AB Parts. ControlNet Coax Tap. Installation Instructions. (Cat. Nos TPR, -TPS, -TPYR, -TPYS) What s in This Document

Similar documents
Installation Instructions

Compact I/O End Caps/Terminators

POINT I/O Field Potential Distributor Module

POINT I/O Field Potential Distributor Modules

XM-441 Expansion Relay Module

XM-360 Process Module, XM-361 Temperature Module, and XM-362 Isolated Temperature Module

XM-440 Master Relay Module

Siemens Automation Products Siemens AG All rights reserved A5E AB, 08/2017 1

FLEX I/O Digital Input and Output Modules

IMPORTANT: Read carefully before installation and retain for future reference. NOTE: Installation must be conducted by licensed electrician.

Certificate of Compliance

SEL-3422 Motor Relay HMI Quick-Start Guide

NGC-40-IO Control and monitoring modules for use with the Raychem NGC-40 system Installation Instructions

MODELS SafeSite LED Linear, Class I Div. 1 2 & 4 Versions

INSTALLATION INSTRUCTION In-Ground Color Changing

System 350 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules

HEARTH PRODUCTS KITS AND ACCESSORIES. KIT CONTENTS (See Figure 1) TOOLS NEEDED

PH:

Product ID. General. TE CONNECTIVITY SENSORS /// EXxxHyy Ex-Atex & NA 09/2017 Page 1

ChemScan mini Analyzer for Low Ammonia Monitoring Installation, Operation and Maintenance Manual

Installation Instructions

SZ-PIR04N ZigBee Motion Detector Installation Guide

SLC 500 Power Supplies

INSTALLATION INSTRUCTION In-Ground

Installation Instructions If you have questions, call 800-GE-CARES or visit our website at:

QUICK START GUIDE. Lono, LLC 686 East 110 South, Suite 102 American Fork, UT 84003

Lumination TM Volumetric Retrofit Kit

SkyNEST WASP Portable Kit, Smart Receiver and SCADA Gateway with Solar Panel USER MANUAL

Tetra MAX. LED Lighting System. BEFORE YOU BEGIN Read these instructions completely and carefully. Installation Guide

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

Stopper Station Series SS-2008 Push Button Pneumatic Timer Button

CXB Series SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. LED Luminaire TO INSTALL: INSTALLATION INSTRUCTIONS INSTRUCTIONS D INSTALLATION

GE Monogram. Installation Instructions. Built-In Dishwashers. with Optional Trim Kit. Models ZBD5600 ZBD5700 ZBD5900

Certificate of Compliance

PH:

GARAGE DOOR OPENER KIT

Stopper Station Series Push Button Models SS2xx2, SS2xx5, SS2xx9

PEDESTAL INSTALLATION INSTRUCTIONS INSTRUCTIONS D INSTALLATION DU PIÉDESTAL

200i User s information manual

Gas Equipment. Volume 1 January/February Issue date: February 4, 2009

Wireless Outdoor Air Reset Adaptor PN:

QAA 142 Termination instructions Self-regulating trace heaters type ELSR-NA and -HA in Div1 with heater entry kit EL-HAZELECT Kit part No: 09CA051

Certificate of Compliance

Instruction Manual Advanced Mini Block Heaters Advanced Mini Block Heater with Heated Lid

Lumination TM Controls Accessory LPL Series Controller Box

Installation Instructions

2007 XYCOM AUTOMATION, LLC.

Illuminated Stopper Station Push Button

Intelligent Home Solutions Quick Start Guide. Monitor your home from anywhere with your smartphone

Wi-Fi DOOR/WINDOW SENSOR

Gas Equipment. Volume 4 June/July Issue date: June 27, 2007

INSTRUCTION & SERVICE MANUAL D1xS1 & D1xS2 ALARM HORNS For Use In Hazardous Locations - Gas

FINAL DRAFT INTERNATIONAL STANDARD

ADT. Pulse 2017ADT LLC

Installation Instructions If you have questions, call or visit our website at:

INSTRUCTION MANUAL. D1xB2XH2 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information

INSTRUCTION MANUAL. D1xB2XH1 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information

SOLA SM II Light Engine Instruction Manual

Installation Instructions

Low Voltage Fan Coil Thermostat ST101ZB. Quick Start Guide. For other language versions, please visit

Kit Instructions COMMON VENT KIT (PVC AND DURAVENT)

Location Requirements

Laptop Computer (OLPC)

Draft - develop and review

Certificate of Compliance

Atomic Digital Office Clock

Yale Real Living Key Free Push Button Deadbolt B1 with Installation and Programming Instructions

Nest x Yale Lock Programming/Troubleshooting Guide

INTRODUCTION. Industry Canada: Canadian ID: 6982A-YRHCPZW0 (Z-Wave); 6982A-YRHCPZB0 (Zigbee)

INSTALLATION INSTRUCTIONS

Operation & Care Instructions Save For Future Reference ABOUT THE MACHINE

AGA TOTAL CONTROL. Model No. - TC3

Micro800 Programmable Controller External AC Power Supply

Gas Equipment. Volume 3 May Issue date: May 11, 2007

Occupancy Sensor OCS 100W Setup Guide

ASPEC Positive Pressure Manifold. User's Guide

Installation, Operation and Maintenance Manual

INSTRUCTION MANUAL. E2xB05 & E2xB10 Xenon Beacons For use in Hazardous Locations

MAXLITE RKT LED Retrofit Kit

Lunera Smart T8 4ft. Installation Guide. Installation Description

MICROWAVE OVEN UNDER-THE-CABINET INSTALLATION INSTRUCTIONS INSTRUCTIONS D INSTALLATION FOUR À MICRO-ONDES SOUS PLACARD MURAL

WINDSHEAR STORM and WINDSHEAR STORM DELUXE MODEL NO: 98778/98780

Wireless Alarm Bar TM Installation Guide

Installation Instructions If you have questions, call 800-GE-CARES or visit our website at:

CAUTION CAUTION WARNING. Vulcan RT Heater With Remote Temperature Controller

CB TEST CERTIFICATE. Personal Computer. Acer Computer (Shanghai) Limited 3F, No. 168 Xizang Medium Road Huangpu District, Shanghai CHINA

1495D. Installation and Operation Manual, 230 Voltage 2/16/2017

Certification Supplement Manual

UNI 321. User s Guide

Installation, Operation and Maintenance Manual

EcoView Thermostat. Product Description. Installation. Product Number. Caution Notations. Required Tools. Expected Installation Time.

Technical Manual for the Strobe - SM87 HXB

Installation Instructions

USER'S INFORMATION MANUAL SERIES 2 GAS - FIRED

Escape Series Walk-in Bathtub Models 5128 and 5332 (soaker, water, air and microbubble jet models)

Installation, Operation and Maintenance Manual

USER'S INFORMATION MANUAL SERIES 2 GAS - FIRED

Switching power supply. Additional Information on page 2 Input rating: Vac, 50-60Hz, 2.5A Output rating: 24Vdc, 8.33A max., 200W max.

Tank, Heater, and Control Operation Manual REV. E DATE: 04May2015

Yale Real Living Assure Lock Push Button Deadbolt Installation and Programming Instructions (YRD216)

Transcription:

Installation Instructions ControlNet Coax Tap (Cat. Nos. 1786-TPR, -TPS, -TPYR, -TPYS) What s in This Document Use this document as a guide when installing a ControlNet coax tap. To: See Page: verify package contents 1 select where to mount the tap 4 mount the tap 4 For reference on: See Page: mounting dimensions 7 specifications 6 Important: For information on planning and installing your ControlNet cable system, see the ControlNet Cable System Planning and Installation Manual, publication 1786 6.2.1. Verify Your Package Contents Make sure you have these items before you discard any packing material. tap (1786-TPR, -TPS, -TPYR or -TPYS) BNC connector kits dust cap screws universal mounting bracket If an item is missing or incorrect, contact your Allen-Bradley distributor or sales office. 41644 AB Parts

2 ControlNet Coax Tap CSA Statement When the product is marked with the CSA Hazardous Location marking, it is suitable for use in Class I, Division 2 Hazardous Locations and nonhazardous locations only when installed with products bearing the Allen-Bradley ControlNet name or logo, and like certifications. CSA Hazardous Location Approval CSA certifies products for general use as well as for use in hazardous locations. Actual CSA certification is indicated by the product label as shown below, and not by statements in any user documentation. Example of the CSA certification product label: CL I, DIV 2 GP A,B,C,D TEMP To comply with CSA certification for use in hazardous locations, the following information becomes a part of the product literature for this CSA-certified industrial control product. This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only. The products having the appropriate CSA markings (that is, Class I, Division 2, Groups A, B, C, D) are certified for use in other equipment where the suitability of combination (that is, application or use) is determined by the CSA or the local inspection office having jurisdiction. Important: Due to the modular nature of a programmable control system, the product with the highest temperature rating determines the overall temperature code rating of a programmable control system in a Class I, Division 2, location. The temperature code rating is marked on the product label as shown. Temperature code rating: CL I, DIV 2 GP A,B,C,D TEMP /RRNÃIRUÃWHPSHUDWXUH FRGHÃUDWLQJÃKHUH The following warnings apply to products having CSA certification for use in hazardous locations. ATTENTION: Explosion hazard - Substitution of components may impair suitability for Class I, Division 2. Do not replace components unless power has been switched off or the area is known to be non-hazardous. Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous. Do not disconnect connectors unless power has been switched off or the area is known to be non-hazardous. Secure any user-supplied connectors that mate to external circuits on this equipment by using screws, sliding latches, threaded connectors, or other means such that any connection can withstand a 15 Newton (3.4 lb.) separating force applied for a minimum of one minute. CSA logo is a registered trademark of the Canadian Standards Association.

ControlNet Coax Tap 3 Complément d information Si ce produit porte le marquage CSA, il convient à une utilisation en environnements dangereux de Classe 1, Division 2 et non dangereux uniquement s il est installé avec des produits portant le nom ou le logo ControlNet d Allen-Bradley ou des certifications similaires. Approbation d utilisation en environnements dangereux par la CSA La CSA certifie des produits pour une utilisation générale aussi bien que pour une utilisation en environnements dangereux. La certification CSA en vigueur est indiquée par l'étiquette produit et non par des indications dans la documentation utilisateur. Exemple d'étiquette de certification d'un produit par la CSA : CL I, DIV 2 GP A,B,C,D TEMP Pour satisfaire à la certification CSA en environnements dangereux, les informations suivantes font partie intégrante de la documentation des produits industriel de commande industrielle certifiés. Cet équipement ne convient qu à une utilisation en environnements de Classe 1, Division 2, Groupes A, B, C, D, ou non dangereux. Les produits portant le marquage CSA approprié (c'est à dire, Classe 1, Division 2, Groupes A, B, C, D) sont certifiés pour une utilisation avec d'autres équipements, les combinaisons d applications ou d utilisations étant déterminées par la CSA ou le bureau local d'inspection qualifié. Important : De par la nature modulaire des systèmes de commande programmables, le produit ayant le code de température le plus élevé détermine le code de température global du système dans un environnement de Classe 1, Division 2. Le code de température est indiqué sur l'étiquette produit. Code de température : CL I, DIV 2 GP A,B,C,D TEMP Le code de température est indiqué ici Les avertissements suivants s'appliquent aux produits ayant la certification CSA pour une utilisation en environnements dangereux. DANGER : Risque d explosion La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnements de Classe 1, Division 2. Couper le courant ou s assurer que l environnement est classé non dangereux avant de remplacer des composants. Couper le courant ou s assurer que l environnement est classé non dangereux avant de débrancher l équipement. Couper le courant ou s assurer que l environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs fournis par l utilisateur pour se brancher aux circuits externes de cet équipement à l aide de vis, loquets coulissants, connecteurs filetés ou autres, de sorte que les connexions résistent à une force de séparation de 15 newtons (1,5 kg - 3,4 lb) appliquée pendant au moins une minute. Le sigle CSA est la marque déposée de l'association des Standards pour le Canada. AB Parts

4 ControlNet Coax Tap Select Where to Mount Your Tap Use these guidelines to select where to mount your taps. There is no spacing requirement between taps; you can install two adjacent taps using a barrel connector (1786-BNC). Make sure the mounting location is convenient for your cable routing. Make sure the mounting location allows your wiring to meet these requirements: In conduit - installation of RG6 Quad Shield type coax cable conforms to this pull force and bend radius: For this coax cable: The pull strength should not exceed: The bend radius should exceed: PVC 42.75kg (95lbs) 76.2mm (3.0 in) FEP 61.65kg (137lbs) 69.9mm (2.75 in) Not in conduit - installation of RG6 Quad Shield type coax cable conforms to this bend radius: For this coax cable: The bend radius should exceed: PVC 38.1mm (1.5 ) FEP 35.6mm (1.4 ) Tap drop cable 25.4mm (1.0 ) Do not mount the tap in a position that routes the dropline cable over any ac power terminals on nearby modules. ATTENTION: Do not allow any metal portions of the tap, such as the universal mounting bracket screws or connectors to contact any conductive material. This contact could cause noise on the network. Mount Your Taps You can mount your ControlNet tap (T-tap or Y-tap): to a universal mounting bracket, and then mount the tap and bracket as an assembly through the body holes in the tap using: screws and flat washers and a tie wrap. Once you have mounted your taps, you can store or discard any unused universal mounting brackets. See page 7 for universal mounting bracket and tap mounting dimensions.

ControlNet Coax Tap 5 Mounting a Tap Using a Universal Mounting Bracket 1. Align the universal mounting bracket with the mounting holes on the tap. 2. Using screws provided with the tap, attach the tap to the universal mounting bracket. Y-tap universal mounting bracket dust cap T-tap universal mounting bracket (provided with tap) 20084-M dust cap 20080-M Use only the screws that are packaged with the tap. They are the proper length and head style. ATTENTION: Do not over tighten the screws. Over tightening the screws can damage the tap. The applied torque should be 0.2-0.4 N-m (1-2 ft.-lbs). 3. Mount the tap and bracket assembly to: a DIN Mounting Rail or another mounting surface universal mounting bracket universal mounting bracket Use four screws to attach the universal mounting bracket to another surface suitable fixture DIN rail 20081-M 20082-M Mount the universal bracket on specified Allen-Bradley mounting rails or DIN rails #3 style symmetrical (35 X 7.5mm) Type of rail Cat. No. Type of rail Cat. No. A-B rail 1492-N1 Din Rail #3 199-DR1 1492-N22 1492-DR5 1492-N44 1492-DR6 1492-DR7 AB Parts

6 ControlNet Coax Tap Mounting a Tap Through Body Holes Mount the tap to a suitable fixture using: a tie wrap or screws and flat washers body holes tie wrap body holes screws and flat washers (not supplied) You can use a variety of screw types. 41645 41646 ATTENTION: Do not over tighten the screws. Over tightening the screws can damage the tap. The applied torque should be 0.2-0.4 N-m (1-2 ft.-lbs). Do not use screws larger than #8 in these holes. Important: The suitable fixture can be conductive and/or grounded because of the electrical isolation provided by these body holes. Specifications The following table lists the specifications for the ControlNet taps. Operating temperature Storage temperature Relative humidity -0 to 60 C (32 to 140 F) -40 to 85 C (-40 to 185 F) 5 to 95% noncondensing

ControlNet Coax Tap 7 Mounting Dimensions Use these mounting dimensions to mount your taps and universal mounting brackets. Universal Mounting Bracket 58.42 mm (2.30 in) 49.53 mm (1.95 in 30.94 mm (1.218 in) 19.05mm (0.75 in) 9.53 mm (0.375 in) 15.47 mm (0.609 in) 20170-M Taps T-tap 35.56 mm (1.40 in) 15.24 mm (0.60 in) Y-tap 30.23 mm (1.19 in) 15.24 mm (0.60 in) 33.02 mm (1.30 in) 25.4 mm (1.00 in) 39.37 mm (1.55 in) 31.37 mm (1.235 in) 20168 20169 AB Parts

ControlNet is a trademark of ControlNet International, Ltd. Publication PN 955135-79 Supersedes Publication 1786-5.7 - December 1995 Copyright 1999 of Rockwell International Corporation. Printed in the U.S.A.