B. Provide unique numbers for all applicable equipment, valves, and similar.

Similar documents
C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

HVAC BASIC MATERIAL AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

DUKE UNIVERSITY CONSTRUCTION STANDARDS

DESIGN STANDARDS SECTION PLUMBING FIXTURES AND EQUIPMENT. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.

SECTION PLUMBING

DESIGN STANDARDS SECTION Toilet rooms and utility rooms to have floor drains at lowest point.

SECTION LABORATORY and DE-IONIZED WATER SYSTEMS STANDARD CONSTRUCTION STANDARD

AIRPORT PLUMBING DESIGN STANDARDS REV. 2 11/02/2015

OKLAHOMA STATE UNIVERSITY - BUILDING DESIGN STANDARDS

LAV FCO WCO NOTES: CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR MOUNT HEIGHTS AND SPECIAL MOUNTING INSTRUCTION AND LIMITATIONS.

DOMESTIC WATER PACKAGED BOOSTER PUMPS

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD

A. Section Joint Sealants: Seal fixtures to walls and floors.

AIRPORT PLUMBING DESIGN STANDARDS REV. 3 3/18/2016

UNIVERSITY OF MISSOURI Building Hydronic Piping and Pump Systems 2017 Q3

SECTION BASIC MATERIALS AND METHODS

DIVISION 15 MECHANICAL

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

HWC NOTES: CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR MOUNT HEIGHTS AND SPECIAL MOUNTING INSTRUCTION AND LIMITATIONS.

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

A. This Section includes the following domestic water piping specialties:

SECTION DOMESTIC WATER PIPING SPECIALTIES

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

A. All fixtures shall meet the requirements of ANSI A117.1, ANSI Z124.2 and the State of Texas Accessibility Standards (TAS).

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

1.1 This section applies to air handling units for HVAC Systems.

PLUMBING DESIGN GUIDELINES SECTION DESIGN GUIDELINES DUVAL COUNTY PUBLIC SCHOOLS

DIVISION 22: PLUMBING DESIGN STANDARDS TABLE OF CONTENTS

SECTION HYDRONIC PIPING AND SPECIALTIES

DESIGN GUIDELINES AND TECHNICAL STANDARDS

ICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."

2. All necessary storm and sanitary pumps shall be tied into emergency power, and sump levels shall be monitored electronically through the B.A.S.

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

GENERAL PLUMBING REQUIREMENTS

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

SECTION HYDRONIC PIPING

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D20 PLUMBING 02/18

Design and Construction Standards SECTION PLUMBING EQUIPMENT

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION STEAM CONDENSATE PUMPS

B. Shop Drawings: Include diagrams for power, signal, and control wiring.

DESIGN GUIDELINES SPLIT TYPE AIR TO AIR HEAT PUMPS PAGE 1 of 6

BSD Technical Standard. Division 22: Plumbing

Division 23 - HVAC Switzerland Beallsville K-12. Section HYDRONIC PIPING SECTION HYDRONIC PIPING PART 1 - GENERAL

Mechanical Inspection Plumbing

SECTION PLUMBING EQUIPMENT

DOCUMENT TABLE OF CONTENTS

A. This section includes design and performance information for fire protection and suppression systems.

DIVISION 23 HVAC Hydronic Piping Systems

DESIGN STANDARDS SECTION Toilet rooms and utility rooms to have floor drains at lowest point.

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

4. Provide brass valve tags marked for the service. See pertinent service specification for valve type.

2016 Plumbing Supplemental Plan Review List

Ratio Architects, Inc. Section Refrigerant Piping

REFRIGERANT PIPING SYSTEM

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Level I Chapter 1 Worksheet

TECHNICAL. Series 18. Pump Packages

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 "Building Services Piping.

B. Related Sections: The following Sections contain requirements that relate to this Section.

SECTION WET-PIPE SPRINKLER SYSTEMS

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

REFRIGERANT PIPING

SECTION REFRIGERANT PIPING

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

PROJ. NO SECTION REFRIGERANT PIPING

SPRINKLERS TABLE OF CONTENTS

SECTION SECTION DESIGN REQUIREMENTS

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

TABLE OF CONTENTS Limitations of Authority...6 Table Swimming Pool, Spa, and Hot Tub Permit Fees...7

GARCIA GALUSKA DESOUSA Consulting Engineers

Lee s Summit West High School Boiler #3 Replacement SECTION CONDENSING BOILERS

University of Rochester October 17, 2008 Brooks Landing Business Center

SECTION WATER BASED FIRE SUPPRESSION SYSTEMS

DESIGN STANDARDS SECTION 15600

PLUMBING REQUIREMENTS

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

University of Delaware

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

SECTION (15530) - REFRIGERANT PIPING

DIVISION 21 - FIRE SUPPRESSION

2). Crane Co. 4). Kohler Co. 5). Universal-Rundle Corp. Revised September 29, 2017 Commercial Plumbing Fixtures

Willoughby Industries - Security Products

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

SECTION PLUMBING EQUIPMENT

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

Transcription:

UDIVISION 22 PLUMBING 22 00 00 PLUMBING BASIC MECHANICAL REQUIREMENTS A. Provide a list of symbols on drawings. B. Provide unique numbers for all applicable equipment, valves, and similar. C. Schedule all mechanical equipment on drawings. D. Do not show or put plumbing or other piping in transformer vaults, elevator hoistways, elevator equipment rooms, telecommunications equipment rooms, or electrical equipment rooms, unless required to supply room. E. Restroom piping chase shall be 3-0 minimum width with piping located to allow full access. F. Each main line strainer shall have valved sensing points at inlet and outlet, piped to a common pressure gauge. 22 05 00 COMMON WORK RESULTS FOR PLUMBING BASIC MECHANICAL MATERIALS AND METHODS A. General 1. Pipe routing may be modified as required to clear building structures, openings, lights, ducts, or other services. 2. Route piping parallel to building lines. 3. Provide sufficient unions, flanges and valves to permit removal of equipment. 4. Spacing shall be adequate to permit servicing valves and specialties and replacing sections of pipe. 5. Slope pipe to permit complete draining. Install drain valves at low points, vents at high points. Connect branch piping to top of main or sub main (install valve in branch connection). B. Utility Connections 1. Specify that Constructor is to notify Owner s Representative to coordinate connection of services onto existing systems. 2. Constructor to purchase and install the domestic water meter from Cedar Falls Utilities. 1

Also install conduit and wiring for remote reader. Oversize incoming domestic water service by 25% to allow for some future expansion. Constructor shall be required to furnish and install the water meter(s) and coordinate installation with the utility. Specify Badger meter with remote read in cubic feet (gallons will not be accepted). C. PIPE AND PIPE FITTINGS 1. Plastic pipe shall not be used unless required for specialty piping. Verify with Owner s Representative. 2. Dielectric unions or dielectric couplings should be used where two dissimilar metals are connected together. 3. Subject to meeting Code requirements pipe materials should be according to UNI STANDARD PIPE SCHEDULE (below). 4. Specify piping system test pressures for all services. 5. Flanged steam and return lines shall have Flexitallic gaskets. 6. All direct buried pipe shall have tracer wire with XHHW-2 insulation (Rhinomarker/Copperhead or approved equal). 7. Install auto flow valve on hot water recirculation line at the hot water connection point to limit water velocity to prevent erosion corrosion. 22 05 19 METERS AND GAGES FOR PLUMBING PIPING A. As a general rule, gages or gage openings are required on all piping systems to facilitate operation of the system. The campus has a central building automation system that remotes gage functions to a central location. B. Gage range shall be one and one half (1.5) times the normal operating pressure/temperature of the fluid being measured. C. The designer should use the following philosophy in the application of gages on systems. 1. Where a gage is to be used by the operator on a regular basis, we prefer to have the gage physically installed with a ball valve for replacing the gage. 2. Where a gage is to be used by the operator on a regular basis and the application is of a differential pressure nature (pumps, strainers, etc.) we prefer to have one gage and piping to either side of the differential, physically installed. 3. Where the gage is needed for occasional use but not needed every day by an operator, we do not prefer to have a gage physically installed. We prefer to have a P/T plug 2

S SPEC. S S schedule S S Black S SPEC. S S Black installed at this location. D. Where gages are installed, we prefer gages to be at least 4 for piping systems and that they be readable without the use of a ladder. E. All gages serving pumps shall be liquid filled with snubbers. 22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT A. Pipe hangers supporting water ScoldS lines shall not bear directly on piping. Hanger should be outside of insulation, bearing on metal insulation shield and insulating block. B. Insulation shield length and gauge shall be as specified in the current edition of MSS-SP69. C. Insulation block shall be the same length and circumference of the insulation shield. 22 06 00 SCHEDULES FOR PLUMBING A. UUNI STANDARD PIPE SCHEDULE UInside Building 1. Potable hot and cold water above ground 2 ½ and under: Copper tube, type L. SPEC. NO. 1 3 and over Copper tube, type L, grooved. SPEC. NO. 14 Hot water recirculation lines SPEC. No. 15 or SPEC No. 1 2. Potable hot and cold water underground Copper tube, type K. SPEC. NO. 2 S3. Heating hot water 2 and under: Copper tube, type L. NO. 1 2 ½ and over: Black steel pipe, 40. SPEC. NO. 3 Uor steel pipe, schedule 40. NO. 13 S4. Chilled water Copper tube, type L. SPEC. NO. 1 Uor steel pipe, schedule 40. 3

S S Black S SPEC. S SPEC. S SPEC. S SPEC. S SPEC. NO. 3 Uor steel pipe, schedule 40. NO. 13 5. Condensate drain Copper tube, type L. SPEC. NO. 9 or SPEC No. 16 S6. Steam-low pressure 15 PSIG Black steel pipe, schedule 40. NO. 3 S7. Steam-high pressure 155 PSIG Black steel pipe, schedule 40. NO. 3 S8. Steam condensate return Black steel pipe, schedule 80. NO. 4 S9. Specialty piping Verify material required for each project with Owner. 10. Natural gas Exposed: Black steel pipe, schedule 40. SPEC. NO. 11 Concealed: Black steel pipe, schedule 40 SPEC. NO. 11 11. Acid waste and vent, including traps Polypropylene. SPEC. NO. 8 12. Compressed air equipment room Black steel pipe, schedule 40. SPEC. NO. 3 13. Compressed air medical and lab Copper tube, type L. SPEC. NO. 1 14. Vacuum Copper tube, type L. SPEC. NO. 1 15. Sprinkler Black steel pipe, schedule 40. SPEC. NO. 10 B. UNI STANDARD PIPE SPECIFICATIONS SPEC. NO. 1 Pipe: Type L hard temper copper, ASTM B88. 4

Solder type with 95-5 solder. Wrought copper solder joint, ANSI B16.22. SPEC. NO. 2 Pipe: Type K soft temper copper, ASTM B88. Solder type with Sil-fos, or flared type. Wrought copper solder joint, ANSI B16.22, or brass flared fittings, ANSI B16.26. Note: 1. No fittings under floor slabs or inaccessible. SPEC. NO. 3 Pipe: Schedule 40 black steel, ASTM A120, or A53 < 25 PSI ASTM A53 or A106 Grade B > 25 PSI Joints, Unions, High pressure: 2 and under: socket weld High pressure steam piping fittings shall be steel. Low pressure: 2 and under: Malleable iron or cast iron screwed fittings, ANSI B16.3, 125 lb. (S) 175 lb. (WOG). 2 ½ and over: Butt weld schedule 40 steel fittings, ANSI B16.9. Flanges: 2 ½ and over: Forged steel welding neck or slip-on, 150 PSIG, ANSI B16.5. SPEC. NO. 4 Pipe: Schedule 80 black steel, ASTM A120. Joints, Unions, High pressure: 2 and under socket weld Low pressure: 2 and under: Malleable iron screwed fittings, ANSI B16.3, 125 lb. (S) 175 (WOG). 2 ½ and over: Butt weld schedule 80 steel fittings, ANSI B16.9. Flanges: 2 ½ and over: Forged steel welding neck or slip-on, 150 5

PSIG, ANSI B16.5. SPEC. NO. 5 Pipe: Schedule 40, galvanized steel, ASTM A120, or A53. Screwed. Galvanized cast iron drainage type, ANSI B16.12. SPEC. NO. 6 Pipe: Schedule 40, galvanized steel, ASTM A120, or A53. Bolted clamp type coupling with grooved end lock. Victaulic or equal Galvanized malleable iron, grooved ends, ASTM-A47. Use q drainage type for storm lines. SPEC. NO. 7 Pipe: Cast iron soil pipe, service weight, coated inside and out, ASTM A74. Bell and spigot, or molded elastomeric gasket type with push-on joints. SPEC. NO. 8 Pipe: Polypropylene flame retardant pipe, schedule 40, Fuseal or equal. Charlotte acid waste glued pipe preferred. Electrical fusion type. Socket type to match piping. SPEC. NO. 9 Pipe: Type L hard temper copper, ASTM B88. wrought Solder type with 95-5 solder. Cast brass solder joint drainage type ANSI B16.23 or copper solder joint drainage type, ANSI B16.29. 6

SPEC. NO. 10 Pipe: Schedule 40 black steel, ASTM A120 or A53. Note: Screwed or flanged. 2 ½ and over: Screwed, flanged, or grooved. Screwed: cast iron 125 lb. class, ANSI B16.4, or malleable iron, 150 lb. class, ANSI B16.3. Flanged: cast iron 125 lb. class, ANSI B16.1. Grooved: malleable iron, U.L. listed and FM approved. 1. Plain end fittings and couplings are not approved. 1. Use of welded joints must be approved by Owner. SPEC. NO. 11 Pipe: Schedule 40 black steel, ASTM A120, or A53. Unions: 2 and under: Welded 2 ½ and over: Welded and flanged. 2 and under: Socket weld steel fittings, ANSI B16.11, 2000 lb. 2 ½ and over: Butt weld schedule 40 steel, fittings, ANSI B16.9. 2 and under: Malleable iron ground joint with brass seat, 250 lbs. (S) 500 lb. (WOG) Flanges: 2 ½ and over: Forged steel welding neck or slip-on, 150 PSIG, ANSI B16.5. Note: 1. No flanged connections in concealed spaces. SPEC. NO. 12 Pipe: Cast iron soil pipe, service weight, coated inside and out, No-Hub, ASTM A74. Neoprene sealing sleeve with Type 301 stainless steel shield and screw type clamps. SPEC. NO. 13 Pipe: Schedule 40, black steel, ASTM A135, or A53. 7

Bolted clamp type coupling with grooved end lock. Victaulic or equal. Black malleable iron, grooved ends, ASTM-A47. SPEC. NO. 14 Pipe: Type L hard temper copper, ASTM B88. Bolted clamp type coupling with grooved end lock, ASTM A-536. Victaulic or equal. Cast bronze, grooved ends, ASTM B-584-87, or wrought copper, grooved ends ASTM B-75. Note: 1. Fluid velocity in roll groove area must be less than 5 fps. SPEC NO. 15 SPEC NO. 16 SPEC NO. 17 Uponor Wirsbo pipe with expansion fittings preferred. Written approval from the Owner is required. PVC piping Concrete storm sewer piping C. UPipe Schedule and Specifications Notes 1. This information is given as a general guide. Design Professional is responsible that piping, fittings, etc. are suitable for service intended. 2. All welding shall conform as to workmanship, testing and general requirements with welding section ANSI B31. 22 07 00 PLUMBING INSULATION A. General 1. Pipe insulation shall conform to or exceed minimum thicknesses stated in ASHRAE/IESNA 90.1, codified version. 2. SDo not insulate chilled water control valves in fan coils. Locate valve over drain pan. 3. Items concealed, valves, strainers, unions,s balance dampers,s etc. shall be clearly marked on the outside of the covering. 4. SProvide removable insulation blankets for high pressure steam system valves, 8

expansion joints & similar. 5. SFor high pressure steam and condensate located in tunnels, provide 0.024 inch aluminum jackets over insulation. 6. The following systems shall be insulated. All cold piping shall have complete vapor barrier protection. B. Materials a) Cold potable water piping. b) Refrigerant suction piping. c) SDuctwork as required by service. d) SChilled water piping, valves and accessories. e) SChiller evaporator. f) Roof drain piping. g) Condensate drain piping. h) Hot potable water piping. i) SHeating hot water piping. j) SSteam piping. k) SCondensate return piping. l) Plumbing vents for five feet below roof. m) Heat exchangers. n) Storage water heaters. o) Air eliminating units. 1. All products shall conform to NFPA Sections 90A and 90B with special regard to fire hazard classification requirements of NFPA No. 255, latest revision, including vapor barriers and adhesives. All products shall possess a flame spread rating of not over 25, without evidence of continued progressive combustion and a smoke developed rating no higher than 50. 22 11 23 PUMPS 9

A. Pumps shall be provided with motors, starters, controls, strainers, pressure gauges, vibration isolators, check valves, isolation valves and taps for flow measurement. B. Drawing set shall include a pump schedule indicating number, capacities, pressures, motor horsepower, rpm and other pertinent data for all pumps. C. SHot water pumps shall be bronze fitted. D. SChilled water pumps shall have stainless steel sleeves. E. Pumps shall be set on a concrete foundation above the finished floor with vibration isolators when required to avoid sound or vibration transmission. F. Two (2) sets of strainer mesh are to be supplied with pumps. A fine mesh startup strainer and a running size mesh. G. Where possible, use end suction pumps instead of split casing pumps. All pumps 1 h.p. and larger are to be base mounted pumps. H. Generally, the preferred pump is the Grundfos line. Alternate manufacturers include B&G and Taco. I. All circulating pumps must have a ball, or butterfly valve on either side of the pump. Do not use a check valve for a stop function. J. The inlet to pumps needs to be 7 straight diameters as a minimum, or suction diffusers may be used as an alternate. K. Pumps which require removal from the system piping for servicing the impeller are unacceptable. L. Use submersible pumps for sewage ejection and sump pumping applications. M. All pumps are to have mechanical seals. N. Provide service space around all pumps. No pumps to be tight to ceilings or walls. O. If triple duty valves are used, provide additional isolating valve to insure tight shut-off system for pump maintenance. P. SContact Owner for well water pump type. 22 13 00 FACILITY SANITARY SEWERAGE UServiceU UMaterial 10

semi-instantaneous 1. Sanitary and vent, underground. Cast iron soil pipe. SPEC. NO. 7 2. Sanitary and vent, above ground. 1 ½ and under: Galvanized steel pipe. SPEC. NO. 5 Uor Copper tube, type L. SPEC. NO. 9 2 and over: Cast iron soil pipe. SPEC. NO. 7 Uor Cast iron soil pipe. SPEC. NO. 12 22 14 00 FACILITY STORM DRAINAGE Storm underground 1. Storm above ground Cast iron soil pipe. Cast iron soil pipe. SPEC. NO. 16 or 17 SPEC. NO. 7 Uor Cast iron soil pipe. SPEC. NO. 12 22 30 00 PLUMBING EQUIPMENT A. In general, steam fired Sstorage or S water heaters shall be used. SUse of storage units only if adequate access exists for replacement. B. SStorage water heaters shall have cement lining. This lining shall be applied after heater is installed on site. Factory applied cement linings will not be accepted. C. Semi-instantaneous water heaters shall have copper lining and 10 year non-prorated warranty on tank and heat exchanger. D. SStorage water heater tanks shall have 5 year non-prorated warranty on tank and lining. Confirm the amount of superheat in the low pressure steam system in order to correctly specify the hot water heater. E. Working pressure shall be 150 psig. 22 40 00 PLUMBING FIXTURES A. Show all valve locations on drawings. Show all cleanout locations on drawings. B. Provide isolating valves on all items subject to repair or replacement. Including, but not limited to bathroom fixtures, sinks and hose bibs. 11

tsype. C. Stop valves on lavatories with sensor operated mixing valves shall include integral check valves accessible through the removable valve handle and cap. D. SIsolation valves installed on high-pressure UmainsU should be installed with start-up bypass valves. E. All valves should be rising stem valves except where ball valves are used. F. SBalancing valves shall be Griswold control valve (IRIS model) or equal by Victraulic, B & G and should be installed on each heating and cooling unit and at each hot or chilled water pump. Design Professional to schedule cartridge sizes for valves S. G. SGate valves are preferred for steam and condensate return service where sufficient room to maintain. If ball valves are used for steam, provide slow-closing operator. No cast iron valves strainers, fittings, and similar on high pressure 125 psig or greater steam service up to, and including, the building pressure relief valve. Valves to be 150 pound class with Flexitallic Flexicarb style CG flange gaskets. H. SFor high pressure steam mains, install bypass containing a globe valve for main warm-up. I. Provide valving to isolate branch sections of main lines. Apollo lead free ball valves prefered. I. SValves required to isolate energy source shall have locking mechanism for lockout tagout. SJ. Require strainers upstream of all pumps and control valves in chilled water and hot water applications. K. SRequire strainers ahead of control valves and traps in steam applications. L. SCollecting and dirt leg sizing and diagram are found in the appendix. M. SAdd drip pockets per ASHRAE handbook. N. SExpansion joints shall be packed metal expansion joint S Hyspan 3500 series for basis of design. P. Use wall hung water closets. Q. Water closets shall be siphon jet flush valve type with elongated bowl and black open front seat with check hinge. Low water usage. Color shall be white. Use Sloan as basis of design for flush valves. R. Urinals shall be washout flush valve type with integral side panels. Low water usage. Use Sloan as basis of design for flush valves. 12

Use All S. Service sinks shall be floor type Sprecast Sreceptor with hose, hose bracket, mop hanger and pail hook double supply spout set at 36 above receptor rim. Install sanitary panels on wall around sink 3 minimum height. T. Lavatory faucets shall conform to ASHRAE/IESNA 90.1, codified version. Sloan and Delta faucets preferred. U. Use electric water coolers with bottle fillers and total filled display. No filters allowed. V. Install ADA compliant fixtures as required. W. Provide floor drains in all toilet rooms and mechanical rooms. X. SProvide wall hydrant to all mechanical rooms.s Provide a hose bib in mechanical rooms within 20 of each air handler to facilitate air handling unit cleaning. Provide a freeze-proof hose bib near condensing units at exterior locations. Y. Provide loose key hose bibs on all exterior walls of the building. Install with an isolation ball valve on the interior. Z. Provide vacuum breakers on all faucets with hose connections. This shall include lab faucets, but exclude distilled water faucets. AA. In public areas, use hard-wired sensor type flush valves and faucets. S other areas to have low flows. Sloan or Delta is the preferred SfaucetS brand. S Sloan or Delta as basis of design for flush valves and faucets. BB. Provide eye washes and safety showers to meet EH&S standards. Haas eye and face stations preferred. CC. Fume hood water service vacuum breakers shall not be located within hood. DD. Do not use pop-up lavatory drains in public areas. Provide perforated or grid drains. EE. Roof drains shall be Zurn Z100 or equal. Specify 15 diameter main roof drain with an aluminum dome grate and a no-hub outlet joint connection. 4 diameter pipe size shall be standard unless requested by consultant to use different size for a specific purpose. FF. Install manual bypass piping and valves on backflow preventers for annual testing and service. GG. Water softeners to have a sample port installed close to the units for testing hardness. HH. Restrooms should be built with a pipe chase between rooms and wide enough to allow easy access for servicing waste and water lines. Cleanouts for sewer lines will be in the chase so the lines can be serviced without entering the rooms. Cleanouts must be installed at the end of each sanitary run and well above the flow line. 13