Study on an environmental simulation system of low/high temperature. for great space

Similar documents
Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler

Experimental Investigation of the Padding Tower 1. for Air Dehumidifier

Refrigerator and Heat Pump Objectives

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

,Chaojian He6, f. School of Guangxi University, Nanning , China.

AN EXPERIMENTAL REFRIGERATOR WITH AN INVERSE AIR CYCLE FOR FREEZING IQF FOOD PRODUCTS

Experimental Research of Air Source Heat Pump Frosting and Defrosting in a. Double Stage-Coupling Heat Pump

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Experimental Research on Monomial Cooling Measure of Greenhouse in Summer

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Dynamic Models of a Home Refrigerator

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

An Introduction of Below-Freezing and Humidity Environment Controlling Technology Equipped on Brake Test Equipment

State Grid Zhejiang Electric Power Corporation Electric Power Research Institute, Hangzhou, , China

Available online at ScienceDirect. Energy Procedia 70 (2015 ) Yanjun Dai*, Xian Li, Ruzhu Wang

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Purdue e-pubs. Purdue University

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

A Novel Heat Recovery System for High Temperature and High Humidity Gas Qing Hao1, a, Meng Si2, b

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Air Liquide Advanced Technologies Division Sassenage, 38360, France

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Chapter 10. Passive Cooling Contents

Study on an Air-Side Heating Source Liquid Desiccant Regeneration Model

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

FEEDGAS FOR MODERN HIGH-PERFORMANCE OZONE GENERATORS. Bruce T. Stanley. Ozonia Ltd Duebendorf, Switzerland 1999

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

EN aquatech.piovan.com

Impact of indirect evaporative air cooler type on the performance of desiccant systems

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

The Low-Temperature Radiant Floor Heating System Design and Experimental Study on its Thermal Comfort

New Design for Energy Saving Water Dispensers

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Analysis of Heating Systems and Scale of Natural Gas-Condensing Water Boilers in Northern Zones

Hybrid Refrigerated/Desiccant Compressed Air Dryers

Experimental study of hybrid loop heat pipe using pump assistance for high heat flux system

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

K.F. Fong *, C.K. Lee, T.T. Chow

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Design of Mine Safety Detection Alarm Based on Single-chip Mingtao Ma

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Investigation, Analysis and Solution of Higher Noise of Heat Pump Water Heater

Analysis of the influence of open door size on fire smoke diffusion law in protective engineering

Application of the VRV Air-Conditioning System Heat Recovery Series in. Interior Zone and Analysis of its Energy Saving

Moisture can be very disruptive to a dust. Preventing moisture problems in your dust collector

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Experimental Study on the Effects of Compression Parameters on Molding Quality of Dried Fish Floss

How to ensure Thermal Comfort in buildings with CFD

The Energy Consumption Investigation of the Hotel Central. Air-conditioning System and the Research of Energy Saving Measures

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

Experimental Study on Performance of Double pipe Length on Instantaneous Air Source Heat Pump Water Heater. Yin Shaoyou 1, a

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

A new method for preventing air-source heat pumps and refrigerators from frosting

Performance investigation of Air-conditioning system using ejector as expansion device

Experimental study of fan coil assisting radiant floor heating system

Adsorption refrigeration system using waste heat

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

Rust, corrosion and leakages threaten even the best network. Only Quality Air Solutions. in optimal shape. air distribution

Indoor Thermal Environment of Residential Buildings in Three Cities of China

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

A study of Transient Performance of A Cascade Heat Pump System

Dynamic performance of a novel dew point air conditioning for the UK buildings

Structure Design and Simulation of Intelligent Anti-blocking Sink

Customers. The core of our innovation. Feeding&Conveying Drying Dosing Temperature Control Refrigeration. Granulation

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE

White paper Compressed air drying

Chapter 11 REFRIGERATION CYCLES

Numerical Analysis of Water Temperature Distribution in the Tank of. ASHPWH with a Cylindrical Condenser

Development of Bionic Air Cooler Used in High Temperature Coal Mine

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Performance of an Improved Household Refrigerator/Freezer

Transcription:

International Conference on Advances in Energy and Environmental Science (ICAEES 2015) Study on an environmental simulation system of low/high temperature for great space Weike Pang1, a*, Tianping Liu1, b, Jun Wang1, c 1 School of Aeronautic Science and Engineering, Beihang University, Beijing, China a vke_java@163.com, bliutp@buaa.edu.cn, cwangjun@buaa.edu.cn Keywords: air turbine, dew-point temperature, self-adaption adjustment Abstract An environmental simulation system of low/high temperature for great space that is for a function test on its unfolding structure of some aerials is designed based on air refrigeration principle. According to its practical run at chamber temperature of -70 C, its main parts such as driers, turbines, environmental chamber are investigated. The experiment results show that it is viable to adopting refrigeration way of air turbine for an environmental system of great space simulating low/high temperature. It is not only fulfilled with their temperature demand during those experiments, but also their humidity demand. The subsystem of driers works well and matches with its regeneration, which the wave of dew-point temperature reduces during its switch stage. Meanwhile, the energy is saved. The air turbine could adjust its cooling capacity by itself according to load changes. The pressure of environmental chamber keeps to be about 30~100Pa, so the whole system could run safely, stably and reliably. Background The technology of environmental simulation is one of important conditions for present researches. After an appropriate laboratory that could simulate their practical run environment is constructed, their function parameters of new developed products could be tested and analyzed here. It will cut down their improved and optimized periods greatly. As a result, their developed efficiency of new products goes up [1]. The environmental simulation system of low and high temperature mainly focuses on the laboratory temperature. Additionally, those parameters of humidity, pressure and cleanness are asked to give some control strategies [2] [3]. As far as aeronautics and astronautics projects, there are some unique traits about space environmental simulation [4]. An environmental simulation system for function test of some aerials affiliated to astronautics institutes is demanded to adjust its chamber temperature from -100 C to +130 C. Overall, it takes a refrigeration way of air turbine [5]. Based on its run state of non-fog, non-dew and non-frost in the chamber, the subsystems of air driers, refrigeration and chamber are studied with aerial load at lowest temperature of -70 C. 2015. The authors - Published by Atlantis Press 567

Process principle and project practicality air compressor 1 filter 1 air tank 1 intake valve turbine 1 air supply panel water cooler drier 1 cooling reclaim air compressor 2 filter 2 drier 2 air tank 2 electric heater exhaust fan turbine 2 exhaust valve environmental chamber circulating fan Fig.1 Process principle of the environmental simulation system As shown in figure 1, outdoor air is compressed firstly by air compressors. After then its pressure becomes high and is referred to as high-pressure air. Next, the high-pressure air goes into driers to remove most of vapor inside air and further becomes dry air of high pressure. The processed preliminarily air is collected in an air tank together and the wave of air current disappears here. The air with steady pressure steps into a boosting-turbine unit to be compressed again, and then cooled in a water cooler. Later, the air cooled by water comes into an energy exchanger with cooling reclaim. The cold air is cooled again by exhaust air whose temperature is lower from the chamber. Consequently, the air becomes colder and reuses lots of cooling by heat transferring. The colder air finally gets into a turbine to swell and drops down its own temperature. At last, the air whose pressure and temperature drop down is gave into the chamber by an intake valve. Now, an environment with low temperature is simulated. Moreover, the turbulence of given air should be down to keep the test zone of products in a stable state. Accordingly, some radiant exchangers are fixed up along indoor walls. They also could be switched to a cooling way of air supply by panels[6]. When an environment of high temperature is simulated, the intake valve and exhaust valve should be shut down. The indoor air is transported through an electric heater by a circulating fan at first. Then the air of high temperature that is heated returns to the chamber by air supply panels. Again and again, the set temperature could get finally. The practical projects are shown partly in figure 2 and figure 3. Fig.2 Some zone of the chamber Fig.3 Some zone of the refrigeration subsystem Data disposal and analysis The humidity field of environmental chamber is affected mainly by its dew-point temperature of given air. The moisture content of compressed air processed by driers is an important factor that 568

adjusts the humidity field actively. The surplus moisture transferred from primary air should be taken away by the given air. So the drier is a key part to control the humidity. The process of driers is adsorption and regeneration, and its regeneration consists of heating, cooling, and pressure balance respectively. A drier subsystem is made up of two driers and they work alternately. If one drier is dehumidifying, the other stops to regenerate. The main part of each drier is a pressure container that is defined as tank A and tank B. The pressure trend of two tanks in a whole period is shown in figure 4. The waiting time to work again that one drier finishes its pressure balance starts earlier than the stop time that the other finishes dehumidifying and then switches to heat. According to its practical run, its waiting time is about 30 minutes. Therefore, the drier subsystem could work stably and reliably. So, the wave of dew-point temperature is low during the two driers switch each other. The operating pressure of the drier at a state of dehumidifying is 7bar. The operating pressure of the drier at a state of heating or cooling is 0 (1bar in absolute pressure); its pressure at a state of awaiting return to 7bar. Fig.4 Pressure trend of a drier subsystem Fig.5 Temperature trend of regeneration air in a drier subsystem The regeneration of driers is a stage of its desiccant heated and then cooled by air. The air is heated by an electric heater, and it could be heated to a high temperature of 195 C. The cold source is some throttled air that is taken from the processed dry air. It is about 2%~4% of processed dry air in volume flow. The hot air transfers heat to these desiccants and its temperature goes down 569

obviously. With the moisture in desiccants decreases, the heat transferred from hot air goes down gradually. As a result, its temperature of desiccant goes down less than before. When it returns a set temperature, there is little moisture in desiccants. Now, heating is completed to start cooling and then the electric heater turns off. On the other hand, heating time could be set according to its regeneration load. If there is a heavy load, the heating time may increase, but it is not more than three hours. When it is heated overtime, it would be stopped heating compulsively and starts cooling too. So their switch time of two driers is not affected. If there is a light load, the heating time would be shortened so that its input energy reduces and could save some energy. In figure 5, those desiccants switch to cool during its first period according to its air temperature at outlet of regeneration way; and during its second period they switch to cool according to its heating time. The stage of cooling desiccants goes though common air cooling firstly and then dry air cooling. The first cooling goes short and its time is about several minutes. The second cooling is major and its time is about 2.5 hours. As far as first cooling, after electric heater turns off, the air temperature of heating way goes down greatly. However, there is some remaining heat and it could also heat those desiccants as heating stage before. So its air temperature at outlet of regeneration way goes on to increase as its heating stage. When next cooling starts, the air of heating way is shut and some dry air is throttled to cold air to cool those desiccants again. The air of regeneration way makes those desiccants cool and its own temperature goes up. With the temperature reduction of desiccants, its temperature of outlet air would go up to a maximum. After then, with the temperature reduction of desiccants continually, the air of regeneration way transfers less heat and its temperature goes up less than before. As a result, its temperature of outlet air goes down gradually than before too. Fig.6 Speed trend of turbines during refrigeration The practical operating state of air turbines is affected by its cooling load in chamber and some external factors. On one hand, while its temperature of chamber goes down, the whole cooling load reduces gradually. On the other hand, while its suction temperature of turbines goes down, the discharge temperature of turbine decreases. Because the whole cooling load drops, the refrigeration capacity of turbine drops accordingly. Additionally, there is a constant load if its cooling rate of air in chamber is similar. So the suction change of turbines would affect its run. As shown in figure 6, with its low suction and discharge temperature except other constant parameters, its refrigeration capacity would go up; but it would not. That is because its rotational speed goes down and flow rate reduces. Consequently, its refrigeration capacity keeps stable. During temperature-controlled stage, its cooling load in chamber and suction temperature do not change so its rotational speed does not change either. During temperature-return stage, its discharge temperature goes up for its high temperature of suction. Therefore, its rotational speed of turbine goes up to prevent its refrigeration capacity from dropping down. The feature of self-adaption adjustment keeps the system operating 570

steadily, and saves lots of energy. Fig.7 Pressure trend in chamber during test Fig.8 Temperature trend in chamber during test As shown in figure 7, the pressure of chamber keeps a little higher than outdoors. It is about 30~100Pa higher. As far as an environment of low temperature, if its pressure of cold air is higher than outdoor, it could prevent external air from getting into its chamber. Comparatively speaking, external air is wetter and its temperature is higher than indoor. Moreover, those insulations of chamber are shrunk at a cold state. Therefore, there may be some gaps and outdoor air may enter into its chamber via these gaps. If so, its thermal and humidity balance would be broken. Consequently, its temperature and humidity in chamber would go up. Seriously, there may be some fog in its chamber and some function tests of developed products are forced to break off. During its stage of air substitution in chamber, its temperature keeps at about 40 C. After its dew-point temperature of chamber air goes down at -70 C, the cooling stage begins. At the first stage of cooling, cold given air mixes with the dry air in chamber to make its temperature low. When the first stage is over, its temperature could decrease at about -20 C as shown in figure 8. Next, at the second stage, the cold given air is switched to radiant exchangers in chamber. Its temperature of chamber goes on to reduce by a way of indirect cooling. On the other hand, during its switch stage at -20 C,there is about 30 minutes for temperature stabilization. So there is thermal adaption time for chamber materials. Then, according to function tests of this product, the temperature of chamber goes down at -68 C. Meanwhile, the key drive parts of this product also goes down at -68 C though they are heating locally by some micro heaters at the same time. After then, its temperature of chamber begins to return. During its return, the practical unfolding stage of this tested aerial at low temperature is simulated. About an hour later, its temperature of chamber return at -53 C and the aerial unfolding is over. Finally, according to its test need, the stable temperature field could keep some time and then return as outdoor environment. Conclusions Based on its practical run, it is viable to adopting refrigeration way of air turbine for an environmental system of great space simulating low/high temperature. It is not only fulfilled with their temperature demand during those experiments, but also their humidity demand. Some results shows following: 1) The subsystem of driers works well and matches with its regeneration, which the wave of dew-point temperature reduces during its switch stage. Meanwhile, the energy is saved. 2) The air turbine could adjust its cooling capacity by itself according to load changes. 3) The pressure of environmental chamber keeps to be about 30~100Pa, so the whole system could run safely, stably and reliably. 571

References [1] Wang Jun. Present status and development of environment simulation technology in China [J]. Aerospace manufacturing technology, 2004.08 [2] Chang Haijuan. Study on Pressure Control Strategy of High-altitude Multi Environmental Parameter Simulation Cabin System [J]. Acta Armamentarii, 2008, 29(11) [3] Li Ke, Pang Liping, Liu Wangkai. System model simulation and control method used in environmental simulation chambers [J]. Journal of Beijing University of Aeronautics and Astronautics, 33 (5) [4] Zhu Yu. Feature and present situation of space environmental simulation with the develop trend in China [J]. Science information of Jiangsu, 2013.12 [5] Du Jiantong. Characteristics and Key Technologies for Air Cycle Refrigerating [J]. Cryogenics and Superconductivity, 1999, 27 (3) [6] Cui Yi. Optimization study of simulation on high altitude environmental simulation for large aircraft [J]. Cryogenics, 2008.03 572