Guidelines for Specifying Structured Plumbing Systems January, 2007

Similar documents
Let s Go Back to the Future!

Hot-Water Circulation

Meeting the One-Cup Challenge

Hot Water Delivery Systems in the ICC Green Code. ACEEE Hot Water Forum

Energy, Water, and Time Efficient Hot Water Systems

Single Dwelling Unit Hot Water System Distribution Project Name: Enforcement Agency: Permit Number:

Making Crimp Connections

Domestic Hot Water Recirculation Systems Application, Selection & Installation Guide

Domestic Hot Water Systems and Plumbing Products

plumbing for greywater

Wood Manor. Developer. 24/28/32 Series. Developer. Your Local Wood Manor Dealer is: Some Items Shown May Be Optional

Much water and energy

A Model of In-Home Hot Water Distribution Systems Energy Losses Using EPANET, Public Domain Software For Pipe Networks

Proponent: Edward R. Osann, on behalf of Natural Resources Defense Council; Ryan Meres, on behalf of Institute for Market Transformation.

The smart way to instant hot water comfort.

SHARKBITE CONNECTING SYSTEM

Hot Water Distribution System Losses in a Net-Zero Home

This presentation is posted for public use. ACEEE does not endorse any product or service.

HERS Verified Single Dwelling Unit Hot Water System Distribution (Page 1 of 6)

Pre-Drywall Property Inspection

Case Study - Yardley Park Road Gerpex MLCP and Press Fit System, Underfloor Heating and Manifold Based Sanitary Systems

Potable Piping System

Hot Water Recirculation Loop Field Verification Requirements

Tortolita Preserve - Home Site 8

CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT PLUMBING. Test Code: 5924 Version: 01

ACT D MAND KONTROLS System FACTS AND QUESTIONS (FAQ)

Tube Clamp Submittal Information Revision A: July 25, 2013

Save Water... Save Energy With Efficient Hot Water Delivery

Matrix of changes for the National Standard Plumbing Code July 2013

Fundamentals of Hydronic Design

Plumbing Technology/Plumber CIP Task Grid

PureFlow. PureFlow. Fittings system This section doesn t meet California AB1953, Vermont ACT 193 and NSF 61 Annex G Standards.

CONNECTION SYSTEM AUGUST Reliance Worldwide USA

Perkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet

Piping for and installation of radiators in accordance with 'Safe Water Installation'

APEX. FAMILY of HOMES. from Redman Homes

PLUMBING SPECIFICATIONS FOR 1744 JOHNSON ST.

Master Bath Makeover

2012 UPC Chapter 6 Water Systems Part 2 RV

UPONOR Ltd. Specification for UPONOR Q&E PEX Shrinkfit Plumbing Systems

TANKLESS WATER HEATER HEATING SOLUTIONS

Plumbing Fundamentals. Ron Grendzinski

Test Code: 8117 / Version 1

NAVIEN AMERICA INC FITCH AVENUE IRVINE, CALIFORNIA, USA

Denotes a new question! Denotes a revised/revisited question. September 2009 General:

endless advances for your customers WATER HEATING SOLUTIONS FOR BUILDERS

FACULTY RESIDENCE. About the Residence

RESCOM 2100 HOT WATER BASEBOARD RADIANT HEATING Unique, slim-design baseboard radiators

PLUMBING INSTALLATIONS

CONNECTION SYSTEM JULY

5816 TIDEWOOD AVENUE FEATURES AND BENEFITS

TRUMAN STATE UNIVERSITY PRESIDENT S RESIDENCE RENOVATION

WARRANTY POLICY & RECOMMENDED MAINTENANCE

REGISTRATION EXAMINATION, NOVEMBER 2017 TRADESMAN PLUMBER ANSWER SCHEDULE

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS

Examples of Acclaim s Energy-Efficiency Green Technology

CONNECTION SYSTEM Reliance Worldwide USA

Zurn PEX New Product. Zurn PEX New Product. Zurn PEX Large Diameter Compact Tool

Classification criteria

Mini Tender Section 1.1 External Wall Insulation, Mechanical and Electrical Installation

APPENDIX A. A 3.2 Determine the elevation of the highest. A 3.3 Subtract the sum of loss in static pressure

Friday, March 8, 13. Furniture Arrangement & Traffic Patterns

Pro Vent TM. Provent Systems Inc Capital Circle Lawrenceville Georgia

MATERIALS Traps TRAPS. No. IPC IRC Description

INFINITI K APPLICATIONS MANUAL. Indoor Residential and Tankless Water Heaters. Warning: Follow each appliance's instructions precisely.

sjvhomes.com Kitchen Features

Savannah Station Price List

ProVent Systems Plumbing Fundamentals. Educational Literature. Comparison of ProVent Design Rules and The International Plumbing Code

Mojave Series. Homes. Single Section. Adventure Homes of Indiana. Your adventure begins here.

PLUMBING REQUIREMENTS

GIANT. Little. Guidelines for Sizing. Pump Company. Sewage Pumps & Systems. Sewage Pumps & Systems

Moen Posi Temp Cartridge Cleaning Instructions Pdf

TUBS & SURROUNDS FIBERGLASS TUB STANDARD FIBERGLASS GARDEN TUB

Safe at Home. Suggestions for Homeowner Created in partnership with the Administration on Aging. Assessor: Assessor: Homeowner Name: Address:

2012 Holmes Building Systems, LLC

ENGLISH. Recirculation with On-Demand Accessories User Guide 1

WATER HAMMER ARRESTORS & MISC. SPECIALTIES

That allows for installation of a lowresistance ducts system directly from the appliance. CONSTANT FLOW FANS

24/28 Series. Leola, Pennsylvania Division of Skyline Corporation. Some Items Shown May Be Optional

Wastewater. Guidelines for Sizing mscdirect.com. Call MSC today to learn about the latest LittleGiant products.

Every manufactured and modular home Champion builds is professionally designed and engineered. Built by craftsmen in a controlled factory

Standard Features List

FAIRA TRANSPARENCY REPORTS th St SW, 301, Lynnwood, WA May 31 st, 2017

ADVANTAGE HOME SERIES

Clean. Safe. Reliable. WaterPEX.

POTABLE PIPING SYSTEM

CALL FOR FLEXIBLE SOLUTIONS SHARKBITE WATER HEATER PRODUCTS

... Green Building Details

Ecodrain V1000. Selection and Installation Guide for Residential Applications TM MC TM

Single Section Homes. titanhomesny.com. shown with site-built porch by others. titanhomesny.com

Single Section Homes. shown with site-built porch by others. titanhomesny.com

Building and Safety Division Civic Center Dr, Bellflower, CA, (562) x

8483D 3 BED- 2 BATH 944 SQ.FT.

DESIGNER KITCHEN WITH PREMIUM APPLIANCES 1407 & 1409 Military Trail Features & Finishes 1. Open concept kitchen with NEFF designer cabinetry and Caesa

6 PIPING ARRANGEMENTS

CERV Fan and Duct Sizing Information

CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX A - RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM 1 2 1/AC AC SS SS/CC

Bradford 20 Wide Series

IMPORTANT INFORMATION. Revised Dishwasher Installation Instructions

New Custom Home Melody Lane. Bethesda, MD Specifications for Construction. Available for purchase at $3,495,000

Transcription:

Guidelines for Specifying Structured Plumbing Systems January, 2007 PART I - GENERAL A. Description This section includes requirements for materials for the installation Structured Plumbing systems for hot water delivery. Figure 1 contains a drawing of the Structured Plumbing concept. B. Submittals 1. Provide plumbing layout showing location of circulation loop, length of branch lines, diameter of circulation loop and all branch lines, location of on-demand pump and location of all activation mechanisms. 2. Provide materials list showing materials utilized. 3. Provide Certificates of Compliance with all applicable codes. Figure 1 Structured Plumbing with a Dedicated Return line Return (¾ inch minimum) Pump, Controls and Thermo-sensor (in one of these two locations) Twig Trunk Hot Water Piping Water Heater ¾ inch ½ inch Hot Wide Radius Elbows Structured Plumbing Page 1 of 5

PART 2 DEMAND CONTROLLED CIRCULATION SYSTEMS A. Materials 1. Pump a. The pump shall operate on-demand, meaning that it shall receive a signal to turn on from a user shortly prior to the desired hot water draw. The pump shall not operate continuously, on a timer, on an aquastat based temperature controller or by a combination of timer and aquastat. Show the location of the pump on the plumbing layout. b. The pump must have the capacity to overcome the pressure drop in the circulation loop and still move the water relatively quickly. The smaller the diameter, the longer the length and the more additional restrictions to flow (such as 90 degree turns through elbows and tees), the greater the pressure drop. In general, the greater the pressure drop in the circulation loop, the bigger the pump. c. Follow the sizing guidelines recommended by the manufacturers of Demand Controlled Recirculation Systems. 2. Controls and Activation Mechanisms a. The controls shall be electronic and operate on the principal of shutting off the pump with a rise in temperature (Delta-T). If the thermo-sensor that measures temperature rise fails to operate, the electronic controls must have a lock out to prevent operation above 105 o F degrees. The electronic controls shall also have a fail safe timer to prevent extended operation of the pump if the sensor fails or is damaged. b. Refer to the manufacturers of Demand Controlled Recirculation Systems to select appropriate activation mechanisms for the specific application. c. Hard Wired Activation Mechanisms i. Button. Buttons shall be normally-open, momentary close switches. ii. Motion Sensor. Motion sensors shall make a momentary contact when motion is sensed. After the signal is sent, the sensor shall go into a lock out mode for a short period of time to prevent sending a signal to the electronic controls while the circulation loop is still hot. iii. Other including flow switch or door switch d. Wireless Activation Mechanisms i. Button. Same as above. ii. Motion Sensor. Same as above. 3. Demand Controlled Recirculation Systems include the pump, electronic controls and activation mechanisms. These systems must be certified to meet nationally accepted plumbing and electrical standards (for example, IAPMO/UPC and UL/ULC). Acceptable manufacturers of these systems shall be ACT Inc., Metlund Systems, Taco, or Wirsbo or equivalent. Structured Plumbing Page 2 of 5

B. Execution 1. Pump a. Install pump(s), controls and activation mechanisms in accordance with applicable codes and manufacturer s instructions. b. Pump(s) shall be installed to facilitate repair and replacement 2. Activation Mechanisms a. In general, provide one activation mechanism for each hot water location. Provide an explanation if less than one activation mechanism per location is needed. Show location of all activation mechanisms on the plumbing layout. b. Hard Wired Activation Mechanisms i. Button located on a switch plate in a convenient location. ii. Motion Sensor located to trigger when someone gets near the hot water location. c. Wireless Activation Mechanisms i. Button. Give these to the homeowner so that they can put them where convenient. Possible locations include near the kitchen sink, at the head of the bed in the master bedroom, in the laundry room, on the mirror in the guest bathroom. ii. Motion Sensor located to trigger when someone gets near the hot water location. d. Other including flow switch or door switch i. Refer to manufacturers of Demand Controlled Recirculation Systems to select one of these activation mechanisms. 3. Circulation Loop a. System shall have a line that returns water to the hot water heater. Either a dedicated return line shall be installed (See Figure 1), or the cold water line may be used as a temporary return. A dedicated return line shall be installed if motion sensors are used to activate the pump. Show the location of the circulation loop on the plumbing layout. b. A check valve shall be installed in the circulation loop to prevent unintentional circulation of the water (thermo-syphoning) and back flow when the system is not operating. This check valve may be included with the pump. c. The supply portion of the circulation loop shall be sized in accordance with applicable plumbing codes. The circulation loop shall have a minimum diameter of ¾ inch nominal anywhere in the loop including the return from the last fixture to the water heater. This applies to both dedicated and cold-water line returns. d. Locate all fixtures no more than 10 plumbing feet from the circulation loop. The distance includes all fittings and shall be measured from the loop to the place where the pipe serving each fixture comes through the wall or floor, or connects to the valve (such as for showers and tubs, which are generally hidden). Structured Plumbing Page 3 of 5

e. Keep the restrictions to flow in the circulation loop to a minimum by minimizing the number of fittings. i. Rigid Pipe (e.g. copper and CPVC, and larger diameters of Cross-linked Polyethylene (PEX) and PEX-Al-PEX 1. Elbows minimize to the extent practical the number of hard 90 degree elbows since these have a major impact on the equivalent feet and increase the resistance that the pump must overcome. Use manufactured wide sweeping elbows or bendable copper. Preferred radius is 8-12 times pipe diameter. 2. Couplings minimize the number. 3. Tees required for branch lines. Where applicable, mini-manifolds with multiple tees may be used. ii. Flexible Pipe (e.g. copper, PEX, PEX-Al-PEX and CPVC) 1. Elbows minimize the number to the extent practical of hard 90 degree elbows since these have a major impact on the equivalent feet and increase the resistance that the pump must overcome. Use the tubing s flexibility to make the bends. Follow manufacturer s instructions for minimum radius on all bends. 2. Couplings minimize their use since they also increase the equivalent feet and resistance. In general, make the joints at the tees for the branches. 3. Tees required for branch lines. Where applicable, mini-manifolds with multiple tees may be used. 4. Branch Lines a. Branch lines shall be the shortest possible length from the recirculation line to the fixture with a maximum distance of 10 feet. Exceptions may be requested for island sinks, tubs (not tub-shower combos) and washing machines, and must be approved by the builder. b. Select the diameter of the branch lines in accordance with the UPC, in general ½ or less. Exceptions must be approved by the builder. c. Each fixture should be served with its own branch line. Example exceptions include: a branch line serving two sinks so that the total distance from the water heater to each sink is less than 10 plumbing feet, or a water heater serving a sink and a shower or tub/shower combo. Exceptions must be approved by the builder. d. Minimize the number of fittings in the branch lines to the extent practical, particularly hard elbows. 5. Insulation a. All hot water lines shall be insulated from the water heater to as near as practical to every fixture. This includes the supply portion of the circulation loop, the dedicated return line and all branch lines. b. Minimum R-4 pipe insulation shall be used. An exception may be requested for the branch lines. c. Install in accordance with the pipe insulation manufacturer s specifications. Pay particular attention to details at elbows and tees and all joints. Structured Plumbing Page 4 of 5

6. Commissioning the system a. Purge all pipes before installing the pump to remove air and other unwanted materials. b. Get the water heater(s) up to the desired temperature in accordance with the water heater manufacturer s instructions. c. Follow the manufacturer s instructions applicable to each pump, controls and activation mechanisms to ensure that the system is operating correctly. d. Preheat the circulation line to check for proper operation. e. Measure how much water comes out of each fixture before hot water arrives. It should be less than two cups at all fixtures except those for which an exception has been approved. 7. Customer Education a. Provide the homeowner with all warranty and operational material supplied by the manufacturer. Instructions need to explain how to prime or preheat the circulation loop. This information should advise the customer how and when the system should be turned off to prevent damage and what to do in the event of a water or electricity outage. C. Warranties 1. All hot water circulation systems shall have a minimum of a two year warranty from the date of manufacture. Structured Plumbing Page 5 of 5