Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

Similar documents
Installation and Maintenance "L" and "LS" Series

AIC Series Float & Thermostatic Steam Trap Installation and Maintenance Instructions

ICS Float and Thermostatic Steam Trap Installation and Operation Manual

SH-300, SH-900, SH-1500, SH-1600 and SH-1700 Bimetallic Steam Trap Installation and Operation Manual

INSTALLATION, OPERATION

INSTALLATION, OPERATION

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Series 1140 and 1141 Temperature Regulators

SH-2000, SH-2500, AB-3000 Bimetallic Steam Traps Installation and Operation Manual SH-2000

Liquid Drainers LIQUID DRAINERS

Bulletin 301-N SERVICE GUIDE. Armstrong Inverted Bucket Steam Traps

SERVICE GUIDE Armstrong Inverted Bucket Steam Traps

Series B Inverted Bucket Steam Traps

Inverted Bucket Steam Traps

MODELS N150/300/675/900/1500/2500/2600 INSTALLATION, SERVICING AND MAINTENANCE INSTRUCTIONS

INSTALLATION, OPERATION

Hoffman Specialty General Catalog

TABLE OF CONTENTS STEAM TRAPS INVERTED BUCKET SERIES PAGE FLOAT AND THERMOSTATIC SERIES PAGE THERMOSTATIC THERMODISC B0 26. How to Select All 107

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-214(C) Series 61 Low Water Cut-Off OPERATION

YARWAY PROCESS THERMODYNAMIC STEAM TRAPS SERIES 40/40D AND C250/260

S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions

Silhouette. Feedwater Heater. Boiler Feedwater

Main Steam Vents. Hoffman Specialty Regulators. How to Select Steam Vents

Installation and Testing of Inverted Bucket Steam Traps Manual

VENTS. Main Steam Vents. How to Select Steam Vents. For Steam Vent selection information, please refer to Selection Guidelines on page 133.

Mini Pump Trap. Features: n Low maintenance - No leaking seals, impeller or motor problems reducing maintenance and downtime.

Series 47 and 247 Mechanical Water Feeders. Series 47-2 and Combination Mechanical Water Feeder/Low Water Cut-Off ! WARNING

TITAN FLOW CONTROL, INC.

FT600 & FT601* Steam Traps Float & Thermostatic Steam Trap. Float & Thermostatic STEAM TRAPS

568X, 587X, 588X Series

Audi-Larm Audible Alarm

TECHNICAL INSTRUCTIONS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR POINT OF USE STEAM FIRED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL PS

Steam Trap BK 45 BK 45-U BK 45-LT BK 46

INFINITY FLUIDS CORPORATION

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

KINNEY OIL MIST ELIMINATORS

Installation, Operation & Maintenance Instructions

! WARNING. Replacement Head Mechanism INSTRUCTION MANUAL MM-413F

INSTRUCTION AND REPAIR MANUAL

THERMOSTATIC STEAM TRAPS

OPERATION & MAINTENANCE MANUAL FOR VIL VERTICAL INLINE PUMPS TYPES CS, CC, RC, AND DS

REF. NO Clamp Assembly 8 1 set Gasket (4 per set) S.S. Lock-washer 3/8 x 1/ Brass Impeller 3.

13-1. Temperature Regulator

Inverted Bucket Float & Thermostatic Radiator Traps STEAM CONTROL PRODUCTS STEAM TRAPS

Instructions for Installation, Operation, Care and Maintenance

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

STEAM TRAPS FOREST PRODUCTS LIBRARY FOREST RESEARCH LABORATORY OREGON STATE UNIVERSITY. Information Reviewed and Reaffirmed. August No.

SELF-PRIMING CENTRIFUGAL PUMPS BMLS-M & BMLS-H

Operating Manual. Model: Float-Controlled Condensate Trap, PN Safety instructions. 2 General description and usage

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

MODEL SS1B PLUS PACKAGED STEAM GENERATOR SG-101. Installation, Operation & Maintenance Instructions. Instruction No.

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

OPERATING AND MAINTENANCE MANUAL FOR INSTANTANEOUS STEAM FIRED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL F

The right trap for the right application.

6. Cooling System XCITING 400i. This chapter covers the location and servicing of the cooling system components for the KYMCO XCITING 400i.

THE THERMOSTATIC STEAM TRAP

INSTALLATION & OPERATING INSTRUCTIONS

SuperKlean Washdown Products

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

PT15 MATERIAL : DIMENSIONS - Nominal in inches. AVAILABLE SPARES: Disc (Packet of 5) ORDERING INFORMATION: Refer to "HOW TO ORDER" page.

541D19 SERIES. Technical Manual. A Division of Aquion Partners L.P.

569, 570, 571, 572 Series

Model: 1100 Float-Controlled Condensate Trap, PN 25

Blowdown Separator & Aftercoolers Installation, Operation, & Maintenance

Bringing Energy Down to Earth

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

F-P, F-L, FT-P AND FT-L SERIES 2/3 JACKETED DIRECT STEAM TILTING & STATIONARY KETTLES PARTS AND SERVICE MANUAL

Water Distiller Service Manual

SECTION HEATING BOILER FEEDWATER EQUIPMENT

Oil burners fuel unit with solenoid valve

LP30 High Integrity Low Level Alarm Probe Installation and Maintenance Instructions

INSTRUCTION MANUAL. Keep this manual in a safe place for future reference FREE FLOAT TYPE STEAM TRAPS JH-B SERIES JH5RL-B JH5RH-B JH7RH-B JH7.

Heat Exchanger Block Replacement Instructions

SERVICE MANUAL. For Service & Parts please call APK THERMAL at or SAFETY INSTRUCTION

TECHNICAL INSTRUCTIONS

STEAM SYSTEMS TOP SAFETY ITEMS FOR STEAM OPERATIONS. July, 2018

Blowdown Separator & Aftercoolers

DESCRIPTION AND INSTALLATION

TECHNICAL INSTRUCTIONS

Specifications Information and Repair Parts Manual 316A-95, 316B-95, 393A-95, 393B A-95 thru 394D-95, 399A-95

FOOD WASTE DISPOSER INSTALLATION AND USE MANUAL

569, 570, 571, 572 Series

INSTALLATION INSTRUCTIONS

F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual

SERIES 'HE' PLASTIC HORIZONTAL PUMP MODEL: H2 x1½

A AD Oil burners fuel unit. deltapumps.com. DE A-AD_en_0709.pdf Page 1/1

TECHNICAL INSTRUCTIONS

OWNERS GUIDE TO INSTALLATION AND OPERATION

Installation and Maintenance Manual Forbes Marshall Tracer Line Trap FMMST63

ASSEMBLY and INSTALLATION INSTRUCTIONS. Pipe wrench Ratchet 3/8 socket 9/16 socket 11/16 socket 3/16 Allen key 3/32 Allen key 9/64 Allen key

STEAM TRAPS

TECHNICAL DATA. Wet 26a. February 22, 2009

DESCRIPTION OF GAGE ASSEMBLY

Oil burners fuel unit with solenoid valve

THE THOMPSON MODEL A STEAMER NEW UNIT ASSEMBLY INSTRUCTIONS

UNIVERSAL STYLE STEAM TRAPS WU450 Series

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Transcription:

Armstrong J Series, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual This bulletin should be used by experienced personnel as a guide to the installation and maintenance of J Series float and thermostatic steam traps, condensate controllers, and liquid drainers. Selection or installation of equipment should always be accompanied by competent technical assistance. We encourage you to contact Armstrong or its local representative if further information is required. IB-48-EN Please read and save these instructions.

Armstrong J Series steam traps, condensate controllers, and liquid drainers have capacities to 25,000 lbs. of hot condensate per hour. The inlet and outlet connections are 2 NPT for operating pressures to 175 psig saturated steam. TABLE 1: Orifice Sizes and Operating Pressures. This table gives the maximum operating pressures for each orifice size: DO NOT EXCEED RATED OPERATING PRESSURES. Maximum Operating Pressure Table 1. J Series Installation Orifice Size 15 1-1/16 30 3/4 75 9/16 125 1/2 175 7/16 1. Series J steam traps, condensate controllers, and liquid drainers have individual requirements for installation. A) and Thermostatic Steam Trap Install the trap so that its inlet connection is below the liquid level in the equipment to be drained. Figure 1 shows the recommended piping method. B) Condensate Controller The condensate controller s ability to handle flash steam enables it to operate efficiently with siphon drained equipment. Figure 2 shows the recommended piping method. C) Liquid Drainer Install the liquid drainer with its inlet connection below the liquid level in the equipment to be drained. Figure 3 shows the recommended piping for a liquid drainer. 2. Before installing any trap, blow down the piping that leads to the unit s inlet. Use full line pressure. Be sure the maximum operating pressure (MOP) of the unit is adequate for the installation. (The MOP is stamped on the casting.) 3. Set the unit as shown in Figure 1, 2, or 3, with the flange resting on the floor or on a platform for support. Then install and tighten the inlet and discharge piping to secure the unit in its operating position. Use good piping practices to avoid excessive strain on the piping. 4. To allow for maintenance and provide maximum service, install a valve on each side of the unit, and a 2 Y-type strainer ahead of the inlet. All valves should be of the full-ported type to avoid restricting flow. 2

Note: Use good piping practices. Make inlet piping as short as possible with a minimum of elbows and other restrictions. Install a dirt pocket in the line ahead of the unit as shown in Figures 1 and 3. 5. Liquid Drainers must be back vented to avoid air-binding. Do not reduce the pipe size to less than 1 for the back vent. Connect as shown in Figure 3. Use a full ported valve in the back-vent line. Remember that the pressure in the drainer is the same as in the unit drained. Only the difference ni liquid levels produces flow. Minimize fittings and length of pipe between the vessel and the drainer. 6. If condensate is discharged to an overhead return, insure that adequate differential pressure exists across the trap to elevate the condensate. Install a check valve in the discharge piping near the unit to prevent back-flow when the system is not in operation. 7. Series J units do not require priming. They are ready for operation when installed. Heat Exchanger Vacuum Breaker (Optional) Strainer (Optional) Air Vent Cap Dirt Pocket *Return Line Figure 1 Drain Plug Figure 2 Water Seal J Series C.C. Version with Integral Flash Steam Release Receiver Vent Line Strainer (Optional) Dirt Pocket Discharged Line Figure 3 3

Maintenance Check the internal mechanism of these units for damage or wear at least once a year. A) Opening the Unit 1. Close the valves in both supply and discharge lines. If the unit is hot, allow it to cool. (Liquid Drainer: close the valve in the back vent line.) 2. Remove the drain plug from the bottom of the body and allow the liquid to drain. Caution: Do not attempt to remove the body without first removing the thermostatic air vent or fixed orifice and coupling. 3. Before removing the body. a) Steam trap. Remove the air vent cap ( 1 1/2 plug) from the top of the body. When the cap is removed, the thermostatic air vent extends through the top of the body. Using a spanner wrench or pliers, remove the thermostatic air vent and gasket. Inspect the vent for damage. The valve should be away from the valve seat. If you have the facilities, place the air vent in a pan of water and heat it to boiling. The valve should close. If the bellows is collapsed or ruptured, discard it and install a new one. If the unit includes a vacuum breaker, it is located in the air vent cap. Blow through the vacuum breaker from atmosphere side to be sure that it opens; suck air from that same side to be sure that it closes tightly. If the vacuum breaker does not operate properly, discard it and install a new one. b) Condensate Controller. Remove the air vent cap from the body. Remove the fixed orifice air vent and the coupling from the air relief tube. c) Liquid Drainer. Disconnect the back-vent or secondary steam piping from the drainer body. 4. Put blocks under the body of the unit to support it and remove the 8 bolts that attach the body to the cap. To facilitate handling, turn a lifting lug into the 1 1/2 NPT hole in the top of the body. A hoist can be attached to the lifting lug. 5. Carefully pull the body back from the cap, lifting slightly as you pull. Remove and discard the old gasket. 6. Inspect all of the moving parts. Remove all worn or damaged parts and replace them with new parts. Figures 4, 5, 6, and 7 show all critical or moving parts. Check that each item is in good condition and operates normally. Inspect the lever and guide pin assembly for indications of wear. See that the float is not dented or corroded. Look for pinhole leaks in the float. 7. If parts are worn or damaged, refer to Section B, Replacing The Mechanism or skip to Section C Reassembly of Trap. 8. After inspection and repair, clean the gasket surfaces and place a new gasket between the body and the cap. Replace the body carefully to avoid damaging the internal parts. Install and tighten the eight bolts. 9. Screw the drain plug into the bottom of the body and tighten it securely. 10. a) Steam Trap. Place the thermostatic air vent, with gasket installed, into the coupling at the top of the air relief tube. Tighten with a spanner wrench or pliers. Screw the air vent cap into the top of the body and tighten the cap with a wrench. b) Condensate Controller. Screw the fixed orifice and coupling onto the upper end of the air relief tube. Screw the air vent cap into the top of the body and tighten with a wrench. c) Liquid Drainer. Reconnect the back-vent piping. 11. Open the valves in the supply and discharge lines. For liquid drainers, also open the valve in the back-vent line. Check the equipment for normal operation. 4

Cap Thermostatic Air Vent Cap Fixed & Coupling Orifice Air Relief Tube Air Relief Tube Valve & Seat Valve & Seat Figure 4. & Thermostatic Trap Figure 5. Condensate Controller Cap Pipe Plug DO NOT REMOVE! Valve & Seat Figure 6. Liquid Drainer Air Relief Tube Cap Valve Lever Assembly Stem 1/32 Clearance Lock Nut & Post Guide Pin Assembly Valve Retainer Valve Valve Seat Figure 7. Detail of the Mechanism 5

B) Replacing the Valve and Seat 1. Remove the two (2) guide plate screws. The mechanism, except for the valve and seat, should be free from the cap. 2. Remove the valve seat from the cap. Be sure that the threads in the cap are not damaged and that the beveled mating surface in the cap is clean and free of erosion. 3. Install a new valve seat in the cap and tighten it securely. Pipe dope or lubricant must not be used on valve seat threads. The seal is made, not by the threads, but by metal to metal contact at the ground end of the valve seat. Make sure the seating area in the cap is clean before screwing the valve seat into position. Note: The valve and seat are a lapped and matched set. Never replace only a valve or only a valve seat. Be sure that the new valve and seat are the correct orifice size for your operating pressure. The orifice size is stamped on the valve seat, valve lever, and guide pin assembly. Parts with different orifice stampings should never be used together. 4. Install new valve, lever and guide pin assembly. Securely tighten the two guide plate screws. The ever simply hooks over the guide pins for installation. 5. Check for alignment of the guide pins. Hold the lever and valve against that valve seat with the valve contacting its seat and the two fulcrum points resting on the face of the seat. When the lever is held in this position, the guide pins should be centered in the guide pin holes as in Figure 8. When correctly aligned, the lever will move sideways the same distance to the right. (Figure 9) as to the left (Figure 10). Should the guide pins be out of line for any reason, they should be bent slightly so they will be centered in the guide pin holes as shown in Figure 8. For example, the guide pins in Figures 11 and 12 are not properly aligned and should be tapped lightly with a hammer, or similar tool, in the direction of the arrows. If the pins are too far apart or too close together, a similar procedure should be followed to position them concentrically. 6. Hold the valve in the valve seat with the lever s two fulcrum points resting on the face of the valve seat. Using an adjustable wrench turn the lock nut down on its post until there is approximately 1/32 clearance between the nut and the extension of the valve lever which is under the nut. See Figure 7. 7. Be sure that the float is screwed tightly to the stem of the valve lever assembly, then install the body on accordance with steps 1-4 of Section C below. Guide Pin Lever Valve Seat Fulcrum Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 6

C) Reassembly of Trap 1. After inspection and repair, clean the gasket surfaces and place a new gasket between the body and the cap. Replace the body carefully to avoid damaging the internal parts. Install and tighten the eight bolts. (See Figure 13 for bolt tightening sequence.) 2. Screw the drain plug into the bottom of the body and tighten it securely. 3. a) Steam Trap. Place the thermostatic air vent, with gasket installed, into the coupling at the top of the air relief tube. Tighten with a spanner wrench or pliers. Screw the air vent cap into the top of the body and tighten the cap with a wrench. b) Condensate Controller. Screw the fixed orifice and coupling onto the upper end of the air relief tube. Screw the air vent cap into the top of the body and tighten with a wrench. c) Liquid Drainer. Reconnect the back-vent piping. 4) Open the valves in the supply and discharge lines. For liquid drainers, also open the valve in the back-vent line. Check the equipment for normal operation. 7

Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. Armstrong International IB-48-EN Printed in U.S.A. - 11-3-2017 2017 Armstrong International, Inc.