Dimplex High efficiency air-to-water heat pump for indoor installation. (Low temperature) Order reference

Similar documents
Starting current with soft starter Fuse protection

Starting current with soft starter Fuse protection. Connection heating Seal of approval MCS (valid until)

Starting current with soft starter Fuse protection. Heat source connection

Starting current with soft starter Fuse protection

Data sheet SI 24TE. Brine-to-water heat pump with two performance levels

Product Range Overview 2010

WARMTEPOMPEN DIMPLEX. POMPES À CHALEUR DIMPLEX.

PRODUCT DATA SHEETS HEAT PUMPS

Product Range. Overview 2015.

Technical data LA 60TU

Technical data LA 9S-TU

Technical data LA 60TUR+

A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser

Technical data LA 28TBS

For a future without oil and gas.

Advance Split

VIESMANN. VITOCAL Air/water heat pumps. Technical guide. VITOCAL 300-A Type AWC-I and AW-O. VITOCAL 350-A Type AWH-I and AWH-O

BWL air heat pumps BWS brine heat pumps

WZS 82(H)(K)3M 20 I B0W I I I (263) (288) 7.0

Split inverter air-to-water heat pump CERTIFIED BY CERTITA. option 30/35-40/45

Air / Water Heat Pump - Compact Design Modulating 8 18 kw

A w rld of new product innovation new product launches

MODEL LA 6 MI LA 9 MI LA 12 MI LA 16 MI. Heat output (kw)/cop at A-15/W35 5.9/ / / /2.33

HIGH-POWER HEAT PUMPS. Up to 300 kw

80HMA. Comfort Module Range for Monobloc Heat Pumps. Compact comfort module. DHW management possibility. Multi zone option control.

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

SOLUTIONS DE TRAITEMENT HEATING SOLUTIONS. Comfort Module 5-20 kw. Choose the easy heating solution!

A-Class. A-Rated Homes with Dimplex heat pumps. The name you can trust. Building Regulations and Part L Compliance made easy with Dimplex. dimplex.

Planning guide. (2010/09) en

Product Line Introduction. Karl Zhang Technical support engineer

80HMA. Comfort Module Range for Monobloc Heat Pumps. Nominal heating capacity 4-20 kw Nominal cooling capacity 4-20 kw. Features

LZT High efficiency air to water heat pumps with E.V.I. compressors

Do you want a versatile solution

Geolo THE GROUND SOURCE HEAT PUMP PLUSES

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

Outline principle. Application Houses with water-borne heating systems. Alternative Select the desired configuration by highlighting the boxes below.

AIR TO WATER HEAT PUMPS. Hot water and comfortable ambient temperature all year round

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

Efficient heating that won t cost the earth

LZA High efficiency air to water heat pumps with HP compressor

HT V2 HT Split

Saving energy comes naturally to us.

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

your tree NEW TREE for you Several facts on trees: Follow our Green Tree heat pumps

Technical description. Atec.

VIESMANN VITOCAL 300-G Brine/water and water/water heat pump Single and two-stage, from 21 kw

NABILATON PRO. The Nabilaton Pro heat pumps consist of MDV brand outdoor units and suitable hydraulic modules from Nabilaton.

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

High temperature air-to-water heat pumps

TOSHIBA AIR CONDITIONING

PAC BT LOW TEMPERATURE HEAT PUMP WITH DHW TANK INCLUDED

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Savings and performance worth celebrating! The DHP-AQ new air source heat pump from Danfoss

Technical specifications

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES

Planning guide. Atec.

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

WPM 2006 plus WPM 2006 R WPM 2007 plus WPM 2007 R

WATER TO AIR DUCTABLE INDOOR HORIZONTAL HEAT PUMP

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

Outdoor Reset Control Theory FULL versus PARTIAL reset

Superior. A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler. Outputs 120, 160, 200, 240, 280 kw

Oilon Ground Source Heat Pumps

HEAT PUMPS EN - flyer 10/p/2017 Made in Poland

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

Aluminium range of condensing boilers. Works every time. Designed to meet carbon reduction targets. Lifetime service and support

ELFOEnergy Duct Inverter

Monobloc. Distributed by. Copyright 2018 LG Electronics. All rights reserved.

Air to water Heat Pump System

HPWH 300 HPWH 300HE. Installation and Operating Instructions. Hot Water Heat Pump for Outdoor Installation. English FD 9501

HIGH EFFICIENCY POOL DEHUMIDIFIER AND CONDITIONER WITH HIGH HEAT RECOVERY RATES. Air treatment unit. Swimming pool waste air 28 C-65%

PROJECT PLANNING AND INSTALLATION MANUAL

30AW. Reversible Air to Water Heat Pump PRODUCT SELECTION DATA. Monobloc inverter. Compact, reliable and efficient. More than a Heat Pump

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

30RQV NEW. Nominal cooling capacity kw Nominal heating capacity kw AIR-TO-WATER HEAT PUMPS HEATING. Easy and fast installation

ECOFOREST GEOTERMIA. ecogeo. Ground/Air Source Heat Pumps.

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT

Blue Box Epsilon Echos +

w Outdoor Unit w Hydro Indoor Unit w Hot Water Tank *** Projected Availability Q ***


Products catalogue THERMODYNAMIC SOLUTIONS FOR EFFICIENCY CHALLENGES

50A KP 70A KP 90A KP 120A KP 150A KP 210A

SmartRad Planning Manual

and sanitary hot water Catalogue 2009

AGEO CALEO. Water-to-water high temperature heat pumps USE RANGE DESCRIPTION. Designed to replace a conventional boiler and produce domestic hot water

Press. Heat pumps from Viessmann: efficient heat generation with renewable energy and electricity

Installation, operating and servicing instructions

Frequently Asked Questions

your comfort. our world. Altherma Flex Type Renewable heat pump system for every environment

Installation and operating instructions. DK energy storage and DK energy buffer

LZT High efficiency air to water heat pumps with E.V.I. compressors

MAKING MODERN LIVING POSSIBLE. Technical description DHP-M.

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

ALFÉA EXCELLIA DUO. more. less AIR TO WATER HEAT PUMP

Heating with airborne and geothermal heat

SHERPA DHW 75. Th e multifunctional air-water split heat pump. COP > 4 DHW 75 C

Type summary Albatros 2

EFG ENERGY OPTIMISING SYSTEMS

Transcription:

Data sheet LI 9TU High efficiency air-to-water heat pump for indoor installation. Max. flow temperature: 60 C Casing colour: White (similar to RAL 9003) Brown-red design screen (RAL 3011) Heat pump for heating purposes for indoor installation with integrated WPM Econ5Plus control. Sound-optimised through the use of slow-running EC 3D radial fan, an encapsulated compressor housing and a free-swinging compressor baseplate for solid-borne sound insulation. High coefficients of performance (COP) through high-performance evaporator, electronic expansion valve and compliance with the requirements of EN 14511 for larger volume flows on the heat consumption side. High operational safety through sensor monitoring of the refrigeration circuit with demand-based defrosting; integrated thermal energy metering (display of the calculated quantity of thermal energy for heating and domestic hot water preparation on the heat pump manager). The integrated air circuit with 90 air deflection enables installation in a corner without air ducts or wall installation with air ducts on the air outlet side. Variable installation thanks to air intake from the rear, flexible air outlet to the right, left or top, and the option of making the hydraulic connections from right to left. The control panel is integrated in a design screen and can also be used as wired remote control using the wall mounting set (special accessories MS PGD). Universal design for low-temperature heating systems with flexible expansion options for: - Room temperature control via Smart RTC (special accessory) - Bivalent or bivalent-renewable operating mode - Distribution systems with unmixed and mixed heating circuits - Use of load-variable tariffs (SG Ready) At an external temperature of -10 C, the maximum flow temperature that can be achieved is 56 C. Flow and return sensor integrated; external sensor (standard NTC-2) in the scope of supply. Dirt trap and flow rate switch built in. Technical data Dimplex High efficiency air-to-water heat pump for indoor installation. (Low temperature) Order reference LI 9TU Heat pump code 1009 Casing colour White (similar to RAL 9003) Max. flow temperature 60 C Lower operating limit heat source (heating operation) / Upper operating limit heat source (heating operation) -20 to 35 C Heat output A-7/W35 / COP A-7/W35* 5,4 kw / 3,0 Heat output A2/W35 / COP A2/W35* 6,8 kw / 3,9 Heat output A7/W35 / COP A7/W35* 8,5 kw / 4,7 Heat output A10/W35 / COP A10/W35* 8,9 kw / 5,0 Nominal power consumption according to EN 14511 at A2/W35 1,7 kw Nominal power consumption according to EN 14511 at A7/W35 1,8 kw Sound power level 49 db (A) Sound pressure level in 1 m 42 db (A) Refrigerant / Amount of refrigerant R410A / 3,7 kg Max. heating water flow rate / Pressure drop 1,5 m³/h / 19300 Pa Heat source flow (min.) 3700 m³/h Dimensions (W x H x D)** 960 x 1560 x 780 mm Weight 256 kg Rated voltage 3/N/PE ~400 V, 50 Hz Starting current 16 A Fuse protection*** C 10 A Type of defrosting Reverse circulation Connection heating 1 ¼ inch *Heat output and coefficient of performance (COP) according to EN 14511 **Please note that additional space is required for pipe connections, operation and maintenance. ***Die Absicherung ist als allpolige Trennvorrichtung auszuführen (gemeinsame Abschaltung aller Phasen)! Page 1/6

System accessories LI 9TU Description Heat pumps Order ref. Article number High efficiency air-to-water heat pump for indoor installation. LI 9TU 364060 1 Elasticated sound insulation underlay strips SYL 250 352260 DN 32 double-sphere rubber expansion joint KOMP 32 362060 DN 32 dirt trap SMF 32 362140 Air-to-water heat pump connection kit VSF 25 361790 Heat source accessories Sample 90 air duct bend* LKB 600A 366150 90 air duct bend* LKB 800A 366170 Sealing collar 600 DMK 600-1 356120 1 Sealing collar 800 DMK 800-1 356140 Deflector hood LUH 600 358620 Rain guard for LI RSG 600 340230 1 Rain guard for LI(H) RSG 800 340250 1 Hydraulic accessories Heating water hose connection set SAS 110 340330 1 Free-standing buffer tank 100 l* PSW 100 351090 Free-standing buffer tank 200 l* PSW 200 339830 Dual differential pressureless manifold DDV 25 358390 1 High-efficiency circulating pump DN 25 with coupling relay UP 75-25PK 376740 1 Manifold bar DN 25 VTB 25-2 376360 Manifold bar DN 32 VTB 25-3 376370 Domestic hot water module/unmixed heating circuit module WWM 25 346600 1 Mixed heating circuit module with temperature sensor MMH 25 348640 Mixer module for bivalent systems MMB 25 348880 Electronically controlled wet-running pump, Î p-v, fixed speed and PWM signal UPE 70-25PK 374700 1 3-way ball valve DN 25* DWK 25 364680 Ready-for-use DN 32 stainless steel Wellflex pipe VSE 32-50 362520 Ready-for-use DN 32 stainless steel Wellflex pipe VSE 32-100 362530 Ready-for-use DN 32 stainless steel Wellflex pipe VSE 32-150 362540 Ready-for-use DN 32 stainless steel Wellflex pipe VSE 32-200 362550 Ready-for-use DN 32 stainless steel Wellflex pipe VSE 32-300 362560 Immersion heater pipe assembly* HDLR 450 337450 Heating accessories Fan convector heating with EC fan SRX 080EM 367500 Fan convector heating with EC fan SRX 120EM 367510 Fan convector heating with EC fan SRX 140EM 367520 Fan convector heating with EC fan SRX 180EM 367530 DHW preparation accessories Domestic hot water cylinder 200l with temperature sensor* WWSP 229 374570 Domestic hot water cylinder (300l) with temperature sensor WWSP 335 376760 1 Flange heater for domestic hot water FLH 60 338060 Flange heater for domestic hot water FLHU 70 338070 1 FLH 25M flange heater FLH 25M 349430 Safety valve combination SVK 852 326660 Domestic hot water cylinder (400 l) with temperature sensor* WWSP 442 372840 Design domestic hot water cylinder with sheet metal coverings and temperature sensor* WWSP 442E 353370 400l solar cylinder for heat pump* WWSP 432 SOL 361080 Hydro Tower without regulation* HWK 332 362360 Combination tank heating and domestic hot water preparation* PWS 332 348620 PWS 650 combination tank* PWS 650 367660 Combo tank for heating and domestic hot water preparation with central flow* PWD 750 349100 Pump unit DN 25 for direct connection of the domestic hot water cylinder WPG 25 356030 1 High-efficiency circulating pump DN 25 with coupling relay UP 75-25PK 376740 1 3-way reversing valve DN 25* DWV 25 374770 Control accessories item Item Price Page 2/6

System accessories LI 9TU Description Order ref. Article number Extension for an Ethernet network connection NWPM 356960 Expansion module WPM for a KNX/EIB connection KNX WPM 376350 Extension for a Modbus RTU connection LWPM 410 339410 Remote control for WPM 2006/2007/EconPlus/R* AP PGD 356570 Outside temperature sensor with casing FG 3115 336620 Temperature sensor NTC-10 with metal sleeve NTC-10M 363600 Solar thermal systems accessories Heat exchanger station SST 25 for solar energy systems up to max. 10 m² * Other specific accessories available / required SST 25 348430 Sample Notes: Heat output according to EN 14511 at A2/W35 (A2 = air intake temp. +2 C, W35 = heating water outlet temp. +35 â ƒ). Important information: The combination of the components and the quantities indicated represent a non-binding sample system, which needs to be tested and individually adapted as required. Pump dimensioning must be reviewed according to the pressure loss of the system and the minimum heating water flow rate of the heat pump. item Item Price Page 3/6

Air-to-water heat pump, Integration Diagram, Heat pump and immersion heater Note: The given hydraulic integration schematic is a schematic representation of the key components and serves as an aid for planning your customized system. The current status is available at all times under www.dimplex.de/nc/en/professional/onli ne-planner/hydraulic-integrations.html. It does not contain all the required safety devices, the components needed to maintain constant pressure, or any other additional valves which may be required for maintenance and service work as stipulated by EN 12828. The heat pump manager settings and any external regulation system which may be connected must be adapted to the present integration diagram. Software updates may be required! Page 4/6 Integration Diagram: 10231024

Air-to-water heat pump, Integration Diagram, Heat pump and immersion heater System description: Air-to-water heat pumps with defrosting by reverse circulation extract the energy required for defrosting from the heating system. In the case of air-to-water heat pumps, a buffer tank connected in series, into which the immersion heater is screwed, must be installed in the flow in mono energy systems to ensure defrosting. A dirt trap with a mesh size of between 0.6mm and 0.8mm is to be installed in order to protect the plate heat exchanger from larger dirt deposits. Clean the filter sieve of the dirt trap one day after start-up. These intervals can be extended as soon as no more impurities are detected. When the level of impurities is significantly high (e.g. due to corrosion found in the building), it is recommended that a sludge trap be installed in order to minimise the need for regular cleaning. A permanent corrosion process, caused by the entry of oxygen into the system, is characteristic of heating systems featuring open diffusion. This is best alleviated using an electrophysical anti-corrosion system. Condensate which forms during defrosting must be drained off without risk of frost. Acoustic emissions must be taken into account, and a free air circuit provided for, when the installation location is being selected. Heat pumps without weather-proof protective covers in particular need to be installed outdoors in such a manner that the air outlet is not positioned against the main wind direction. A buffer tank connected in series is recommended for heat pump heating systems, to ensure the minimum heat pump runtime of 6 minutes for all operating statuses. Presettings: Pre-configuration Operating mode Heating circuit 1 Heating circuit 2 DHW preparation DHW preparation request by Domestic hot water preparation flange heater Swimming pool water preparation Setting Mono energy Yes No Yes Sensor Yes No The heat pump supplies a large part of the required heat output. An electric heating element (immersion heater) supplements the heat pump on days when the external temperature lies below the bivalence point. In mono energy systems, the contactor for the immersion heater (E10.1) must be set according to the output. It is controlled (230 V AC) by the heat pump manager via terminals X1/N and J13/NO4. The heat exchanger in the hot water cylinder must transfer the maximum heat output at the maximum heat source temperature. In systems with high hot water consumption (multiple dwellings, industrial applications) the cylinder must be set to the maximum peak demand while taking the shut-off times into account. The maximum heat output and the maximum heating water flow must be adhered to! The contactor for the flange heater (E9) in the hot water cylinder should be dimensioned according to the output and must be supplied by the customer. It is controlled (230 V AC) by the heat pump manager via terminals X1/N and J16/NO10. The maximum heat output of the heat pump and the water flow are to be observed. The dual differential pressureless manifold ensures that the required minimum water flow rate is maintained, independent of both the number of open heating circuits and of how the system is used. Hydraulic isolation is carried out using two connections between flow and return; each connection is fitted with a check valve. The characteristic curve of the pump in the consumer circuit must be set in such a way that a maximum spread of 10 Kelvin is not exceeded, in order to prevent unnecessary surging of the heat pump. Electronically regulated pumps must be operated at a constant pressure. Page 5/6 Integration Diagram: 10231024

Air-to-water heat pump, Integration Diagram, Heat pump and immersion heater Legend: 1. Heat Pump 1.1 Air-to-water heat pump 1.2 Brine-to-water heat pump 1.3 Water-to-water heat pump 1.4 Reversible air-to-water heat pump 1.5 Reversible brine-to-water heat pump 1.6 Reversible water-to-water heat pump 1.7 Air-to-water heat pump split design 2. Heat pump manager 3. Parallel buffer tank 3.1 Buffer tank 4. Hot water cylinder 5. Swimming pool heat exchanger 6. Passive cooling station with cooling controller N6 7. Heating and silent or dynamic cooling 8. Fan convector with 4-wire connection 9. Cooling circuit only 10. Heating circuit only 13. Heat source 15. Hydraulic tower 16. Scalding protection 17. Hydro tower HWK 332 Domestic hot water distribution system: DDV 25 DDV 32 EB KPV KPV 25 MMB 25 MMH 25 VTB 25 WWM 25 Dual differential pressureless manifold (up to 2.0 m³/h)* Dual differential pressureless manifold (up to 2.5 m³/h)* Extension module for compact manifold (up to 2.0 m³/h)* Compact manifold with overflow valve (up to 1.3 m³/h)* In combination with EB KPV (up to 2.0 m³/h)* Mixer module, bivalent (up to 2.0 m³/h)* Mixer module for heating circuit Manifold bar (up to 2.5 m³/h)* Hot water module / unmixed heating circuit (up to 2.5 m³/h)* * Recommended max. heating waterflow Solarthermics: SST 25 Solar station for hot water SOLPU 1 Solar station SOLCU 1 Solar controller T1 Temperature sensor (collector sensor) T2 Temperature sensor (cylinder 1) T3 Temperature sensor (cylinder 2 /optional display function) B3 Hot water thermostat B4 Swimming pool thermostat B7 Thermostat primary circuit E9 Flange heater, hot water E10 2nd heat generator (HG2) E10.1 Immersion heater E10.2 Oil/gas boiler E10.3 Solid fuel boiler E10.5 Solar energy system F7 Safety temperature monitor F10 Flow rate switch K20 Contactor for 2nd heat generator K21 Contactor for immersion heater hot water M11 Primary pump for heating operation M12 Primary pump for cooling operation M13 Heat circulating pump for main circuit M14 Heat circulating pump for heating circuit 1 M15 Heat circulating pump for heating circuit 2 M16 Auxiliary circulating pump M17 Cooling circulating pump M18 Hot water circulating pump M19 Swimming pool water circulating pump M20 Heat circulating pump heating /cooling circuit 3 still M21 Mixer M22 Mixer heating/cooling circuit 2 M25 Circulating pump for heating and domestic hot water preparation N1 Heating controller N2 Cooling controller for reversible heat pumps N3 Room climate control stations N12 Solar controller N17.1 Cooling module general N17.2 Cooling module active N17.3 Cooling module passive N17.4 Solar module WPM Econ SOL R1 External wall sensor R2 Return flow sensor R3 Hot water sensor R4 Return flow sensor for cooling water R5 Temperature sensor for heating circuit 2 R9 Flow sensor (antifreeze) R11 Flow sensor for cooling water R13 Sensor for heating circuit 3 / bivalent-renewable SMF Dirt trap TC Room temperature controller Y5 Three-way distribution valve Y6 Two-way valve Y7 Three-way mixing valve Y8 Three-way valve (closing time max. 10 sec.) Y12 External 4-way reversing valve Y13 Three-way reversing valve Page 6/6 Integration Diagram: 10231024