Florida Department of Transportation

Similar documents
SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM

DACC Health Sciences Building Air Handler Assessment/Study

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION AIR DUCT ACCESSORIES

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

HVAC Controls Upgrades: Requirement Details ( )

November 11, City of Sparks 215 S. 21 st St. Sparks, NV

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

HVAC Controls Upgrades: Requirement Details ( )

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

"This is only the scope of work for the project. For more information, interested parties should contact Procurement at

SECTION AIR OUTLETS AND INLETS

EXHAUST FAN SCHEDULE

"This is only the scope of work for the project. For more information, interested parties should contact Procurement at

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

COMcheck Software Version Mechanical Compliance Certificate

Air Handler Unit (AHU) Equipment Purchase and Delivery Invitation to Bid

Job Name Control Systems Description Date

Computing Services Center

COMcheck Software Version Mechanical Compliance Certificate

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

Attachment F. Campus Capital Needs Sales Surtax Funded Detail Report

SECTION PLUMBING/HVAC FINAL TESTING, ADJUSTING AND BALANCING

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

Union County Vocational - Technical Schools Scotch Plains, New Jersey

COMcheck Software Version Mechanical Compliance Certificate

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

BUILDING VENTILATION GUIDE

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

Linear Floor Heaters

PURCHASING DEPARTMENT LOUISVILLE, KENTUCKY

BUILDING VENTILATION GUIDE FOR LG HVAC SYSTEM INSTALLATION

COMcheck Software Version


CxA to Answer this Section

Notable Changes in the Mechanical Codes

Plenum Fans. Model HPA. Direct Drive

RAMAPO COLLEGE OF NEW JERSEY CCA0803 PHASE II HOUSING REHABILITATION 2012

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

Item No. Description 1. BID PROPOSAL FORM Make the following revisions: a. Replace the BID PROPOSAL FORM with the attached BID PROPOSAL FORM.

Existing Mechanical System Operation

SECTION DUCTWORK

VentZone Systems VentZone Zoned IAQ with Heat Recovery Kits

SECTION DUCTWORK

Cleveland Clinic Design Standards MECHANICAL SYSTEMS DESIGN GUIDELINES HVAC AIR DISTRIBUTION PART I - GENERAL 1.1 SUMMARY

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

15900 HVAC INSTRUMENTATION AND CONTROLS

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

COMcheck Software Version Review Mechanical Compliance Certificate

photo by PFC Price Fan Column

NC State University Design and Construction Guidelines Division 23 Basic Mechanical Requirements

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Building Automation System (BAS) Design Criteria

TESTING, ADJUSTING AND BALANCING

Metasys Integrator TITUS Application

Engineering Guide VAV Diffusers. Please refer to the Price Engineer s HVAC Handbook for more information on VAV Diffusers.

SECTION AIR COILS

Inspection Phase Three. Mechanical, Electrical & Plumbing Section 503

COMcheck Software Version Mechanical Compliance Certificate

DIVISION 15 MECHANICAL

DIVISION 23 - HVAC HVAC Air Distribution

City of Duluth Festival Center 04/25

VentZone Systems VentZone Zoned IAQ with Energy Recovery Kits

CONTENTS. B. System Design and Performance Requirements

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

TECHNICAL SPECIFICATIONS

Florida Department of Transportation 1000 NW 111 th Avenue, Room 6203 Miami, Florida

DIVISION 23 - HVAC HVAC Air Distribution

SECTION TESTING, ADJUSTING AND BALANCING

2006 Washington State Nonresidential Energy Code Compliance Form Washington State Nonresidential Energy Code Compliance Forms Revised July 2007

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS

Civil Engineering Building

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Modular Supply Make-Up Air Unit

Installation Instructions

Selected Laboratory Energy Efficiency Measures

4. OVERVIEW OF MECHANICAL SYSTEM

IAQ: Re-tuning Commercial Buildings

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

B. System Design and Performance Requirements

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

UNIFIED FACILITIES GUIDE SPECIFICATIONS

August 15, 2013 Page 1 of 19

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Transcription:

Page 1 of 7 RICK SCOTT GOVERNOR Florida Department of Transportation 1109 S. Marion Avenue Lake City, Florida 32025 ANANTH PRASAD SECRETARY September 27, 2011 To: Proposal Holders Addendum No: 1, E2Q23, Financial Project # 42786415211 District Materials HVAC Modifications in Columbia County Base bid shall exclude controls work. Please see details in question and answer section below, and in revised scope of services. Alternate #1 is deleted. Scope of Services has been modified; please see attached REVISED scope. Questions and Answers: Mark Houston, Comfort Temp Company: Per the Pre-bid meeting held yesterday for the District Materials HVAC Modification project, in reference to Johnson Controls. I would like to formally request herein that Johnson Controls submits their quotation for Controls Scope of work, clearly indicating what they are providing with their scope as well as any exclusions, prior to the bid date as an Addendum, as was recommended in our meeting yesterday. ANSWER: The controls work for this project is being excluded from the base bid and Johnson Controls is being contracted with separately by the Department to complete the following work: Furnish and install a new unitary controller (UNT) for point of expansion Map points to all items tree Add points to user views and graphics as needed Modify sequences per Attachment D to Scope of Services Verify and check out system operations Coordinate with mechanical, electrical and test and balance contractors All field devices not mentioned above shall be supplied, installed and wired by others The prime contractor and all of their sub-contractors shall schedule and coordinate their work with Johnson Controls. Don Boykin, Southern Aire Contracting, Inc.: All of the contractors bidding this project will need a Mechanical Equipment list and air distribution breakdown in order to get a Test & Balance price. There should be a set of mechanical drawings for this facility showing this information. ANSWER: Please see attached mechanical drawings and air handling unit (AHU) specifications. Note that these drawings are old and may not be completely accurate. The contractor shall field verify all existing information pertaining to this project prior to submitting bid. Please contact John McCarthy at

Page 2 of 7 386-961-7256 to schedule a field visit if required. Also note that the new air balance schedules are located under item #10 of the scope of services. With regards to the Metasys DDC Control system, the METASYS DDC system is a proprietary DDC control system that is owned solely by Johnson Controls. No other company can work on, or provide any parts for this system. With that; All DDC controls that are required for the operation of the equipment needs to be provide and installed by Johnson Controls as a totally separate Sole Source contract. ANSWER: Please see the answer above concerning the exclusion of the controls work from this contract. The contractor shall coordinate with Johnson Controls to ensure that all new field devices installed will be compatible with the existing Metasys control system. Also Attached are revised Bidding documents that must be used for the October 12, 2011 letting or your bid may be found non responsive. You must sign, date and fax a copy of this addendum back to me by close of business today to indicate receipt. A copy of this addendum must be returned with your bid. Company Name Signature Date Thanks, Patsy Elkins, CPPB Contracts Coordinator Phone: 386-758-3703 Fax: 386-758-3791

Page 3 of 7 REVISED SCOPE OF SERVICES LOCATION OF PROJECT Florida Department of Transportation District 2 Materials & Research 1109 South Marion Avenue Lake City, Florida 32025 CONTRACTOR S RESPONSIBILITIES The contractor shall furnish all material and labor required to modify the Heating, Ventilation and Air Conditioning (HVAC) system in the Lake City District Materials building as specified below: 1. Boiler Replacement Disconnect and remove existing boiler and furnish and install new outdoor Raypak H1-0724 (or equal). Removal and installation shall include all utility and plumbing connections as well as startup and testing requirements. (See Attachment F) 2. Asphalt Lab #10 Exhaust Modifications General: The new fan for the Asphalt Lab #10 shall have a maximum capacity of 2,770 cfm at 1-inch water gauge external static pressure. Furnish the new exhaust fan with a variable speed motor and variable frequency drive for speed control. This controls operation for this room follows the current design and provides makeup air to the Asphalt Lab through AHU-1. Overcooling and reheat of the supply air will be required during various conditions in order to maintain room temperature when the exhaust fan is in operation. Control: Exhaust fan speed control shall be regulated by the Direct Digital Controls (DDC) system to maintain exhaust cfm airflow at 100 cfm more than supply cfm as measured at AT-2. Exhaust terminal EV-1 shall be maintained to measure exhaust airflow rate. The integral damper position operation shall be disabled. The damper shall be removed or locked in the full open position. In lieu of maintaining EV-1, furnish a new flow station upstream of the new exhaust fan. Utilize the new flow station to measure exhaust fan airflow and regulate exhaust fan performance. (Recommend contractor consider underlined option due to actual EV-1 location being different than that shown on Attachment C) Make all necessary changes to the DDC controls to automatically achieve the intended operation. (Strike through excluded from contract; controls work shall be performed by Johnson Controls) Provide power to the new fan. The fan variable frequency drive shall be as specified in Attachment B and mounted in AHU-1 mechanical room. Exhaust Fan: The new exhaust fan shall be connected to the 22 x 12 duct downstream from EV-1 and ducted to a new louver with plenum box. (See above recommendation) Provide necessary transitions with flexible duct connections to and from the fan. Provide independent support of the fan utilizing vibration isolation. Cap the unused remaining section of 22 x 12 ductwork airtight. The fan shall be SWSI capable of handling exhaust temperatures up to 250 degrees F. Fan shall be equal to Greenheck BSQ-140-15 as specified in Attachment A, Mark ILF-1A (second fan selection). Louver: Provide a new wall louver for the exhaust from the new exhaust fan. The new louver shall be equal to Ruskin ELF375X, 30 x 36, 2,800 cfm at 0.125 in. w.g. Furnish with 4 inch blades, back draft damper, bird screen and flanged frame. Finish shall be dark bronze. Include exterior rain hood to match existing.

Page 4 of 7 Ductwork: All ductwork and installation shall be in accordance with the latest duct construction standards of SMACNA for 2-inch pressure class. 3. ASSOCIATED CHANGES REQUIRED IN CLAY LAB 11 EV-2 Room Return Air Route a new section of 14 x 12 duct from the outlet of EV-2 to the 18 x 12 return duct to AHU-1 north of the mechanical room. Provide a balancing damper at the new connection. Cap unused sections of ductwork from EV-2 air tight. 4. Disconnect and Remove Exhaust Fan EF-1 Disconnect power and controls from EF-1. and remove the fan in order to make room for new work. (Strike through excluded from contract) Remove the discharge duct to the roof vent. Cap the opening under the roof vent and make repairs to the under-deck roofing insulation at the existing vent hood. Add insulation equal to existing type and thickness at the new roof deck cap. Disable exhaust terminal EV-3 as follows. Disconnect controls and lock each terminal unit s damper in the full closed position. Add a nominal 30 x 30 return air grille with balancing damper at the 34 x 16 return air duct to AHU-1. The return air grille shall draw return air supplied to the Open Office #17. 5. New Diffusers in Lunch Room New diffusers in Room 12 shall be one-way directional pattern diffusers with louvered face, all aluminum construction. Furnish Titus Model TDC-AA, 18 x18 neck with opposed blade damper, or equal. 6. Modify Dust Collection System & AHU-2 Return Ductwork Modify dust collection ductwork to exhaust only the Rock Room and two existing drops at the south wall of the existing Sampling Room. Total exhaust flow rate will be 1,700 cfm. Remove the 12-inch round dust collection main up to the existing 10-inch round size in the Sampling Room. Provide new 10-inch round ductwork from the existing 10-inch up to the dust collector inlet. Refer to Attachment C for details of duct changes. Rebalance the dust collection fan for 1,700 cfm. Modify the drive and replace the motor as required. (Strike through excluded from contract) Modify the AHU-2 supply and exhaust/return system for floor plan changes in the Sample Room. Refer to Attachment C for details of duct changes. Disable exhaust fan 7 (EF-7) and disconnect controls. 7. AHU-2 VFD and Controls Modifications Replace the existing 5 HP constant volume fan motor and drive with a new premium efficiency 7.5 HP motor rated for VAV frequency drive service. Furnish an adjustable frequency drive with by-pass. Furnish a unit suitable for outdoor installation and with all features required to meet the intended sequence and interface with the existing Building Automation System (BAS). Provide for surge protection. Modify the controls sequence of operation for system AHU-2 and associated equipment in accordance with Attachment D. (Strike through excluded from contract; controls work shall be performed by Johnson Controls) 8. Building Pressure Controls (AHU-1 and AHU-2) See Attachment D for the set points and sequence of operation for the building pressure controls. Furnish controls components by Johnson Controls Metasys (or approved compatible alternates). (Contractor shall furnish, install and wire all controls field devices not specifically excluded in Addendum #1; controls work specified in Attachment D and Addendum #1shall be performed by Johnson Controls)

Page 5 of 7 9. Inspect and Seal Ductwork Inspect all ductwork for leaks and seal all findings air tight. Significant leak was identified in 28 x14 supply duct from AHU-1 running north located in the attic over corridor 21. Inspect all ductwork insulation for AHU-1 and AHU-2 and make any required repairs. 10. Test and Balance Refer to Attachment E for the Section 15898 Test and Balance. Rebalance the air side for systems AHU-1 and AHU-2 as follows: ASPHALT LAB EXHAUST FAN - AIR BALANCE SCHEDULE EQUIPMENT EXHAUSTED CONNECTION MAX. CFM EXHAUST SHAKER SW CORNER 4 IN RND. 130 FUME HOOD W/ OVEN 12 IN RND. 1,290 DESPATCH OVEN W/ 12 IN. RND. 1,000 HOOD DESPATCH OVEN, NO 6 IN RND. 250 HOOD INFILTRATION DOOR TRANSFER 100 TOTAL 2,770 NOTE: SET MINIMUM EXHAUST CFM FOR 1,500. AHU-1 AIR BALANCE SCHEDULES AHU-1 AIRFLOW SCHEDULE CONTROL SUPPLY FAN MODE OPERATION SUPPLY AIR OUTSIDE AIR OCCUPIED AND UNOCCUPIED VARIABLE 9,035/ 2,260 3,965 / 695 NOTE 1. NOTES: 1. MINIMUM OUTSIDE AIR IS DETERMINED BY THE BUILDING PRESSURE CONTROLS. ALL CASES PROVIDE OUTSIDE AIR FOR A POSITIVE PRESSURE OF 400 CFM. AHU-1 TERMINAL UNITS & ROOMS NEW SUPPLY AIR (CFM) Zone AT-1 NW Offices 660 Room 2 90 Room 4 180 Room 5 180 Room 6 150 Room 6A 30 Room 8 30 Zone AT-2 Asphalt Lab 11 3,270 Zone AT-3 Clay Lab 11 1,150 Zone AT-4 Conf. & Reception 1 1,300 Room 1 Lobby 630 Room 22 670 Zone AT-5 South Office 520 Room 23 365 Room 23A 155 Zone AT-6 South Office 575 Zone AT-7 Open Office 1,230 Room 15 60

Page 6 of 7 Room 16 90 Room 17 850 Room 25 230 Zone AT-8 South Offices 330 Room 25A 75 Room 25B 255 AHU-2 AIR BALANCE SCHEDULES AHU-2 AIRFLOW SCHEDULE CONTROL EXHAUST MODE ON SUPPLY FAN OPERATION SUPPLY AIR OUTSIDE AIR NORMAL NONE VARIABLE 5,070 / 1,270 820 / 520 EXHAUST- DC-1 OR EF-4 CONSTANT 4,310 2,520 / NOTE 1 LOW EXHAUST- DC-1 AND EF- CONSTANT 5,070 4,290 / NOTE 1 HIGH 4 NOTES: 1. MINIMUM OUTSIDE AIR IS DETERMINED BY THE BUILDING PRESSURE CONTROLS. ALL CASES PROVIDE OUTSIDE AIR FOR A POSITIVE PRESSURE OF 400 CFM. LUNCH #12: MD-1 AIRFLOW SCHEDULE CONTR OL MODE EXHAUST ON SUPPLY FAN OPERATI ON COOLING SUPPLY AIR CFM NORMAL NONE VARIABLE EXHAUS DC-1 OR CONSTAN T - LOW EF-4 T EXHAUS DC-1 AND CONSTAN T - HIGH EF-4 T HEATING SUPPLY AIR CFM 1,100 / 320 550 1,100 / 320 550 1,100 / 320 550 NOTE: MD-1 CONTROL IS IN RESPONSE TO THE SPACE THERMOSTAT AHU-2 ROOMS NEW SUPPLY AIR (CFM) Room 12, Lunch 1,100 Room 18N, North Sample 340 Room 18W, West 440 Sample Room 18S, South 1,000 Sample Room 26 Rock Lab 2,190 All new controls which are to be connected to new or existing equipment and/or building controls must be compatible with the existing Johnson Controls Metasys System. The contractor shall coordinate all mechanical and test and balance work and assist the controls agency by making necessary mechanical corrections to ensure adequate systems operations, and at no additional cost to the Owner. The Contractor s scope of work shall include preparation and submission of AS-BUILT Drawings of equipment and ductwork modifications, controls and sequence of operation for all revised systems and work.

Page 7 of 7 All work shall be performed between the hours of 8:00 A.M. and 5:00 P.M., Monday Friday, and shall be coordinated with the owners project manager to ensure minimal disruption to the building occupants. The contractor shall clear all debris from work areas at the end of each workday. All work shall be performed in accordance with all applicable building codes and permitted through the local permitting agency. Contractor shall field verify all dimensions of required ductwork, equipment and air devices prior to submitting bid. ALTERNATE #1 Lump sum deduction to remove cost for the following controls items: Install new unitary controller (UNT) for point expansion Map points to all items tree Add Points to user views and graphics as needed Modify sequences per Attachment D Verify and check out controls operations Note: All field devices not listed above shall be supplied, installed and wired by the contractor. The contractor shall coordinate all mechanical and test and balance work and assist the controls agency by making necessary mechanical corrections to ensure adequate systems operations, and at no additional cost to the Owner. Alternate #1 is deleted from the contract.