.) Carrier to provide (1) 30RAP0606D-G7F10 AquaSnap Air-Cooled Chiller. 2.) Contractor/Engineer to note motor voltage is 460-3-60. 3.) Contractor/Engineer to note performance data and dimensional information. 4.) Contractor/Engineer to note the following items are provided: A.) Scroll Compressors B.) Microchannel Coils C.) Low Sound D.) Hot Gas Bypass E.) Low Ambient Head Pressure Control F.) BACnet Communications G.) Cooler-Heater H.) Single Point Connection I.) Non-fused Disconnect J.) 7.5HP Dual Pump Package K.) Pump package to be: Armstrong 4360 Model 2D - 5.5 Impeller, 3600 RPM. L.) Wind Baffles (field Installed by others) M.) Chilled Water Storage Tank (field installed by others) N.) Labor for start up O.) 1 st year parts and labor waranty- 12 months from startup or 18 months from shipment, whichever occurs first P.) Years 2-5 compressor only parts & labor warranty Q.) Standard Neoprene vibration isolation (field installed by others) 5.) Contractor/Engineer to note the following items are not provided: A. Suction service valves (not available on size 060) B. Installation, rigging, carting C. Equipment base/pad and anchor bolts D. Any piping or accessories except as noted elsewhere in this proposal E. Electrical work including control and power wiring
Product Data AquaSnap 30RAP010-150 (60 Hz) 30RAP070-150 (50 Hz) Air-Cooled Chillers with Puron Refrigerant (R-410A) 10 to 150 Nominal Tons (60Hz) (35 to 528 Nominal kw) 70 to 150 Nominal Tons (50Hz) (246 to 528 Nominal kw) a30-4827 a30-5347 a30-4826 The AquaSnap chiller is an effective allin-one package that is easy to install and easy to own. AquaSnap chillers operate quietly and efficiently. Value-added features include: Rotary scroll compression HFC Puron refrigerant (R-410A) Low-sound AeroAcoustic fan system Easy to use ComfortLink controls Optional integrated hydronic pump package (60 Hz only) with VFD (variable frequency drive) compatible motors, with optional VFD on size 070-150 models Coil design flexibility Microchannel coil technology available on all units, and RTPF coil technology available on sizes 070-150 Accessory fluid storage tank on size 010-060 models Optional digital scroll compressors on size 010-090 models Features/Benefits Carrier s superior chiller design provides savings at initial purchase, at installation, and for years afterward. Costs less right from the start Carrier s AquaSnap chillers feature a compact, all-in-one package design that installs quickly and easily on the ground or the rooftop. The optional pump and hydronic components (60 Hz only) are already built in; this costs less than buying and installing the components individually. The chiller s fully integrated and pre-assembled hydronic system (60 Hz only) installs in minutes. No other chiller in this class installs so easily and inexpensively. The preassembled and integrated hydronic module utilizes top-quality components and pumps to ensure years of reliable operation. Carrier Corporation 2014 Form 30RAP-11PD
Unit Report Unit Report For 30RAP060 35%PG Unit Information Tag Name: 30RAP060 35%PG Model Number: 30RAP060 Condenser Type: Air Cooled Compressor Type: Scroll Nameplate Voltage: 460-3-60 V-Ph-Hz Quantity: 1 Manufacturing Source: Charlotte, NC USA Refrigerant: R410A Independent Refrigerant Circuits: 2 Capacity Control Steps: 5 Minimum Capacity: 16.1 % Shipping Weight: 3267 lb Operating Weight: 3062 lb Unit Length: 89 in Unit Width: 93 in Unit Height: 79 in Accessories and Installed Options Cooler Heater Non-Fused Disconnect Low Sound Dual Pump, 7.5 HP Hot Gas Bypass Low Ambient Head Pressure Control BACnet Communications Single Point Chilled Water Storage Tank Wind Baffle Vibration Isolation Package Chiller Warranty Information (Note: for US & Canada only) First Year - Parts Only (Standard) Start-Up with 1st Year Carrier CCS Labor - 1st Unit Compressor Years 2-5 Parts & Carrier CCS Labor Ordering Information Part Number Description Quantity 30RAP0606D-G7F10 Packaged Chiller 1 Base Unit Cooler Heater Non-Fused Disconnect Low Sound Dual Pump, 7.5 HP Hot Gas Bypass Low Ambient Head Pressure Control BACnet Communications Single Point 30RA-900---052 Chilled Water Storage Tank 1 30RA-900---066 Wind Baffle 2 30RA-900---005 Vibration Isolation Package 1 NOTE: ETO must be submitted for hydronic packages having glycol concentration of 30% or higher. Packaged Chiller Builder NACO 3.48 Page 3 of 12
Certified Drawing Certified Drawing for 30RAP060 35%PG Packaged Chiller Builder NACO 3.48 Page 4 of 12
Certified Drawing for 30RAP060 35%PG Packaged Chiller Builder NACO 3.48 Page 5 of 12
Field Wiring Diagram Field Wiring Diagram for 30RAP060 35%PG Packaged Chiller Builder NACO 3.48 Page 6 of 12
Performance Report Summary Performance Report For 30RAP060 35%PG AquaSnap TM Air-Cooled Scroll Chiller Unit Information Tag Name: 30RAP060 35%PG Model Number: 30RAP060 Quantity: 1 Manufacturing Source: Charlotte, NC USA Refrigerant: R410A Independent Refrigerant Circuits: 2 Shipping Weight: 3267 lb Operating Weight: 3062 lb Unit Length: 89 in Unit Width: 93 in Unit Height: 79 in Chiller Pressure Drop: 37.8 ft *Unit pressure drop listed includes losses due to chiller piping, fittings, 40 mesh factory supplied strainer and BPHX. Evaporator Information Fluid Type: Propylene Glycol Brine Concentration: 35.0 % Fouling Factor: 0.00010 (hr-sqft-f)/btu Leaving Temperature: 40.0 F Entering Temperature: 52.2 F Fluid Flow: 104.0 gpm Condenser Information Altitude: 0 ft Number of Fans: 4 Total Condenser Fan Air Flow: 38800 CFM Entering Air Temperature: 95.0 F Integrated Pump Information Dynamic Head At Pump: 112.9 ft Dynamic Head External To Chiller: 75.1 ft Performance Information Cooling Capacity: 49.8 Tons Total Compressor Power: 57.9 kw Total Fan Motor Power: 5.31 kw Pump Power: 5.26 kw Total Unit Power (without pump): 63.2 kw Total Unit Power (with pump): 68.5 kw Efficiency (without pump): 9.46 EER IPLV: 14.35 EER A-Weighted Sound Power Level: 91 dba Accessories and Installed Options Cooler Heater Non-Fused Disconnect Low Sound Dual Pump, 7.5 HP Hot Gas Bypass Low Ambient Head Pressure Control BACnet Communications Single Point Chilled Water Storage Tank Wind Baffle Vibration Isolation Package Electrical Information Unit Voltage: 460-3-60 V-Ph-Hz Connection Type: Single Point Electrical Electrical Amps Circuit 1 Circuit 2 MCA 134.6 --- MOCP 150.0 --- ICF 280.0 --- Rec Fuse Size 150.0 --- All performance efficiency data are without pump. Note: Weights and electrical values do not include separately shipped accessories. An uncoated Novation condenser coil was selected for this product. This is based on an installed location with postal code 08854 and a non-corrosive localized environment. Packaged Chiller Builder NACO 3.48 Page 7 of 12
Summary Performance Report For 30RAP060 35%PG Evaporator contains a glycol or other secondary coolants for freeze protection with a leaving chilled fluid temperature above 32 F and is certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) when tested with water at Standard Rating Conditions. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Sound power measured in accordance with ANSI/AHRI Standard 370-2001. NOTE: ETO must be submitted for hydronic packages having glycol concentration of 30% or higher. Packaged Chiller Builder NACO 3.48 Page 8 of 12
Acoustic Summary Acoustic Summary For 30RAP060 35%PG Unit Parameters Tag Name: 30RAP060 35%PG Model Number: 30RAP060 Condenser Type: Air Cooled Compressor Type: Scroll Chiller Nameplate Voltage: 460-3-60 V-Ph-Hz Quantity: 1 Manufacturing Source: Charlotte, NC USA Refrigerant: R410A Shipping Weight: 3267 lb Operating Weight: 3062 lb Unit Length: 89 in Unit Width: 93 in Unit Height: 79 in Accessories and Installed Options Cooler Heater Non-Fused Disconnect Low Sound Dual Pump, 7.5 HP Hot Gas Bypass Low Ambient Head Pressure Control 1 - Chiller Height Above Ground 2 - Horizontal Distance From Chiller to Receiver 3 - Receiver Height Above Ground BACnet Communications Single Point Chilled Water Storage Tank Wind Baffle Vibration Isolation Package Acoustic Information (Full Load) Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Total Sound pressure at specified distance in a free field, db 47 59 59 59 59 59 57 50 43 66 A-Weighted Sound Pressure Level, dba 8 32 43 50 56 59 58 51 42 63 Sound Power at Chiller Acoustic Center, db 75 87 87 87 87 87 85 79 71 95 A-Weighted Sound Power, dba 36 61 71 78 84 87 86 80 70 91 Notes 1 - Chiller Height Above Ground = 0.0 ft 2 - Horizontal Distance From Chiller to Receiver = 30.0 ft 3 - Receiver Height Above Ground = 3.0 ft Estimated Sound Power levels - db re: 1 picowatt Estimated Sound Pressure levels - db re: 20 micropascal Estimated sound levels given above are assumed to originate at the acoustic center of the chiller. Sound pressure level data used to develop this program was determined in accordance with AHRI Standard 575 for water chillers in a free field and ANSI/AHRI Standard 370 for air cooled chillers. Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. Packaged Chiller Builder NACO 3.48 Page 9 of 12
Detailed Performance Report Detailed Performance Summary For 30RAP060 35%PG Unit Information Tag Name: 30RAP060 35%PG Model Number: 30RAP060 Condenser Type: Air Cooled Compressor Type: Scroll Nameplate Voltage: 460-3-60 V-Ph-Hz Quantity: 1 Manufacturing Source: Charlotte, NC USA Refrigerant: R410A Capacity Control Steps: 5 Minimum Capacity: 16.1 % Shipping Weight: 3267 lb Operating Weight: 3062 lb Unit Length: 89 in Unit Width: 93 in Unit Height: 79 in Minimum Outdoor Operating Temp: -20 F Chiller Pressure Drop: 37.8 ft *Unit pressure drop listed includes losses due to chiller piping, fittings, 40 mesh factory supplied strainer and BPHX. Performance Information Cooling Capacity: 49.8 Tons Total Compressor Power: 57.9 kw Total Fan Motor Power: 5.31 kw Pump Power: 5.26 kw Total Unit Power (without pump): 63.2 kw Total Unit Power (with pump): 68.5 kw Efficiency (without pump): 9.46 EER Accessories and Installed Options Cooler Heater Non-Fused Disconnect Low Sound Dual Pump, 7.5 HP Hot Gas Bypass Low Ambient Head Pressure Control BACnet Communications Single Point Chilled Water Storage Tank Wind Baffle Vibration Isolation Package Electrical Information Unit Voltage: 460-3-60 V-Ph-Hz Connection Type: Single Point Electrical Electrical Amps Circuit 1 Circuit 2 MCA 134.6 MOCP 150.0 ICF 280.0 Rec Fuse Size 150.0 Acoustics Information A-Weighted Sound Power Level: 91 dba Evaporator Information Fluid Type: Propylene Glycol Brine Concentration: 35.0 % Fouling Factor: 0.00010 (hr-sqft-f)/btu Leaving Temperature: 40.0 F Entering Temperature: 52.2 F Fluid Flow: 104.0 gpm Condenser Information Altitude: 0 ft Number of Fans: 4 Total Condenser Fan Air Flow: 38800 CFM Entering Air Temperature: 95.0 F Packaged Chiller Builder NACO 3.48 Page 10 of 12
Detailed Performance Summary For 30RAP060 35%PG Integrated Pump Information Dynamic Head At Pump: 112.9 ft Dynamic Head External To Chiller: 75.1 ft Packaged Chiller Builder NACO 3.48 Page 11 of 12
Detailed Performance Summary For 30RAP060 35%PG Integrated Part Load Value (ARI) IPLV: 14.35 EER Unit Performance Percent of Full Load Capacity, % 100 75 50 25 Percent of Full Load Power, % 100.0 55.8 33.3 19.5 Unloading Sequence A A A A Cooling Capacity, Tons 55.9 41.9 28.0 14.0 Total Unit Power, kw 65.7 36.7 21.9 12.8 Efficiency, EER 10.21 13.72 15.35 13.11 Evaporator Data Fluid Entering Temperature, F 54.0 51.5 49.0 46.5 Fluid Leaving Temperature, F 44.0 44.0 44.0 44.0 Fluid Flow Rate, gpm 134.2 134.2 134.2 134.2 Fouling Factor, (hr-sqft-f)/btu 0.0001 0.0001 0.0001 0.0001 Condenser Data Entering Air Temperature, F 95.0 80.0 65.0 55.0 For some 75% operating points, the efficiency may be calculated at a condenser inlet air operating temperature as much as 0.8 degrees higher. All performance efficiency data are without pump. Note: Weights and electrical values do not include separately shipped accessories. An uncoated Novation condenser coil was selected for this product. This is based on an installed location with postal code 08854 and a non-corrosive localized environment. Evaporator contains a glycol or other secondary coolants for freeze protection with a leaving chilled fluid temperature above 32 F and is certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) when tested with water at Standard Rating Conditions. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Sound power measured in accordance with ANSI/AHRI 370-2001. NOTE: ETO must be submitted for hydronic packages having glycol concentration of 30% or higher. Packaged Chiller Builder NACO 3.48 Page 12 of 12
LEGEND EXV Electronic Expansion Valve MCHX Microchannel Heat Exchanger RTPF Round Tube, Plate Fin (Condenser Coil) *All units have Victaulic connections, sized for IPS Carbon Steel piping. Flow switch and strainer are standard on all units, with or without hydronic package. ENGLISH (cont) UNIT 30RAP 055 060 070 080 090 100 115 130 150 OPERATING WEIGHT (lb) MCHX Condenser Coil, No Pump 2369 2375 3410 3641 3697 4690 5008 6451 6938 MCHX Condenser Coil, Single Pump (60 Hz only) 2713 2719 3812 4035 4061 5089 5407 6850 7337 MCHX Condenser Coil, Dual Pump (60 Hz only) 3056 3062 4092 4390 4411 5374 5692 7135 7622 Al-Cu Condenser Coil, No Pump 3759 4064 4119 5548 5939 7113 7673 Al-Cu Condenser Coil, Single Pump (60 Hz only) 4161 4457 4483 5947 6338 7512 8072 Al-Cu Condenser Coil, Dual Pump (60 Hz only) 4441 4737 4763 6232 6623 7797 8357 Cu-Cu Condenser Coil, No Pump 4359 4784 4839 6388 6899 8193 8873 Cu-Cu Condenser Coil, Single Pump (60 Hz only) 4761 5177 5203 6787 7298 8592 9272 Cu-Cu Condenser Coil, Dual Pump (60 Hz only) 5041 5457 5483 7072 7583 8877 9557 REFRIGERANT TYPE R-410A, EXV Controlled System Total Refrigerant Charge MCHX (lb) 34.3 34.5 60.5 70.2 71.0 88.3 100.9 110.4 119.5 Refrigerant Charge MCHX (lb) Ckt A/Ckt B 16.9/17.4 17.1/17.4 25.5/35 35.1/35.1 35.5/35.5 39.3/49.0 50.6/50.3 51.2/59.2 60.0/59.5 Total Refrigerant Charge RTPF (lb) 150.0 169.2 170.0 192.0 213.0 239.2 264.0 Refrigerant Charge RTPF (lb) Ckt A/Ckt B 65.5/84.5 84.6/84.6 85.0/85.0 87.0/105.0 106.5/106.5 107.5/131.7 132.0/132.0 COMPRESSORS Scroll, Hermetic Quantity 4 4 5 6 6 5 6 6 6 Speed (Rpm) 3500 3500 3500 (60 Hz)/ 2900 (50Hz) (Qty, Tons) Ckt A (2) 13 (2) 15 (2) 15 (3) 13 (3) 15 (1) 20 (1) 25 (3) 20 (3) 20 (3) 25 (Qty, Tons) Ckt B (2) 15 (2) 15 (3) 15 (3) 15 (3) 15 (3) 20 (3) 20 (3) 25 (3) 25 Oil Charge (Pt) Ckt A/Ckt B 13.8/13.8 13.8/13.8 13.8/20.6 20.6/20.6 20.6/20.6 28.4/42.6 42.6/42.6 42.6/42.6 42.6/42.6 No. Capacity Steps Standard 4 4 5 6 6 5 6 6 6 With Hot Gas Bypass 5 5 6 7 7 6 7 7 7 Digital Compressor Option 44 44 55 66 66 Minimum Capacity Step (%) Standard 23 25 20 15 17 19 17 15 17 With Hot Gas Bypass 13 16 13 9 11 13 11 9 11 Digital Compressor Option 8 8 6 5 5 Capacity (%) Circuit A 46 50 40 46 50 43 50 44 50 Circuit B 54 50 60 54 50 57 50 56 50 COOLER Brazed, Direct-Expansion Plate Heat Exchanger Weight (lb) (empty) 160.4 160.4 197 228 245 267 304 334 378 Net Fluid Volume (gal) 5.0 5.0 4.3 5.0 6.8 7.4 8.6 9.5 10.9 Maximum Refrigerant Pressure (psig) 565 565 450 450 450 450 450 450 450 Maximum Water-Side Pressure Without Pump(s) (psig) 300 300 300 300 300 300 300 300 300 Maximum Water-Side Pressure With Pump(s) (psig) 150 150 150 150 150 150 150 150 150 CHILLER WATER CONNECTIONS (in.) Inlet and Outlet, Victaulic (IPS Carbon Steel)* 2 1 / 2 2 1 / 2 3 3 3 4 4 4 4 Drain (NPT) 1 / 2 1 / 2 1 / 2 1 / 2 1 / 2 1 / 2 1 / 2 1 / 2 1 / 2 CONDENSER FANS Standard Low-Sound AeroAcoustic Type Plastic Type, Axial, Vertical Discharge Fan Speed (Rpm) 850 850 850 (60 Hz)/710 (50 Hz) No. Blades...Diameter (in.) 9...30 9...30 9...30 9...30 9...30 9...30 9...30 9...30 9...30 No. Fans 4 4 5 6 6 7 8 9 10 Total Airflow (Cfm), 60 Hz 38,800 38,800 48,500 58,200 58,200 67,900 77,600 87,300 97,000 Total Airflow (Cfm), 50 Hz 40,512 48,614 48,614 56,716 64,819 72,921 81,024 Optional Value Sound Type Propeller Type, Axial, Vertical Discharge Fan Speed (Rpm) 1140 1140 1140 (60 Hz)/950 (50 Hz) No. Blades...Diameter (in.) 4...30 4...30 4...30 4...30 4...30 4...30 4...30 4...30 4...30 No. Fans 4 4 5 6 6 7 8 9 10 Total Airflow (Cfm), 60 Hz 41,800 41,800 51,250 61,500 61,500 71,750 82,000 92,250 102,500 Total Airflow (Cfm), 50 Hz 42,809 51,371 51,371 59,932 68,494 77,056 85,618 CONDENSER COILS Novation MCHX Aluminum Tube, Aluminum Fin Novation MCHX Aluminum Tube, Aluminum Fin or RTPF Quantity (Ckt A/Ckt B) 1/1 1/1 2/3 3/3 3/3 3/4 4/4 4/5 5/5 Total Face Area (sq ft) 66 66 124.7 149.6 149.6 174.5 199.4 224.4 249.3 Maximum Refrigerant Pressure (psig) 656 656 656 656 656 656 656 656 656 HYDRONIC MODULE (Optional, 60 Hz Only) Pump(s), Strainer with Blowdown Valve, Expansion Tank, Pressure Taps, Drain and Vent Plugs, Flow Switch, and Balance Valve Pump Single or Dual, Centrifugal Monocell Pump(s), 3500 Rpm. Dual pumps with check valves and isolation valves. Expansion Tank Volume (gal) Total/Acceptance 10.3/10.3 CHASSIS DIMENSIONS (ft - in.) Length 7-5 7-5 12-7 12-7 12-7 15-11 15-11 19-4 19-4 Width 7-9 7-9 7-4 7-4 7-4 7-4 7-4 7-4 7-4 Height 6-6 6-6 6-6 6-6 6-6 6-6 6-6 6-6 6-6 7
30RAP UNITS WITHOUT HYDRONIC PACKAGE (SIZE 060 SHOWN) FIELD POWER SUPPLY TO EXPANSION TANK VIBRATION ELIMINATOR GATE VALVE VALVE PRESSURE GAGE FLOW SHUT OFF VALVES PUMP GATE VALVE VIBRATION ELIMINATOR FLOW LEGEND Airflow Through Condenser HEAT TAPE INSULATION IS RECOMMENDED ON ALL EXPOSED PIPING IF AMBIENT TEMPERATURE <32 F (0 C) AND NO ANTIFREEZE SOLUTION IS IN SYSTEM NOTES: 1. Chiller must be installed level to within 1 / 8 in. per foot (10.4 mm per meter) to maintain proper compressor oil return and hydraulics. 2. Wiring and piping shown are general points-of-connection guides only and are not intended for a specific installation. Wiring and piping shown are for a quick overview of system and are not in accordance with recognized standards. 3. All wiring must comply with applicable local and national codes. 4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or appropriate ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers) handbook for details. Power Wiring Chilled Water Piping a30-4869 30RAP UNITS WITH HYDRONIC PACKAGE (SIZE 060 SHOWN) FIELD POWER SUPPLY VIBRATION ELIMINATOR FLOW GATE VALVE LEGEND Airflow Through Condenser VIBRATION ELIMINATOR Power Wiring NOTE 5 HEAT TAPE INSULATION IS RECOMMENDED ON ALL EXPOSED PIPING IF AMBIENT TEMPERATURE <32 F (0 C) AND NO ANTIFREEZE SOLUTION IS IN SYSTEM Chilled Water Piping NOTES: 1. Chiller must be installed level to within 1 / 8 in. per foot (10.4 mm per meter) to maintain proper compressor oil return and hydraulics. 2. Wiring and piping shown are general points-of-connection guides only and are not intended for a specific installation. Wiring and piping shown are for a quick overview of system and are not in accordance with recognized standards. 3. All wiring must comply with applicable local and national codes. 4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or appropriate ASHRAE (American Society of Heating, a30-4870 Refrigerating, and Air-Conditioning Engineers) handbook for details. 5. Air separator required as close to chiller as possible (except primary/secondary systems). 57
TYPICAL PIPING DIAGRAM ON 30RAP UNITS WITH HYDRONIC PACKAGE 14 2 7 12 11 3 5 6 13 1 4 12 11 9 8 6 10 LEGEND 1 Strainer (40 Mesh)/Blow-Down Valve 2 Expansion Tank (sizes 010-060 only) 3 Pump 4 Electric Heater 5 Air Vent Connection Port 6 Pressure/Temperature Access Port 7 Heat Exchanger 8 Flow Switch 9 Balance Valve/Drain Plug 10 Pressure Relief 11 Isolation Valves 12 Flex Connections 13 Pressure Reducing/Fill Valve 14 Air Separator and Vent --- Factory Supplied a30-4871 NOTE: Hydronic packages are not available for 50 HZ applications. 59