Owners Manual Refrigerated Air Dryer MHT SERIES

Similar documents
Owners Manual UA75 TO UA1200 SERIES Refrigerated Air Dryer

DRYMAX DRYMAX DRYMAX DRYMAX

Owner s Manual Refrigerated Compressed Air Dryers Model F-100

Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350

Owner s Manual Refrigerated Compressed Air Dryers Models F-3528, F-3529, F-3530, F-3531 & F-3532

Owner s Manual Refrigerated Compressed Air Dryer Model F-50

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

NEWGATE TECHNOLOGIES, INC.

UA Series Air Dryers. 10 Year Warranty Limited ( SCFM) Setting a new standard in Quality and Reliability WAS 360

UA Series Air Dryers. 10 Year Warranty Limited ( SCFM) Setting a new standard in Quality and Reliability WAS 360

GRF-SERIES REFRIGERATION TYPE NON CYCLING STANDARD

HX Series. Compressed Air Dryers 10 to 2400 scfm. Setting a new standard in Quality and Reliability DRYMAX DRYMAX DRYMAX

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual

Refrigerated Air Dryers VF Series. DHT Series. Non-Cycling 10-2,000 scfm scfm

Refrigerated Air Dryers

Rev. A AUGUST 2012 RNP SERIES REFRIGERATED COMPRESSED AIR DRYERS OPERATOR MANUAL RNP25 RNP35 RNP50

GTX Series Thermal Xchange Cycling Refrigeration Dryers GREAT LAKES AIR ANDARD ELECTRONIC DRAIN 5 -YEAR WARRANTY F PRESSURE DEWPOINT

REFRIGERATED AIR DRYERS

Noncycling Refrigerated Air Dryers Range AD 10 to AD 4000

600-10,000 scfm AES Series. AES Series Energy Saving. Refrigerated Air Dryer ,000 scfm. Front Page

WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS

HIGH INLET TEMPERATURE REFRIGERATED AIR DRYERS. GHRN Series

THERMAL MASS CYCLING REFRIGERATED AIR DRYERS. GTRC Series

RNP SERIES 33 F 39 F 1 C 4 C OFF OPERATOR MANUAL

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

PROdry. High Inlet. Temperature. refrigerated. compressed air. dryers. Contents. For Sales & Service please contact:

NON-CYCLING REFRIGERATED AIR DRYERS. GSRN Series

T-Series Air Conditioner T53 Model

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

MR Series Heatless Mini Regenerative Desiccant Dryer. Operator s Manual

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS

GRF Series Non-Cycling Refrigeration Dryers ANDARD ELECTRONIC DRAIN STANDARD ELEC SS EXPANSION VALVE F PRESSURE DEWPOINT

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

OWNER/OPERATOR MANUAL COMPONENTS, INSTALLATION, OPERATION AND SERVICE INSTRUCTIONS

T-Series Air Conditioner T15 Model

Installation and Operation Guide For

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

DX SERIES DIRECT EXPANSION ENERGY SAVING AIR DRYER

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

CHILLER. Operator s & Installation Manual

REFRIGERATED DRYER USER MANUAL

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions

Energy saving refrigeration dryers SCFM. Purifying your compressed air, increasing your efficiency.

CHEF BASE CABINETS Installation, Operation and Maintenance Instructions

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-Series Air Conditioner T20 Model

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

Instruction Manual. Refrigerated Air Dryer

Above & Beyond. Refrigerated Compressed Air Dryers

MODULAR HIGH CAPACITY REFRIGERATED AIR DRYERS. GMRN & GMRC Series

RNC Series SCFM Global Air Treatment

Otherwise, you can continue reading the file on the following pages.

RNC Series SCFM Global Air Treatment

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

CHEF BASE CABINETS Installation, Operation and Maintenance Instructions

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap. Operation & Maintenance Manual MDX MODELS 18 THRU 250

Full Range Systems. Mokon Troubleshooting Guide Model 311. Process/Water Loop. Problem Possible Cause Corrective Measure. Process pump will not start

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet

CHC Series High Capacity Refrigerated Dryer 2,000 20,000 SCFM

REFRIGERATED AIR DRYERS

ThermoStar Refrigeration Air Dryers

SCFM REFRIGERATED COMPRESSED AIR DRYERS. CRN Series

NON-CYCLING REFRIGERATED AIR DRYERS. RNC Series

next generation R 1 cycling refrigerated compressed air dryers flow capacity: scfm ( Nm 3 /hr)

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

VSA Series Air Dryer. User s Guide

Refrigerated Air Dryers

BOTTOM MOUNT REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain. Operation & Maintenance Manual MODELS MDX

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

MANUFACTURED with high-quality components and innovative techniques. DESIGNED for economical, trouble-free performance and long-life reliability

Rev. None AUGUST 2012 MDM SERIES MODULAR MEMBRANE AIR DRYERS OPERATOR MANUAL MDM1 MDM4 MDM9 MDM13 MDM24 MDM49 MDM66 MDM106 MDM138

CNC Series Refrigerated Air Dryer CFM

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

High-Capacity Cycling Refrigerated Compressed Air Dryer. RTM Series

BOTTOM MOUNT REFRIGERATORS & FREEZERS Installation, Operation and Maintenance Instructions

Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

Installation and Operation Guide For MCF-49FD, MCF-23FD MCR-49FD, MCR-23FD

HEATLESS REGENERATIVE DRYERS

Compressed Air System Products That Save Energy & Improve Operations. Dry, Clean Air for Sensitive Equipment. Refrigerated Air Dryers

ACT REFRIGERATING AIR DRYER USER S MAINTENANCE AND SPARE PARTS MANUAL. Air - Water Cooled CANADA 7425MUM182_EN_

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

A Division of Numatics. 201 Series Refrigerated Air Dryer. Models UA through UA Installation, Operating, & Maintenance Manual

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

TABLE OF CONTENTS FOR YOUR SAFETY

Operation regulations must be strictly obeyed.

Installation Manual BCS2000/3000

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Heated Desiccant Air Dryer

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner ADVANTAGE RP55 SERIES

Transcription:

Owners Manual Refrigerated Air Dryer MHT SERIES IMPORTANT: READ THIS MANUAL CAREFULLY. IT CONTAINS IN- FORMATION ABOUT SAFETY AND THE SAFETY OF OTHERS. ALSO BECOME FAMILAR WITH THE PROPER INSTALLATION AND CON- TROLS OF THE AIR DRYER BEFORE OPERATING. ONLY QUALIFIED, TRAINED AND LISCENSED PERSONAL SHOULD SERVICE OR OPER- ATE THIS EQUIPMENT. CAUTION:THIS MACHINE CONTAINS HIGH PRESSURE GAS AND ELECTRICITY.

2 TABLE OF CONTENTS INTRODUCTION, RECEIVING, DATA LABEL 3 HOW THE AIR DRYER WORKS 4 DESCRIPTION OF COMPONENTS 5 INSTALLATION 6 DRYER CONTROLS, START UP, INITIAL RUN PROCEDURE 7 WEEKLY MAINTENANCE, SETTING DRAIN TIMER 8 ADJUSTING SUCTION PRESSURE/EVAP TEMP 9 TROUBLESHOOTING & ELECTRICAL SCHEMATICS 10 TECHNICAL DATA 11 NOTE: If you need service on your dryer please have the following information: 1. Model # 2. Serial # 3. Voltage 4. Nature of the problem 5. Name of distributor that dryer was purchased from 2

3 INTRODUCTION Thank you for selecting an MHT Series refrigerated air dryer from MACAIR INC. The refrigerated air dryer is specifically designed and manufactured for drying and purifying compressed air generated by an air compressor. PLEASE READ THIS INSTRUCTION MANUAL CAREFULLY BEFORE USING THE DRYER. Please pay attention to the precautions in transportation, installation and operation that are listed in this manual. Please use the dryer according to our application guide and be sure to perform the proper preventative maintenance recommended in this manual. Failure to perform the preventative maintenance will void the air dryer warranty. Refrigeration used in this air dryer is environmentally friendly R134a and is available at local refrigeration wholesalers. Direct any question not covered in this manual to your distributor or call MACAIR at (248) 624-6300. Before calling with any questions always have the air dryer model #, serial # and pressure gauge readings. Service and maintenance can be obtained from your distributor. If you do not know your distributor please contact the factory. Authorization # must be obtained from MACAIR INC. before any parts or dryers are returned to the factory. MACAIR INC. will not be responsible for anything returned without authorization. RECEIVING AND INSPECTION 1. The dryer cannot be tilted on its side or upside down during shipping. 2. Use forklift from the bottom of the dryer when installing and moving. 3. Dryers are shipped F.O.B. factory. Immediately upon arrival check the dryer for possible damage. If damage is found, report it to the carrier and file a damage claim. 4. Check dryer data label to be sure you have the right dryer. Check the data labels voltage and amperage to be sure it is correct and the one you ordered. 5. Check refrigeration gauges for pressure. If gauges read 0 PSIG STOP! Do not start dryer. Call your distributor for service. This could mean there is a leak and refrigerant has leaked out. DATA LABEL The data label is affixed to the outside of the cabinet. This label identifies the air dryer s model and serial numbers and important technical data. Before installing the dryer check all of the information on the data label for the correct model and voltage. If the model number and voltage are incorrect do not install the dryer. Do not put power to the dryer. Call your local distributor. 3

4 HOW THE AIR DRYER WORKS MHT Series refrigerated compressed air dryers use refrigeration cooling to condense entrained moisture out of the compressed air stream. Warm saturated air enters the air-to-air heat exchanger at the dryer inlet. In the air-to-air heat exchanger the inlet air is pre-cooled by the outgoing cold air. The pre-cooled air then enters the air-to-refrigerant heat exchanger where it is cooled to its lowest point by the refrigeration in the evaporator. As the air is cooled, moisture in the air changes from a vapor to a liquid. The liquid condensate is removed from the airstream by the separator and discharged from the dryer by the automatic drain valve. The cold air is reheated by incoming warm air as it passes back through the air-to-air heat exchanger. Pre-cooling the inlet air reduces the heat load on the refrigerant compressor, permitting the use of a smaller refrigerant compressor. The outgoing cold air is reheated by the incoming hot air. As a result the outlet air is warmed up as it leaves the dryer. This prevents the outlet pipe from sweating. The air exits the dryer and is now clean and dry, ready for use. 4

5 DESCRIPTION OF COMPONENTS (1) ADX HEAT EXCHANGER MODULE- (Aluminum, Direct Expansion) The compact aluminum module contains the air-to-air heat exchanger, the air-to-refrigerant heat exchanger and the moisture separator. (2) REFRIGERANT COMPRESSOR The main function of the compressor is to circulate the refrigerant. The compressor pumps refrigerant to the other components in the system so they can perform heat transfer functions. The compressor also separates the high pressure from the low pressure side of the refrigeration system. (3) CONDENSER Condenses the vapor into a liquid. (4) FILTER-DRIER Absorbs and filters out any moisture or debris that maybe in the refrigeration system. Moisture can cause freeze-ups and dirt particles can plug capillary tubes causing system malfunctions. (5) CAPILLARY TUBE The metering device meters liquid refrigerant from the liquid line to the evaporator. The capillary tube is a restriction that separates the high pressure side from the low pressure side in the refrigeration system. (6)LP1 - LOW PRESSURE SAFETY CUT OUT Prevents damage to the refrigerant compressor in the event of a refrigerant leak or low refrigerant pressure. (7) HOT GAS BYPASS VALVE HGBV respond to changes in suction pressure. As the air flow (or heat load) on the dryer changes the suction pressure will change. An increase in air flow causes an increase an increase in suction pressure. A decrease in air flow causes a decrease in suction pressure. During periods of low air flow the HGBV meters hot gas from the hot gas line of the high side to the inlet of the air-torefrigerant. (9) PS1 - HIGH PRESSURE SAFETY SHUTDOWN- Prevents damage to the refrigerant compressor and other components in the event of high refrigerant pressure due to fan motor failure, dirty condenser or over-capacity. (10) PS2 - FAN CYCLING SWITCH Cycles the condenser fan motor on and off to maintain the proper condensing pressure dryer period of fluctuating loads and ambient conditions. (12) REFRIGERATION SUCTION PRESSURE GAUGE Continuously monitors the refrigerant suction or low side pressure. Is used as a troubleshooting device. Should Read: On R134a dryers. (28 psig to 34 psig) (13) Y STRAINER (15) CONDENSATE DRAIN (16) CONDENSER FAN MOTORS Drives ambient air over condenser coils. 5

6 INSTALLATION AND LOCATION CONTINUED VENTILATION Install dryer only in a well-ventilated, clean, dry area and keep at least 3 feet between the dryer, other equipment and the walls. DRYER LOCATION Make sure there is approximately 3 feet around the dryer for service and maintenance purposes. Do not install the dryer outside. The air dryer must not be exposed to direct sunlight, rain or snow. Do not install the dryer in an environment with fire, high temperature or low temperatures. Make sure the dryer is installed in an environment that is clean and dry. Dust and dirt particles will clog the air-cooled condenser. A clogged and dirty condenser will reduce the performance of the dryer and will eventually cause damage to it. AMBIENT TEMPERATURES Suitable ambient temperature for the refrigerant dryer is a MIN of 40 F to a Max of 110 F. The performance of the dryer will be significantly decreased when the air dryer is subject to temperatures higher than 110 F. For installations with ambient temperatures higher than 110 F it is recommended to use a water-cooled condenser on the dryer. Contact your distributor for details. SELECTING PROPER IN AND OUT PIPING AND PIPING DESIGN Pipe diameter should be sized according to air flow requirements. Do not mix the air inlet and outlet air flow. It is recommended that a vibration absorber be installed on the dryer inlet and outlet to eliminate vibration from the compressor. Do not use the inlet and outlet of the air dryer to support the weight of the air piping. 3 VALVE BYPASS AND ISOLATION VALVES Should be installed on the air dryer outlet and inlet ports to allow for bypassing, depressurizing and proper maintenance and servicing of the air dryer. CONDENSATE DRAINS Condensate drains must be properly piped from the dryer to prevent moisture re-entrainment. The dryer is equipped with an automatic drain valve that controls the discharge of the condensate and a manual valve to manually drain condensate. The user must run a drain line to an environmentally approved condensate collection/disposal system. 6

7 ELECTRICAL INSTALLATION The dryer data label lists the electrical power requirements for the air dryer. The user must confirm that the line voltage matches the voltage listed on the data label. (Warning Operating the air dryer with improper line voltage will void the warranty.) Provide the proper size wire, disconnect switches and fuses in accordance with applicable codes. Field wiring must comply with local and national fire safety and electrical codes. Standard dryer s enclosures and controls are designed to meet NEMA 1 Type 1 electrical standards. All wiring is complete. Connect power leads as indicated in the electrical schematic. Ground the frame properly. Once power is connected turn the power on to the dryer. MAXIMUM WORKING PRESSURE - 232 psig. CAUTION: BREATHING AIR APPLICATIONS This dryer has not been tested for breathing air applications. The owner is advised to do its own testing and use for breathing air applications at own risk. DRYER CONTROLS 1. On/Off switch Turns the refrigerant compressor on/off. 2. Power On Light Indicates there is power to the dryer. 3. Digital Dew-Point Temp. Indicator indicates the approximate dew point temp of the compressed air. 4. Refrigerant Suction Pressure Gauge 5. Hot Gas Bypass Valve Controls the evaporator pressure 6. Fan Cycling Switch Cycles the condenser fan on and off based on the condensing pressure. (See Figure 1) 7. High Pressure Shutdown w/manual reset Cut Out 300 PSIG 8. Low Pressure Shutdown Cut Out 10 psig / Cut In 25 psig 9. Programmable Electronic Auto-Drain Valve Automatically controls the draining of liquid condensate removed by the dryer. START UP The following procedure must be followed to start your air dryer. Failure to follow this start up procedure will void your warranty. If problems occur during start up, contact your distributor. 1. Turn off the On/Off switch. 2. Verify the main electrical supply voltage matches the voltage specified on the data label. 3. Do not turn the dryer on during this warm up period. 4. Check the proper connection and support of the compressed air lines to the dryer. 5. Check dryer bypass and isolation valve system. 6. Confirm that the inlet and ambient air temperature, pressure and flow to the dryer meet specified requirements. 7. Confirm that the condensate drain lines from the separator are properly piped to an environmentally approved disposal system. INITIAL RUN PROCEDURE After start up and checks are complete and after the main electrical power to the dryer has been turned on 1. Turn ON the dryer On/Off switch. 2. After 15 seconds observe the refrigerant suction pressure gauge. It should start to pull down immediately. 3. Let the dryer run for 15 minutes. 4. Check the refrigerant suction pressure gauge Should Read: On R134a dryers ( 28 psig to 34 psig) 6. Check the DEWPOINT TEMP INDICATOR. After about 15 min it should read 35 F to 39 F. 7. Verify that the condenser fan motor is operating. The fan will cycle on and off. 8. Allow compressed air to flow through the dryer. 9. Confirm that condensate is discharging from the condensate drain. This may take 30-60 min. 10. Make sure bypass valves are closed and 100% of the air from the compressor is flowing through the dryer. 7

8 WEELKY MAINTENANCE Clean air cooled condenser coils Blow off all dust and dirt that is on the condenser fins with a compressed air maintenance gun. While cleaning condenser fins take caution to no damage the fins. WARNING: DRYER FAILURE DUE TO A DIRTY CONDENSER IS NOT COVORED UNDER WARRANTY HOW TO SET THE CONDENSATE DRAIN OPEN & CLOSED TIME (LOCATE DRAIN VALVE) 1. The OPEN (ON) time is adjustable from 0.5 sec to 10 sec. Drains are set at factory to open for 6 sec. When drain opens the on light will light. 2. The CLOSED (OFF) time is adjustable 0.5 min to 45 min. Drains are set at factory to stay closed for 10 min. When drain is closd the off light will light. You may increase or decrease this based on moisture levels in the air. Push the TEST button to manually open the drain valve. 8

9 HOW TO MAKE MINOR REFRIGERANT SUCTION PRESSURE (EVAP TEMP) ADJUSTMENTS 1. Keep dryer running under a no load by turning off or bypassing the compressed air. 2. Remove dryer top and locate the Hot Gas Bypass Valve. 3. Remove cap on Hot Gas Bypass Valve and using an allen wrench turn valve counter clockwise to decrease the suction pressure and clockwise to increase the suction pressure. Make 1/2 turn adjustments and wait 2 to 3 minutes for suction pressure to stabilize. Make more adjustments if needed. MHT130 MHT75 & MHT100 MHT25 & MHT40 9

TROUBLE SHOOTING GUIDE 10 PROBLEM CAUSE SOLUTION Evaporator temp is to low Hot gas bypass valve needs adjusting Evaporator pressure gauge bad Capillary tube blocked Temp or Pressure reset set to low Refrigerant leak Adjust or replace Replace Replace Reset Find leak, fix and add refrigerant Ambient temp is to high Hot gas valve needs adjusting Evaporator temp is to high Condenser blocked or plugged Flow is to high going in dryer Compressor valves are damaged ELECTRICAL SCHEMATICS MHT25 Improve ventilation in area Adjust or replace Clean condenser Change air compressor Replace compressor MHT40-MHT130 10

11 TECHNICAL DATA TECHNICAL SPECIFICATIONS DRYER MODEL MHT40 MHT60 MHT100 MHT130 RATED CAPACITY IN SCFM 25 75 100 125 200 PRESSURE DROP (PSID) 1.2 1.4 1.6 1.75 1.8 MIN/MAX INLET PRESSURE MAX INLET TEMP MIN/MAX AMBIENT TEMP 20 PSIG / 230 PSIG 120F 45 F / 110 F VOLTAGE 115-1-60 230-1-60 VOLTAGE RANGE 126-103 253-187 REF COMPRESSOR HP 1/3 1/3 1/2 3/4 1 RLA: RUN LOAD AMPS 5.82 5.82 9.5 13.7 7 LRA: LOCK ROTOR AMPS 32 32 48 69 41 MAX FUSE SIZE 20 20 20 30 15 MIN. CIRCUIT CAPACITY 11.54 11.54 12.4 18.5 9.9 REFRIGERANT TYPE REFRIGERANTE AMOUNT REFRIG. SUCTION PRESSURE MHT25 R134a SEE DATA LABEL 28 PSIG SHIPPING WGT (LBS) 115 180 195 205 250 11

12 MACAIR INC. 4123 PIONEER DRIVE WALLED LAKE, MI 48390 www.macair1.com MAY 2015 12