SDG&E Feeder Protection Philosophy:

Similar documents
Microgrid Fault Protection Based on Symmetrical and Differential Current Components

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions

Distribution Control Center Operator Training

What Utility Analytics means to Exelon

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

Transmission Line Protection End to End Testing

Electrical Energy department

SENTINEL D - Fault Passage Monitoring

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

AQ 100 Series. Arc Flash Protection System

SENTINEL A - Fault Passage Indicator

Major Fault Caused by Stator Winding Circuit Ring Failure

VAMP 120 & 121. Arc flash detection units. Product picture

Communications Point Data Base for Communications Protocol IEC

Installation, Operating and Maintenance Manual

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

Fault Indicators for the Safe, Reliable, and Economical Operation of Modern Power Systems

PGR-8800 TECHNICAL FAQ

Guide Specification Model CTG Automatic Transfer Switch

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

CIRCUIT BREAKER FAIL PROTECTION

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits

Lecture 4 Power System Protection. Course map

FCR 05, FCR 07. Power factor correction controller. User and service manual

Palak Parikh, Lalit Lopez GE Digital Energy. Acknowledgment: Scottish and Southern Energy(SSE)

TELECOMMUNICATION EQUIPMENT LOCATED IN THE VICINITY OF PROPOSED DISTRIBUTION HV EARTHS

Three Terminal 230kV System Protection and Restoration at Calpine s Creed and Goose Haven Energy Centers Suisun City, California

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Table of Contents. Protective Relays

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits

Root Cause Analysis Report Tesoro Golden Eagle Refinery Refinery Power Outage

Moulded case circuit brakers

Synchrophasor Technology in Control Centers Clemson University, SC March 12, 2014 Vikram S. Budhraja

To: Honorable Public Utilities Board Submitted by: /s/ Douglas Draeger AGM Engineering and Operations

APPLICATION NOTE. Applying pressure sensing in arc flash protection applications with air magnetic circuit breakers

Event Detection System (EDS)

End To End Optical Beam Smoke Detector. Additional Information

Intelligent Security & Fire Ltd

NextGen SCADA Europe 2013

Standard PRC Transmission Relay Loadability

CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS.

FlameGard 5 MSIR HART

Description (Data Point Name) Unit Size

SECTION AUTOMATIC TRANSFER SWITCHES

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

MAINTENANCE OF LV SWITCHGEAR SECTOR / ENGINEERING TECHNICAL & CERTIFIED TRAINING COURSE

FlameGard 5 UV/IR HART

2000 Series. Program Entry Guide. Control Panels

CONTACTORS FOR AEROSPACE GROW SMARTER AND MORE CAPABLE

M2500 Engine Controller Installation Manual

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC

Power System Protection Part 2 Dr.Prof. Mohammed Tawfeeq. Zones of Protection

National Grid / DG Installation Process Guide per NY SIR / July 2011 ver. 1.0

Electric Power Group Presents. Welcome!

BE1-50/51B with S1 Case or FT-11 sized Case and Cover For non-retrofit applications, see Product Bulletin UHD.

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

Development of standards for MV Switchgear for Arc Flash protection. ABB Group May 20, 2013 Slide 1

Ground Fault Protection Improvement Study

Surface Acoustic Wave Technology based Temperature Monitoring of High Voltage and High Current Switchgear Boxes

Detailed Instructions

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC

Oven Control System Operation - Ver 2.8

Solid State Relays SOLITRON MIDI Current Sensing Type RJCS, RJCSR

THERMAL DIAGNOSIS OF MV SWITCHBOARDS: A COST-EFFECTIVE, DEPENDABLE SOLUTION BASED ON AN OPTICAL SENSOR

Relay Performance Index for a Sustainable Relay Replacement Program

Guide to Transmission Equipment Maintenance

Operation and use. Functions and characteristics

EUROBOX SERIES TYPES CM... SM... MM...

PowerLogic ION Setup Meter Configuration Software Configuration Guide

INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS: RESIDUAL CURRENT DEVICES

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

SECTION AUTOMATIC TRANSFER SWITCHES

Lago SD3. Differential Controller with Speed Control. Operating and Installation Instructions

Flostop TS D7E and A8E. Operation Manual

COCB_ Circuit Breaker (2 state inputs/ 2 control inputs)

Ground Fault Protection Improvements to Prevent Fires Description of problem and potential solutions Presented by Bill Brooks, PE Principal, Brooks

M O T I O N DETECTORS. The Paradox series of motion detectors. combines advanced features and patented. technologies to provide a high level of

FACILITY CONNECTION STANDARD

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators

Contents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7

Applications and Discussions of Arc Flash Protection Relay as a Main Busbar Protection in MV Switchboards

Total Connect Box. User manual

DKG-108 POWER FACTOR CONTROLLER

5. CBS Alarms Responding to a CBS Alarm Understanding the Alarm Condition A-CBS-008 Circuit Breaker Sentinel Page 109 of 156

NFPA Edition Review

Division 26 ELECTRICAL TABLE OF CONTENTS

38-SDMS-04 REV. 0 SPECIFICATION FOR ANNUNCIATOR SYSTEMS FOR PRIMARY DISTRIBUTION SUBSTATION

Results of Recent DOE Research on Development of Cable Condition Monitoring and Aging Management Technologies

Continuous, real-time detection, alarming and analysis of partial discharge events

M2000 Engine Controller

Energy Saving Drives for Hot Strip Mills

LineVision TM. Non-Contact Transmission Line Monitoring and Dynamic Line Rating

I/O ZONE 560/583 AND OPERATION MANUAL

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24..

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification

Transcription:

SDG&E Feeder Protection Philosophy: Reliability Without Compromising Safety Karl Iliev System Protection and Control Engineering (SPACE) SDG&E 1

SDG&E Distribution System 22,000 miles of lines 60% underground and 40% overhead Reactively Grounded Three wire (Grounded) and Four wire systems Nominally 12kV and 4kV Distribution >160 distribution substations >700 medium power transformers (138/12kV & 69/12kV) 2

Traditional Distribution Circuit (Simplified) R Tie SUBSTATION

Distribution Circuit of Today (Simplified) R IR R IR R F6 SUBSTATION R AE R IR PME 10 F6 R IR R F6

Distribution Circuit of Today (Simplified) PV LINE MONITOR RECLOSER RECLOSER Zone 3 Zone 2 TRAYER Vz N.O. Vy Vy Vz VOLTAGE REG Zone 1 Vv IR Zone 4 CB SUBSTATON 5

System Protection is a Balancing Act SPEED SENSITIVITY SELECTIVITY SECURITY SIMPLICITY FAST TO MINIMIZE DAMAGE RELAY SEES FAULT REMOVE FAULTED ELEMENT ONLY DO NOT TRIP FALSELY SIMPLE CONTROL SCHEMES

Protection Philosophy: Non traditional layers of protection: FCP Falling Conductor Protection detects break in conductor Speed Trips before the fault Coordination FCP should be first SGF Sensitive Ground Fault detects high impedance ground fault Slow 3.5 to 5.5 seconds Coordination between devices is unlikely Could Trip on Load Advanced SGF More sensitive than SGF using adaptive set point, spike counting, and/or harmonics (Cooper DCD, SEL ArcSense, or IR algorithm) Slower > 5 seconds Coordination between devices is unlikely Could Trip on Load and external faults or other system conditions Operational Changes: Reclosing Policy Changes (Disable reclosing during elevated fire risk) Eliminate Fuse Saving Schemes Pulse Closing Devices HLT Hot Line Tag allows fast trip, does not protect from contact Profile 3 Fast and Sensitive for safety during high risk fire conditions Fast cycles Coordination between devices is unlikely

Falling Conductor Protection (FCP) Phase Angle Comparison Requires PMUs and high speed communication Detection Methods dv/dt (change Detection) V0 & V2 magnitude V0 & V2 angle Synchrophasor Data Visualization Source 1 2 3 4 Source 2 1 PMU1 PMU2 PMU3 PMU4 FC 1 not aligned with the other PMUs Source 1 3 4 Source 2 1 2 PMU1 PMU2 PMU3 PMU4 1 and 2 aligned with each other 3 and 4 aligned with each other FC Sequence Components Analysis 8

High Impedance Faults Random and Dynamic Requires Advanced Strategies because they are NOT like conventional (3P, PP and LG) faults. High Impedence Faults can be exhibit near zero fault current. We typically see 5 50 amp events

Sensitive Ground Fault (SGF): T SGF Element GROUND Similar to conventional ground protection element but is set more sensitively with a longer time delay to detect high impedance faults. The setting is fixed and typically 5 30A higher than neutral current trending on PI seen by the recloser for one year. Challenge is distinguishing Low Current Faults vs Load Imbalance I

SGF Pickup Setting vs. Neutral Load Current Neutral: 0 25 A

High Impedance Faults Cannot detect ½ cycle spiking with conventional SGF definite time elements.

Advanced SGF Introduces innovative logic to increase sensitivity Spike detection and accumulator algorithms to address both random, intermittent spiking and sustained low level ground faults Adaptive set point control to continuously adjust the spike pick up setting based on average neutral current loading Harmonic spike detector for arcing faults Optimizes sensitivity across the load range Reduces the need for field setting revisions due to system changes Each vender has different technology and algorithms

Advanced SGF Cooper DCD

Advanced SGF Intelliruptor Fault Starts - 01:54:05 (0 sec) Final Reset - 01:54:46 (40 sec) Trip - 01:55:27 (82 sec) 45 40 35 30 25 20 15 10 5 0 seconds si nce begi nni ng of event

Ground Spike Duration IR Data Fault Starts - 01:54:05 (0 sec) Final Reset - 01:54:46 (40 sec) Trip - 01:55:27 (82 sec) 80 70 69 # of pickup events 60 50 40 30 20 10 0 20 2 3 4 2 0 < to.25.25 < to.50.50 < to.75.75 < to 1.0 1.0 < to 5.0 5.0 < # Spikes & Duration, sec (Max = 6.9 sec) Avg Drop Out = 0.046 sec

Advanced SGF SEL ArcSense Complex algorithms independent of neutral current Uses SDI (sum of difference current) calculations of odd harmonics between each successive cycle. Uses adaptive learning of circuit history and trending to fine tune sensitivity.

Profile 3/Hot Line Tag (HLT) Time Profile 3 PHASE GROUND Profile 1 Current

Intellirupter (IR) PulseClosing SDG&E Implemented to increase SCADA penetration in backcountry Multiple IRs on Circuits Unique PulseClosing Technology Confirms there s no fault on the line before initiating point on wave closing Reduction in fire risk due to reduced arcing produced Conventional reclose results in 170ms of fault current Pulseclose results in only 5ms of fault current 19

Protection Philosophy: Continuous Improvement Undesirable Feeder Operations (UFO) Cross departmental team to investigate UFOs with a charter to review outages where the unexpected protection device or more than on device, isolates the circuit fault. Essential to understand impacts caused by the ever increasing feeder complexity. Increases awareness and improve operating procedures. Balances risk, reliability, and cost

Undesirable Feeder Operation (UFO) Team Year Investigated UFOs UFO % of Total 2015 73 59 2.95 2016 55 48 2.07 2017 65 18 0.94 Completed UFO Initiatives Include: Expand high impendence fault detection (Advanced SGF) through various vender technology (e.g. SEL, S&C, Cooper) Enable Autosectionalizing switch positions that were previously disabled Reprogram of all Trayer Switches for better protection coordination (Trayer Switches were operating faster than expected, not allowing time for fuses to operate) Redefined Fuse Sizing Criteria to determine fuse sizes based on historical load as opposed to connected KVA 21

Multiple Adjacent Recloser Staggering (MARS): SGF settings currently set with 5 sec delay. Poses issues when multiple reclosers in series. Settings to be staggered by 0.5 sec. R1 R2 R3 SGF Time Delay: 5.5s SGF Time Delay: 5.0s SGF Time Delay: 4.5s SGF Time Delay: 4.0s

Example #1: Profile 3 Success UFO: Yesterday we had an outage with no cause determined. Today, we had another outage, currently patrolling again. Same devices tripped with profile 3 enabled. Outage Cause: Broken strand of AWAC Isolation Devices: R1 & R2 Investigation: Both R1 and R2 tripped and saw targets on A & B. Both devices were set to profile 3 and the fault current for A & B was greater than 400A UFO: No 12kV Sub R1 R2 2 65A 2 25A

Example #1: Profile 3 Success

Example #2: Profile 3 Frustration UFO: SCADA Device tripped on unbalance. Grid reports TL tripped open at same time. Full patrol will have to wait for daylight. Outage Cause: Phase Ground Fault on 69kV System Isolation Devices: R1 & R2 Investigation: Both R1 and R2 tripped on unbalance UFO: Yes 69/12kV Sub R1 R2

Example #2: Profile 3 Frustration 26

Example #3: Advanced SGF Frustration Investigation: Feeder tripped via electromechanical relays and locked out (went through it s full reclosing cycle). At the same time, neighboring circuits saw outages: R1 and R2 tripped and locked out on Advanced SGF targets due to bus voltage fluctuations. These reclosers were downstream of the fault. The cause of the outage was bad tees in a man hole, which all three circuits share in common. Reclosers tripped on DCD (fundamental frequency and THD). Outage Cause: Bad Tees Isolation Devices: Feeder CB, R1, R2 UFO: Yes R1 Sub MH R2

Example #3: Advanced SGF Frustration Fault location R2 R1 Cir1: 9.1% OH / 89.9% UG Cir2: 22.3% OH / 77.7% UG Cir3: 40.0% OH / 60% UG

Example #3: Advanced SGF Frustration

Example #3: Advanced SGF Frustration

Example #3: Advanced SGF Frustration

Example #3: Advanced SGF Frustration

Example #4: Falling Conductor Protection Investigation: FCP trip occurred. It was raining at the time and this is suspected to be related. ETS patrolled and no damage was found. Comm was noticed to be going in and out. There were data gaps but not during the event. The cause appears to be a faulty voltage sensor that reported a sharp change in voltage. Outage Cause: FCP Trip on V0 Faulted Sensor Isolation Devices: CB, R1 Follow Up: Short term solution is to raise the voltage threshold(s) in the field. Long term we will need to get a better sensor. UFO: Yes

Example #4: Falling Conductor Protection PV LINE MONITOR RECLOSER RECLOSER Zone 3 Zone 2 TRAYER Vz N.O. Vy Vy Vz VOLTAGE REG Zone 1 Vv IR Zone 4 CB SUBSTATON 34

Example #4: Falling Conductor Protection No high current change fluctuation was detected at any of the SCADA devices that could have caused the sudden drop in voltage on B phase

Example #4: Falling Conductor Protection Voltage differences between line and load sensors for reclosers, including a drop on B phase on the z side of R

Example #4: Falling Conductor Protection The drop in the voltage on B phase at recloser 1 caused the zero sequence voltage to trip above the pickup value of 400V

Example #4: Falling Conductor Protection Voltage on multiple MVRs in area show similar issues during rain.

Elimination of ALL risk is impossible Selectivity Security Adv.SGF Multiple SRs AE FCP IT FLISR Speed Profile 3/HLT SGF TCC Sensitivity Simplicity 39