Installation Instructions

Similar documents
Split system air conditioner. *S4BE - 018KB, 024KB, 030KB, 036KB (1.5, 2, 2.5, & 3 Ton) Series

1.5, 2, 2.5, & 3 ton, Single phase, r-22 Models 3, 3.5, 4, 4.5, & 5 ton Three phase, r-22 Models

User s Information and Installation Instructions

User s Information/Installation Instructions

Split system air conditioner

User s Information/Installation Instructions

User s Information and Installation Instructions

User s Information and Installation Instructions

IMPORTANT. JT5BD Series 13 SEER USER S MANUAL / INSTALLATION INSTRUCTIONS SPLIT SYSTEM HEAT PUMP - R-22

User s Information and Installation Instructions

Q6SE Series 14 SEER. Single Package Heat Pump - Single Phase - R410A

IMPORTANT INSTALLATION INSTRUCTIONS 14 SEER, SINGLE PHASE MODELS SPLIT SYSTEM AIR CONDITIONER

Installation Instructions

Installation Instructions

Outdoor Air Conditioner. 10 SEER Standard Efficiency Split System. To Operate Your Air Conditioner for Cooling m

USER'S MANUAL/INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

C7 Series Split System Uncased Indoor Coils

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Apartment Fan Coil

USER'S MANUAL/INSTALLATION INSTRUCTIONS

13 SEER USER S MANUAL & INSTALLATION INSTRUCTIONS Single Package Air Conditioner - Single Stage, R-410A IMPORTANT

Installation Instructions

INSTALLATION INSTRUCTIONS Low Ambient Kit NASA201LA, NASA401LA

T4BE - 018, 024, 030, 036, 042, 048, & 060 (1.5, 2, 2.5, 3, 3.5, 4, & 5 Ton) Series

NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.

Installation Instructions

Installation Instructions

Fig. 1 - Unit PHD4 and WPH4

Owner s Information Manual

USER s MANUAL & INSTALLATION INSTRUCTIONS. Single Package Heat Pump IMPORTANT:

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

Wiring Diagrams. 9AB4-12 Air-Cooled Remote Condenser INDEX OPERATING SEQUENCE ACCESSORIES LEGEND AND NOTES FOR FIG. 1-6

Installation Instructions

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

Installation Instructions

Residential Piping and Long Line Guideline

USER S MANUAL AND INSTALLATION INSTRUCTIONS IMPORTANT

INSTALLATION INSTRUCTIONS

Packaged Heat Pumps. Owner s Guide to Operating and Maintaining Your Heat Pump

38TKB Air Conditioning Unit Installation and Start-Up Instructions

Installation in Standard & Variable Speed Indoor Air Handlers IMPORTANT

Packaged Air Conditioning Units. Owner s Guide to Operating and Maintaining Your Air Conditioner. This manual should be left with the owner.

Installation Instructions

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

Installation Instructions

Installation Instructions

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION GUIDE. AAN & AEN Series - Manufactured Housing Electric Furnace. 1. Safety Instruction. 2. Inspection ! CAUTION CAUTION `!

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Fig. 1 - Unit PGD4, PGS4, WPG4

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA

Installation Instructions

INSTALLATION INSTRUCTIONS

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS

Horizontal/Side Discharge Condensing Units

Owner s Information Manual

PACKAGE AIR CONDITIONER

SERVICE MANUAL FOR 6537 & 6538 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioner

USER s MANUAL & INSTALLATION INSTRUCTIONS IMPORTANT

Installation Instructions

Installation Instructions

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

MODEL 598A TWO-SPEED PLUS CENTRAL AIR CONDITIONER

Installation Instructions

Installation Instructions

INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioners

Installation Instructions

INSTALLATION INSTRUCTIONS

Installation Instructions

INSTALLATION INSTRUCTIONS

Installation Instructions

INSTALLATION INSTRUCTIONS R-410A Split System Air Conditioner

Installation, Operation & Maintenance: Field-Installed Electric Heater for RXT Series Units

Installation Instructions

INSTALLATION INSTRUCTIONS R 22 or R 407C Air Conditioner Outdoor Component

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

INSTALLATION AND MAINTENANCE INSTRUCTIONS. MCE4 Series. Electric Cooling Package Unit. Save these instructions for future reference

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS R 410A Two Stage Split System Heat Pumps

Installation Instructions

INSTALLATION INSTRUCTIONS R 410A Two Stage Split System Heat Pumps

Installation Instructions

INSTALLATION INSTRUCTIONS R 410A Split System Heat Pumps

Installation Instructions

CONDENSING UNIT INSTALLATION INSTRUCTIONS. AIR CONDITIONING INSTALLATION & SERVICE REFERENCE Important Safety Instructions. Shipping Inspection

OWNER S MANUAL. R 410A Ductless Split System Air Conditioner and Heat Pump

Condensing Unit Installation and Operating Instructions

Transcription:

Export Series Split System Air onditioners & Heat Pumps Installation Instructions Single & Three Phase, -410A, 1-5 Ton units Important Safety Information... 2 Unit Installation... 3 General Information... 3 Before You Install the Unit... 3 Locating the Equipment... 3 Packaging emoval... 3 Ground Level... 3 ooftop... 3 onnecting efrigerant Tubing Between the Indoor & Outdoor Unit... 4 Electrical Wiring... 4 Pre-Electrical hecklist... 4 Line Voltage... 4 Thermostat / Low Voltage onnections... 5 Grounding... 5 Unbalanced 3-Phase Supply Voltage... 5 everse otation Verification... 6 Startup & Adjustments... 6 Pre - Start hecklist... 6 Start-up Procedures... 6 Air irculation - Indoor Blower... 6 Short ycle Protection... 6 System ooling... 6 System Heating... 6 Defrost ycle Timer... 6 Defrost ontrol Board... 7 Operational Information... 7 Normal Defrost Operation... 7 Defrost Test Procedure... 7 Anti Short ycle Timer Test... 7 efrigerant harging... 7 harging the Unit in A Mode with Outdoor Temperatures Above 55 F... 8 Unit Maintenance... 8 omponent Functions... 9 eplacement Parts... 9 harging Tables - ooling Mode... 10 Air onditioner harging Tables... 10 Table 2. harging Table for 1 Ton Units... 10 Table 3. harging Table for 1.5 Ton Units... 11 Table 4. harging Table for 2 Ton Units... 11 Table 5. harging Table for 2.5 Ton Units... 11 Table 6. harging Table for 3 Ton Units... 12 Table 7. harging Table for 3.5 Ton Units... 12 Table 8. harging Table for 4 Ton Units... 12 Table 9. harging Table for 5 Ton Units... 13 Heat Pump harging Tables... 13 Table 10. harging Table for 1 Ton Units... 13 Table 11. harging Table for 1.5 Ton Units... 13 Table 12. harging Table for 2 Ton Units... 14 Table 13. harging Table for 2.5 Ton Units... 14 Table 14. harging Table for 3 Ton Units... 14 Table 15. harging Table for 3.5 Ton Units... 15 Table 16. harging Table for 4 Ton Units... 15 Table 17. harging Table for 5 Ton Units... 15 harging Tables - Heating Mode... 16 Table 18 harging Table for 1 Ton Units... 17 Table 19. harging Table for 1.5 Ton Units... 17 Table 20. harging Table for 2 Ton Units... 17 Table 21. harging Table for 2.5 Ton Units... 18 Table 22. harging Table for 3 Ton Units... 18 Table 23. harging Table for 3.5 Ton Units... 18 Table 24. harging Table for 4 Ton Units... 19 Table 25. harging Table for 5 Ton Units... 19 Wiring Diagrams... 20 Figure 2. Single Phase Air onditioner... 20 Figure 3. Three Phase Air onditioner... 21 Figure 4. Single Phase Heat Pump... 22 Figure 5. Three Phase Heat Pump... 23 INSTALL. / PEFOMANE HEKLIST... 24 IMPOTANT ATTENTION INSTALLES: It is your responsibility to know this product better than your customer. This includes being able to install the product according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product. Safety should always be the deciding factor when installing this product and using common sense plays an important role as well. Pay attention to all safety warnings and any other special notes highlighted in the manual. Improper installation of the furnace or failure to follow safety warnings could result in serious injury, death, or property damage. These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Please read all instructions carefully before starting the installation. eturn these instructions to the customer s package for future reference. DO NOT DESTOY. PLEASE EAD AEFULLY AND KEEP IN A SAFE PLAE FO FUTUE EFEENE.

important SAFETY INFOMATION INSTALLE: Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WANING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. AUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage. WANING: ELETIAL SHOK, FIE O EXPLOSION HAZAD Failure to follow safety warnings exactly could result in serious injury or property damage. Improper servicing could result in dangerous operation, serious injury, death or property damage. Before servicing, disconnect all electrical power to the indoor blower. When servicing controls, label all wires prior to disconnecting. econnect wires correctly. Verify proper operation after servicing. WANING: Split System Air onditioners & Heat Pumps leave the factory with a nitrogen holding charge. Follow all charging instructions for maximum unit performance and efficiency. Some local codes require licensed installation/service personnel to service this type of equipment. efrigerant charging must be done by qualified personnel familiar with safe and environmentally responsible refrigerant handling procedures. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death. AUTION: Split System Air onditioners & Heat Pumps use -410A refrigerant. DO NOT use any other refrigerant in these units. Use of another refrigerant will damage these units. WANING: Unless noted otherwise in these instructions, only factory authorized parts or accessory kits may be used with this product. Improper installation, service, adjustment, or maintenance may cause explosion, fire, electrical shock or other hazardous conditions which may result in personal injury or property damage. WANING: The information listed below and the next page must be followed during the installation, service, and operation of this furnace. Failure to follow safety recommendations could result in possible damage to the equipment, serious personal injury or death. The installer must comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedence over any recommendations contained in these instructions. onsult local building codes and the National Electrical ode (ANSI I) for special installation requirements. This equipment contains liquid and gaseous refrigerant under high pressure. DO NOT USE ANY POTION OF THE HAGE FO PUGING O LEAK TESTING. Installation or servicing should only be performed by qualified trained personnel thoroughly familiar with this type equipment. All electrical wiring must be completed in accordance with local, state and national codes and regulations and with the National Electric ode (ANSI/NFPA 70) or in anada the anadian Electric ode Part 1 SA.22.1. Installation of equipment may require brazing operations. Installer must comply with safety codes and wear appropriate safety equipment (safety glasses, work gloves, fire extinguisher, etc.) when performing brazing operations. Follow all precautions in the literature, on tags, and on labels provided with the equipment. ead and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment. Use caution when handling this appliance or removing components. Personal injury can occur from sharp metal edges present in all sheet metal constructed equipment. Fully annealed, refrigerant grade copper tubing should be used when installing the system. efrigerant suction line tubing should be fully insulated. This unit is designed for outdoor installations only and should be positioned as described on page 3. 2

Unit INSTallATION General Information Split system series air conditioners and heat pumps are designed only for outdoor rooftop or ground level installations. These units have been tested for capacity and efficiency in accordance with AHI Standards and will provide many years of safe and dependable comfort, providing they are properly installed and maintained. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards. To achieve optimum performance and minimize equipment failure, it is recommended that periodic maintenance be performed on the unit. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools. Before You Install the Unit The cooling load of the area to be conditioned must be calculated and a system of the proper capacity selected. It is recommended that the area to be conditioned be completely insulated and vapor sealed. heck the electrical supply and verify the power supply is adequate for unit operation. The system must be wired and provided with circuit protection in accordance with local building codes. If there is any question concerning the power supply, contact the local power company. The indoor section (air handler, furnace, etc) should be installed before routing the refrigerant tubing. efer to the indoor unit's installation instructions for installation details. All units are securely packed at the time of shipment and upon arrival should be carefully inspected for damage prior to installing the equipment at the job site. Verify coil fins are straight. If necessary, comb fins to remove flattened or bent fins. laims for damage (apparent or concealed) should be filed immediately with the carrier. Please consult your dealer for maintenance information and availability of maintenance contracts. Please read all instructions before installing the unit. Locating the Equipment Survey the job site to determine the best location for mounting the outdoor unit. Overhead obstructions (Figure 1), poorly ventilated areas, and areas subject to accumulation of debris should be avoided. Sufficient clearance for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance. See Figure 1 for minimum clearances to obstructions. onsideration should be given to availability of electric power, service access, noise, and shade. 24" for Service Access DO NOT OBSTUT TOP OF UNIT 6 from Building or Structure 48 12" or 18 See Note 12" or 18 See Note NOTE: Units require full perimeter clearances. Installer must maintain 18 between two units or 12 between single unit and structure. 2 Mounting Pad Figure 1. learance equirements Packaging emoval To prevent damage to the tubing connections, carefully remove the carton and user s manual from the equipment. Discard the shipping carton. Ground Level Ground level installations must be located according to local building codes or ordinances and these requirements: learances must be in accordance with those shown in Figure 1. A suitable mounting pad (must be provided and be separate from the building foundation. The pad must be level and strong enough to support the unit s weight. The slab height must be a minimum of 2 (5 cm) above grade and with adequate drainage. See Figure 1. ooftop The method of mounting should be designed so that it does not overload roof structures or transmit noise to the interior of the structure. The roof must be structurally capable of handling the weight of the unit. Full perimeter support is required under the unit. Support must be made of weather resistant materials and installed prior to unit installation. The support must be built to raise the unit 6" above the roof. 3

onnecting efrigerant Tubing Between the Indoor & Outdoor Unit AUTION: When servicing, cover or seal openings to minimize the exposure of the refrigerant system to air to prevent accumulation of moisture and other contaminants. After outdoor and indoor unit placement has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices. When connecting refrigerant linesets together, it is recommended that dry nitrogen be flowing through the joints during brazing. This will prevent internal oxidation and scaling from occurring. efrigerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing. efrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation. Tubing should be kept clean of foreign debris during installation. Every effort should be made by the installer to ensure that the field installed refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices to insure reliable system operation and longevity. The maximum recommended interconnecting refrigerant line length is 75 feet, and the vertical elevation difference between the indoor and outdoor sections should not exceed 20 feet. If precise forming of refrigerant lines is required, a copper tubing bender is recommended. Avoid sharp bends and contact of the refrigerant lines with metal surfaces. A filter dryer is provided with the unit and must be installed in the liquid line of the system. If the installation replaces a system with a filter dryer already present in the liquid line, the filter dryer must be replaced with the one supplied with the unit. The filter dryer must be installed in strict accordance with the manufacturer s installation instructions. Optional equipment such as liquid line solenoid valves, low ambient, etc., should be installed in strict accordance with the manufacturer s installation instructions. ELETIAL WIING WANING: To avoid risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply. Label all wires prior to disconnection when servicing the unit. Wiring errors can cause improper and dangerous operation All electrical connections must be in compliance with all applicable local codes and ordinances, and with the current revision of the National Electric ode (ANSI/ NFPA 70). For anadian installations the electrical connections and grounding shall comply with the current anadian Electrical ode (SA 22.1 and/or local codes). Pre-Electrical hecklist Verify that the voltage, frequency, and phase of the supply source match the specifications on the unit rating plate. Verify that the service provided by the utility is sufficient to handle the additional load imposed by this equipment. efer to the unit wiring label for proper high and low voltage wiring. Verify factory wiring is in accordance with the unit wiring diagram (Figures 12-15, pages 21-24). Inspect for loose connections. Phase balance on 3 phase units must always be checked. See Unbalanced 3-Phase Supply Voltage section (page 7). Line Voltage A wiring diagram is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram before making any electrical connections to the outdoor unit. An electrical disconnect must be located within sight of and readily accessible to the unit. This switch shall be capable of electrically de-energizing the outdoor unit. The means for disconnection from the supply must have a contact separation of at least 3mm in all poles. For Austrian installations, a "Type A" residual current device must be used. Line voltage to the unit should be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the unit. Incoming field wiring and minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label. Any other wiring methods must be acceptable to authority having jurisdiction. The outdoor unit requires both power and control circuit electrical connections. efer to the wiring diagrams for identification and location of outdoor unit field 4

wiring interfaces. Make all electrical connections in accordance with all applicable codes and ordinances. Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes. See the unit rating plate for minimum circuit ampacity and maximum overcurrent protection limits. Provide power supply for the unit in accordance with the unit wiring diagram, and the unit rating plate. onnect the line-voltage leads to the terminals on the contactor inside the control compartment. Use only copper wire for the line voltage power supply to this uni. Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit. Use of rain tight conduit is recommended. 208/230 Volt units are shipped from the factory wired for 230 volt operation. For 208V operation, remove the lead from the transformer terminal marked 240V and connect it to the terminal marked 208V. Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NE (ANSI/NFPA 70), applicable local codes, and the instructions provided with the equipment. Thermostat / Low Voltage onnections Thermostat connections should be made in accordance with the instructions supplied with the thermostat and the indoor equipment. The outdoor unit is designed to operate from a 24 VA lass II control circuit. The control circuit wiring must comply with the current provisions of the NE (ANSI/ NFPA 70) and with applicable local codes having jurisdiction. The low voltage wires must be properly connected to the units low voltage terminal block. The thermostat should be mounted about 5 feet above the floor on an inside wall. DO NOT install the thermostat on an outside wall or any other location where its operation may be adversely affected by radiant heat from fireplaces, sunlight, or lighting fixtures, and convective heat from warm air registers or electrical appliances. efer to the thermostat manufacturer s instruction sheet for detailed mounting and installation information. Grounding WANING: The unit cabinet must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. Do not use gas piping as an electrical ground! This unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical ode (ANSI/NFPA 70) or the SA 22.1 Electrical ode. Use the grounding lug provided in the control box for grounding the unit. Unbalanced 3-Phase Supply Voltage Voltage unbalance occurs when the voltages of all phases of a 3-phase power supply are no longer equal. This unbalance reduces motor efficiency and performance. Some underlying causes of voltage unbalance may include: Lack of symmetry in transmission lines, large single-phase loads, and unbalanced or overloaded transformers. A motor should never be operated when a phase imbalance in supply is greater than 2%. Perform the following steps to determine the percentage of voltage imbalance: 1. Measure the line voltages of your 3-phase power supply where it enters the building and at a location that will only be dedicated to the unit installation (at the units circuit protection or disconnect). Example: AB = 451V B = 460V A = 453V 2. Determine the average voltage in the power supply. In this example, the measured line voltages were 451, 460, and 453. The average would be 454 volts (451 + 460 + 453 = 1,364 / 3 = 454). 3. Determine the maximum deviation: Example: From the values given in step 1, the B voltage (460V) is the greatest difference in value from the average: 460-454 = 6 Highest Value 454-451 = 3 454-453 = 1 4. Determine percent of voltage imbalance by using the results from steps 2 & 3 in the following equation. % Voltage Imbalance =100 x 100 x Example: 6 454 = 1.32% max voltage deviation fromaverage voltage average voltage The amount of phase imbalance (1.32%) is satisfactory since the amount is lower than the maximum allowable 2%. Please contact your local electric utility company if your voltage imbalance is more than 2%. 5

everse otation Verification After making all of the power connections to the unit, the rotation of the compressor must be checked. If the rotation is in the wrong direction, the compressor will make an abnormally loud noise. To check the rotation perform the following steps: 1. Make sure the outside power disconnect is in the OFF position. 2. Set the indoor thermostat to a set point that will call for cooling. 3. etun to the outside power disconnect and switch it to the ON position. If the compressor is making an abnormally loud noise, immediately switch the outside power disconnect to the OFF position. 4. Switch any two of the three power leads at the power connections to the unit. 5. Seteturn to the outside power disconnect and swith it to the ON position. 6. Verify that the compressor is now running properly. STAT UP & ADJUSTMENTS Pre-Start heck List Verify the unit is level and has sufficient clearances for unobstructed airflow. Verify the outdoor coil and top of the unit are free from obstructions and debris, and all equipment access/ control panels are in place. Verify that the line voltage power leads are securely connected and the unit is properly grounded. Verify that the low voltage wires are securely connected to the correct leads on the low voltage terminal strip. Verify that the power supply branch circuit overcurrent protection is sized properly. Verify that the thermostat is wired correctly. Start-Up Procedures WANING: This unit is equipped with a crankcase heater. Allow 24 hours prior to continuing the start up procedures to allow for heating of the refrigerant compressor crankcase. Failure to comply may result in damage and could cause premature failure of the system. This warning should be followed at initial start up and any time the power has been removed for 12 hours or longer. Air irculation - Indoor Blower 1. Set the thermostat system mode on OFF and the fan mode to ON. 2. Verify the blower runs continuously. heck the air delivery at the supply registers and adjust register openings for balanced air distribution. If insufficient air is detected, examine ductwork for leaks or obstructions. 3. Set the thermostat fan mode to AUTO and verify the blower stops running. NOTE: On 3 phase air handler models only - If blower is spinning opposite of arrow direction, shut off the main power to the unit and switch any two field wires at the disconnect. DO NOT alter unit wiring. Short ycle Protection 1. Operate the system in cooling mode and observe the temperature setting of the thermostat. Gradually raise the set-point temperature until the unit de-energizes. 2. Immediately lower the set point temperature of the thermostat to its original setting and verify that the indoor blower is energized and outdoor unit remains de-energized. 3. After approximately 5 minutes, verify the outdoor unit energizes and the temperature of the discharge air is cooler than the room temperature. System ooling 1. Set the thermostat s system mode to OOL and the fan mode to AUTO. Gradually lower the thermostat temperature setpoint below room temperature and verify the outdoor unit and indoor blower energize. 2. Verify blower wheel is spinning in direction indicated by arrow. Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary. 3. Verify HI and LO refrigerant pressures. NOTE: If refrigerant pressures are abnormal and the compressor is rotating backwards, shut off main power to the unit and switch any two field wires at the disconnect. DO NOT alter unit wiring. 4. Allow the system to operate for several minutes and then set the temperature selector above room temperature. Verify the fan and compressor cycle off with the thermostat. NOTE: The blower should also stop unless fan switch is set to the ON position. System Heating 1. Set the thermostat's system mode to HEAT and the temperature mode to below room temperature. 2. Verify the outdoor unit and indoor fan stop running. After 5 minutes, increase the temperature on the thermostat to it's maximum setting. 3. Verify the outdoor unit and indoor blower energize. Feel the air being circulated by the indoor blower and verify that it is warmer than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary. Defrost ycle Timer The defrost cycle timer controls the time interval of the hot gas defrost after the defrost sensor closes. It is located in the lower left corner of the defrost control board on the of the control panel. Three interval settings are available: 30, 60, and 90 minutes. Time setting selection is dependent on the climate where the unit is being installed. 6

In dry climates, a 90 minute setting is recommended. In moist climates, a 30 minute setting is recommended. To set the cycle timer, place the timing pin on the defrost control board to the desired time interval post. NOTE: All units are shipped from the factory with the default time setting of 30 minutes. Longer settings are recommended for drier climate areas and shorter time intervals are recommended for moist climate areas. Maximum heating performance can be acheived by setting the time to 90 minutes. Defrost ontrol Board Operational Information Terminals - must have 24±V present between them in order for the time delay and defrost sequences to be operational. A jumper between the - DFT test pins will communicate to the board that the defrost T-stat is closed (if the compressor is running). The defrost thermostat tells the board whether a defrost cycle needs to be started or terminated. NOTE: The defrost T-stat is closed at 32 F or below and is open at 68 F or above, but it s state is unknown if the temperature is between 32 F and 68 F. With the DFT closed, the unit will run for 30/60/90 minutes in heat mode and then defrost the outdoor coil. The defrost will turn off the outdoor fan, turn on the compressor and raise the coil temperature to 68 F. This will open the DFT and terminate the defrost. If the DFT does not open the defrost will end after 10 minutes. To over-ride the defrost board and initiate a faster defrost test in 5, 10 or 15 seconds as determined by the 30, 60 or 90 minute defrost pin settings (factory setting is 30 minutes), jumper the TEST terminal to the (common) terminal while the compressor is in heat mode. This will bypass the compressor off delay when the unit goes into defrost test and if left in defrost test, the delay will be bypassed when the test is terminated by the processor. NOTE: If the jumper is removed before the test is over, the processor will perform the remainder of a normal defrost. See bullett 2 above. To switch from no-delay to delay, remove the pin from the no - delay pin location and shift it to the delay pin location. The delay/no-delay pin concerns compressor operation during defrosts. The default setting is delay. eciprocating compressors should only use this setting in conjunction with an approved hard start kit. Scroll compressors that have noise issues while going into or coming out of defrost should use this 30 second delay to reduce the defrost noise. Manually initiating a defrost will cause the compressor to run continually when entering defrost. Normal defrost operation To test normal defrost operation when the temperature is above 35 F, jumper to DFT on the board and allow the unit to run for 30 minutes. Defrost will continue until the to DFT jumper is removed or for 10 minutes. emove the jumper. The 5 minute time delay feature can be shortened 1 time to 1 second by jumping the Test to terminal. emove the jumper and repeat as desired. NOTE: If jumper is left on the Test to common pins permanently, the defrost cycle will become inoperable. Defrost Test Procedure 1. Jumper to DFT at the test terminals. 2. With unit running in heat mode, short the TEST terminal to the common terminal near it. This will speed up the board and cause it to enter defrost mode in 5/10/15 seconds depending on the defrost time selection. ompressor delay will not function during speed-up. 3. This test will end in 5 seconds if the TEST-common short is not removed. 4. emove both the short and the to DFT jumper to terminate the defrost cycle. The 30 second compressor delay should operate normally. 5. Test is complete, reset thermostat to home owner preference. Anti Short ycle Timer Test The 5 minute time delay feature can be bypassed or shortened to 1 second by jumping the Test to terminal. NOTE: If jumper is left on the Test to common pins permanently, the defrost cycle will become inoperable. efrigerant harging WANING: Split System Air onditioners & Heat Pumps leave the factory with a nitrogen holding charge. Follow all charging instructions for maximum unit performance and efficiency. Some local codes require licensed installation/service personnel to service this type of equipment. efrigerant charging must be done by qualified personnel familiar with safe and environmentally responsible refrigerant handling procedures. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death. After refrigerant line connections are completed, it is required that you leak check and evacuate the indoor section and all line connections (using proper methods) before finalizing the full system refrigerant charge. 7

To achieve rated capacity and efficiency, the compressor must be exposed to refrigerant for at least 24 hours prior to running and then the compressor must be run for a minimum of 12 hours. ooling mode charging charts are applicable only to matched assemblies of NODYNE equipment and listed airflows for the indoor coil. Outdoor units with non-ahi lsited indoor coils are not recommended and deviations from rated airflows or non-listed combinations may require modification to the expansion device and refrigerant charging procedures for proper and efficient system operation. efer to Table 1 for correct restrictor sizes and Tables 2-17 (pages 10-15) to determine the ideal amount of sub-cooling for a given liquid pressure. The refrigerant charge can be checked and adjusted through the service ports provided external to the outdoor unit. Use only gage line sets which have a Schrader depression device present to actuate the valve. A common suction port for heating mode charging is included and located on the compressor access panel above the outdoor unit service valves. Heat Mode Verification Tables (Tables 18-25, pages 17-19) are provided for quick reference when the unit is in heating mode and for the inspection of the liquid line pressures and temperatures. harging the Unit in A Mode with Outdoor Temperatures Above 55 F (for optimized sub-cooling of 10 F to 12 F) 1. With the system operating at steady-state, measure the liquid refrigerant pressure (in PSIG) at the outdoor unit service valve. 2. Measure the liquid refrigerant temperature (in Fahrenheit) at the service valve. 3. Determine the required liquid refrigerant pressure. efer to Tables 2-17 (pages 10-15). If the pressure measured in Step 1 is greater than the required liquid refrigerant pressure determined in Step 3, then there is too much charge in the system. emove refrigerant and repeat Steps 1 through 3 until the system is correctly charged. If the pressure measured in Step 1 is less than the required liquid refrigerant pressure determined in Step 3, there is too little charge in the system. Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged. Model estrictor Size (Inch) Outdoor Indoor (Heat Pumps) Table 1. Orifice Usage for Split System Air onditioners & Heat Pumps Unit MAINTENANE WANING: To prevent electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply. Proper maintenance is important to achieve optimum performance from the heat pump. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools. If you do not possess these skills, contact your dealer for maintenance. onsult your local dealer about the availability of maintenance contracts. outine maintenance should include the following: Inspect and clean or replace air filters at the beginning of each heating and cooling season, or more frequently if required. Inspect the outdoor coil at the beginning of each cooling season. emove any debris. lean the outdoor coil and louvers as necessary using a mild detergent and water. inse thoroughly with water. Inspect the electrical connections for tightness at the beginning of each heating and cooling season. Service as necessary. AUTION: System harge -410A (oz.) A/ H.P. 2 Ton 0.057 0.049 65 75 2 1/2 Ton 0.064 0.057 68 78 3 Ton 0.069 0.061 70 82 4 Ton 0.077 0.064 88 100 5 Ton 0.083 0.066 93 105 The unit should never be operated without a filter in the return air system. eplace disposable filters with the same type and size. Do not add additional oil to motors unequipped with oil tubes. The compressor is hermetically sealed at the factory and does not require lubrication. 8

OMPONENT FUNTIONS High Pressure Switch (HPS) - A high-pressure switch is factory-installed and located in the compressor discharge line internal to the outdoor unit. The switch is designed to de-energize the system when very high pressures occur during abnormal conditions. Under normal conditions, the switch is closed. If the discharge pressure rises above 575 psig, then the switch will open and de-energize the outdoor unit. The switch will close again once the liquid pressure decreases to 460 psig. Please note that the switch interrupts the thermostat inputs to the unit. When the switch opens and then closes, there will be a 5 minute short cycling delay before the outdoor unit will energize. Low Pressure Switch (LPS) - A low-pressure switch is factory-installed in select models only. If provided, this located in the suction line internal to the outdoor unit. The switch is designed to protect the compressor from a loss of charge. Under normal conditions, the switch is closed. If the suction pressure falls below 5 psig, then the switch will open and de-energize the outdoor unit. The switch will close again once the suction pressure increases above 20 psig. Please note that the switch interrupts the thermostat inputs to the unit. When the switch opens and then closes, there will be a 5 minute short cycling delay before the outdoor unit will energize. EPLAEMENT PATS eplacement parts are available through all Nordyne distributors. Please have the complete model and serial number of the unit when ordering replacement parts. Electrical: apacitors ompressors ontactors Pressure Switches elays Motors: Blower Motor Fan Motor omponents: Blower Assembly abinet Panels Expansion Valves Temperature Limit Switches Thermostats Time Delay elays Transformers Fan Grille Filter/Driers 9

Legend efrigerant harging tables - ooling Mode Only Application notes on the use of cooling mode charging tables NOTES: Shaded boxes indicate flooded conditions. ated design values. The suction pressure will be lower than design value if outdoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design. 1. All pressures are listed psig and all temperatures in F 2. Discharge temperatures greater than charted values indicate an undercharged system. 3. Discharge temperatures LESS than charted values indicate an overcharged system. This equipment s cooling system contains refrigerant under high pressure. Always use safe and environmentally sound methods when handling refrigerant handling or servicing the unit. eview the factory literature and safety warnings prior to servicing. When repairing system leaks, always use a nitrogen (inert) gas to protect the refrigerant system and pressure check the repair before re-charging. Always replace the filter-dryers when performing any repair to the refrigeration system with one capable of acid removal. After completing the repairs, evacuate the system to 350-500 microns and weigh in the refrigerant to the amount specified on the unit rating label. harging tables are valid for a variety of indoor, return air conditions and are most influenced by the outdoor ambient temperature, outdoor fan operation and the unit operating voltage. Before using these charts, make sure the unit is in a stable operating mode. As shown in Tables 2-17 (pages 10-15), the ideal system sub-cooling can vary over the range of operation. eference the tables to determine the ideal amount of sub-cooling for a given liquid pressure. Units charged to other values will not perform at the rated unit efficiency (EE) or rated oefficient of Performance (OP) in heating mode. To inspect a systems operation using quality instruments, match the measured liquid temperature to the units chart. The measured liquid pressure reading should be within 3% of the tables value for most installations. For systems that are operating with more than a 5% deviation, inspect the unit for the proper voltage and phase balance and the refrigeration system for leaks. Units that are operating at less then 95% of the nominal voltage or with a 2% phase imbalance may see a more significant deviation than the amount stated above. DO NOT use the tables in systems that have a fan cycling under low-ambient control. efer to the low-ambient kit instructions for more information. (If applicable) Air onditioner & Heat Pump efrigerant harging Tables Three Phase Units 70 75 80 85 90 95 100 105 Table 2. Air onditioner & Heat Pump harging Table (3 Ton Units) - Orifice Matches 124 126 301 139 128 302 151 327 146 130 304 162 329 156 353 150 132 303 184 331 165 356 159 380 157 402 157 134 304 200 332 184 358 170 383 163 406 164 429 162 136 333 198 359 184 385 172 410 172 433 168 455 166 138 361 198 387 185 412 182 437 175 460 172 482 172 140 389 199 414 191 439 184 464 178 487 177 142 416 201 442 194 466 188 491 183 144 444 204 469 197 494 192 146 471 207 496 201 148 499 210 10

70 75 80 85 90 95 100 105 Table 4. Air onditioner & Heat Pump harging Table (4 Ton Units) - Orifice Matches 118 120 295 128 122 296 140 319 134 124 297 151 322 144 345 138 126 297 172 324 154 347 147 370 143 392 143 128 298 189 324 172 349 158 373 149 395 150 417 147 130 325 186 351 171 375 159 399 158 421 153 442 150 132 352 185 377 171 401 168 425 160 447 157 468 155 134 379 186 403 176 427 169 451 163 472 161 136 406 187 430 179 453 172 477 166 138 432 189 456 182 479 176 140 458 191 482 185 142 484 194 70 75 80 85 90 95 100 105 Table 5. Air onditioner & Heat Pump harging Table (5 Ton Units) - Orifice Matches 118 120 315 144 122 316 155 341 146 124 318 167 343 156 366 148 126 317 194 345 166 369 157 391 152 413 149 128 317 211 345 188 370 170 395 158 417 156 438 152 130 346 202 372 184 396 168 420 165 442 158 463 154 132 373 197 398 180 422 175 446 165 467 160 488 158 134 400 195 424 183 448 174 471 167 492 163 136 427 194 451 184 474 175 497 169 138 453 194 477 185 500 177 140 479 194 503 186 142 505 195 11

Air onditioner & Heat Pump efrigerant harging Tables Single Phase Units 70 75 80 85 90 95 100 105 Table 6. Air onditioner & Heat Pump harging Table (2 Ton Units) - Orifice Matches 129 131 276 126 133 278 138 300 131 135 279 149 302 141 323 135 137 279 170 304 151 326 143 346 140 366 139 139 280 187 305 168 328 153 349 146 370 147 389 144 141 306 182 330 167 352 153 373 155 393 150 412 148 143 331 180 354 166 377 162 397 157 416 154 435 153 145 356 180 379 170 401 163 421 160 440 158 147 381 181 403 172 425 165 444 164 149 406 182 428 175 449 169 151 430 184 452 178 153 454 187 155 70 75 80 85 90 95 100 105 Table 7. Air onditioner harging Table (2.5 Ton Units) - Orifice Matches 123 125 297 101 127 298 112 321 115 129 300 123 324 125 347 127 131 301 134 326 135 350 136 373 140 395 146 133 302 151 328 145 353 141 376 146 399 153 422 156 135 329 160 355 155 380 150 403 161 426 163 448 166 137 357 168 382 163 407 167 430 169 453 172 475 176 139 384 177 409 175 434 175 457 178 480 182 141 411 186 436 185 461 185 485 187 143 439 195 463 194 488 195 145 466 204 491 203 147 493 212 149 12

70 75 80 85 90 95 100 105 Table 9. Air onditioner & Heat Pump harging Table (3 Ton Units) - Orifice Matches 125 127 294 82 129 295 93 317 101 131 296 105 319 111 342 117 133 299 110 322 121 345 125 368 133 391 141 135 299 127 325 128 349 128 372 139 395 149 418 154 137 326 142 351 142 376 142 399 157 422 161 445 166 139 353 156 378 154 403 162 426 167 449 172 472 178 141 380 169 405 170 430 173 454 178 477 184 143 407 181 432 183 457 186 482 190 145 435 193 460 195 484 198 147 462 205 487 207 149 489 216 151 70 75 80 85 90 95 100 105 119 121 303 106 123 304 117 328 119 125 306 128 330 129 354 130 127 307 139 332 139 356 139 380 143 403 148 129 308 156 334 149 360 144 383 149 407 155 430 157 131 336 164 362 158 387 153 410 163 434 164 457 166 133 363 172 389 165 415 169 438 170 461 172 484 175 135 391 180 417 177 442 176 466 178 489 181 137 419 188 444 186 469 185 493 187 139 447 196 472 194 497 194 141 474 204 500 203 143 502 212 145 Table 9. Air onditioner & Heat Pump harging Table (4 Ton Units) - Orifice Matches 13

Heat Pump Verification tables - Heating Mode Only Application notes on the use of heating-mode charging tables: Legend Shaded boxes indicate flooded conditions. ated design values. Suction pressure will vary from design value if outdoor air flow, entering dry bulb, or entering wet bulb temperatures vary. NOTES: 1. All pressures are listed psig and all temperatures in F 2. Discharge temperatures greater than charted values indicate an undercharged system. ead all notes and warnings for the ooling-mode charging tables prior to using these Heating-mode charge verification tables. Always use safe and environmentally sound methods when handling refrigerant handling or servicing the unit. eview the factory literature and safety warnings prior to servicing. When repairing system leaks, always use a nitrogen (inert) gas to protect the refrigerant system and pressure check the repair before re-charging. Always replace the filter-dryers when performing any repair to the refrigeration system with one capable of acid removal. After completing the repairs, evacuate the system to 350-500 microns and weigh in the refrigerant to the amount specified on the unit rating label. Before using Tables 18-25 (pages 17-19), determine the outdoor ambient temperature and the return air temperature to the unit. Locate the appropriate location on the units verification table based on those measurements to determine the ideal liquid line pressure and temperature. Verify the outdoor fan and compressor are running and the outdoor coil is free from frost accumulation. Also verify the system is not operating in defrost mode before inspecting the system. Always use quality instruments that are in good working order to measure the actual operating point of the refrigeration system. The liquid line temperature should be within 2 degrees of the ideal value and the pressure should be within 2%. The most reliable way of verifying the system is at the correct charge is to evacuate the system and weigh in the charge to the amount shown on the rating label. However, if an inspection with these verification tables does not line up with the values shown and the ambient temperature is above 50 F, then a more accurate way to inspect the system for proper charge is with the cooling mode charging tables. Switch the unit into cooling mode and allow it to operate and stabilize for a few minutes then inspect the unit operation with the cooling mode tables and procedures. Before changing the unit charge, always inspect the following items first: 1. Inspect the liquid line temperature on the inlet and outlet of the filter dryers. If it is the factory dryer and in good condition there should be no temperature difference. If the temperature difference is larger than 5, replace the filter dryer with one that is bi-directional and has acid removal capability. efer to the unit PL for the recommended part number and size. 2. Inspect the units input voltage. Units operating at less than 95% of the nominal voltage may deviate more from the chart then previously stated. 3. Inspect the input voltage for a phase imbalance. Units with greater then a 2% disparity will not operate at the rated performance. 4. Verify that the unit filters are installed and are clean. The pressure drop across the filters should not exceed 0.08 in-w.. 5. Inspect the indoor coil, indoor blower and blower motor for cleanliness, clogging, and proper operation. 6. Inspect the system for leaks. If any leaks are detected, repair them immediately. e-inspect the return air and ambient temperatures and verify that the correct system point on the verification chart was selected. DO NOT use the tables in systems that have the fan cycling under a low-ambient control. Low-ambient controls are for cooling operation. In heating mode, the low ambient control should be disabled. Unless the unit is in defrost mode, the outdoor fan should always operate in conjunction with the compressor. 14

Heat Pump efrigerant harging Tables - Three Phase Units 0 10 20 30 40 50 60 27 251 151 41 269 154 55 287 157 69 305 160 83 309 166 96 323 175 109 337 184 28 258 149 42 275 152 56 292 155 70 308 158 84 316 163 97 330 170 110 344 178 29 265 147 43 281 150 57 297 153 71 312 156 85 323 160 98 337 166 111 351 172 30 272 145 44 287 148 58 301 151 72 316 154 86 330 157 99 344 161 112 358 165 31 279 143 45 293 146 59 306 149 73 319 152 87 337 154 100 351 157 113 365 159 32 286 141 46 299 144 60 311 147 74 323 150 88 344 151 101 358 152 114 372 153 33 293 139 47 305 142 61 316 145 75 327 148 89 351 149 102 365 148 115 379 147 Table 20. Heat Pump harging Table (3 Ton Units) - Orifice Matches 0 10 20 30 40 50 60 24 254 160 38 274 161 52 294 161 66 314 162 78 323 167 88 345 177 98 366 187 25 261 158 39 280 159 53 298 159 67 317 160 79 330 164 89 352 172 99 373 181 26 268 156 40 285 157 54 303 157 68 321 158 80 337 161 90 359 168 100 380 175 27 275 154 41 291 155 55 308 155 69 325 156 81 344 159 91 366 164 101 387 169 28 282 152 42 297 153 56 313 153 70 328 154 82 351 156 92 373 159 102 394 162 29 289 150 43 303 151 57 318 151 71 332 152 83 358 153 93 380 155 103 401 156 30 296 148 44 309 149 58 322 149 72 336 150 84 365 150 94 387 150 104 408 150 Table 18. Heat Pump harging Table (4 Ton Units) - Orifice Matches 0 10 20 30 40 50 60 25 260 162 37 279 163 49 298 164 60 318 165 72 323 169 84 336 176 95 349 183 26 267 160 38 285 161 50 303 162 61 322 163 73 330 166 85 343 171 96 356 176 27 274 158 39 291 159 51 308 160 62 325 161 74 337 164 86 350 167 97 363 170 28 281 156 40 297 157 52 313 158 63 329 159 75 344 161 87 357 163 98 370 164 29 288 154 41 303 155 53 318 156 64 333 157 76 351 158 88 364 158 99 377 158 30 295 152 42 309 153 54 322 154 65 336 155 77 358 155 89 371 154 100 384 152 31 302 150 43 314 151 55 327 152 66 340 153 78 365 152 90 378 149 101 391 146 Table 19. Heat Pump harging Table (5 Ton Units) - Orifice Matches 15

0 10 20 30 40 50 60 33 239 146 47 264 155 61 288 165 75 312 174 88 322 183 101 341 190 113 359 198 34 246 144 48 269 153 62 293 163 76 316 172 89 329 180 102 348 186 114 366 192 35 253 142 49 275 151 63 298 161 77 320 170 90 336 177 103 355 181 115 373 185 36 260 140 50 281 149 64 302 159 78 323 168 91 343 174 104 362 177 116 380 179 37 267 138 51 287 147 65 307 157 79 327 166 92 350 171 105 369 172 117 387 173 38 274 136 52 293 145 66 312 155 80 331 164 93 357 169 106 376 168 118 394 167 39 281 134 53 299 143 67 317 153 81 334 162 94 364 166 107 383 163 119 401 161 Table 21. Heat Pump harging Table (2 Ton Units) - Orifice Matches 030K 0 10 20 30 40 50 60 33 218 182 47 252 185 60 286 188 73 320 191 87 334 195 101 353 202 115 371 209 34 225 180 48 258 183 61 291 186 74 323 189 88 341 192 102 360 197 116 378 202 35 232 178 49 264 181 62 295 184 75 327 187 89 348 190 103 367 193 117 385 196 36 239 176 50 270 179 63 300 182 76 331 185 90 355 187 104 374 189 118 392 190 37 246 174 51 276 177 64 305 180 77 334 183 91 362 184 105 381 184 119 399 184 38 253 172 52 281 175 65 310 178 78 338 181 92 369 181 106 388 180 120 406 178 39 260 170 53 287 173 66 315 176 79 342 179 93 376 178 107 395 175 121 413 172 Table 23. Heat Pump harging Table (2.5 Ton Units) - Orifice Matches 16

0 10 20 30 40 50 60 30 225 174 44 254 175 57 283 175 70 313 176 84 329 179 97 354 185 110 379 191 31 232 172 45 260 173 58 288 173 71 317 174 85 336 176 98 361 180 111 386 184 32 239 170 46 266 171 59 293 171 72 320 172 86 343 173 99 368 176 112 393 178 33 246 168 47 272 169 60 298 169 73 324 170 87 350 170 100 375 171 113 400 172 34 253 166 48 278 167 61 303 167 74 328 168 88 357 168 101 382 167 114 407 166 35 260 164 49 284 165 62 307 165 75 331 166 89 364 165 102 389 162 115 414 160 36 267 162 50 289 163 63 312 163 76 335 164 90 371 162 103 396 158 116 421 154 Table 24. Heat Pump harging Table (3 Ton Units) - Orifice Matches 0 10 20 30 40 50 60 32 258 173 43 282 178 54 306 184 65 330 189 78 345 195 92 375 201 106 405 207 33 265 171 44 288 176 55 311 182 66 333 187 79 352 192 93 382 196 107 412 200 34 272 169 45 294 174 56 315 180 67 337 185 80 359 189 94 389 192 108 419 194 35 279 167 46 300 172 57 320 178 68 341 183 81 366 186 95 396 187 109 426 188 36 286 165 47 306 170 58 325 176 69 344 181 82 373 184 96 403 183 110 433 182 37 293 163 48 311 168 59 330 174 70 348 179 83 380 181 97 410 178 111 440 176 38 300 161 49 317 166 60 335 172 71 352 177 84 387 178 98 417 174 112 447 170 Table 25. Heat Pump harging Table (4 Ton Units) - Orifice Matches 17

WIING DIAGAM electrical Diagrams Split System Air onditioner (Outdoor Section) NOTES: 1. Disconnect all power before servicing. 2. For supply connections use copper conductors only. 3. Not suitable on systems that exceed 150 volts to ground. 4. For replacement wires use conductors suitable for 105 deg. 5. For ampacities and overcurrent protection, see unit rating plate. 6. onnect to 24 vac/40ca/class 2 circuit. See furnace/airhandler installation instructions for control circuit and optional relay/transformer kits. 7. Anti-Short ycle Timer (AST) may or may not be installed in the unit. If desired, AST is factory installed on select models only or may be field installed as shown using manufacturer s approved kit. If not present, connect Yellow and Black wires per Note 6. L1 T1 H - ontactor oil H - rankcase Heater HPS - High Pressure Switch F 24 VOLT FIELD ONNETIONS 208/230V H (OPTIONAL) HPS S OMPESSO S AST (SEE NOTE 7) AST LEGEND: FIELD WIING LOW VOLTAGE HIGH VOLTAGE L2 OMPESSO ONTATS OUTDOO FAN MOTO AST (SEE NOTE 7) HPS YELLOW Figure 2. Wiring Diagram for Single Phase Air onditioners Single Phase 1. ouper le courant avant de faire letretien. 2. Employez uniquement des conducteurs en cuivre. 3. Ne convient pas aux installations de plus de 150 volt a la terre. T1 T3 SEE NOTE 6 OANGE F DUAL APAITO H ED O YELLOW BLAK BLUE BLAK 710388B BLAK S OUTDOO FAN MOTO ED O ED BLAK ANKASE HEATE (OPTIONAL) YELLOW ONTATO ED O ED BLAK S T1 L1 ED BLAK L2 STAT ELAY GOUNDING SEW L1 L2 GND 710388B (eplaces 710388A) 0109 3 YELLOW 2 1 STAT APA YELLOW O YELLOW BLAK BLAK O BLK WHT 18