Technical Data Manual Model Nos. and pricing: see Price List

Similar documents
Technical Data Manual Model Nos. and pricing: see Price List

Technical Data Manual Model Nos. and pricing: see Price List

Technical Data Manual

Operating Instructions and User s Information Manual for use by engineers and heating contractors VITOTRONIC 100 IMPORTANT

Technical Data Manual for use by heating contractor VITOROND 200

Technical Data Manual Model Nos. and pricing : See Price List

Installation Instructions. Replacement of Control Console, Part No , Safety and Installation Requirements

Technical Data Manual Model Nos. and pricing : See Price List

Installation Instructions VITOTRONIC 200

Technical Datasheet. Solo Innova Models 30 and 50. Benefits at a Glance: Solo Innova

Application Guide. Vitodens 200-W B2HA,B2HB Residential Boiler

Installation Instructions for use by heating contractor. VITOCELL r 300-H CAUTION IMPORTANT. Read and save these instructions for future reference.

Technical Data Manual Model Nos. and pricing : See Price List

Installation Instructions for use by heating contractor. VITOCELL r 100-V CAUTION IMPORTANT. Read and save these instructions for future reference.

Installation Instructions for use by heating contractor. VITOCELL r 100-B CAUTION IMPORTANT. Read and save these instructions for future reference.

Installation, Operating and Service Instructions for use by heating contractor. VITOCELL r 300-W CAUTION IMPORTANT

Application Guide. Vitodens 222-F B2TB Residential Boiler

Technical Data Manual

WATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

Technical Datasheet. FHG-S Models 28, and 45. Benefits at a Glance: State Route 22 Salem, NY 12865

Technical Data Manual Model Nos. and pricing: see Price List VITOCROSSAL 300

Technical Data Manual Model Nos. and pricing: see Price List

AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

VIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler.

Multi-Heat. Multi-Heat Datasheet Version Tarm Biomass 4 Britton Lane Lyme, NH 03768

Installation Instructions VITOTRONIC 300

Technical Data Manual Model Nos. and pricing: see Price List

Application Guide. Vitodens 100-W B1HA/B1KA Residential Boiler

Operating Instructions and User s Information Manual VITOROND 200 WARNING WARNING IMPORTANT. Read and save these instructions for future reference.

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

CONDENSING HIGH EFFICIENCY BOILERS

WATER HEATERS / BOILERS GSB8-E. Gas-Fired Steam Boiler PRODUCT SPECIFICATIONS. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB E

Installation and Operating Instruction Supplement Use in conjunction with the original technical literature supplied by Riello. Riello Burner WARNING

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

VITOSOL. Solar hot water heating systems Flat plate and vacuum tube solar collectors

Date: Project #: Engineer: Prepared By: Bid Date:

Peerless Boilers. Series MI. Residential Gas Boilers

High efficiency, cast-iron gas boiler

SENTRY. High efficiency, cast-iron gas boiler LOWER PROFILE MAKES PROBLEM INSTALLATIONS EASY

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh

BUDERUS. Quality. Versatility. Efficiency. Superior Design. Comfortable. Efficient. Intelligent Heating. Conventional Gas Boilers

GSB8. CONSERVATOR Gas-Fired Steam Boiler. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB S MODEL NUMBER IDENTIFICATION FEATURES

OWNERS MANUAL MODEL DO110 & DO180 IS CERTIFIED TO: Unit Serial # Purchased From Company Address

Utica Boilers MAC Submittal

DESIGNER S GUIDE COPPER-FIN

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Technical Data Manual Model Nos. and pricing: see Price List

AFUE 95% Heating Input 50,000 to 200,000 Btuh

WM97+ Wall Mount Boiler

200i Boiler manual. Installation and operation instructions. Also read and follow: 200i Control manual 200i Vent/Air manual

Mascot. Gas-Fired Residential and Commercial Wall-Mounted Boiler. Easy Installation, 96% Efficiency, Fully Condensing

Get The Edge Over The Competition with The Summit

DOM-5. Domestic Hot Water Heaters & Boilers

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater

Introduction Engineering and Design Manual

Raypak Residential Products

G124X - G234X - G334X Atmospheric Gas Boilers

DIVISION FINNED WATER-TUBE BOILERS

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater

Aqua Balance. User s Information Manual. WMB-155C Wall Mount Gas-Fired Combination Boiler Heating and Domestic Hot Water

Commercial Water Heaters. Genesis. Water Heater Design Guide

ULTRA SERIES 4 HIGH EFFICIENCY CONDENSING BOILER

NAVIEN AMERICA INC FITCH AVENUE IRVINE, CALIFORNIA, USA

Highlights MBH 95% efficiency ENERGY STAR Qualified Low NOx emissions Space-saving design. 95% Efficient. Modulating Technology

GENERAL BASIC INSTALLATION INSTRUCTIONS INDIRECT GAS FIRED WATER HEATERS PARKER BOILER CO.

Models UBSSC-050 UBSSC-075 UBSSC-100 UBSSC-150 UBSSC-200 UBSSC-299 WALL MOUNTED GAS BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL

VIESMANN VITOLADENS 300-C Oil condensing boiler 12.9 to 28.9 kw

DIVISION FINNED WATER-TUBE BOILERS

Bosch Buderus SSB255/399/512 Stainless Steel Condensing Boiler

Suggested Specifications Prestige Excellence 110

HIGH-EFFICIENCY DOWNFLOW / HORIZONTAL FURNACE INSTALLER'S INFORMATION MANUAL

MPO IQ 87% AFUE. Limited Lifetime Warranty! control. Oil-Fired, High Efficiency, 3-Pass Water Boiler. system GREATER ENERGY SAVINGS

HIGH-EFFICIENCY UPFLOW FURNACE INSTALLER'S INFORMATION MANUAL

Warmth, efficiency, and total peace of mind.

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS

MODELS LFP4218/LFP6018 TOP VENT GAS FIREPLACE

LAARS MINI-THERM Gas-Fired Residential Hydronic Boilers

ULTRA SERIES 4 HIGH EFFICIENCY CONDENSING BOILER HIGH EFFICIENCY CONDENSING BOILER

SERIES 19A. mith PRESSURIZED WET BASE

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO.

A Better Boiler Just Got Better. Better Boilers. New Size Available. Express Setup. Load Status. User Setup. Installer Setup. Diagnostics.

STEAM / GAS APPLICATION GUIDE

WATER-TUBE POOL HEATERS

Hybrid Series. Innovative Heating Solutions continentalheatingandcooling.com

FXLF-9. High Efficiency Water Heaters and Boilers

INSTALLATION INSTRUCTIONS

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Boiler Manual Installation and Operation Instructions

Contents. Hazard definitions

User s Information Manual Models: 45, ,000 Btu/hr

Revitalize Building Mechanical Systems (4619)

Hybrid Series. Innovative Heating Solutions continentalheatingandcooling.com

Operating Instructions

Heating Systems Company LAARS INTRODUCES. The MASCOT LX. A Boiler. An All-in-One Answer to Your Home Heating and Hot Water Needs

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

SERIES 24. Series 24 Features. Commercial, Forced Draft, Hot Water or Steam Boiler. The right fit for any commercial job

WATER-TUBE POOL HEATERS

Technical Datasheet. P4 Pellet Boiler Models 8/15, 20/25, 32/38, 48/60. Benefits at a Glance:

LAARS MINI-THERM Gas-Fired Residential Hydronic Boilers

Transcription:

VITOGAS 0 Cast iron hot water heating boiler 65 to MBH / 19 to 59 kw Technical Data Manual Model Nos. and pricing: see Price List Vitogas 0 ECD Series Gas-/Propane-Fired Boiler cast iron construction atmospheric Heating input: 65 to MBH 19 to 59 kw 01/8

Product Information Vitogas 0 Impressive performance, yet a very compact design. Due to its compact dimensions, the Vitogas 0 is ideal for installation in small mechanical rooms and even in closets. In addition to saving space, the Vitogas 0 is economical in two ways - initial investment and operational cost. The benefits at a glance: H Economical, compact, withintegrated draft hood for vertical chimney venting. H High operational reliability and a long service life due to special high-grade gray cast iron with lamellar graphite and uniform heat transfer to avoid stress fractures. H Compact dimensions therefore suitable for installation in almost any mechanical room, or even closet installation. H Problem-free transport into difficult-to-access boiler rooms due to light weight and compact design. H Large diameter, stainless steel burners provide quiet, reliable performance; seasonal efficiency of up to 83.7%. H Optimal operation due to wide water passageways and a wet-base, sectional design. Heat exchanger surfaces of special high-grade gray cast iron for high operational reliability and a long service life 2

Technical Data Technical data Boiler Model Model No. ECD-65 ECD-80 ECD-0 ECD-115 ECD-140 ECD-155 ECD-180 ECD- CSA input CSA output / DOE output MBH kw MBH kw 65 19 54 16 80 23 66 19 A.F.U.E. *1 *2 % 83.7 8 8 8 8 83.4 83.2 83.0 Heat exchanger surface area ft 2 m 2 14.32 1.33 14.32 1.33 Cast iron sections 3 3 4 4 5 5 6 6 Burners 2 2 3 3 4 4 5 5 Manifold pressure Natural gas Propane gas w.c. w.c. Max. gas supply pressure *3 w.c. 14 14 14 14 14 14 14 14 Overall dimensions Overall depth Overall width Overall height Height Height of Vitocell-H DHW tank under boiler 160 to ltr / 42 to USG capacity 13½ 340 35 03 13½ 340 35 03 0 29 83 24 21. 1.96 17 432 35 03 115 34 95 28 21. 1.96 17 432 35 03 140 41 116 34 27.99 2.60 21 3 35 03 155 45 129 38 27.99 2.60 21 3 35 03 180 149 44 34.88 3.24 25 635 35 03 59 166 49 34.88 3.24 25 635 35 03 3 ltr / USG capacity 4 ltr / 120 USG capacity Weight, boiler with insulation, burners and packaging Boiler water content Max. operating pressure lbs kg USG ltr psig kpa Boiler connections Boiler supply and return Ø (male thread) 233 6 2.6 9.9 233 6 2.6 9.9 285 130 13.2 285 130 13.2 157 4.3 16.5 157 4.3 16.5 423 1 7.1 26.8 423 1 7.1 26.8 1¼ 1¼ 1¼ 1¼ 1¼ 1¼ 1¼ 1¼ Gas supply connection Ø ½ ½ ½ ½ ½ ½ ½ ½ (male thread) Vent pipe collar 5 5 6 6 7 7 7 7 *1 Each Vitogas 0 ECD Series boiler sold in North America must be ordered with a vent damper to comply with minimum A.F.U.E. requirement of 80% (when utilizing a natural draft chimney). If power venting, order wall vent system only and do not order a vent damper. See Price List. *2 With intermittent pilot electronic ignition system and vent damper. *3 If the gas supply pressure is higher than the maximum permissible value, a separate field supplied gas regulator must be installed upstream of the boiler gas train. " For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product. 3

Technical Data FGC Overall Width a Overall Depth b BWS GC BWR 13 / 330 26½ / 673 Overall Height Height Legend BWR Boiler Water Return BWS Boiler Water Supply FGC Flue Gas Collar GC Gas Connection 3 / 76 Vitogas 0, ECD Series Vitocell-H 0 or 300 (see separate Technical Data Manuals) Note: Support Bars are installed lengthwise for ECD-65 through ECD-115 and widthwise for ECD-140 through ECD-. Widthwise installation is pictured. The Base Pan is installed between the boiler and the Support Bars (also shown). c Dimensions Boiler Model a b ECD -65-80 -0-115 -140-155 -180-6¾ 170 15 381 6¾ 170 15 381 8.5 216 14¾ 375 8.5 216 14¾ 375 ½ 267 14½ 368 ½ 267 14½ 368 12½ 318 14 352 12½ 318 14 352 With Vitocell-H DHW tank under boiler c USG ltr 34 to 130 to 3 34 to 130 to 3 34 to 130 to 3 34 to 130 to 3 3 120 4 3 120 4 3 120 4 3 120 4 4

Technical Data Standard Equipment / Boiler Control Alternatives Recoended Minimum Clearances The Vitogas 0 is designed for closed loop, forced circulation hot water heating systems only. Closet installation, ECD-65 to -155 Alcove installation, ECD-180 and - Top clearance: 18 460 1 25 Top clearance: 18 460 1 25 6 / 1 1 25 6 / 1 1 25 6 1 24 6 Installation on combustible flooring A Base Pan (Optional Equipment) must be ordered if the Vitogas 0, ECD Series is to be installed on combustible flooring. See Price List. Mounting the Vitogas 0 on a Vitocell-H The Vitogas 0 can be mounted on a Vitocell-H as shown previously to reduce the footprint of heating equipment in the mechanical room. Two Support Bars and one Base Pan are necessary. Order a Support Bar Kit from the Price List. Do not attempt to install combinations not listed in the Price List. Standard Equipment Boiler shell with mounted insulation jacket and atmospheric burners for natural gas or propane gas (as per order) conforming to national and local regulations. Standard equipment includes 30 psig pressure relief valve, pressure gage, installation fittings, and cleaning brush. Boiler Control Standard control (included with boiler) control with temperature gage, adjustable high limit, and fixed high limit. Vitotronic -H, HK1M Series (Optional Equipment) Digital mixing valve mounted heating circuit control with outdoor reset function to operate a heating circuit with a mixing valve. 5

System Design Considerations System Design Considerations Boiler selection The boiler model size should be based on an accurate heat loss calculation of the building. The boiler selected must be compatible with the connected radiation. Chimney For proper operation of the Vitogas boiler, all products of combustion must be safely vented to the outdoors, while ensuring that flue gases do not cool prematurely. It is critical that the chimney system be properly designed and sized to handle the relatively cool flue gas temperatures which the Vitogas boiler produces. Flue gases which cool too quickly and produce condensation lead to damages if the chimney diameter is too large and the chimney system is not well insulated. If a calculated chimney diameter lies between two values, the larger diameter should be selected. Intermediate vent section The intermediate (vertical and horizontal) section of venting between the boiler vent pipe collar and the chimney must be of the identical diameter as the vent connection of the boiler. Use the shortest possible path between the boiler and the chimney. A maximum of two elbows may be installed in the intermediate section. Avoid the use of two level 90 elbows. The intermediate section must be sealed pressure tight at the boiler vent pipe collar and at the chimney connection. Ensure any test port for combustion values is sealed as well. The chimney connection length between the boiler vent pipe collar and the chimney must be installed with insulation. We recoend consulting a reputable chimney installer for advice in project-specific circumstances. Warranty excerpts Our warranty does not cover damages resulting from the following: - installation or service by unqualified and - not licensed personnel - corrosion caused by flue gas condensation - due to low boiler water and/or return water - temperatures - operation with contaminated fill and - supplementary feed water For detailed warranty information, please read warranty sheet supplied with product. 6 Combustion air supply The boiler must not be located in areas or rooms where chemicals containing chlorine, bromine, fluorine, or other corrosive chemicals are stored. Examples include refrigerants, bleach, paint, paint thinner, hair spray, cleaning solvents, water softener salt, etc. The combustion air must not be contaminated with the above mentioned, or other aggressive or corrosive chemicals. Boiler should never be installed in areas where excessive dust, high humidity, or risk of frost exist. Ensure adequate ventilation and supply of fresh combustion air. Consult Viessmann with uncertainties in regard to a suitable boiler installation location. This boiler/burner unit needs clean fresh air for safe operation and must be installed so that there are provisions for adequate combustion and ventilation air. For natural gas or propane, use the Natural Gas Installation Code CAN/CSA-B149.1 or B149.2 (Canada), or National Fuel Gas Code ANSI Z223.1 (USA), and/or provisions of local codes. The sizing methods outlined in the above codes must be used when installing a round duct to supply combustion air from the outside. Observe local jurisdictional requirements. System layout The boiler water temperature limit is factory set to 167 F / 75 C. The boiler water temperature limit can be increased by altering the adjustable high limit to increase the supply water temperature. To minimize piping losses of the system however, we recoend that the radiation and domestic hot water production in the system be designed for a 158 F / 70 C boiler supply water temperature (new systems). Water quality Treatment for boiler feed water should be considered in areas of known problems, such as where a high mineral content and hardness exist. In areas where freezing might occur, an antifreeze may be added to the system water to protect the system. Please adhere to the specifications given by the antifreeze manufacturer. Do not use automotive silicate based antifreeze. Please observe that an antifreeze/water mixture may require a backflow preventer within the automatic water feed and influence components such as diaphragm expansion tanks, radiation, etc. A 40% antifreeze content will provide freeze-up protection to - F / -23 C. Do not use antifreeze other than specifically made for hot water heating systems. System also may contain components which might be negatively affected by antifreeze. Check total system frequently when filled with antifreeze. Advise system operator/ultimate owner that system is filled with a glycol mix. The heating contractor must provide an MSDS (Material Safety Data Sheet) for the antifreeze used to the system operator/ultimate owner. Oxygen diffusion barrier underfloor tubing The boiler warranty does not cover leaks resulting from corrosion caused by the use of underfloor plastic tubing without an oxygen diffusion barrier. Such systems must have the non-oxygen diffusion barrier tubing separated from the boiler with a heat exchanger. Viessmann recoends the use of underfloor plastic tubing with an oxygen diffusion barrier. Low water cut-off A low water cut-off may be required by local codes. If boiler is installed above the radiation level, a low water cut-off device of approved type must be installed in all instances. An approved type low water cut-off device must be provided by the heating contractor. Do not install an isolation valve between the boiler and the low water cut-off.

Installation Examples Installation Examples Important! These examples depict possible piping layouts for Viessmann product equipped with Viessmann System Technology. For boiler and tank combinations, please install only the feasible combinations listed in the Price List. These are simplified conceptual drawings only! Piping and necessary componentry must be field verified. Proper installation and functionality in the field is the responsibility of the heating contractor. Without a mixing valve Heating circuit Spring-loaded flow check valve Circulation pump Pressure relief valve Precharged expansion tank Domestic hot water storage tank (indirect-fired) DHW Pump Module The installation of the check valve to restrict gravity circulation in the heating supply pipe prevents uncontrolled heat flow to the heating system by gravity during priority switching of domestic hot water heating or during suer operation. 7

Installation Examples With a 4-way mixing valve to regulate heating circuit, with domestic hot water control, and with boiler activation capability Viessmann Manufacturing Company (U.S.) Inc. 45 Access Road Warwick, Rhode Island 02886 USA Tel. (401) 732-0667 Fax (401) 732-0590 www.viessmann-us.com info@viessmann-us.com 8 Heating circuit Spring-loaded flow check valve Circulation pump Pressure relief valve Precharged expansion tank Domestic hot water storage tank (indirect-fired) Vitotronic -H, HK1M Series mixing valve control Viessmann Manufacturing Company Inc. 7 McMurray Road Waterloo, Ontario N2V 2G5 Canada Tel. (519) 885-6300 Fax (519) 885-0887 www.viessmann.ca info@viessmann.ca Technical information subject to change without notice. Printed on environmentally friendly (recycled and recyclable) paper.