The electrical wattage needed by the circulator is:

Similar documents
Circulators high efficiency ECM Circulators

Distribution Efficiency: The Under-appreciated Benefit of Hydronics

Outdoor Reset Control Theory FULL versus PARTIAL reset

"Best Practices in Modern Hydronic Heating - THE DETAILS

Hydraulic Separation Moving Beyond Priamry / Secondary Piping...

InDEX. A Technical Journal from Caleffi Hydronic Solutions

GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS

LOW TEMPERATURE HYDRONIC HEATING FOR COLD CLIMATES TRAVIS SMITH PRESIDENT T AND T MOUNTAIN BUILDERS INC

6 PIPING ARRANGEMENTS

Air-to-Water Heat Pumps + Boilers A Dynamic Duo

- Data Brochure Universal Reset Module 422

Welcome To. System Benefits With ECM PUMPS

union swing check valve spring loaded check valve purging valve pressure relief valve relief valve metered balancing valve

Applications and Piping Strategies for Condensing Boilers - Introduction

Donʼt do this with ANY hydronic heat source! Heat transfer between the water and the upper floor surface is severely restricted!

Dear Hydronic and Plumbing Professional, Dear Hydronic Professional,

- Data Brochure Universal Reset Module 423

2.A MANIFOLD SHUNTS MINI SHUNTS

Wilo Stratos Z vs. standard three piece bronze domestic recirc pump

Dear Hydronic Professional, Dear Hydronic Professional,

The Universal Reset Control 363 is a microprocessor based control designed to maximize the comfort and efficiency provided by a hydronic

Installation & Operation Manual

Selecting Circulators TD10 EFFECTIVE: SUPERSEDES:

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

Hydronic Mechanical Panels

- Data Brochure Universal Reset Control 364

Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014

Radiant Heating. Systems

Hydronic Solutions for Low Energy Houses

CONTROLLED CHILLED BEAM PUMP MODULE

- Essay Control Functions and Benefits

CONTROLLED CHILLED BEAM PUMP MODULE

- Data Brochure Boiler Control 274

EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money. How hydronic heating systems work

Boiler Demand Mix 1 Demand Mix 2 Demand DHW Demand Setpoint Demand

A Primary Concern by John Siegenthaler, P.E. October 1, 2005

THE HEATING BOX. Training Manual. Model KD-HBO100 & KD-HBC100. * KD-HB100 (Open-Loop System) * KD-HBC100 (Close-Loop System)

Versa- Hydro. up to 96% Efficient

hydronics WHAT S WRONG WITH THIS SCHEMATIC?

Modular Panel System for Radiant Floor Heating MICRO-BOILERS MODULAR PANEL SYSTEMS

ProRadiant Controls, Valves and Actuators

Application Guide. Vitodens 100-W B1HA/B1KA Residential Boiler

INSTALLATION MANUAL GEO-BOOST GROUND LOOP HEAT EXCHANGER

ronblank.com to receive credit Lance MacNevin REHAU Inc Edwards Ferry Rd. Leesburg, VA

Heat Pumps COMFORT NEED IT. When You

Using ECM Smart Circulator Pumps in Primary Pump Applications in Hydronic Systems

HPS Controls Ltd. Series 600 LFI / CFI Series 700 HFS Zone Control Stations. Heating and Radiant Floor Zone Control Stations

INSTALLATION MANUAL GEO-BOOST GROUND LOOP HEAT EXCHANGER

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

DEEMED SAVINGS TECHNICAL ASSUMPTIONS

PEERLESS PUREFIRE Installation, Operation, and Maintenance Instructions Supplement - PF-460 NOTICE. Exhaust Vent/Air Intake Size

Combined Space and Water Heating: Making it Work

Panel Radiators. For Buderus Panel Radiator models: Applications Manual. - Model 21 - Model 22 - Towel Warmers

Caleffi Hydronic Solutions Contact: Rex Gillespie, Director of Marketing Phone: (414)

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control.

Advanced Hydronic Control Solutions for Geothermal heat pumps

Water Piping and Pumps

Technical Product Guide

DHW / Setpoint Demand WWSD Modulation Boiler Output (x10,000 BTU/hr) External Input Signal Offset / Priority Override

COMPASS HIGH-EFFICIENCY WET-ROTOR CIRCULATORS

Flow Reversal in Primary/Secondary Systems by John Siegenthaler, P.E. April 17, 2007

- Data Brochure Mixing Control 360

Solstice Air to Water Heat Pump

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

Trials Tribulations & Rewards High T Heating Systems

know exactly what you are getting before you order it. You can order with confidence knowing th each panel is completely tested before it ships.

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall.

Modular Panel System for Radiant Floor Heating.

INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE

Radiant Mixing Block

Grundfos is pleased to announce the sales release of many exciting new products.

Variable Speed Outdoor Reset 00 Circulator (00-VR)

Lowara ecocirc and ecocirc PREMIUM

Best Practices for Condensing Boilers

Parameter guide 95M-200 GAS-FIRED DIRECT VENT MODULATING HOT WATER BOILER WARNING WARNING

Trim Pump Impellers. Fredrick/Weinman Engineered Products 2-1/2 KH, 2-1/2 x 3 x 12

B-40/B-41 Modulating Temperature Controller

Application Guide. Vitodens 200-W B2HA,B2HB Residential Boiler

TOTAL SYSTEM EFFICIENCY: CONTROL STRATEGIES & SYSTEM DISTRIBUTION. David Grassl PE Mechanical Engineer Principal

ASHRAE JOURNAL ON REHEAT

A Technical Introduction to Cool Thermal Energy Storage Commercial Applications

New ways of balancing two-pipe systems

prestige Control Application Supplement - TriMax

WWSD. Power. DHW Demand. Maximum. Supply. Minimum Boiler DHW. Zone 1 / Cooling. Pump / Vlv. System Pump. UnOccupied. of full output NRTL/C LR 58223

Raypak Residential Products

A Review of Hydronic Balancing of Cooling Water Circuit

Outdoor Reset IQ Option Card, p/n

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

- Data Brochure Mixing Control 361

Daikin Altherma/Viessmann Integration Notes (used with schematics M1 thru M5)

prestige Control Application Supplement - ACVMax

Installation & Operation Manual

COMMERCIAL HVAC SYSTEMS Water Source Heat Pump Systems

Advanced Heating & Hot Water Systems. High Efficiency Residential & Commercial Space Heating

SERIES 24. Series 24 Features. Commercial, Forced Draft, Hot Water or Steam Boiler. The right fit for any commercial job

Method to test HVAC equipment at part load conditions

- Data Brochure Boiler Control 264

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

Ve r s a - Hyd ro. 96% Efficient. The cost effec t i ve. ersa-hydro

Transcription:

The electrical wattage needed by the circulator is: w e = 0.4344 f P n w/w A current-generation wet-rotor circulator has a maximum wire-towater efficiency in the range of 25 percent. If we put the data from previous example into this formula we get the electrical wattage required to maintain flow in the circuit. w e = 0.4344 f P n w/w = 0.4344 5 3.83 0.25 = 33.2watts

Consider that a flow of 5 gpm in a circuit with a 20 ºF temperature drop is moving about 50,000 Btu/hr, and the electrical power to run the conveyor belt according to the last calculation is 33.2 watts. The distribution efficiency of such a circuit is: n d = Q w e = 50,000Btu / hr 33.2watt =1506 Btu / hr watt Compare this to a 4-ton rated geothermal water-to-air heat pump delivering 48,000 Btu/ hr using a blower operating on 1080 watts. The distribution efficiency of this delivery system is: n d = Q w e = 48,000Btu / hr 1080watt = 44.4 Btu / hr watt These numbers mean that the hydronic system delivers heat to the building using only 2.9 percent (e.g. 44.4/1506) of the electrical power required by the forced air delivery system. With good design itʼs possible to achieve distribution efficiencies > 3000 Btu/hr/watt This will become increasingly important in low energy and net zero buildings...

Other factors to Consider The heat output from most hydronic heat emitters (including radiant panel circuits) increases rapidly at low flow rates but very slowly at high flow rates (assuming constant supply temperature). At 50 percent of design flow rate heat output is about 89 percent of design output. Implication... If the heat emitters are 11% or more oversized, the system could likely still deliver design load output at 50% or less of its current flow rate. Upward heat output of circuit (Btu/hr) 10000 9000 8000 7000 6000 5000 4000 3000 2000 1000 0 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 40 35 30 25 20 15 10 5 0 Temperature drop of circuit (ºF) Flow rate through circuit (gpm)

This graph shows the relationship between system flow rate vs. operating hours for a typical Northern climate. Recognizing that partial flow is common, circulator engineers have developed intelligent operating algorithms for variable speed circulators.

What happens when a zone valve closes?

What would be the ideal pump curve for a hydronic system using valve based zoning? Answer: a perfectly flat pump curve zone valves DHW CW A perfectly flat pump curve would all steady flow rate in every zone circuit, regardless of which other zones are on.

Approximating a flat pump curve with P bypass valve A P bypass valve helps limit changes in differential pressure, but does so parasitically by throttling away head energy

Approximating a flat pump curve with P bypass valve By varying the speed of the circulator it is possible to produce the same net effect as would be produced by a perfectly flat pump curve. This is called CONSTANT DIFFERENTIAL PRESSURE CONTROL

Constant differential pressure control This is all regulated by P.I.D. control

PROPORTIONAL DIFFERENTIAL PRESSURE CONTROL This method is best for systems where the heat source and/or mains piping leading to the load circuits dissipate a substantial portion of the circulator head.

How does a ECM Circulator work?

Small ECM circulators now available in North America Grundfos Alpha: Provides constant and proportional differential pressure and three fixed speed settings. 6-50 watt electrical input. Wilo Stratos ECO 16F: Provide constant and proportional differential pressure. 5.8-59 watt electrical input. Bell & Gossett ECOCIRC, Provides manual adjustable speed setting (VARIO model), and proportional differential pressure (AUTO model). 5-60 watt electrical input. Taco Bumblebee Temperature based speed control. 9-42 watts electrical input Armstrong COMPASS Provides constant and proportional differential pressure and three fixed speed settings. 3-45watt electrical input.

Circulators high efficiency ECM Circulators Larger ECM circulators now available in US Wilo STRATOS circulators Grundfos MAGNA Taco Viridian Heads to 45 feet, flows to 345 gpm power inputs to 1600 watts B&G ECO XL

Current European circulator rating system All these circulators rated A on the energy labeling system from Europump (European Association of Pump Manufacturers). Single or multi-speed wet-rotor circulators like those commonly used in North America would be rated D or E on this scale.

Computer modeling has been used to predict electrical energy savings for an intelligently-controlled circulator with ECR motor operating in the proportional pressure mode. Savings in electrical energy are 60 to 80 percent relative to a fixed speed circulator of equal peak performance in the same application.

Fixed speed circulator vs. P valve versus variable speed pressure regulated circulator zone valves differential! pressure! bypass! valve! (required) zone AUTO! valves circulator eliminate the differential! pressure! bypass valve standard! (fixed speed)! circulator + Zoning with valves and a fixed speed circulator requires a differential pressure bypass valve. Zoning with valves and an AUTO circulator eliminates need (and cost) of a differential pressure bypass valve.

A real price comparison... All prices taken for same internet-based supplier (April 2013) B&G NRF-22 circulator B&G P bypass valve B&G AUTO circulator + vs. $85.95 $61.95 $169.95 $147.90 Can you install this valve (with adapter fittings) and labor for $22.05? This comparison ignores the saving in electrical energy associated with the AUTO circulator

A real price comparison... Energy savings comparison B&G AUTO 19-14 Conventional zone circulator operating 3000 hours per year in area where electricity costs $0.13/kwhr.! (80watt) " # 3000hr yr $ % &! " # 1kwhr $ 1000whr % &! " # $0.13 kwhr $ % & = $31.2 yr $169.95 Based on European modeling, an ECM circulator operating with proportional differential pressure control reduces electrical consumption by about 60% comparison to a conventional wet rotor circulator of same max curve performance. B&G NRF-22 circulator savings = ( 0.6)$31.20 = $18.72 / yr Simple payback on higher cost of AUTO versus NFR22: $84.00/$18.72 = 4.5 years Payback on higher cost of AUTO versus NFR22 assuming 5% per year inflation on cost of electricity = 4.0 years $85.95 cost difference $84.00

Supplying a homerun distribution system panel radiator TRV thermostatic radiator valves! on each panel radiator TRV TRV TRV TRV TRV pressure-regulated! variable speed circulator 1/2" PEX or PEX-AL-PEX tubing thermal storage tank manifold station + homerun piping thermostatic radiator valves pressure regulated circulator thermal mass @ heat source hydronics heaven

The modern way to install fin-tube baseboard: Thermostatic radiator valve on each baseboard ECM-based pressureregulated circulator.

foyer (under window) foyer (under window) Examples of systems using pressure regulated circulators boiler reset control HL LWCO MRHL back up circulator 20"x72" 3/4" zone valve 1/2" PEX-AL-PEX 20"x72" 1/2" PEX-AL-PEX Bride's room 1.5" copper 1.5" copper VS Circulator (constant delta P) 1" copper panels under windows in sanctuary 24"x72" model 22 24"x72" model 22 207,000 Btu/hr oil-fired boiler 1/2" PEX-AL-PEX 1" zone valve 1" copper 1.5" copper 1.5" copper 1/2" PEX-AL-PEX 1" zone valve 1/2" PEX-AL-PEX fellowship room fellowship room Nursery 24"x72" model 11 24"x64" model 11 24"x72" model 11 DPBV fellowship room 20"x48" model 11 24"x72" model 11 24"x72" model 11 fellowship room fellowship room 1" copper fellowship room thermostat 1" zone valve 1/2" PEX-AL-PEX 1" copper 1.5" copper 1.5" copper 1/2" PEX-AL-PEX 24"x48" TRV 24"x72" model 22 sanctuary thermostat 1" zone valve 1/2" PEX-AL-PEX 24"x72" model 22 panels under windows in sanctuary 1.5" copper 1.5" copper 1.5" copper 1.5" copper 1.5" copper 1/2" PEX-AL-PEX 24"x72" model 22 1/2" PEX-AL-PEX pastor's office 20x64" model 11 TRV 24"x16" model 11 bathroom 24"x16" model 11 bathroom secretary 24"x72" model 11 TRV 1" copper 1" copper 24"x72" model 22 Ladies Sunday School library TRV TRV TRV 1" copper choir room TRV 20x64" model 11 14"x72" model 22 14"x72" model 11

VENT Examples of systems using pressure regulated circulators HEATING & COOLING SYSTEM! MULTIPLE HEATING ZONES! MULTIPLE COOLING ZONES! INDEPENDENT FLOW CONTROL! USING ZONE VALVES ON EACH H.P. Diverter valves prevent thermal migration:! chilled water into heating headers! heated water into chilled water headers Buffer tanks serve as hydraulic separators between headers and distribution systems heating mode heating mode reversing! valve evaporator condenser reversing! valve evaporator condenser insulate all chilled water piping! to prevent condensation insulate all chilled water piping! to prevent condensation chilled water air handlers zone! valve heating mode reversing! valve diverter! valve flocal flocal evaporator condenser variable-speed! pressure-regulated! circulator geothermal manifolds variable-speed! pressure-regulated! circulator water-to-water! heat pump zone! valves temperature! sensor variable-speed! pressure-regulated! circulator to / from other heating zones hydro! separator purging! valves purge chilled water buffer tank earth loop circuits fluid feeder variable-speed! pressure-regulated! circulator temperature! sensor variable-speed! pressure-regulated! circulator warm water buffer tank

Adjust circulator speed - not a balancing valve Concept: It s wasteful to install a circulator with greater hydraulic power than required, and throttle away some of this head with a balancing valve. oversized! fixed speed! circulator VARIO! circulator head (feet) balancing! valve pump curve! (3-speed circulator)! (low speed) Head energy! throttled! away by! balancing! valve system head loss curve head (feet) pump curve (3-speed circulator)! (low speed)! VARIO! circulator! operating! region system head loss curve 0 0 desired flow rate flow rate (gpm) This is especially beneficial in small zones. 0 0 desired flow rate flow rate (gpm) pump curve, VARIO circulator! adjusted to desired flow rate

Outdoor Reset Control: Theory & Implementation supply water temperature (ºF) 190 170 150 130 110 90 fin-tube convector (RR=1.38) panel radiator (RR=1.0) thin slab rad. floor (RR=0.69) s la b r a dia n t f loo r (RR=0.31) 180 ºF 150 ºF 125 ºF 105 ºF 70 70 60 50 40 30 20 10 0-10 Outdoor outdoor temperature (ºF)

Outdoor Reset Control Theory An ideal heating system would continually adjust its rate of heat delivery to match the heat loss of a building. This allow inside air temperature to remain constant regardless of outside conditions. Outdoor reset control was developed with this objective in mind. An outdoor reset controller measures outdoor air temperature then calculates what water temperature should be supplied to the distribution system based on that outdoor temperature. This calculated temperature is called the target supply temperature. The target supply temperature is continually updated through repeated calculations so itʼs always valid for the current outside conditions. Outdoor reset controllers also operate devices such as the systemʼs heat source, or a mixing device to steer the water temperature supplied to the system toward the calculated target value.

Outdoor Reset Control Theory Outdoor reset control is based on two basic heat transfer principles: Principle #1: The rate of building heat loss is proportional to the difference between inside and outside air temperatures. Imagine a building with a design heat loss of 80,000 Btu/hr when the inside air temperature is 70ºF., and the outside air temperature is -10 ºF. This building s heat loss coefficient (UA) is: UA building = 80,000Btu / hr [ 70 ( 10)]º F = 80,000Btu / hr 80º F = 1000 Btu hr º F A formula can be written based on the heat loss coefficient that allows the building s heat loss to be calculated for any indoor and outdoor temperature: Heat loss = 1000 ( T indoor - T outdoor )

Outdoor Reset Control Theory Principle #2: The rate of heat output from a hydronic heat emitter is approximately proportional to the difference between the supply water temperature and the inside air temperature. Imagine that the building above was equipped with a radiant floor heating system that could release the design load of 80,000 Btu/hr when supplied with 110 ºF water. Note that the difference in temperature between the water and inside air is 40 ºF. under these conditions. The heat output coefficient of the heating system is: heat output coefficient = 80,000Btu / hr [ 110 70]º F system heat output = 2000 ( T sup ply - T indoor ) == 80,000Btu / hr 40º F = 2000 Btu hr º F

Outdoor Reset Control Theory Heat loss = 1000 ( T indoor - T outdoor ) system heat output = 2000 ( T sup ply - T ) indoor Combining these two equations yields: T supply = T indoor + 1000 T indoor - T outdoor 2000 ( ) T supply = T indoor + ( 0.5) ( T indoor - T outdoor ) If the indoor temperature is set to 70ºF, and this equation is plotted, the following graph is created: target supply temperature (ºF) 120 110 100 90 80 T target = 70 + 0.5 design load conditions ( )! ( 70 - T outdoor ) reset line no load conditions 70 70 60 50 40 30 20 10 0-10 Outdoor temperature (ºF)

Outdoor Reset Control Theory target supply temperature (ºF) 120 110 100 90 80 The slope of the reset line is called the reset ratio T target = 70 + 0.5 reset line 70 70 60 50 40 30 20 10 0-10 Outdoor temperature (ºF) RR = T wd! T wnl T ad! T anl = T ad! T anl design load conditions ( )! ( 70 - T outdoor ) no load conditions 110! 70 70! (!10) = 40 80 = 0.5 T target = 70 + ( 0.5)! ( 70 - T outdoor ) supply water temperature (ºF) 190 170 150 130 110 The reset ratio can be adjusted to match the combined effect of building heat loss and heat output of the distribution system. 90 fin-tube convector (RR=1.38) panel radiator (RR=1.0) thin slab rad. floor (RR=0.69) s la b r a dia n t f loo r (RR=0.31) 70 70 60 50 40 30 20 10 0-10 Outdoor outdoor temperature (ºF) 180 ºF 150 ºF 125 ºF 105 ºF

Outdoor Reset Control Theory T ad! T anl The reset ratio is calculated by taking the change in supply water temperature, and dividing by the corresponding change in outdoor air temperature. target supply temperature (ºF) 120 110 100 90 80 T target = 70 + 0.5 design load conditions ( )! ( 70 - T outdoor ) reset line no load conditions 70 70 60 50 40 30 20 10 0-10 Outdoor temperature (ºF) RR = T wd! T wnl T ad! T anl = 110! 70 70! (!10) = 40 80 = 0.5 T target = 70 + ( 0.5)! ( 70 - T outdoor )

Outdoor Reset Control Theory Outdoor reset control can be implemented two ways: 1. Controlling the temperature leaving a on/off heat source (a.k.a. boiler reset control ) 2. Controlling the temperature leaving a modulating heat source (a.k.a. boiler reset control ) 3. Controlling the temperature supplied to the distribution system using a mixing device (a.k.a. mixing reset control ) mixing device on/off heat source modulating heat source

Outdoor Reset Control Theory 1. Controlling the temperature leaving a on/off heat source (a.k.a. boiler reset control ) Supply water temperature (ºF) 130 120 110 105 100 90 80 heat source is off control differential = 10ºF There must be some differential, above and below the target temperature to prevent short cycling the heat source. contacts on reset control! open to turn off heat source calculated target temperature contacts on reset control! close to turn on heat source 70 60 heat source is on 70 60 50 40 30 20 10 0-10 -20 Outdoor temperature (ºF) on/off heat source

Outdoor Reset Control Theory 1. Controlling the temperature leaving a on/off heat source (a.k.a. boiler reset control ) There must be some differential, above and below the target temperature to prevent short cycling the heat source. Supply water temperature (ºF) 130 120 110 105 100 90 heat source is off control differential = 10ºF 80 heat source is on 70 70 60 50 40 30 20 10 0-10 -20 Outdoor temperature (ºF) control differential = 10ºF reset line contacts on reset control! OPEN to turn off heat source calculated target temperature contacts on reset control! CLOSE to turn on heat source Supply water temperature (ºF) 130 120 110 100 90 variable! differential heat source is off 80 heat source is on 70 70 60 50 40 30 20 10 0-10 -20 Outdoor temperature (ºF) reset line contacts on reset control! OPEN to turn off heat source calculated target temperature contacts on reset control! CLOSE to turn on heat source

Outdoor Reset Control Theory 2. Controlling the temperature leaving a modulating heat source (a.k.a. boiler reset control ) Most modulating heat sources have an internal outdoor reset controller. heating load (Btu/hr) 100% They modulate the burner and continually monitor the supply temperature, trying to keep it close to the target temperature. heating load profile on at 30%, then stabilize ramp down hold at 20%, then off 20% minimum modulation = 20% of full output time (hr) 10% heat source must cycle on/off to supply loads! under 20% of full output modulating heat source

Outdoor Reset Control Theory 3. Controlling the temperature supplied to the distribution system using a mixing device (a.k.a. mixing reset control ) boiler loop A C mixing! assembly B D distribution system 6 hardware options for mixing assembly A C A C A C motor &! actuator conventional boiler B mixing w/ two 3-way! thermostatic valves D B mixing w/ single 3-way motorized valve D B mixing with 4-way motorized valve D A C A C A C A wide variety of mixing devices can by controlled to provide outdoor reset. B injection mixing w/! 2-way thermostatic valve D B injection mixing w/! 2-way motorized valve D B direct injection mixing w/! variable speed pump D

Outdoor Reset Control Theory 3. Controlling the temperature supplied to the distribution system using a mixing device (a.k.a. mixing reset control ) A wide variety of mixing devices can by controlled to provide outdoor reset. floating control signal! 2-10 VDC control signal! 4-20 milliamp control signal sensors floating control signal! 2-10 VDC control signal! 4-20 milliamp control signal sensors controller 24 VAC controller 24 VAC floating control signal! 2-10 VDC control signal! 4-20 milliamp control signal actuator 2-way! motorized! valve actuator 3-way! motorized! mixing! valve actuator sensors controller 24 VAC 4-way! motorized! mixing! valve variable frequency AC voltage controller sensors 120 VAC variable! speed! injection! pump