MT-374B/364B Operation User s Guide. The Anti-Sweat Energy Saving Controller user s manual

Similar documents
Anti-sweat Energy Saver Installation guide

Refrigerant Leak Detector Manual

Ammonia Leak Detector Manual

OVEN INDUSTRIES, INC.

Rev Pulse Modulating Anti- Sweat Control (PMAC II) Installation and Operation Manual

Ethernet General Purpose

Installation Guide. Bacharach HGM300 to LonWorks FT-10 Communications Adapter

OPTIONAL CONTROLLER. Kit P/N _A. December 2016 ANTI-CONDENSATE HEATER FOR REACH-IN GLASS DOORS. Spanish French

General Purpose IO Technical Manual

ECO N DATE DESCRIPTION OF CHANGE CHG

Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions

Carbon Monoxide Transmitter

SAPCON SMART-SSI. Continuous Speed Indicator. Users Manual. . Introduction. . General Description. . Principle of Operation. .

Refrigeration and Air Conditioning Controls. User s manual. Degree Master Controller in AKC 55 Systems ADAP-KOOL REFRIGERATION AND AIR CONDITIONING

Rev Pulse Modulating and Anti- Sweat Control (PMAC II Solo) Installation and Operation Manual

21-light Remote Annunciator. Owner s Manual

SmarTemp Control fx 2.0

ATS Annunciator - MODBUS

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg.

Dryer Controller M720

Rev 7 06-APR MultiFlex Condensing Unit Board (CUB-II and CUB-TD) Installation and Operation Manual

SACE PR021/K SIGNALLING UNIT

ELECTRONIC COMMUNICATING THERMOSTAT

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

CU-IQ MANUAL 1. DESCRIPTION Radio Control Panel CU-IQ

RF SCOUT PLUS INSTRUCTION MANUAL. Dielectric, LLC 22 Tower Rd. Raymond, ME Phone: January 2015, Rev B 1

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

Analog Input Module IC670ALG630

Networkable Fan Coil Controller Specification and Installation Instructions

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

Model 17A00 Expansion Enclosure

Application Guide. CCU2 Chiller Controller. Self-Contained Interoperable Controller Model UCP-1 for Software Version 2.

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free

SyringeHeater.com. Syringe Heater. Thermo-Kinetic Heat Clamping. Model: HEATER-KIT-1LG HEATER-KIT-5SP

Added password for IP setup page : Password must be in IP format!

RS485 MODBUS Module 8AI

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Introduction. OM-THA2

Element. Controller. Manual for use and maintenance. Element. Climate Controller. Ag/MIS/UMGB /17 Rev 1.0 P/N:

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

EVO192 v3.0 Fire and Burglary What s New

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

Pump Logic User Manual CB-1000 P/N ILK-CB1000-1

RC802/ B 8E1 Modular Fiber-Optic Multiplexer (Rev. M) User Manual

User Manual. Dryer Controller M720

STATUS ALARM HISTORY ALARM RESET

MODEL MARINE WIND TRACKER

DCA4. Digitally controlled Audio Matrix. Current Thinking. Product Specification March Document Number DDC DCA ACS

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

EC Series Wall Unit Humidifier

Ambient Temperature/ Relative Humidity & Dew Point Temperature Sensors to USB Output. Model LFS108B

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

The Kryos LN2 Liquid Level Control & Cryogenic Temperature Control

Operation and Maintenance Manual OM 897-3

METEOROLOGICAL INSTRUMENTS

C-Bus Four Channel Analogue Output Unit Installation Instructions

METEOROLOGICAL INSTRUMENTS

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

Greentrol Automation, Inc.

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

Dry Contact Probe DCP (#30008)

METEOROLOGICAL INSTRUMENTS

OEM REFRIGERANT GAS SENSORS for Leak Detection & Measurement

RC-2000 Thermostat Installation Instructions

EXPERT TRI-STAR. Temperature controller. User s Manual

DESCRIPTION NOTE. Temperature and Humidity Sensors MODEL 1260B

GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions

Sierra Model 951 Digital Flo-Box. Instruction Manual Part Number IM-951 Revision A 09-05

Instruction Manual SCD24. Read this document prior to installation. Contents

WM3000 WIRELESS MODULES

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

MT Alliance Refrigeration Technician s Manual

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

LUMA-NET 804CP / 808CP REMOTE CONTROL PANEL

FW-SIREN2EXT -8/9F FW-SIREN2CP -8/9F

Preliminary Release. Room Temperature

NO ONE DARES COME CLOSE O WNER S GUIDE 7756V

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions

DIGITAL LIGHT CONTROLLER

RCS Residential Control Systems Inc.

HAI Omni-Bus Network Installation. 5. Typical Application

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

Model TZ43. ZWave Thermostat INSTALLATION AND OPERATION MANUAL DCN: /22/08 *** IMPORTANT NOTICE ***

Series Digital Controller Instruction Sheet

MODEL WIND TRACKER

GPS Evaluation Kit EVA1037/1080

BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES. READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION.

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

FCD-wire Contents. List of Figures

Humidity Controller Specification and Installation Instructions. Model HRO20

INSTALLATION INSTRUCTIONS

CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

Transcription:

MT-374B/364B Operation User s Guide Parker Hannifin Canada Micro Thermo Technologies TM 12855 Brault Street Mirabel, QC J7J 0C4 Office phone 450-668-3033 Introduction The Anti-Sweat Energy Saving Controller user s manual The Anti-sweat Energy Saver model MT-374B is an MT-Alliance compatible controller that modulates the power delivered to a maximum of 4 anti-sweat heaters channels pulsed sequentially according to the dew point in the supermarket where the controller is installed. Temperature and humidity measurement are used to calculate how much heating it is required to avoid condensing on glass doors. The processor board work without user interface when networked with an MT-Alliance computer but the Anti-sweat Energy Saver can work as standalone with the Local User Interface MT-364B ordered separately. The Anti-sweat Energy Saving processor board can also host the old version of User Interface MT-3610. 75-PHW-1012 R2.1 MT Anti-Sweat Standalone User Manual.docx RL 2016-09-27 Page 1 of 7

Boards presentation: The processor board. The processor board powered from an external 24 Vac 40 VA transformer is an autonome controller with alarm and fail safe features that can drive up to 4 SSR channels with MOSFET. It can be configured through a LonWorks FTT-10A network or with the local user interface board. Any required settings are saved in its non volatile memory and the firmware can be updated remotely via the network. It host a LED display that show the % of energy saved. A B A B MT-374B LED1 : Network Activity pilot FTT-10A Network Connection Two pairs of pins connections for daisy chaining Heater driver output Short Circuit indicator (D24 D27) 4 Outputs: 24Vdc pulsed 100mA Maximum Limited HTR1 HTR2 HTR3 HTR4 Temperature sensor input (10k thermistor type 2) + Humidity Sensor input (0-5V) 0 Vdc Output (Sensor common) 24 Vdc Output for sensor power MANUAL BYPASS RESET Power POWER SERVICE WINK BYPASS LED LED STATUS CLEAR ALARM HEAT PULSE ALARM STATUS % SAVING F/ C Saving Out (0-5Vdc) + Alarm Out (N/O dry contact) Earth Gnd 24 Vac L2 24 Vac L1 2AG 2A Fuse Component description: %Saving: This display the percentage of energy saved compare to having the heater ON 100% of the time. A 0-5Vdc output signal is provided to monitor savings. Reset Button: When reseted the 374B controller will not drive the heaters for 60 seconds Power LED: Remain ON as long as the board is powered with 24VAC. Service Button: Use this button to pair the 374B controller with the MT Alliance PC. Manual Bypass: Flip this switch to disable the power savings. The heaters will heat at 100%. This bypass is for emergency usage. Don t leave it like this forever. 75-PHW-1012 R2.1 MT Anti-Sweat Standalone User Manual.docx RL 2016-09-27 Page 2 of 7

Alarm Status: This LED latches if one sensor is missing for longer than Dew Point Set Time or when dew point is higher than Dew Point High Limit for longer than Dew Point Set Time. The output power will be forced to 100% and will display FP for Full Power, %Saving will be 0, there will be no alarm sound but the normally open dry contact will remain close as long as the Alarm status is ON. If thereafter the dew point becomes lower than the limit, the Alarm Status LED will remain ON but the output power for heating will not be forced to full any more. Clear Alarm Button: Use this button to reset the alarm status. Alarm will be repeated after Dew Point Set Time if the Dew Point is still too high or if sensor still not fixed. F/ C Unit selector: Put jumper on the C side to have temperature and dew point display in Celsius. No jumper or jumper on the left side will display temperature and dew point in F. This jumper has no effect when the Anti-sweat Energy Saving Controller is in non-standalone mode nor to the LonMark Object temperature/dew point reading unit shown at the PC. LED1: near the network connector indicate the activity on the FTT-10A network. When a message is transmitted from the node (TX), this LED will flash in green. When a message is receive from the network (RX), this LED will flash in red. When messages are receive and transmit at the same time, this LED will flash yellow. This feature is useful to diagnostic communication to the network and if the service pin activate the transmission of the neuron ID message for the installation process. LED D24 to D27 near the Heater Driver connector light if the channel is overloaded. There are 4 outputs to connect to the external SSR. A 100 ma auto resettable fuse protects each one. If current is over 100 ma for this output the polyfuse will open and the LED will blink. It may have too many SSR connected in parallel to this channel. If the over current condition disappear the system return to normal operating mode without any required action. When an over current condition exists on a channel it will not affect the normal operation of the others. The HEAT PULSE LED show the duty cycle of the driving pulse delivered to the 4 Heater Driver outputs. Wink LED is ON for 1 sec and OFF for 4 sec when the program is running normally. When a wink command is received from the Alliance, the duty cycle change to 4 sec ON and 1 sec OFF. The board must be reset to end the wink command. 75-PHW-1012 R2.1 MT Anti-Sweat Standalone User Manual.docx RL 2016-09-27 Page 3 of 7

Physical Installation: The Anti-sweat Energy Saving board comes on a snaptrack. Remove the board from the snaptrack and secure the snaptrack on a solid surface inside of an electric panel using screws. Put back the Anti-sweat Energy Saving board by clipping it on the snaptrack. Make all wiring connection accordingly to the diagram connection on page 1 or on a drawing provided from Parker Hannifin Engineering advisor. Use a Micro Thermo Temperature and Humidity combo sensor p/n 023-0026. A connection to earth ground must be made for proper 24VAC power filtering, and provide EMC and ESD protection for the FTT-10A transceiver. MT-Alliance Installation: The MT-374B can be installed on MTA 7.2.3 or later but it is possible to install it on version 6.0 with a patch supplied by MTT technical support. See Anti-sweat MTA installation Guide PUID 72-MTA-1037 for MT Alliance installation and configuration. 75-PHW-1012 R2.1 MT Anti-Sweat Standalone User Manual.docx RL 2016-09-27 Page 4 of 7

The Local User Interface With this piggyback board the user can view and enter all the configuration parameters that set the workable values on site via 4 momentary rocker switches. The user may read Ambient Temperature, % Relative Humidity, Dew Point and % Power values on four 2 digits 7 segments LED displays. MT-364B AMBIENT AMBIENT %RH DEW POINT % POWER TEMPERATURE SELECT SELECT TEMP %RH SW1 DEW1 CAL. SW4 CAL. DEW2 UP HIGH LIMIT PWR1 PWR2 DOW SW2 SW3 SET TIME SET DEW POINT ALARM Configuration of the Anti-sweat Energy Saver with the Local User Interface. There are four rocker switches on the Local User Interface Board: SW1: to select the temperature or humidity parameter for calibration. SW2: to increment or decrement the value of the selected parameter. SW3: to select the High Limit or Set Time of Dew Point Alarm SW4: to select the transfer function parameters of the control. In normal position, the Local User Interface Board is in Monitor Mode. In this mode the displays show the temperature and humidity read by the respective sensors, (local or via a remote SNVT), the dew point calculated from the current temperature and humidity, and the % power delivered to the antisweat heaters according to the transfer function control parameters. The standalone mode is factory set to 1 to enable setup changes via the local user interface. Once installed in Alliance V6+ this mode is changed to 0 to be exclusively controlled by the PC with its own set of settings. To enable local UI again change the LonMark Object UCPTModeStandAlone to 1. Settings configured locally and used in standalone mode are different from those configured by the PC through the network. To change a settings the SET button is used in conjunction with any other switch on the Local User Interface Board to increase or decrease the corresponding (flashing) value by pushing the SET switch Upward or Downward respectively. First select the parameter by pushing and maintaining the corresponding button (SW1, SW3 and SW4) in the desired position. While holding, push on the SET button (SW2) Upward to increase the value and Downward to decrease the value. Press and hold for fast increase/decrease. 75-PHW-1012 R2.1 MT Anti-Sweat Standalone User Manual.docx RL 2016-09-27 Page 5 of 7

Temperature Calibration (Offset) On the Local User Interface Board, select the Temperature parameter by pushing and maintaining the SW1 button at the CAL. TEMP. position, the TEMPERATURE display will start to blink to indicate that the system is ready to change the value. While holding, push the SW2 SET switch in Up or Down position to change the Temperature value in the corresponding direction. Disabled when temperature is coming from SNVT. Humidity Calibration (Offset) On the Local User Interface Board, select the Humidity parameter by pushing and maintaining the SW1 button at the CAL. HUM. position, the HUMIDITY display will start to blink to indicate that the system is ready to change the value. While holding, push the SW2 SET switch in Up or Down position to change the Humidity value in the corresponding direction. Disabled for SNVT %RH. Dew Point Alarm High Limit Setting (1-99 F) On the Local User Interface Board, select the Dew Point Alarm parameter by pushing and maintaining the SW3 button at the HIGH LIMIT position, the DEW POINT display will start to blink the HIGH LIMIT value. While holding, push the SW2 SET switch in Up or Down position to change the Dew Point Alarm High Limit value in the corresponding direction. Dew Point Alarm Set Time (0-99 min, default is 5) On the Local User Interface Board, select the Dew Point Alarm parameter by pushing and maintaining the SW3 button at the SET TIME position, the DEW POINT display will start to blink the SET TIME value. While holding, push the SW2 SET switch in Up or Down position to change the Dew Point Alarm Set Time value in the corresponding direction. Transfer Function Parameter Setting. The transfer function of the control is based on two points (P1, P2) each one identified by two coordinates on a DEW/PWR graphic: P1 (DEW1, PWR1) and P2 (DEW2, PWR2) used to modulate the output power according to the dew point. Output timing diagram 100 % Full Pwr2 (80%) % Power (Default) P2 Pwr1 (20%) P1 If Dew Point < Dew1 then %Power = Pwr1, If Dew Point > Dew2 then % Power = Pwr2 0 % 0 F Dew1 (20) Dew2 (55) Dew Point (Default) DPHL (77) 99 F If Dew1 Dew Point Dew2 then Pwr1 %Power Pwr2 If Dew Point > Dew Point Alarm High Limit then %Power = FP (FP = Full Power = 100%) 75-PHW-1012 R2.1 MT Anti-Sweat Standalone User Manual.docx RL 2016-09-27 Page 6 of 7

Operation DEW1 and DEW2 Setting (1-99 F) Select the Dew Point parameter by pushing and maintaining the SW4 button at the DEW1, DEW2 position (left side). To change between DEW1 and DEW2 parameters release and push the button in the same direction. One of the DEW LED will be illuminated to indicate the selection. The DEW POINT display will start to blink the respective value. While holding, push the SW2 SET button in Up or Down position to change the dew point value in the corresponding direction. PWR1 and PWR2 Setting (0-100%) Select the % Power parameter with the SW4 switch by pushing and maintaining at the PWR1, PWR2 position (right side). To change between PWR1 and PWR2 parameters release and push the button in the same direction. One of the PWR LED will be illuminated to indicate the selection. The % POWER display will start to blink the respective value. While holding, push the SW2 SET button in Up or Down position to change the power value in the corresponding direction The Local User Interface Board can be removed from the Processor Board if desired after the configuration process. The parameters are saved on the processor board between configuration sessions. Without the Local User Interface Board the configuration may be done with the MT-Alliance through the network configuration properties of the node accessed by its LonMark Object form of the Command/Status tab of the Custom Node information tool. Please note: If you change the standalone mode you must configure it in the same mode it is intended to run. In other word if you run the Anti-sweat Energy Saver with standalone mode = 0 you must configure it with MT-Alliance through the network then the Local User Interface Board can t be used any more. Only remote and local bypass command work in both mode. Unless bypass is ON at power up the Anti-sweat Energy saver will prevent heating for 60 sec. When running it will pulse each heater channel sequentially with a duty cycle according to the % Power. If dew point is higher than Dew Point High Limit for longer than Dew Point Set Time the output power will be forced to Full Power, there will be no alarm sound but the normally open dry contact will remain close as long as the Alarm status is ON. If thereafter the dew point becomes lower than the limit, the Alarm Status LED will remain ON but the output power for heating will not be forced to full any more. This alarm function can be used to detect repetitive moisture problem. If the temperature or the humidity value comes from the network via a SNVT and the communication fails, the reading will switch to the local sensor. If no remote sensor and no local sensor temperature or humidity is found the corresponding missing sensor display and the Dew Point display will show bars "- -" the system will put the Outputs to a full power 100% duty cycle and the % Power will show "FP" for Full Power and the %Saving will be 0%. You will get the alarm status after the Dew Point Set Time expires. 75-PHW-1012 R2.1 MT Anti-Sweat Standalone User Manual.docx RL 2016-09-27 Page 7 of 7