Tranquility 22 Compact Ultra Efficiency (TY) Series Submittal Data

Similar documents
Tranquility 30 Two-Stage (TT) Series

Tranquility Vertical Stack (TSL) Series

Tranquility Console (TRC) Series Submittal Data

Tranquility Vertical Stack (TSM) Series

Tranquility Vertical Stack (TSM) Series Submittal Data

VERTICAL STACK (VHS) SERIES

THE TRANQUILITY 16 COMPACT (TC) SERIES

HEAT CONTROLLER, INC. HSS Series 1 1/2 to 5 Tons Indoor Split System Geothermal Heat Pumps

*20D082-05NN* 20D082-05NN

ENGINEERING DESIGN GUIDE: GENESIS COMPACT (GC) SERIES 0.5 TO 5 TON HORIZONTAL AND VERTICAL UNITS

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

ENGINEERING DESIGN GUIDE: GENESIS STANDARD (GR) SERIES 0.5 TO 5 TON HORIZONTAL AND VERTICAL UNITS

Genesis Compact (GC) Series Submittal Data

THE SMART SOLUTION FOR ENERGY EFFICIENCY ENGINEERING DESIGN GUIDE: CONSOLE (CCE) SERIES 0.5 TO 1.5 TON CONSOLE UNITS WATER-SOURCE HEAT PUMP SYSTEMS

Product Data. Single-Package Horizontally Mounted Water Source Heat Pumps with Electronic

ENGINEERING DESIGN GUIDE: TRANQUILITY 27 TWO-STAGE (TT) SERIES 2 TO 5.5 TON HORIZONTAL AND VERTICAL EARTHPURE UNITS

Product Data. Features/Benefits. AQUAZONE 50PCH,PCV Compact Water Source Heat Pumps with PURON Refrigerant (R-410A) 50 Hz

Product Data. AQUAZONE 50HQP Large Capacity Horizontal Water Source Heat Pumps with PURON Refrigerant (R-410A) 6 to 10 Nominal Tons

GEOTHERMAL SPLIT SYSTEMS CLIMATEMASTER

Commercial and Residential Water Source Heat Pumps Boiler/Tower and Geothermal Applications

ACDU02 Communicating Service Tool

ClimaDry II. Table of Contents. ClimaDry II Whole House Dehumidification Option. Tranquility 30 Tranquility 20

GUIDE SPECIFICATIONS AQUARIUS ii

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

Water Source Heat Pumps

ENGINEERING SPECIFICATIONS

Refrigeration/Troubleshooting Manual

GT-PW (50YEW) Water-To-Water Series. WATER-TO-WATER PURON SYSTEMS SIZE 010 [10 kw]

MAC-120HE-03 Air-Cooled Chiller

ENGINEERING SPECIFICATIONS

SpaceKeeper Console (SKC)

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

Water Source Heat Pumps. Energy efficient heating and cooling commercial applications

Engineered for flexibility and performance

Mammoth Water Source Heat Pumps

Greensource Residential Water Source Heat Pumps. Simply Smart. i Series: SV Model. boschheatingandcooling.com

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

June PRODUCT DESIGN GUIDE Whisperline Console

BasicTroubleshooting Information and Guidelines

GEOTEC GV Series High Efficiency Geothermal/Water Source Packaged Step-Capacity Heat Pump R-410A

Half Round Evaporators

CA Model Water Source Heat Pump

GUIDE SPECIFICATIONS AQUARIUS ii

PAJ3. Product Specifications

Geothermal HIGH EFFICIENCY HEATING & COOLING. the logical choice for energy efficient residential heating and cooling

GUIDE SPECIFICATIONS. WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers. WW Reverse Cycle Chillers / Low Temperature Boilers

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

62DA,DB,DC,DD,DE,DF07-38

DXair Pool Dehumidifiers

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

Tranquility 22 (TZ) Series

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

technical guide Water-Cooled Self-Contained Units

RSG16**S1M. Split System Air Conditioner 16 SEER

LV Split Systems Water Source Heat Pump

Residential Application/Design Manual

FF1DNA, FF1DNE FAN COIL UNITS. Sizes 018, 024, 030. Form No. PDS FF1D.18.3 FEATURES FF1D

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

Midea R410A Tropical ClimaCreator Series Rooftop Package 220V 3Ph 60Hz Technical Manual

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps

BCE4 PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER WITH VARIABLE SPEED APPLICATION INSTALLATION CABINET COMPONENTS CONTROLS WARRANTY

Catalog SmartSource Two-Stage Horizontal & Vertical Water Source Heat Pumps

MH1WC4W-06-1-B Chilled/Hot Water 1-Way Cassette Fan Coil

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

Model Number Tons Nom. CFM (L/s) Dimensions H x W x D in. (mm) Filter Size in. (mm) Ship Wt lbs.(kg)

CFFWA4P-12-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 36,000 BTUH

CFFWA4P-16-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 48,000 BTUH

Greensource iseries Water Source Heat Pumps. SV Model. Made in Florida boschheatingandcooling.com

Versatec Specification Catalog

CFFWA4P-08-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 24,000 BTUH

VertiCool Aurora Engineering Guide

SPECIFICATION CATALOG. Commercial 0.75 to 6 Tons. Geothermal/Water Source Heat Pump

Tranquility (THW) Water-To-Water Series. WATER-TO-WATER SYSTEMS SIZES Hz [10 kw]

Water-Cooled Self-Contained Units

PAR5. Product Specifications

FCC Fan-Coil Units High-Performance, Vertical

ARBOR SERIES CONDO. Arbor Condo Series Installation Manual. Water Source/Geothermal Heat Pump R-410A Refrigerant Commercial

C13-Series Engineering Guide

Product Data. FV4B Direct Expansion Variable Speed Fan Coil Puron Refrigerant. Sizes 002 thru 006

Tranquility Digital Quick Start Guide

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

R4H4. Product Specifications

Greensource Residential Geothermal Heat Pumps. Invisible Comfort. Si Series: CE Model. boschheatingandcooling.com

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

Product Data. Features/Benefits. 28CB, 28LA Direct-Expansion. evaporator coils. 7 1 / 2 and 10 Nominal Tons Cooling

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled

TRANQUILITY THW WATER-TO-WATER. WATER-TO-WATER SYSTEMS SIZES 008, 010, AND 012 [8, 10 and 12 kw]

Split System Heat Pumps

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

P8SE Series. 14 SEER, Single Phase Packaged Air Conditioner TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 3, 4, 5 Ton Units

Commercial High-Efficiency Condensing Units

EP Model. EP Model Water Source Heat Pump. ½ to 6 Ton

COMMON WATERSIDE ECONOMIZER APPLICATIONS:

Transcription:

Tranquility 22 Compact Ultra Efficiency (TY) Series Submittal Data Models TYH/V024-060 60Hz - HFC-410A *LC992* LC992 Rev.: November 27, 2018

Table of Contents TY Compact Ultra Efficiency Series Unit Features 3 igate Communicatg Controls 6 Selection Procedure 7 TY Series Nomenclature 10 Performance Data AHRI/ASHRAE/ISO 13256-1 11 Performance Data TY H/V 024 (Part Load) 12 Performance Data TY H/V 024 (Full Load) 13 Performance Data TY H/V 030 (Part Load) 14 Performance Data TY H/V 030 (Full Load) 15 Performance Data TY H/V 036 (Part Load) 16 Performance Data TY H/V 036 (Full Load) 17 Performance Data TY H/V 042 (Part Load) 18 Performance Data TY H/V 042 (Full Load) 19 Performance Data TY H/V 048 (Part Load) 20 Performance Data TY H/V 048 (Full Load) 21 Performance Data TY H/V 060 (Part Load) 22 Performance Data TY H/V 060 (Full Load) 23 Part Load Performance Data Correction Tables 24 Full Load Performance Data Correction Tables 25 Antifreeze Correction Tables 26 ECM Blower Control 27 Blower Performance Data 28 Physical Data 29 TY - Horizontal Dimensional Data 30 TY - Vertical Upflow Dimensional Data 32 Corner Weights 34 Electrical Data 35 TY Series Wirg Diagram Matrix 36 Typical Wirg Diagram Sgle Phase TY Units with DXM2 Controller 37 Typical Wirg Diagram Sgle Phase TY Units with DXM2 Controller and MPC 38 Typical Wirg Diagram Three Phase 208/230V TY Units with DXM2 Controller 39 Typical Wirg Diagram Three Phase 208/230V TY Units with DXM2 Controller and LON 40 Typical Wirg Diagram Three Phase 460V TY Units with DXM2 Controller 41 Engeerg Specifications 42 Performance Sheet 48 Revision History 50 Document page number is shown next to part number (e.g. LC992-3 = page 3). Sce not all pages are typically used the submittals process, the page number the lower right corner can still be used (page of ). LC992-2

Unit Features THE TRANQUILITY 22 TWO-STAGE (TY) SERIES The TY comes with all the reliability features the ClimateMaster Tranquility Series is known for. They clude superb efficiency ratgs, quiet operation and application flexibility. Tranquility 22 units are available vertical upflow and horizontal configurations capacities of 24, 30, 36, 42, 48, and 60 Mbtuh. Other features clude the next generation Copeland UltraTech two-stage scroll compressor, variable speed ECM fan motor, and digital communicatg controls. It also has one of the dustry s smallest footprts, makg it suitable for stallation tight places and for replacement/retrofit projects. Available sizes 2 tons (7.0 kw) through 5 tons (17.6 kw) with multiple cabet options (vertical upflow and horizontal) the Tranquility 22 offers a wide range of units for most any stallation. The Tranquility 22 has an extended range refrigerant circuit, capable of ground loop (geothermal) applications as well as water loop (boilertower) applications. Standard features are many. Copeland UltraTech two-stage unloadg scroll compressor, ECM variable fan motor, microprocessor controls, galvanized steel cabet, powder coated and sulated galvanized steel dra pan, and acoustic type fiber sulation are just some of the features of the novative Tranquility 22 Series. quietest units on the market. Compressors are mounted on specially engeered sound tested EPDM grommets to a heavy gauge mountg plate, which is then isolated from the cabet base with rubber grommets for maximized vibration/sound attenuation. The easy access control box makes stallg and matag the unit easier than any other water-source heat pump currently production. Options such as coated air coil, DDC controls, and high efficiency MERV rated air filters allow customized design solutions. igate technology is the next generation telligent control by usg two-way communication to provide a gateway to the system. The igate control system allows end-users and contractors to monitor the performance of the unit, custom tailor its operation, and diagnose any issues, right from the thermostat. The Tranquility 22 (TY) Series water-source heat pumps are designed to meet the challenges of today s HVAC demands with one of the most novative products available on the market. ClimateMaster s exclusive double isolation compressor mountg system makes the Tranquility 22 one of the LC992-3

Unit Features UNIT FEATURES Sizes 024 (2 ton, 7.0 kw) through 060 (5 tons, 17.6 kw) EarthPure (HFC-410A) refrigerant Copeland UltraTech two-stage unloadg scroll compressors ECM variable speed fan motor with soft start DXM2 two-way communicatg controller Exceeds ASHRAE 90.1 efficiencies Part load operation significantly lowers annual operatg costs Galvanized steel construction Powder coated and sulated galvanized steel dra pan Cabet led with acoustic type fiber sulation Unique double isolation compressor mountg with vibration isolation for quiet operation Insulated divider and separate compressor/air handler compartments TXV meterg device Extended range (20 to 120 F, -6.7 to 48.9 C) operation Advanced Controls - igate communicatg control provides advanced unit functionality and comprehensive configuration, monitorg and diagnostic capabilities through digital communication lks with the variablespeed fan motor, variable-speed source pump (or modulatg valve) and communicatg thermostat or configuration/diagnostic tool. 7 temperature sensor puts for system protection and control Anti-short cycle and over/under voltage protection High pressure, loss of charge, and condensate overflow protection LED fault and status dication at controller Service tool port for optional setup and diagnostics at unit LonWorks, BACnet, Modbus and Johnson N2 compatibility options for DDC controls Field convertible discharge air arrangement for horizontal units Easy access control box Unit Performance Sentel performance monitorg system Eight Safeties Standard Variety of options cludg DDC controls, MERV rated air filters, coated air coils, staless steel dra pans and electrical service disconnects. LC992-4

igate Communicatg Controls igate Information gateway to monitor, control and diagnose your system Tranquility 22 is equipped with dustry-first, igate Information Gateway 2-way communicatg system that allows users to teract with their system pla English igate makes Tranquility Series the easiest products to stall and service. Fan Communicatg Thermostat Or Monitor/Configure Installers can configure Tranquility 22 units from the thermostat, cludg: Air flow, loop delta T, water-flow option configuration, unit configuration, accessory configuration, and demand reduction (optional, to limit unit operation durg peak times). Users can look up the current system status: temperature sensor readgs and operational status of the blower and pump. Diagnostic Tool Two-Way Communication Sensors Precise Control The new DXM2 board enables telligent, 2-way communication between the DXM2 board and smart components like the communicatg thermostat, and fan motor. The Intelligent DXM2 board uses formation received from the smart components and sensors to precisely control operation of the variable speed fan to deliver higher efficiency, reliability and creased comfort. Diagnostics igate takes diagnosg units to a next level of simplicity, by providg a dashboard of system and fault formation, pla English, on the igate thermostat/ service tool. igate Service Warng warns the occupant of a fault and displays dealer formation (if programmed), fault description, possible causes and current system status (temperature readgs, fan RPM and water flow status) to provide to a dealer on the phone. In igate Service Mode, the service personnel can access fault description, possible causes and most importantly, the conditions (temp, flow, i/o conditions, configuration) at the time of the fault and at the time of the call. Manual Operation mode allows the service personnel to manually command operation of the thermostat outputs and blower speed from the thermostat, to help troubleshoot specific components. With igate communicatg system, consumers and contractors have a gateway to system formation never before available. AIRFLOW SELECTION CFM HEAT STAGE 1 600 HEAT STAGE 2 750 AUXILIARY HEAT 850 EMERGENCY HEAT 850 COOL STAGE 1 525 COOL STAGE 2 700 COOL DEHUMID 1 425 COOL DEHUMID 2 550 CONTINUOUS FAN 350 HEAT OFF DELAY 60 COOL OFF DELAY 30 PREVIOUS POSSIBLE FAULT CAUSES LOW WATER COIL TEMP NEXT LOW WATER TEMP - HTG LOW WATER FLOW - HTG LOW REFRIG CHARGE - HTG INCORRECT LT1 SETTING BAD LT1 THERMISTOR PREVIOUS FAULT TEMPERATURE CONDITIONS LT1 LOW WATER TEMP HEAT 1 11:11 AM 11/14 LT1 TEMP 28.1 LT2 TEMP 97.3 HOT WATER EWT 121.5 COMP DISCHARGE 157.7 LEAVING AIR 92.7 LEAVING WATER 34.9 ENTERING WATER 42.1 CONTROL VOLTAGE 26.4 PREVIOUS One-Way Communication LC992-5

Selection Procedure Reference Calculations Heatg LWT = EWT - HE GPM x 500 HR LWT = EWT + GPM x 500 Coolg LC = TC - SC LAT = EAT + HC CFM x1.08 LAT (DB) = EAT (DB) - SC CFM x1.08 S/T = SC TC Legend and Glossary of Abbreviations BTUH = BTU( British Thermal Unit) per hour CFM = airflow, cubic feet/mute COP = coefficient of performance = BTUH output/btuh put DB = dry bulb temperature ( F) EAT = enterg air temperature, Fahrenheit (dry bulb/wet bulb) EER = energy efficiency ratio = BTUH output/watt put MPT = male pipe thread ESP = external static pressure (ches w.g.) EWT = enterg water temperature GPM = water flow U.S. gallons/mute HE = total heat of extraction, BTUH HC = air heatg capacity, BTUH HR = total heat of rejection, BTUH HWC = hot water generator (desuperheater) capacity, Mbtuh FPT = female pipe thread KW = total power unit put, kilowatts LAT = leavg air temperature, F LC = latent coolg capacity, BTUH LWT = leavg water temperature, F MBTUH = 1000 BTU per hour S/T = sensible to total coolg ratio SC = sensible coolg capacity, BTUH TC = total coolg capacity, BTUH WB = wet bulb temperature ( F) WPD = waterside pressure drop (psi & ft. of hd.) Conversion Table - to convert ch-pound (English) to S-I (Metric) Air Flow Water Flow Ext Static Pressure Water Pressure Drop Airflow (L/s) = CFM x 0.472 Water Flow (L/s) = gpm x 0.0631 ESP (Pa) = ESP ( of wg) x 249 PD (kpa) = PD (ft of hd) x 2.99 LC992-6

Performance Data Selection Notes For operation the shaded area when water is used lieu of an antifreeze solution, the LWT (Leavg Water Temperature) must be calculated. Flow must be mataed to a level such that the LWT is mataed above 40 F [4.4 C] when the JW3 jumper is not clipped (see example below). Otherwise, appropriate levels of a proper antifreeze solution should be used systems with leavg water temperatures of 40ºF [4.4 C] or below and the JW3 jumper should be clipped. This is due to the potential of the refrigerant temperature beg as low as 32 F [0 C] with 40 F [4.4 C] LWT, which may lead to a nuisance cutout due to the activation of the Low Temperature Protection. JW3 should never be clipped for standard range equipment or systems without antifreeze. Example: At 50 F EWT (Enterg Water Temperature) and 1.5 GPM/ton, a 3 ton unit has a HE of 22,500 Btuh. To calculate LWT, rearrange the formula for HE as follows: HE = TD x GPM x 500, where HE = Heat of Extraction (Btuh); TD = temperature difference (EWT - LWT) and GPM = U.S. Gallons per Mute. TD = HE / (GPM x 500) ER Heatg - EAT 70 F Airflow CFM HC kw HE LAT COP 0 710 11.6 1.05 8.2 85.1 3.25 0 825 11.7 1.02 8.4 83.2 3.38 38.3 710 13.6 1.09 10.1 87.8 3.66 38.3 825 13.8 1.06 10.3 85.5 3.81 39.2 710 14.2 1.09 10.7 88.5 3.81 39.2 825 14.4 1.06 10.9 86.1 3.97 4 39.8 710 14.4 1.09 10.9 88.8 3.86 7 39.8 825 14.6 1.06 11.1 86.3 4.02 35.3 710 16.1 1.15 12.3 90.9 4.08 5 35.3 825 16.2 1.12 12.6 88.2 4.25 37.9 710 16.7 1.15 13.0 91.8 4.25 37.9 825 16.9 1.12 13.3 89.0 4.42 38.3 710 16.9 1.16 13.2 92.1 4.30 38.3 825 17.1 1.12 13.5 89.2 4.47 30.7 710 18.3 1.18 14.5 93.9 4.56 30.7 825 18.5 1.14 14.8 90.8 4.75 33.4 710 19.1 1.18 15.2 94.8 4.73 3.4 825 19.3 1.15 15.5 91.6 4.93 1 710 19.3 1.18 15.4 95.1 4.78 825 19.5 1.15 15.7 91.9 4.98 710 20.4 1.21 16.5 96.6 4.93 5 20.6 1.18 16.8 93.2 5. 21.2 1.22 17.3 97.7 1 18 17 6 TD = 22,500 / (4.5 x 500) TD = 10 F LWT = EWT - TD LWT = 50-10 = 40 F In this example, as long as the EWT does not fall below 50 F, the system will operate as designed. For EWTs below 50 F, higher flow rates will be required (open loop systems, for example, require at least 2 GPM/ton when EWT is below 50 F). LC992-7

Selection Procedure Step 1 Step 2 Determe the actual heatg and coolg loads at the desired dry bulb and wet bulb conditions. Obta the followg de sign parameters: Enterg water temperature, water flow rate GPM, air flow CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 450 CFM per ton. Unit water pressure drop should be kept as close as possible to each other to make water balancg easier. Go to the ap pro pri ate tables and fd the proper dicated water flow and water tem per a ture. Step 3Select a unit based on total and sensible coolg conditions. Select a unit which is closest to, but no larger than, the actual coolg load. Step 4 Step 5 Step 6 Step 7 Step 8 Enter tables at the design water flow and water temperature. Read the total and sensible coolg capacities (Note: terpolation is per mis si ble, ex trap o la tion is not). Read the heatg capacity. If it exceeds the design criteria it is acceptable. It is quite normal for Water- Source Heat Pumps to be selected on coolg capacity only sce the heatg output is usually greater than the coolg capacity. Determe the correction factors associated with the variable factors of dry bulb and wet bulb. Corrected Total Coolg = tabulated total coolg x wet bulb correction. Corrected Sensible Coolg = tabulated sensible coolg x wet/dry bulb correction. Compare the corrected capacities to the load re quire ments. Normally if the capacities are with 10% of the loads, the equipment is ac cept able. It is better to undersize than oversize, as undersizg improves humidity control, reduces sound levels and extends the life of the equip ment. When completed, calculate water temperature rise and assess the selection. If the units selected are not with 10% of the load cal cu la tions, then review what effect chang g the GPM, water temperature and/or air flow and air tem per a ture would have on the corrected capacities. If the desired capacity cannot be achieved, select the next larger or smaller unit and repeat the procedure. Remember, when doubt, undersize slightly for best performance. Example Equipment Selection For Cool g Step 1 Load Determation: Assume we have determed that the appropriate coolg load at the desired dry bulb 80 F and wet bulb 65 F con di tions is as follows: Total Coolg...22,000 BTUH Sensible Coolg...18,200 BTUH Enterg Air Temp...80 F Dry Bulb / 65 F Wet Bulb Step 2 Design Conditions: Similarly, we have also obtaed the followg design pa ram e ters: Enterg Water Temp...90 F Water Flow (Based upon 10 F rise temp.)...4.5 GPM Air Flow...600 CFM Step 3, 4 & 5 HP Selection: After makg our prelimary selection (TYH024 - Full Load), we enter the tables at design water flow and water tem per a ture and read Total Coolg, Sens. Coolg and Heat of Rej. ca pac i ties: Total Coolg...22,500 BTUH Sensible Coolg...16,500 BTUH Heat of Rejection...28,800 BTUH Step 6 & 7 Enterg Air and Airflow Corrections: Next, we determe our correction factors. Table Ent Air Air Flow Cor rect ed Corrected Total Coolg = 22,500 x 0.976 x 0.967 = 21,235 Corrected Sens Coolg = 16,500 x 0.919 x 1.089 = 16,513 Corrected Heat of Reject = 28,800 x 0.969 x 0.972 = 27,126 Step 8 Water Temperature Rise Calculation & As sess ment: Actual Temperature Rise...12.1 F When we compare the Corrected Total Coolg and Corrected Sensible Coolg figures with our load re quire ments stated Step 1, we discover that our selection is with +/- 10% of our sensible load requirement. Fur ther more, we see that our Cor rect ed Total Coolg figure is with 1,000 Btuh of the actual di cat ed load. LC992-8

TY Series Nomenclature 1 2 TY SERIES TY = Tranquility 22 Digital CONFIGURATION V = Vertical Up H = Horizontal UNIT SIZE 024 030 036 042 048 060 3 V REVISION LEVEL A = 030, 042, 048 B = 024, 036, 060 4 5 6 7 8 9 10 11 12 13 14 0 2 4 A G D 3 0 B L T VOLTAGE G = 208/230/60/1 E = 265/60/1 F = 460/60/3 H = 208/230/60/3 CONTROLS D = DXM2 M = DXM2 w/lon P = DXM2 w/mpc B = DXM2 w/disconnect K = DXM2 w/lon {S = DXM2 w/mpc CABINET SUPPLY AIR FLOW & MOTOR CONFIGURATION RETURN AIR FLOW CONFIGURATION HEAT EXCHANGER OPTIONS Standard 15 S T B S STANDARD S = Standard Supply Configuration Top TYV Back TYH Straight TYH WATER CIRCUIT OPTIONS 0 = None OPTION RANGE 1 A J K 2 C L M 3 E N P 4 G R S ULTRA QUIET NO YES NO YES Motor ECM ECM ECM L = Left Return R = Right Return V = Left Return, Staless Steel Dra Pan W = Right Return, Staless Steel Dra Pan Non-Coated Air Coil Copper Cupro-Nickel B G 1 FILTER 2 FILTER RAIL RAIL YES NO NO YES NO YES NO NO YES NO YES NO NO YES NO YES NO NO YES NO 1 FILTER FRAME NO YES NO YES T Plated Air Coil Copper Cupro-Nickel A J NO NO 2 FILTER FRAME YES NO YES NO NO YES NO YES NO NO YES NO YES NO LC992-9

Performance Data AHRI/ASHRAE/ISO 13256-1 ASHRAE/AHRI/ISO 13256-1. English (I-P) Units Model TY*024 Part TY*024 Full TY*030 Part TY*030 Full TY*036 Part TY*036 Full TY*042 Part TY*042 Full TY*048 Part TY*048 Full TY*060 Part TY*060 Full Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump Coolg 86 F Heatg 68 F Coolg 59 F Heatg 50 F Capacity Btuh EER Btuh/W Capacity Btuh COP Capacity Btuh EER Btuh/W Capacity Btuh COP Full Cool 77 F Part Cool 68 F Capacity Btuh EER Btuh/W Full Heat 32 F Part Heat 41 F Capacity Btuh 18,100 16.1 20,600 5.2 20,300 27.2 16,700 4.4 19,400 22.2 14,700 4.0 23,700 14.3 28,000 4.6 26,500 21.7 23,000 4.1 24,600 16.0 17,800 3.6 21,900 15.2 26,300 5.0 24,900 24.8 22,000 4.3 24,200 20.9 19,400 3.9 28,500 14.0 35,800 4.6 32,300 20.7 30,000 4.2 29,900 15.7 23,800 3.6 25,800 17.2 29,900 5.3 29,000 29.4 24,900 4.6 27,300 23.4 21,500 4.0 34,300 15.1 42,000 4.6 38,200 22.3 35,100 4.3 35,200 16.7 27,300 3.6 31,000 15.8 36,800 5.1 35,200 26.4 30,500 4.3 34,000 22.0 26,900 3.8 41,100 14.3 50,200 4.6 46,300 21.3 42,300 4.1 43,100 16.1 33,300 3.4 34,100 15.2 39,500 5.5 39,200 26.8 32,600 4.6 37,600 21.2 29,200 4.1 45,900 14.0 53,800 4.9 51,800 20.9 45,000 4.4 48,100 15.5 35,600 3.7 45,500 17.7 49,000 5.3 50,400 28.9 39,800 4.5 48,600 23.7 34,800 4.0 61,700 15.7 67,500 4.8 68,000 22.7 55,400 4.3 63,200 17.3 43,700 3.6 Coolg capacities based upon 80.6 F DB, 66.2 F WB enterg air temperature Heatg capacities based upon 68 F DB, 59 F WB enterg air temperature Ground Loop Heat Pump ratgs based on 15% antifreeze solution All ratgs based upon operation at lower voltage of dual voltage rated models COP ASHRAE/AHRI/ISO 13256-1. Metric (S-I) Units Model TY*024 Part TY*024 Full TY*030 Part TY*030 Full TY*036 Part TY*036 Full TY*042 Part TY*042 Full TY*048 Part TY*048 Full TY*060 Part TY*060 Full Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump Coolg 30 C Heatg 20 C Coolg 15 C Heatg 10 C Capacity kw EER Btuh/W Capacity kw COP Capacity kw EER Btuh/W Capacity kw Full Cool 25 C Part Cool 20 C Full Heat 0 C Part Heat 5 C LC992-10 COP Capacity kw EER Btuh/W Capacity kw 5.30 4.7 6.04 5.2 5.95 8.0 4.89 4.4 5.68 6.5 4.31 4.0 6.94 4.2 8.20 4.6 7.76 6.4 6.74 4.1 7.21 4.7 5.22 3.6 6.42 4.5 7.71 5.0 7.30 7.3 6.45 4.3 7.09 6.1 5.69 3.9 8.35 4.1 10.49 4.6 9.47 6.1 8.79 4.2 8.76 4.6 6.98 3.6 7.56 5.0 8.76 5.3 8.50 8.6 7.30 4.6 8.00 6.9 6.30 4.0 10.05 4.4 12.31 4.6 11.19 6.5 10.28 4.3 10.31 4.9 8.00 3.6 9.09 4.6 10.79 5.1 10.32 7.7 8.94 4.3 9.96 6.4 7.88 3.8 12.05 4.2 14.71 4.6 13.57 6.2 12.40 4.1 12.63 4.7 9.76 3.4 9.99 4.5 11.58 5.5 19 7.9 9.55 4.6 11.02 6.2 8.56 4.1 13.45 4.1 15.77 4.9 15.18 6.1 13.19 4.4 14.10 4.5 10.43 3.7 13.3 5.2 14.36 5.1 14.77 8.5 11.66 4.3 14.24 6.9 10.20 3.9 18.1 4.6 19.78 4.5 19.93 6.7 16.24 4.0 18.52 5.1 12.80 3.5 Coolg capacities based upon 27 C DB, 19 C WB enterg air temperature Heatg capacities based upon 20 C DB, 15 C WB enterg air temperature Ground Loop Heat Pump ratgs based on 15% antifreeze solution All ratgs based upon operation at lower voltage of dual voltage rated models COP

Performance Data TY H/V 024 (Part Load) 600 CFM Nomal (Rated) Airflow Coolg,600 CFM Nomal (Rated) Airflow Heatg EWT F Performance capacities shown thousands of Btuh WATER / BRINE COOLING - EAT 80/67 F HEATING - EAT 68 F FLOW GPM PD PSI PD FT TC SC kw HR EER HC kw HE LAT COP 20 30 40 50 60 70 80 90 100 110 120 5.00 3.65 8.4 10.757 1.12 6.921 84.6 2.8 2.50 0.81 1.9 22.825 15.401 0.62 24.947 36.7 12.477 1.14 8.582 87.2 3.2 3.80 1.82 4.2 22.992 15.408 0.58 24.962 39.8 13.070 1.15 9.154 88.1 3.3 5.00 2.90 6.7 23.032 15.367 0.56 24.939 41.2 13.370 1.15 9.444 88.6 3.4 2.50 0.51 1.2 22.388 15.200 0.70 24.784 31.9 14.832 1.17 10.851 90.8 3.7 3.80 1.39 3.2 22.710 15.358 0.65 24.913 35.2 15.570 1.18 11.559 92.0 3.9 5.00 2.35 5.4 22.824 15.400 0.62 24.947 36.7 15.941 1.18 11.916 92.5 4.0 2.50 0.33 0.8 21.743 14.840 0.80 24.477 27.1 17.145 1.19 13.070 94.4 4.2 3.80 1.10 2.6 22.201 15.097 0.73 24.699 30.3 18.009 1.20 13.898 95.7 4.4 5.00 1.96 4.5 22.383 15.197 0.70 24.782 31.8 18.442 1.21 14.312 96.4 4.5 2.50 0.25 0.6 20.906 14.384 0.92 24.048 22.7 19.395 1.22 15.224 97.9 4.7 3.80 0.94 2.2 284 14.695 0.84 24.346 25.6 20.363 1.23 16.151 99.4 4.8 5.00 1.70 3.9 21.727 14.831 0.80 24.469 27.0 20.844 1.24 16.610 100.1 4.9 2.50 0.24 0.6 19.895 13.884 1.06 23.521 18.7 21.560 1.25 17.294 101.2 5.1 3.80 0.85 2.0 20.575 14.214 0.97 23.876 21.3 22.604 1.26 18.293 102.8 5.2 5.00 1.55 3.6 20.870 14.365 0.93 24.030 22.5 23.116 1.27 18.783 103.6 5.3 2.50 0.26 0.6 18.723 13.375 1.23 22.914 15.2 23.617 1.28 19.262 104.4 5.4 3.80 0.83 1.9 19.489 13.700 1.12 23.309 17.4 24.704 1.29 20.302 106.0 5.6 5.00 7 3.4 19.829 13.853 1.07 23.486 18.5 25.228 1.30 20.805 106.8 5.7 2.50 0.29 0.7 17.402 12.873 2 22.247 12.3 25.541 1.30 21.104 107.3 5.8 3.80 0.83 1.9 18.238 13.183 1.30 22.667 14.1 26.631 1.31 22.151 109.0 5.9 5.00 3 3.3 18.616 13.332 1.24 22.859 15.0 27.146 1.32 22.646 109.8 6.0 2.50 0.30 0.7 15.945 12.378 1.64 21.538 9.7 3.80 0.82 1.9 16.837 12.676 1.50 21.968 11.2 5.00 0 3.2 17.244 12.817 4 22.169 11.9 2.50 0.26 0.6 14.360 11.865 1.89 20.803 7.6 3.80 0.78 1.8 15.296 12.167 1.74 21.232 8.8 Operation Not Recommended 5.00 1.36 3.1 15.726 12.306 1.67 234 9.4 2.50 0.13 0.3 12.658 11.290 2.17 20.060 5.8 3.80 0.67 1.6 13.626 11.623 2.01 20.477 6.8 5.00 1.26 2.9 14.074 11.772 1.93 20.675 7.3 Interpolation is permissible; extrapolation is not. All enterg air conditions are 80 F DB and 67 F WB coolg, and 70 F DB heatg. AHRI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB coolg and 68 F DB heatg. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. Operation below 60 F EWT requires optional sulated water/refrigerant circuit. See performance correction tables for operatg conditions other than those listed above. See Performance Data Selection Notes for operation the shaded areas. For quiet operation and long term reliability it is recommended that systems be designed to avoid contuous operation the outled areas. If operation the shaded area is required please refer to the TE or TZ product family. LC992-11

Performance Data TY H/V 024 (Full Load) 750 CFM Nomal (Rated) Airflow Coolg, 750 CFM Nomal (Rated) Airflow Heatg EWT F Performance capacities shown thousands of Btuh WATER / BRINE COOLING - EAT 80/67 F HEATING - EAT 68 F FLOW GPM PD PSI PD FT TC SC kw HR EER HC kw HE LAT COP 20 30 40 50 60 70 80 90 100 110 120 6.00 4.80 11.1 15.583 8 10.517 87.2 3.1 3.00 1.18 2.7 29.725 19.717 1.10 33.481 27.0 17.490 1.53 12.257 89.5 3.3 4.50 2.43 5.6 30.231 20.140 1.02 33.703 29.7 18.342 1.56 13.036 90.6 3.5 6.00 3.93 9.1 30.470 20.355 0.97 33.783 3 18.811 1.57 13.464 91.2 3.5 3.00 0.83 1.9 28.965 19.167 1.20 33.075 24.0 20.432 1.61 14.948 93.2 3.7 4.50 1.93 4.5 29.539 19.573 1.13 33.387 26.2 268 1.63 15.896 94.4 3.9 6.00 3.27 7.6 29.807 19.782 1.09 33.521 27.4 22.035 1.65 16.415 95.1 3.9 3.00 0.61 28.086 18.640 1.31 32.570 2 23.355 1.68 17.622 96.8 4.1 4.50 1.59 3.7 28.742 19.023 1.23 32.948 23.3 24.559 1.71 18.722 98.3 4.2 6.00 2.79 6.5 29.049 19.223 1.19 33.122 24.3 25.215 1.73 19.320 99.1 4.3 3.00 0.50 1.2 27.062 18.135 5 31.994 18.7 26.232 1.75 20.246 100.3 4.4 4.50 1.37 3.2 27.815 18.496 1.35 32.415 20.6 27.580 1.79 270 102.0 4.5 6.00 2.46 5.7 28.168 18.685 1.30 32.617 21.6 28.307 1.81 22.128 102.9 4.6 3.00 0.46 1.1 25.868 17.644 1.61 31.375 16.0 29.033 1.83 22.783 103.8 4.6 4.50 1.24 2.9 26.731 17.990 9 31.816 17.9 30.491 1.88 24.092 105.6 4.8 6.00 2.24 5.2 27.136 18.168 4 32.035 18.9 31.268 1.90 24.786 106.5 4.8 3.00 0.46 1.1 24.477 17.148 1.83 30.736 13.3 31.727 1.91 25.194 107.1 4.9 4.50 1.19 2.7 25.463 17.493 1.68 31.180 15.2 33.251 1.97 26.540 109.0 5.0 6.00 2.10 4.9 25.928 17.667 1.61 304 16.2 34.050 2.00 27.239 109.9 5.0 3.00 0.48 1.1 22.862 16.612 2.12 30.105 10.8 34.278 2.01 27.437 110.2 5.0 4.50 1.16 2.7 23.984 16.982 1.92 30.531 12.5 35.816 2.07 28.761 112.1 5.1 6.00 2.03 4.7 24.515 17.160 1.83 30.752 13.4 36.604 2.10 29.427 113.1 5.1 3.00 0.49 1.1 20.994 15.983 2.49 29.505 8.4 4.50 1.15 2.7 22.265 16.414 2.24 29.899 10.0 6.00 1.98 4.6 22.869 16.614 2.12 30.107 10.8 3.00 0.45 1.0 18.841 15.184 2.97 28.963 6.4 4.50 1.10 2.6 20.277 15.729 2.65 29.308 7.7 6.00 1.92 4.4 20.960 15.971 2.50 29.495 8.4 3.00 0.33 0.8 16.369 14.104 3.56 28.507 4.6 4.50 1.01 2.3 17.989 14.834 3.16 28.788 5.7 Operation Not Recommended 6.00 1.83 4.2 18.760 15.152 2.99 28.946 6.3 Interpolation is permissible; extrapolation is not. All enterg air conditions are 80 F DB and 67 F WB coolg, and 70 F DB heatg. AHRI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB coolg and 68 F DB heatg. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. Operation below 60 F EWT requires optional sulated water/refrigerant circuit. See performance correction tables for operatg conditions other than those listed above. See Performance Data Selection Notes for operation the shaded areas. For quiet operation and long term reliability it is recommended that systems be designed to avoid contuous operation the outled areas. If operation the shaded area is required please refer to the TE or TZ product family. LC992-12

Performance Data TY H/V 030 (Part Load) 750 CFM Nomal (Rated) Airflow Coolg, 750 CFM Nomal (Rated) Airflow Heatg EWT F 20 30 40 50 60 70 80 90 100 110 120 GPM Interpolation is permissible; 6.0 extrapolation 1.8is not. 4.1 17.9 13.6 2.32 25.8 7.7 All enterg air conditions are 80 F DB and 67 F WB coolg, and 70 F DB heatg. AHRI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB coolg and 68 F DB heatg. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. Operation below 60 F EWT requires optional sulated water/refrigerant circuit. See performance correction tables for operatg conditions other than those listed above. See Performance Data Selection Notes for operation the shaded areas. For quiet operation and long term reliability it is recommended that systems be designed to avoid contuous operation the outled areas. If operation the shaded area is required please refer to the TE or TZ product family. Performance capacities shown thousands of Btuh WPD COOLING - EAT 80/67 F HEATING - EAT 68 F PSI FT TC SC kw HR EER HC kw HE LAT COP 6.0 4.4 10.2 15.7 9 10.6 87.3 3.1 3.0 1.6 3.6 27.1 17.7 0.85 30.0 31.9 17.2 1.51 12.0 89.1 3.3 4.5 2.5 5.8 27.3 17.7 0.79 30.0 34.5 17.8 1.52 12.6 89.9 3.4 6.0 3.6 8.4 27.3 17.8 0.77 29.9 35.7 18.2 1.52 13.0 90.4 3.5 3.0 1.2 2.8 26.5 17.4 0.96 29.8 27.7 19.5 1.55 14.2 92.0 3.7 4.5 2.0 4.7 26.9 17.6 0.88 30.0 30.5 20.3 1.56 14.9 92.9 3.8 6.0 3.1 7.1 27.1 17.7 0.85 30.0 31.9 20.7 1.56 15.3 93.5 3.9 3.0 0.9 2.0 25.7 17.1 1.09 29.4 23.6 21.8 1.58 16.4 94.9 4.0 4.5 1.6 3.6 26.3 17.3 1.00 29.7 26.3 22.7 1.60 17.3 96.0 4.2 6.0 2.6 6.1 26.5 17.4 0.96 29.8 27.7 23.2 1.61 17.7 96.6 4.2 3.0 0.8 1.9 24.6 16.6 1.23 28.8 19.9 24.2 1.62 18.7 97.8 4.4 4.5 1.5 3.4 25.3 16.9 1.14 29.2 22.3 25.2 1.64 19.6 99.1 4.5 6.0 2.3 5.3 25.6 17.1 1.09 29.4 23.6 25.8 1.65 20.2 99.8 4.6 3.0 0.8 1.8 23.4 16.1 0 28.2 16.7 26.6 1.66 20.9 100.7 4.7 4.5 3.2 24.2 16.4 1.29 28.6 18.7 27.7 1.68 22.0 102.2 4.8 6.0 2.2 5.0 24.5 16.6 1.24 28.8 19.8 28.4 1.69 22.6 102.9 4.9 3.0 0.8 1.8 22.1 15.5 1.59 27.5 13.9 29.0 1.70 23.2 103.7 5.0 4.5 3.2 22.9 15.9 7 27.9 15.5 30.2 1.72 24.4 105.3 5.2 6.0 2.1 4.9 23.3 16.1 1 28.1 16.5 30.9 1.73 25.1 106.1 5.3 3.0 0.8 1.8 20.7 14.9 1.80 26.8 11.5 31.3 1.73 25.4 106.6 5.3 4.5 3.2 21.5 15.3 1.67 27.2 12.9 32.8 1.75 26.8 108.3 5.5 6.0 2.1 4.8 21.9 15.5 1.61 27.4 13.6 33.5 1.75 27.5 109.3 5.6 3.0 0.7 1.7 19.3 14.3 2.03 26.3 9.5 4.5 1.3 3.0 20.1 14.7 1.89 26.6 10.6 6.0 2.0 4.6 20.5 14.8 1.83 26.8 11.3 3.0 0.7 1.5 18.0 13.7 2.29 25.8 7.9 4.5 1.2 2.8 18.8 14.0 2.14 26.1 8.8 6.0 1.9 4.4 19.2 14.2 2.06 26.2 9.3 3.0 0.6 16.8 13.2 2.56 25.6 6.6 4.5 1.1 2.6 17.5 13.5 2.40 25.7 7.3 Operation Not Recommended LC992-13

Performance Data TY H/V 030 (Full Load) 900 CFM Nomal (Rated) Airflow Coolg, 900 CFM Nomal (Rated) Airflow Heatg EWT F GPM Performance capacities shown thousands of Btuh WPD COOLING - EAT 80/67 F HEATING - EAT 68 F PSI FT TC SC kw HR EER HC kw HE LAT COP 20 30 40 50 60 70 80 90 100 110 120 7.5 5.8 13.5 21.8 1.93 15.2 89.2 3.3 3.8 2.0 4.7 35.3 21.8 0 40.1 25.3 23.5 1.99 16.7 90.9 3.5 5.6 3.3 7.7 35.7 22.0 1.31 40.2 27.3 24.5 2.02 17.6 91.8 3.6 7.5 4.9 1 35.8 22.0 1.27 40.1 28.3 25.0 2.03 18.0 92.3 3.6 3.8 1.6 3.7 34.5 21.5 1.53 39.7 22.6 26.6 2.08 19.5 93.8 3.7 5.6 1.8 4.2 35.1 21.7 3 40.0 24.5 27.7 2.11 20.5 94.9 3.8 7.5 1.8 4.2 35.4 21.8 1.39 40.1 25.5 28.3 2.13 21.0 95.5 3.9 3.8 1.2 2.8 33.5 21.0 1.67 39.2 20.0 29.7 2.17 22.3 96.9 4.0 5.6 2.2 5.1 34.2 2 1.57 39.6 21.8 31.0 2.21 23.5 98.2 4.1 7.5 3.5 8.1 34.6 21.5 1.52 39.8 22.8 31.7 2.23 24.1 98.9 4.2 3.8 1.2 2.7 32.1 20.5 1.84 38.4 17.5 32.9 2.27 25.1 100.0 4.2 5.6 2.0 4.6 33.1 20.9 1.72 38.9 19.2 34.4 2.31 26.5 10 4.4 7.5 3.3 7.6 33.5 21.1 1.67 39.2 20.1 35.2 2.34 27.2 102.2 4.4 3.8 1.1 2.5 30.7 19.9 2.03 37.6 15.1 36.0 2.36 28.0 103.0 4.5 5.6 1.9 4.5 31.7 20.3 1.90 38.1 16.7 37.7 2.41 29.4 104.6 4.6 7.5 3.1 7.2 32.2 20.5 1.83 38.4 17.6 38.6 2.44 30.2 105.5 4.6 3.8 1.1 2.5 29.0 19.2 2.24 36.7 13.0 39.2 2.46 30.8 106.1 4.7 5.6 1.9 4.4 30.1 19.7 2.09 37.3 14.4 40.9 2.52 32.4 107.8 4.8 7.5 3.0 7.0 30.7 19.9 2.02 37.6 15.1 41.9 2.55 33.2 108.7 4.8 3.8 1.1 2.5 27.3 18.5 2.49 35.8 11.0 42.2 2.56 33.5 109.1 4.8 5.6 1.9 4.3 28.4 19.0 2.32 36.4 12.2 44.1 2.62 35.2 110.9 4.9 7.5 2.9 6.8 29.0 19.2 2.25 36.7 12.9 45.1 2.66 36.0 111.8 5.0 3.8 1.0 2.3 25.6 17.7 2.77 35.0 9.2 5.6 1.8 4.1 26.7 18.2 2.59 35.5 10.3 7.5 2.8 6.5 27.2 18.4 2.50 35.8 10.9 3.8 0.9 2.2 23.8 16.9 3.10 34.4 7.7 5.6 1.7 3.9 24.9 17.4 2.89 34.8 8.6 Operation Not Recommended 7.5 2.7 6.2 25.5 17.6 2.79 35.0 9.1 3.8 0.9 2.0 5.6 1.6 3.7 23.1 16.5 3.24 34.2 7.1 7.5 2.6 6.0 23.7 16.8 3.13 34.4 7.6 Interpolation is permissible; extrapolation is not. All enterg air conditions are 80 F DB and 67 F WB coolg, and 70 F DB heatg. AHRI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB coolg and 68 F DB heatg. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. Operation below 60 F EWT requires optional sulated water/refrigerant circuit. See performance correction tables for operatg conditions other than those listed above. See Performance Data Selection Notes for operation the shaded areas. For quiet operation and long term reliability it is recommended that systems be designed to avoid contuous operation the outled areas. If operation the shaded area is required please refer to the TE or TZ product family. LC992-14

Performance Data TY H/V 036 (Part Load) 950 CFM Nomal (Rated) Airflow Coolg, 950 CFM Nomal (Rated) Airflow Heatg EWT F Performance capacities shown thousands of Btuh WATER / BRINE COOLING - EAT 80/67 F HEATING - EAT 68 F FLOW GPM PD PSI PD FT TC SC kw HR EER HC kw HE LAT COP 20 30 40 50 60 70 80 90 100 110 120 8.00 4.08 9.4 16.886 1.65 11.250 84.4 3.0 4.00 0.53 1.2 31.006 21.641 0.84 33.877 36.8 19.155 1.67 13.461 86.6 3.4 6.00 1.75 4.0 30.827 21.169 0.79 33.533 38.9 19.900 1.67 14.185 87.4 3.5 8.00 3.29 7.6 30.672 20.865 0.77 33.307 39.7 20.302 1.68 14.576 87.7 3.5 4.00 0.23 0.5 30.914 22.051 0.95 34.146 32.6 22.296 1.70 16.511 89.7 3.9 6.00 1.30 3.0 31.027 21.881 0.88 34.043 35.1 23.201 1.70 17.388 90.6 4.0 8.00 2.70 6.2 31.024 21.736 0.86 33.944 36.3 23.689 1.71 17.860 91.0 4.1 4.00 0.07 0.2 30.373 22.016 1.08 34.055 28.1 25.404 1.73 19.518 92.7 4.3 6.00 1.00 2.3 30.731 22.084 1.00 34.146 30.7 26.456 1.74 20.534 93.7 4.5 8.00 2.27 5.3 30.860 22.071 0.97 34.153 32.0 27.022 1.74 21.080 94.3 4.5 4.00 0.06 0.1 29.464 21.653 1.24 33.686 23.8 28.459 1.76 22.466 95.7 4.7 6.00 0.82 1.9 30.019 21.892 1.14 33.924 26.2 29.643 1.77 23.606 96.8 4.9 8.00 1.99 4.6 30.258 21.979 1.10 34.015 27.5 30.276 1.78 24.214 97.4 5.0 4.00 0.05 0.1 28.257 21.070 2 33.113 19.9 344 1.79 25.338 98.6 5.1 6.00 0.72 1.7 28.963 217 1.32 33.453 22.0 32.738 1.80 26.581 99.8 5.3 8.00 1.81 4.2 29.289 21.572 1.27 33.606 23.2 33.425 1.81 27.242 100.5 5.4 4.00 0.04 0.1 26.813 20.355 1.64 32.401 16.4 34.337 1.82 28.117 10 5.5 6.00 0.69 1.6 27.628 20.757 1.52 32.803 18.2 35.718 1.84 29.442 102.7 5.7 8.00 1.72 4.0 28.019 20.952 6 32.996 19.2 36.446 1.85 30.139 103.4 5.8 4.00 0.09 0.2 25.188 19.581 1.88 31.614 13.4 37.121 1.86 30.786 104.1 5.9 6.00 0.70 1.6 26.075 19.998 1.75 32.040 14.9 38.559 1.87 32.165 105.5 6.0 8.00 1.68 3.9 26.510 20.208 1.68 32.253 15.8 39.310 1.88 32.884 106.2 6.1 4.00 0.13 0.3 23.435 18.804 2.16 30.809 10.8 6.00 0.71 1.6 24.360 19.206 2.01 31.226 12.1 8.00 1.67 3.9 24.822 19.413 1.94 341 12.8 4.00 0.13 0.3 21.604 18.065 2.47 30.046 8.7 6.00 0.69 1.6 22.539 18.433 2.31 30.424 9.8 Operation Not Recommended 8.00 1.66 3.8 23.010 18.626 2.23 30.624 10.3 4.00 0.05 0.1 19.746 17.397 2.82 29.384 7.0 6.00 0.63 1.5 20.665 17.717 2.65 29.695 7.8 8.00 1.62 3.7 21.133 17.888 2.56 29.866 8.3 Interpolation is permissible; extrapolation is not. All enterg air conditions are 80 F DB and 67 F WB coolg, and 70 F DB heatg. AHRI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB coolg and 68 F DB heatg. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. Operation below 60 F EWT requires optional sulated water/refrigerant circuit. See performance correction tables for operatg conditions other than those listed above. See Performance Data Selection Notes for operation the shaded areas. For quiet operation and long term reliability it is recommended that systems be designed to avoid contuous operation the outled areas. If operation the shaded area is required please refer to the TE or TZ product family. LC992-15

Performance Data TY H/V 036 (Full Load) 1150 CFM Nomal (Rated) Airflow Coolg, 1150 CFM Nomal (Rated) Airflow Heatg EWT F Performance capacities shown thousands of Btuh WATER / BRINE COOLING - EAT 80/67 F HEATING - EAT 68 F FLOW GPM PD PSI PD FT TC SC kw HR EER HC kw HE LAT COP 20 30 40 50 60 70 80 90 100 110 120 9.00 4.97 11.5 24.931 2.31 17.044 88.0 3.2 4.50 0.79 1.8 41.039 27.311 1.55 46.314 26.5 27.340 2.36 19.303 90.0 3.4 6.80 2.34 5.4 40.992 26.970 6 45.963 28.1 28.540 2.38 20.424 90.9 3.5 9.00 4.10 9.5 40.878 26.733 2 45.710 28.9 29.167 2.39 21.008 9 3.6 4.50 0.45 1.1 40.682 27.464 1.69 46.433 24.1 31.266 2.43 22.958 93.1 3.8 6.80 1.84 4.2 40.981 27.396 1.59 46.394 25.8 32.709 2.47 24.292 94.3 3.9 9.00 3.44 7.9 41.042 27.301 1.54 46.304 26.6 33.461 2.48 24.986 94.9 3.9 4.50 0.25 0.6 39.889 27.291 1.84 46.184 21.6 35.222 2.53 26.603 96.3 4.1 6.80 8 3.4 40.485 27.443 1.73 46.392 23.4 36.897 2.57 28.132 97.6 4.2 9.00 2.95 6.8 40.700 27.465 1.68 46.435 24.2 37.767 2.59 28.923 98.3 4.3 4.50 0.15 0.4 38.728 26.867 2.03 45.656 19.1 39.178 2.63 30.200 99.5 4.4 6.80 1.26 2.9 39.569 27.185 1.90 46.047 20.8 41.065 2.69 31.896 101.0 4.5 9.00 2.62 6.0 39.915 27.300 1.84 46.194 21.7 42.040 2.72 32.766 101.8 4.5 4.50 0.13 0.3 37.253 26.255 2.25 44.928 16.6 43.101 2.75 33.709 102.6 4.6 6.80 1.13 2.6 38.292 26.691 2.10 45.443 18.3 45.172 2.82 35.535 104.3 4.7 9.00 2.40 5.6 38.747 26.875 2.03 45.665 19.1 46.232 2.86 36.461 105.1 4.7 4.50 0.15 0.4 35.513 25.504 2.51 44.072 14.2 46.958 2.89 37.091 105.7 4.8 6.80 1.07 2.5 36.708 26.021 2.33 44.657 15.8 49.174 2.98 38.998 107.5 4.8 9.00 2.28 5.3 37.250 26.254 2.25 44.926 16.6 50.297 3.03 39.953 108.4 4.9 4.50 0.19 0.4 33.552 24.657 2.81 43.156 11.9 50.712 3.05 40.303 108.7 4.9 6.80 1.06 2.5 34.864 25.224 2.61 43.762 13.4 53.026 3.16 42.232 110.6 4.9 9.00 2.23 5.2 35.473 25.487 2.51 44.053 14.1 54.185 3.23 43.180 111.5 4.9 4.50 0.22 0.5 311 23.741 3.18 42.247 9.9 6.80 1.06 2.5 32.808 24.337 2.94 42.828 11.2 9.00 2.21 5.1 33.466 24.619 2.83 43.118 11.8 4.50 0.21 0.5 29.128 22.779 3.60 412 8.1 6.80 1.05 2.4 30.581 23.390 3.33 41.926 9.2 Operation Not Recommended 9.00 2.20 5.1 31.272 23.682 3.20 42.192 9.8 4.50 0.14 0.3 26.741 21.782 4.10 40.718 6.5 6.80 0.99 2.3 28.227 22.402 3.78 41.126 7.5 9.00 2.18 5.0 28.938 22.699 3.64 41.349 8.0 Interpolation is permissible; extrapolation is not. All enterg air conditions are 80 F DB and 67 F WB coolg, and 70 F DB heatg. AHRI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB coolg and 68 F DB heatg. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. Operation below 60 F EWT requires optional sulated water/refrigerant circuit. See performance correction tables for operatg conditions other than those listed above. See Performance Data Selection Notes for operation the shaded areas. For quiet operation and long term reliability it is recommended that systems be designed to avoid contuous operation the outled areas. If operation the shaded area is required please refer to the TE or TZ product family. LC992-16

Performance Data TY H/V 042 (Part Load) 1100 CFM Nomal (Rated) Airflow Coolg, 1100 CFM Nomal (Rated) Airflow Heatg EWT F GPM Performance capacities shown thousands of Btuh WPD COOLING - EAT 80/67 F HEATING - EAT 68 F PSI FT TC SC kw HR EER HC kw HE LAT COP 20 30 40 50 60 70 80 90 100 110 120 7.5 5.1 11.9 19.8 2.09 12.7 84.6 2.8 3.8 1.6 3.6 38.1 28.2 1.15 42.0 33.1 22.1 2.12 14.9 86.6 3.1 5.6 2.8 6.4 38.3 27.9 1.06 41.9 36.3 23.1 2.13 15.8 87.4 3.2 7.5 4.3 10.0 38.3 27.6 1.02 41.8 37.6 23.7 2.14 16.4 87.9 3.2 3.8 1.2 2.9 37.4 28.2 1.31 41.8 28.6 25.6 2.16 18.3 89.5 3.5 5.6 1.6 3.7 38.0 28.3 1.19 42.0 32.0 26.8 2.17 19.4 90.5 3.6 7.5 1.6 3.7 38.1 28.2 1.13 42.0 33.7 27.5 2.18 20.1 91.1 3.7 3.8 1.0 2.4 36.3 27.8 9 4 24.3 29.1 2.19 21.6 92.5 3.9 5.6 2.0 4.5 37.1 28.1 1.35 41.7 27.5 30.5 2.20 23.0 93.6 4.1 7.5 3.1 7.2 37.5 28.2 1.29 41.9 29.2 31.3 2.21 23.8 94.3 4.2 3.8 1.0 2.3 34.8 27.1 1.71 40.7 20.4 32.5 2.22 25.0 95.3 4.3 5.6 1.8 4.2 35.9 27.6 1.55 41.2 23.2 34.1 2.23 26.5 96.7 4.5 7.5 3.0 6.9 36.4 27.9 7 4 24.7 35.0 2.24 27.3 97.4 4.6 3.8 0.9 2.1 33.1 26.3 1.95 39.8 16.9 35.9 2.25 28.2 98.1 4.7 5.6 1.7 4.0 34.4 26.9 1.78 40.4 19.3 37.6 2.26 29.9 99.6 4.9 7.5 2.8 6.5 35.0 27.2 1.69 40.7 20.7 38.6 2.27 30.8 100.4 5.0 3.8 0.9 2.1 31.1 25.4 2.22 38.7 14.0 39.1 2.27 3 100.9 5.1 5.6 1.7 3.9 32.5 26.0 2.03 39.5 16.0 41.0 2.28 33.2 102.4 5.3 7.5 2.7 6.3 33.2 26.4 1.94 39.8 17.1 41.9 2.29 34.1 103.2 5.4 3.8 0.9 2.0 29.0 24.5 2.51 37.6 11.5 42.2 2.29 34.4 103.4 5.4 5.6 1.6 3.8 30.5 25.1 2.31 38.4 13.2 44.1 2.30 36.2 105.0 5.6 7.5 2.6 6.1 31.2 25.4 2.21 38.8 14.1 45.1 2.31 37.2 105.9 5.7 3.8 0.9 2.0 26.8 23.6 2.83 36.4 9.5 5.6 1.6 3.6 28.3 24.2 2.62 37.2 10.8 7.5 2.6 5.9 29.0 24.5 2.51 37.6 11.5 3.8 0.8 1.9 24.5 22.7 3.16 35.3 7.7 5.6 1.5 3.5 26.0 23.3 2.94 36.0 8.8 Operation Not Recommended 7.5 2.5 5.7 26.7 23.5 2.84 36.4 9.4 3.8 0.8 1.8 5.6 1.5 3.4 23.6 22.4 3.29 34.8 7.2 7.5 2.4 5.5 24.3 22.7 3.18 35.2 7.6 Interpolation is permissible; extrapolation is not. All enterg air conditions are 80 F DB and 67 F WB coolg, and 70 F DB heatg. AHRI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB coolg and 68 F DB heatg. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. Operation below 60 F EWT requires optional sulated water/refrigerant circuit. See performance correction tables for operatg conditions other than those listed above. See Performance Data Selection Notes for operation the shaded areas. For quiet operation and long term reliability it is recommended that systems be designed to avoid contuous operation the outled areas. If operation the shaded area is required please refer to the TE or TZ product family. LC992-17

Performance Data TY H/V 042 (Full Load) 1300 CFM Nomal (Rated) Airflow Coolg, 1300 CFM Nomal (Rated) Airflow Heatg EWT F GPM Performance capacities shown thousands of Btuh WPD COOLING - EAT 80/67 F HEATING - EAT 68 F PSI FT TC SC kw HR EER HC kw HE LAT COP 20 30 40 50 60 70 80 90 100 110 120 10.5 8.3 19.3 29.6 2.83 19.9 89.0 3.1 5.3 2.5 5.8 50.4 36.7 1.94 57.0 25.9 32.4 2.89 22.5 91.0 3.3 7.9 4.7 10.8 51.1 37.2 1.83 57.3 28.0 33.7 2.93 23.7 92.0 3.4 10.5 7.2 16.7 51.3 37.3 1.77 57.4 29.0 34.4 2.94 24.4 92.5 3.4 5.3 2.1 4.8 49.2 35.9 2.12 56.4 23.2 36.9 3.00 26.6 94.2 3.6 7.9 2.2 5.1 50.1 36.5 1.99 56.9 25.2 38.5 3.04 28.1 95.3 3.7 10.5 2.2 5.1 50.5 36.8 1.93 57.1 26.2 39.3 3.06 28.9 95.9 3.8 5.3 1.8 4.1 47.8 35.0 2.32 55.7 20.6 41.3 3.11 30.7 97.4 3.9 7.9 3.4 7.9 48.8 35.7 2.17 56.2 22.5 43.2 3.15 32.4 98.7 4.0 10.5 5.4 12.5 49.3 36.0 2.11 56.5 23.4 44.1 3.18 33.3 99.4 4.1 5.3 1.7 3.9 46.1 34.1 2.55 54.7 18.1 45.8 3.22 34.8 100.5 4.2 7.9 3.2 7.5 47.3 34.8 2.38 55.4 19.8 47.8 3.27 36.6 102.0 4.3 10.5 5.2 11.9 47.9 35.1 2.31 55.7 20.7 48.9 3.30 37.6 102.8 4.3 5.3 1.6 3.6 44.1 33.1 2.81 53.7 15.7 50.1 3.33 38.8 103.6 4.4 7.9 3.1 7.1 45.5 33.8 2.62 54.4 17.3 52.4 3.39 40.8 105.2 4.5 10.5 4.9 11.3 46.1 34.1 2.54 54.8 18.2 53.5 3.42 41.9 106.0 4.6 5.3 1.5 3.5 42.0 32.2 3.10 52.6 13.5 54.4 3.45 42.6 106.7 4.6 7.9 3.0 6.9 43.5 32.8 2.90 53.3 15.0 56.8 3.52 44.8 108.3 4.7 10.5 4.8 11.0 44.2 33.1 2.80 53.7 15.8 58.0 3.55 45.9 109.2 4.8 5.3 1.5 3.4 39.6 31.3 3.44 5 11.5 58.5 3.57 46.4 109.6 4.8 7.9 2.9 6.6 41.2 31.8 3.21 52.2 12.8 61.0 3.65 48.6 11 4.9 10.5 4.7 10.7 42.0 32.2 3.10 52.6 13.5 62.3 3.69 49.7 112.3 5.0 5.3 3.3 37.1 30.4 3.82 50.2 9.7 7.9 2.8 6.4 38.8 31.0 3.57 51.0 10.9 10.5 4.5 10.4 39.6 31.2 3.45 5 11.5 5.3 3.2 34.5 29.6 4.26 49.0 8.1 7.9 2.7 6.2 36.2 30.1 3.98 49.7 9.1 Operation Not Recommended 10.5 4.4 10.1 37.0 30.4 3.84 50.1 9.6 5.3 1.3 3.1 7.9 2.6 6.0 33.4 29.3 4.44 48.5 7.5 10.5 4.2 9.8 34.3 29.6 4.29 48.9 8.0 Interpolation is permissible; extrapolation is not. All enterg air conditions are 80 F DB and 67 F WB coolg, and 70 F DB heatg. AHRI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB coolg and 68 F DB heatg. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. Operation below 60 F EWT requires optional sulated water/refrigerant circuit. See performance correction tables for operatg conditions other than those listed above. See Performance Data Selection Notes for operation the shaded areas. For quiet operation and long term reliability it is recommended that systems be designed to avoid contuous operation the outled areas. If operation the shaded area is required please refer to the TE or TZ product family. LC992-18

Performance Data TY H/V 048 (Part Load) 1250 CFM Nomal (Rated) Airflow Coolg, 1250 CFM Nomal (Rated) Airflow Heatg EWT F GPM Performance capacities shown thousands of Btuh WPD COOLING - EAT 80/67 F HEATING - EAT 68 F PSI FT TC SC kw HR EER HC kw HE LAT COP 20 30 40 50 60 70 80 90 100 110 120 9.0 5.0 11.5 23.1 2.18 15.6 85.0 3.1 4.5 3.3 41.6 28.3 1.37 46.3 30.4 25.3 2.20 17.8 86.7 3.4 6.8 2.7 6.3 42.0 28.2 1.28 46.3 32.7 26.3 2.20 18.8 87.4 3.5 9.0 4.3 9.9 42.0 28.0 1.25 46.3 33.6 26.8 2.21 19.3 87.8 3.6 4.5 1.1 2.6 40.8 28.2 1.54 46.1 26.6 28.8 2.22 21.3 89.3 3.8 6.8 1.3 2.9 4 28.3 2 46.3 29.3 30.0 2.22 22.4 90.2 4.0 9.0 1.3 2.9 41.7 28.3 1.37 46.3 30.5 30.7 2.23 23.1 90.7 4.0 4.5 1.1 2.5 39.9 27.8 1.72 45.7 23.3 32.4 2.24 24.8 92.0 4.3 6.8 2.1 4.9 40.8 28.2 1.57 46.1 26.0 33.8 2.24 26.2 93.0 4.4 9.0 3.4 7.9 41.2 28.3 1.50 46.3 27.4 34.6 2.25 26.9 93.6 4.5 4.5 1.0 2.3 38.3 27.2 1.98 45.1 19.4 36.1 2.25 28.4 94.6 4.7 6.8 2.0 4.6 39.4 27.6 1.79 45.5 22.0 37.7 2.26 30.0 95.8 4.9 9.0 3.2 7.5 39.9 27.9 1.71 45.8 23.3 38.5 2.26 30.8 96.5 5.0 4.5 0.9 2.0 36.5 26.3 2.28 44.2 16.0 39.7 2.27 31.9 97.3 5.1 6.8 1.8 4.2 37.7 26.9 2.07 44.8 18.2 4 2.28 33.7 98.6 5.3 9.0 3.0 6.9 38.3 27.2 1.97 45.1 19.4 42.4 2.28 34.6 99.3 5.4 4.5 0.9 2.0 34.4 25.4 2.63 43.3 13.1 43.2 2.28 35.4 99.9 5.5 6.8 1.8 4.0 35.8 26.0 2.40 43.9 14.9 45.1 2.29 37.3 101.3 5.8 9.0 2.9 6.7 36.4 26.3 2.29 44.2 15.9 46.5 2.41 38.3 102.4 5.7 4.5 0.8 1.8 32.1 24.5 3.01 42.4 10.7 47.0 2.41 38.8 102.7 5.7 6.8 1.7 3.9 33.6 25.1 2.76 43.0 12.2 49.0 2.42 40.8 104.2 5.9 9.0 2.8 6.5 34.3 25.4 2.64 43.3 13.0 50.0 2.42 41.8 105.0 6.1 4.5 0.8 1.8 29.7 23.5 3.42 4 8.7 6.8 1.6 3.7 31.2 24.1 3.16 42.0 9.9 9.0 2.7 6.1 32.0 24.4 3.03 42.3 10.5 4.5 0.7 1.7 27.3 22.6 3.86 40.5 7.1 6.8 1.5 3.5 28.8 23.2 3.59 41.0 8.0 Operation Not Recommended 9.0 2.6 5.9 29.5 23.4 3.46 41.3 8.5 4.5 0.7 1.7 24.8 21.8 4.32 39.5 5.8 6.8 1.5 3.5 26.3 22.3 4.04 40.1 6.5 9.0 2.5 5.9 27.0 22.5 3.90 40.4 6.9 Interpolation is permissible; extrapolation is not. All enterg air conditions are 80 F DB and 67 F WB coolg, and 70 F DB heatg. AHRI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB coolg and 68 F DB heatg. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. Operation below 60 F EWT requires optional sulated water/refrigerant circuit. See performance correction tables for operatg conditions other than those listed above. See Performance Data Selection Notes for operation the shaded areas. For quiet operation and long term reliability it is recommended that systems be designed to avoid contuous operation the outled areas. If operation the shaded area is required please refer to the TE or TZ product family. LC992-19

Performance Data TY H/V 048 (Full Load) 1500 CFM Nomal (Rated) Airflow Coolg, 1500 CFM Nomal (Rated) Airflow Heatg EWT F GPM Performance capacities shown thousands of Btuh WPD COOLING - EAT 80/67 F HEATING - EAT 68 F PSI FT TC SC kw HR EER HC kw HE LAT COP 20 30 40 50 60 70 80 90 100 110 120 12.0 7.6 17.5 32.4 2.88 22.6 88.0 3.3 6.0 2.2 5.2 55.7 36.8 2.32 63.6 24.0 35.2 2.93 25.1 89.6 3.5 9.0 4.3 9.9 56.2 36.8 2.21 63.7 25.4 36.5 2.96 26.4 90.5 3.6 12.0 6.7 15.6 56.3 36.7 2.17 63.7 26.0 37.2 2.97 27.0 90.9 3.7 6.0 1.9 4.4 54.5 36.4 2.51 63.1 21.8 39.7 3.02 29.4 92.5 3.9 9.0 3.8 8.7 55.4 36.7 2.37 63.5 23.4 4 3.05 30.9 93.5 4.0 12.0 6.1 14.0 55.7 36.8 2.31 63.6 24.1 42.3 3.07 31.8 94.0 4.0 6.0 1.7 4.0 53.0 35.6 2.58 61.8 20.5 44.6 3.12 33.9 95.4 4.2 9.0 3.4 7.9 53.8 36.0 2.43 62.1 22.2 46.5 3.16 35.7 96.6 4.3 12.0 5.5 12.7 54.1 36.1 2.36 62.2 22.9 47.6 3.18 36.7 97.3 4.4 6.0 1.6 3.7 51.3 34.9 2.86 61.0 17.9 49.5 3.22 38.5 98.5 4.5 9.0 3.2 7.5 52.5 35.4 2.66 61.6 19.7 51.8 3.26 40.7 99.9 4.7 12.0 5.3 12.2 53.0 35.6 2.57 61.8 20.6 53.0 3.29 41.8 100.7 4.7 6.0 3.3 49.1 34.0 3.21 60.0 15.3 54.6 3.32 43.2 101.6 4.8 9.0 3.0 6.9 50.6 34.7 2.96 60.7 17.1 57.2 3.38 45.6 103.2 5.0 12.0 4.9 11.3 51.3 34.9 2.85 61.0 18.0 58.6 3.41 46.9 104.1 5.0 6.0 3.3 46.5 33.0 3.62 58.9 12.8 59.7 3.44 47.9 104.7 5.1 9.0 2.9 6.7 48.2 33.7 3.34 59.6 14.4 62.5 3.50 50.5 106.5 5.2 12.0 4.8 11.1 49.1 34.0 3.21 60.0 15.3 64.5 3.69 51.9 107.7 5.1 6.0 1.3 3.1 43.8 31.9 4.11 57.8 10.7 65.2 3.71 52.5 108.2 5.2 9.0 2.8 6.5 45.6 32.6 3.79 58.5 12.0 68.2 3.79 55.3 110.0 5.3 12.0 4.7 10.9 46.5 33.0 3.63 58.9 12.8 69.9 3.83 56.8 111.0 5.3 6.0 1.3 3.0 41.0 30.7 4.67 57.0 8.8 9.0 2.7 6.1 42.8 31.5 4.31 57.5 9.9 12.0 4.5 10.4 43.7 31.8 4.13 57.8 10.6 6.0 1.2 2.8 38.3 29.5 5.32 56.5 7.2 9.0 2.6 5.9 40.0 30.3 4.90 56.7 8.2 Operation Not Recommended 12.0 4.4 10.1 40.9 30.6 4.70 56.9 8.7 6.0 1.2 2.8 9.0 2.6 5.9 12.0 4.3 10.0 38.2 29.5 5.36 56.4 7.1 Interpolation is permissible; extrapolation is not. All enterg air conditions are 80 F DB and 67 F WB coolg, and 70 F DB heatg. AHRI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB coolg and 68 F DB heatg. Table does not refl ect fan or pump power corrections for AHRI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. Operation below 60 F EWT requires optional sulated water/refrigerant circuit. See performance correction tables for operatg conditions other than those listed above. See Performance Data Selection Notes for operation the shaded areas. For quiet operation and long term reliability it is recommended that systems be designed to avoid contuous operation the outled areas. If operation the shaded area is required please refer to the TE or TZ product family. LC992-20