Boiler & Water Heater

Similar documents
LAARS MIGHTY THERM 2. High Efficiency Boilers and Volume Water Heaters

LAARS PENNANT. Economical efficiency for greater savings

Date: Project #: Engineer: Prepared By: Bid Date:

Copper Finned Gas-Fired Volume Water Heaters, Boilers and Commercial Pool Heaters. Low NOx, Quiet, Efficient, Space-Saving

Mascot. Gas-Fired Residential and Commercial Wall-Mounted Boiler. Easy Installation, 96% Efficiency, Fully Condensing

TABLE OF CONTENTS BRADFORD WHITE BOILERS

LAARS MINI-THERM Gas-Fired Residential Hydronic Boilers

INDOOR/OUTDOOR, HOT WATER HEATERS AND HYDRONIC HEATING BOILERS

LAARS MINI-THERM Gas-Fired Residential Hydronic Boilers

Models 504 thru 2004 Category I with vertical vent. Models 503 thru 2003 Category IV Venting. CSA Certified Lead Content Less Than.

MASCOT II. Gas-Fired Wall-Mounted Combination Boiler & Water Heater

Proudly assembled in U.S.A

FXLF-9. High Efficiency Water Heaters and Boilers

Proudly assembled in U.S.A

Heating Systems Company LAARS INTRODUCES. The MASCOT LX. A Boiler. An All-in-One Answer to Your Home Heating and Hot Water Needs

G315/6 Cast Iron Boiler

G315/5 Cast Iron Boiler

Proudly assembled in U.S.A

G515/7 Cast Iron Boiler

INTRODUCING THE BRADFORD WHITE 24/7 EXPERT SUPPORT CENTER. TABLE OF CONTENTS. Technical Support: Warranty Support:

DIVISION FINNED WATER-TUBE WATER HEATERS

DOM-5. Domestic Hot Water Heaters & Boilers

Pump-Mounted Water Heaters B4 - Copper Brute Water Heaters Indoor/Outdoor Sizes 500,000-1,825,000 BTU/Hr. Up to 82% Thermal Efficiency

G615/11 Cast Iron Boiler

Models 1005, 1505, 2005 Up to 99% thermal efficiency!

Raptor 320HB & 399HB Submittal Sheet

High Efficiency Commercial Gas Water Heaters

Bid Date: Date: Project Name: Project #: City/St/ZIP: Fuel Type: Natural Gas Propane. Engineer: Factory Option: Contractor: Key Features.

DIVISION FINNED WATER-TUBE WATER HEATERS

Models 1005, 1505, Up to 99% thermal efficiency! Can be vented with PVC pipe Use Option D-32

Weil-McLain part numbers are found in Weil-McLain Boilers and Controls Repair Parts Lists.

Models HD101 thru 2342B

LOW NOx, HIGH EFFICIENCY, HOT WATER SUPPLY AND HYDRONIC HEATING BOILERS

GB Condensing Gas Boiler

Get The Edge Over The Competition with The Summit

Less Than.25% Lead Proudly Assembled in the U.S.A

Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired

Multiple Heater Controller TempTracker Mod+, up to 16 heaters

FTIIIC-10. Domestic Hot Water Heaters and Boilers

GB Condensing Gas Boiler

Models HD101 thru 2342B CSA certified Low Lead Content Less Than -.25% Pb. Proudly made in U.S.A

Raypak Residential Products

Less Than.25 Pb Proudly made in the U.S.A

Less Than.25% Lead Proudly Assembled in the U.S.A

WATER HEATERS / BOILERS GSB8-E. Gas-Fired Steam Boiler PRODUCT SPECIFICATIONS. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB E

RAYPAK ILLUSTRATED PARTS LIST

Product Data. ama. BW1, BW2 & BW3 Gas-Fired Water Boilers Series B

Automatic Circulating Water Heaters

FXLF-4. High Efficiency Water Heaters and Boilers

Product Data BW9 WATER BOILER SERIES B

RAYPAK ILLUSTRATED PARTS LIST

Bosch Buderus SSB800/1000/1000TL Stainless Steel Condensing Boiler

FINNED WATER-TUBE POOL HEATERS

Domestic Hot Water Heaters and Boilers FTIIIC-6

Commercial Gas Water Heaters

up to 99% MBTU Models 300A 400A 500A 700A 850A Can be vented with: PVC, Centrotherm New Versa IC TM Platform CSA Certified Low Lead Content

GB Condensing Gas Boiler

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

GSB8. CONSERVATOR Gas-Fired Steam Boiler. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB S MODEL NUMBER IDENTIFICATION FEATURES

23 11/32 [593] Ø8 AIR INLET [203] 6 5/8 [168] 44 3/4 [1137] TOP VIEW ASUB-31 REV. B 38 11/16 [983] 3 NPT BOILER OUTLET WIRING CONNECTIONS 1 NPT 1 NPT

Bosch Buderus SSB1000TL/TL2/TL3/TL4 Stainless Steel Condensing Boiler

Bosch Buderus SSB255/399/512 Stainless Steel Condensing Boiler

ULTRA HIGH EFFICIENCY. Platform with Touch Screen VERSA IC. Up to 99% thermal efficiency! Proudly assembled in the U.S.A.

COMMERCIAL MODELS: XTHERM 1005 THROUGH 2005

WATER-TUBE POOL HEATERS

New VERSA IC. Platform. Up to 99% thermal efficiency! Proudly made in the U.S.A

MBTU Models 300A 400A 500A 700A 850A. Can be vented with: VERSA IC. Platform. CSA Certified Low Lead Content Less Than.25% Lead.

Models 1005A, 1505A, 2005A 2505, 3005, 3505, Touch Screen VERSA IC. Control Platform. Up to 99% thermal efficiency! ULTRA HIGH EFFICIENCY

FINNED WATER-TUBE POOL HEATERS

Section 12 - REPLACEMENT PARTS Use only genuine LAARS replacement parts.

iq1001, Gen II Submittal Data

Suggested Specifications Prestige Excellence 110

Residential/Commercial Gas Condensing Tankless Models

Installation and Operation Instructions for

CONDENSING, MODULATING, HOT WATER SUPPLY, POOL, AND HYDRONIC HEATING BOILERS

HHA Lyerly Apartments 75 Lyerly Houston, Texas J. Allen Management Managing Agent

Columbia Boiler Company

SERIES 24. Series 24 Features. Commercial, Forced Draft, Hot Water or Steam Boiler. The right fit for any commercial job

HHA Bellerive Apartments 7225 Bellerive Houston, Texas J. Allen Management Managing Agent

Product Data. ama. Model BW9 Gas-Fired Condensing Water Boiler Series A FEATURES

199,000 to 4,000,000 Btu/h 150 to 4500 Gallons Storage

WATER-TUBE POOL HEATERS

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS

Heaters & Heat Pumps. Heaters and Heat Pumps. Heaters and Heat Pumps for Swimming Pools and Spas

iq251, Gen II Submittal Data

AFUE 95% Heating Input 50,000 to 200,000 Btuh

HEATERS AND HEAT PUMPS HEATERS & HEAT PUMPS HEATERS AND HEAT PUMPS FOR SWIMMING POOLS AND SPAS

High efficiency, cast-iron gas boiler

ClearFire - Hydronic Startup Report

up to 99% Efficiency! MBTU Models Can be vented with PVC CSA Verified lead Content Less Than.25% Pb Ultra Low Emissions

Phantom-X 399C/500C. Residential High Efficiency Gas Boilers PHNTM399C, PHNTM500C Submittal Sheet. Wholesaler Job Name Mechanical Contractor

AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

Commercial Boilers and Domestic Water Heaters APG-5

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

VICTORY VSPH VICTORYVSPH THE PERFECT CHOICE FOR. Cast-iron sealed combustion, direct vent gas boiler

940ES Tankless Water Heater

WATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

Hydronic Air Handler Powered by Tankless Technology

TURBOPOWER. Non-Condensing Gas, Oil or Combination Gas/Oil Storage Water Heater. 199 to 4000 MBH 150 to 4500 Gallons Tanks 25-year Warranty. PVI.

Transcription:

MIGHTY THERM2 Date: Project #: Pump-Mounted Boiler & Water Heater MT2H Hydronic Heater MT2V Volume Water Heater Indoor/Outdoor Sizes 500-2000 Submittal Engineer: Project Name: Prepared By: Location: Bid Date: Contractor: Standard Equipment ASME 160 psi working pressure heat exchanger ASME H stamp Two-stage firing Flanged water connections Glass-lined headers External header gaskets Flow switch Temperature pressure gauge Pump, mounted and wired Multiple operating gas valve/ pressure regulators Manual A gas valve Intake air filter Air pressure switch Burner site glass 24V control system 115/24VAC transformer Manual reset high limit External controller connections with selector switch 75 psi (517 kpa) ASME rated pressure relief valve (MT2H) 125 psi (861 kpa) ASME rated pressure relief valve (MT2V) Multiple, removable burner trays Stainless steel burners Built-in draft fan for Category I or III vent systems Hot surface ignition On/Off toggle switch Pump time delay Less than 10 ppm NOx Boiler Model: Boiler MT2H Water Heater MT2V Number of Units: Fuel Natural Propane Heat Exchanger Copper (std. on MT2H, N/A on MT2V) Cupro-Nickel (std. on MT2V) Copper, Reversed (N/A on MT2V) Cupro-Nickel, Reversed Water Trim Glass-Lined Cast Iron Bronze Trim (standard on MT2) Pump Normal Water, Taco Normal Water, Xylem Hard Water, Taco (MT2V only) Hard Water, Xylem (MT2V only) Soft Water, Taco (MT2V only) Soft Water, Xylem (MT2V only) Options CSD-1 200 F Max Controls (std. on MT2V) Low Water Cutoff Auto reset high limit Ignition failure alarm with bell and dry contacts, red trouble and green main gas lights ASME "HLW" Stamp (MT2V only) Reversed heat exchanger

Sizing Gas Water Input 1,3 Output 1,3 Conn. Conn. Shipping Size BTU/h BTU/h Size Size Weight inches 2 inches 2 lbs. kg 500 500,000 425,000 1¼ 2 700 318 750 750,000 638,000 1¼ 2 795 361 1000 999,000 849,000 1½ 2½ 940 426 1250 1,250,000 1,064,000 2 2½ 1035 469 1500 1,500,000 1,277,000 2 2½ 1170 531 1750 1,750,000 1,489,000 2 2½ 1265 574 MT2H 2000 1,999,000 1,701,000 2 2½ 1395 633 MT2V 2000 2,000,000 1,701,000 2 2½ 1395 633 NOTES: 1. Input and output must be derated 4% per 1000 feet above sea level when installed above 2000 feet altitude. 2. Dimensions are nominal. 3. For other boiler ratings: Boiler Horsepower: HP = Output Radiation Surface: EDR sq. ft. = Output 33,475 150 4. Shipping weight is approximate, based on previous units shipped and can be effected by several variables including the various weights for optional pumps and even the green or dry wood used in the crate. Accessories Side-wall vent terminal for indoor unit with horizontal venting Vent terminal for outdoor unit Side-wall combustion air terminal for indoor unit with horizontal ducted air Air terminal for outdoor unit Propane conversion kit Natural gas conversion kit Water Flow MT2H (Boiler) Temperature Rise in Degrees 20 F 11 C 25 F 14 C 30 F 17 C 35 F 19 C Flow Flow Flow Flow Flow Flow Flow Flow Size gpm lpm gpm lpm gpm lpm gpm lpm 500 43 161 34 129 28 107 24 92 750 64 242 51 193 43 161 36 138 1000 85 321 68 257 57 214 49 184 1250 106 402 85 322 71 268 61 230 1500 128 483 102 386 85 322 73 276 1750 N/R N/R 119 451 99 375 85 322 2000 N/R N/R 136 515 113 429 97 368 MT2V (Water Heater) Hard Water Normal Water Soft Water Flow Flow Flow Flow Flow Flow Size gpm lps gpm lps gpm lps 500 90 341 68 257 45 170 750 90 341 68 257 45 170 1000 90 341 68 257 45 170 1250 90 341 68 257 68 257 1500 90 341 68 257 68 257 1750 90 341 68 257 68 257 2000 112 424 112 424 112 424

Recovery WATER TEMPERATURE RISE IN DEGREES 40 F 50 F 60 F 70 F 80 F 90 F 100 F 120 F 140 F Size gph gph gph gph gph gph gph gph gph 500 1276 1020 850 729 638 567 510 425 364 750 1915 1532 1277 1094 957 851 766 638 547 1000 2548 2038 1699 1456 1274 1132 1019 849 728 1250 3189 2551 2126 1822 1594 1417 1276 1063 911 1500 3827 3061 2551 2187 1913 1701 1531 1276 1093 1750 4464 3571 2976 2551 2232 1984 1786 1488 1276 2000 5099 4079 3399 2914 2550 2266 2040 1700 1457 22 C 28 C 33 C 39 C 44 C 50 C 56 C 67 C 78 C Size L/h L/h L/h L/h L/h L/h L/h L/h L/h 500 4821 3857 3214 2755 2411 2143 1929 1607 1378 750 7238 5790 4825 4136 3619 3217 2895 2413 2068 1000 9632 7705 6421 5504 4816 4281 3853 3211 2752 1250 12054 9643 8036 6888 6027 5357 4821 4018 3444 1500 14464 11571 9643 8265 7232 6429 5786 4821 4133 1750 16875 13500 11250 9643 8438 7500 6750 5625 4821 2000 19274 15419 12850 11014 9637 8566 7710 6425 5507 NOTE: gph = gallons per hour, L/h = Liters per hour. Electrical MT2H & MT2V (pump mounted) Boiler / Heater Circuit Size Pump Circuit Size Blower Size Volts Phase Amps Volts Phase Amps Circuit 500 750 15 15 Included 1000-1750 120 Single 20 120 Single 15 in Boiler 2000 20 20 Circuit Pump MT2V Water Heaters Water Category Size SOFT NORMAL HARD HP Amps HP Amps HP Amps 500 1/3 2.8 1/3 2.8 3/4 7.2 750 1/3 2.8 1/3 2.8 3/4 7.2 1000 1/3 2.8 1/2 5.2 3/4 7.2 1250 1/3 2.8 1/2 5.2 3/4 7.2 1500 1/3 2.8 3/4 7.2 3/4 7.2 1750 3/4 7.2 3/4 7.2 3/4 7.2 2000 1 9.8 1 9.8 1 9.8 MT2H Boilers Size HP Amps 500 1/3 2.8 750 1/3 2.8 1000 1/2 5.2 1250 1/2 5.2 1500 3/4 7.2 1750 3/4 7.2 2000 1 9.8 Clearances Appliance Required Clearance From Suggested Service Surface Combustible Material Access Clearances Left Side 1 2.5 24 61 Right Side 1 2.5 24 61 Top 1 2.5 12 30 Back 1 2.5 12 30 Front 1 2.5 36 91 Vent Per venting system supplier's instructions Dimensions in inches cm

Dimensional Air Vent Conn. Conn. Size A B C D E F W V 500 33¾ 86 16¾ 43 6½ 17 10 25 8 20 46¼ 117 6 15 8 20 750 45¾ 116 22¾ 58 6½ 17 10 25 9½ 24 58¼ 148 8 20 10 25 1000 57¾ 147 28¾ 73 6½ 17 10 25 9½ 24 70¼ 178 8 20 10 25 1250 68¼ 173 34¼ 87 10¼ 26 10 25 9 23 80¾ 205 12 30 12 30 1500 78¾ 200 39½ 100 10¼ 26 10 25 9 23 91¼ 232 12 30 12 30 1750 89¼ 227 44¾ 113 10¼ 26 10 25 9 23 101¾ 258 12 30 14 36 2000 99¾ 253 49¾ 127 10¼ 26 10 25 9 23 112¼ 285 12 30 14 36 Dimensions shown in inches cm. Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement. Customer Service and Product Support: 800.900.9276 Fax 800.559.1583 Headquarters: 20 Industrial Way, Rochester, NH 03867 603.335.6300 Fax 603.335.3355 1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 905.238.0100 Fax 905.366.0130 www.laars.com Litho in U.S.A. Laars Heating Systems 1703 Document 1214G