The Low-Temperature Radiant Floor Heating System Design and Experimental Study on its Thermal Comfort

Similar documents
Experimental study of fan coil assisting radiant floor heating system

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Experimental Research on Monomial Cooling Measure of Greenhouse in Summer

Development of Bionic Air Cooler Used in High Temperature Coal Mine

The Energy Consumption Investigation of the Hotel Central. Air-conditioning System and the Research of Energy Saving Measures

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler

Analysis of the Design of an HVAC System in a Public Building

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Experimental Research of Air Source Heat Pump Frosting and Defrosting in a. Double Stage-Coupling Heat Pump

Application of the VRV Air-Conditioning System Heat Recovery Series in. Interior Zone and Analysis of its Energy Saving

The Experimental Research on Grain Storage Heat and Moisture Transfer Siyu Chen 1,2, Wenfu Wu 1,Yan Xu 1,Chunshan Liu 2, Yaqiu Zhang 1, a

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Research on the Monitor and Control System of Granary Temperature and Humidity Based on ARM

Simulation of Full-scale Smoke Control in Atrium

Design of Humidity Monitoring System Based on Virtual Instrument

,Chaojian He6, f. School of Guangxi University, Nanning , China.

DESIGN AND FABRICATION OF A PORTABLE REFRIGERATOR BASED ON PELTIER EFFECT

EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE

Available online at ScienceDirect. Procedia Engineering 135 (2016 )

HEAT TRANSFER COEFFICIENT ENHANCEMENT IN NATURAL CONVECTION FROM HORIZONTAL RECTANGULAR FIN ARRAYS WITH PERFORATIONS

Study on an environmental simulation system of low/high temperature. for great space

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

State Grid Zhejiang Electric Power Corporation Electric Power Research Institute, Hangzhou, , China

The Experimental Study and Simplified Model of. Water Mist Absorbing Heat Radiation

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Analysis of Heating Systems and Scale of Natural Gas-Condensing Water Boilers in Northern Zones

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

The Mode of Urban Renewal Base on the Smart City Theory under the Background of New Urbanization

Experimental Study on the Effects of Compression Parameters on Molding Quality of Dried Fish Floss

AN AVERAGE STANDARD OF A PIECE OF FURNITURE CHANGES IN FORMS, STRUCTURES, AND FITTINGS OF POLISH FUNITURE OVER A TIME PERIOD OF 25 YEARS

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

CFD Analysis of Fire Characteristics on Subway Junction Station

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

Performance Analysis of Heat Pipe using Different Screen Mesh Sizes Manikandan.K * 1, Senthilkumar.R 2,

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

Research on Public Space Renewal Strategy of Small and Medium-sized Towns Based on Spatial Syntax--Taking Liulin Liaoyuan Square as an Example

Design and Realization for the Environmental Protection Type of Pig-Farm Model Based on the Sensor Technology

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Effects of Volute Tongue Clearance and Rotational Speed on Performance of Centrifugal Blower Nitin S. Jadhav *, S. R. Patil

Detection system for optic characteristics of automobile glasses

Two-Pipe Fiber Bragg grating Temperature Sensor Applied in Cable Trench and Cable Pit

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

Performance Study of Triple Concentric Pipe Heat Exchanger

Modeling and Simulation on Temperature Control System of Farm Products Baking Equipment. Liu Jun, Jia Zhenwei, Guo Rongxing

Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater Tunnel

International Journal of Informative & Futuristic Research ISSN (Online):

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Natural Convection Heat Transfer Augmentation from Heat Sinks using Perforated Fins: A Review

The Effect of Quantity of Salt on the Drying Characteristics of Fresh Noodles

2nd International Symposium on Integrative Plant Biology (1st announcement)

DESIGN AND ANALYSIS OF PIPE HEAT EXANGERS WITH INSIDE FINS

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Simulation of Evacuation Process in a Supermarket with Cellular Automata

American International Journal of Research in Science, Technology, Engineering & Mathematics

Experimental Study of Initial Process of Frost on Heat Exchanger Surface of Refrigerated Transport Vehicle

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

A TRNSYS Simulation Case Study on Utilization of Heat Pump For both Heating and Cooling

Study on the North China Rural Water Supply Project O&M Cost Standard Rating

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Energy Performance of a Desiccant and Evaporative Cooling-assisted Airconditioning System under Various Climatic Conditions in China

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

DESIGN OF THE BODY FRAME OF A RAIL DETECTOR

Indoor thermal comfort by controlling heat transfer through building envelope

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Experimental Study and Analysis of Flat Plate Solar Water Heater with Different Flow Rates using of Circulating Pump

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

1st City Issues Tongji International Symposium City & Real Estate Risk Management 2010

Heat Transfer in Evacuated Tubular Solar Collectors

REDUCTION OF NOISE AND VIBRATION OF FRONT LOADING WASHING MACHINE IN SPIN-CYCLE

Design and Development of Water Cooled Condenser for Domestic Refrigerator

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Design and Experimental Studies on Modified Solar Dryer

Experimental Study of Alternatives to Sand in Zeer Pot Refrigeration Technique

Design of Intelligent Humidity Sensing Watering System Based on MCU

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

SOLAR WATER DISTILLATION BY USING WATER IN THE INNER GLASS EVACUATED TUBES

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Analysis on combinations of indoor thermal microclimate parameters in radiant cooled residential buildings and drawing of new thermal comfort charts

Purdue e-pubs. Purdue University

Adaptibility Analysis of nzeb and Passivhaus in Mixture Climates of China

Cooperation of a Steam Condenser with a Low-pressure Part of a Steam Turbine in Off-design Conditions

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Performance of Geosynthetics in the Filtration of High Water Content Waste Material

A Study on the 2-D Temperature Distribution of the Strip due to Induction Heater

Development and Application of Micro Channel Heat Exchanger for Heat Pump

Desiccant-enhanced evaporative (DEVap) cooler system introduction and its comparison with direct expansion (DX) system

ABSTRACT I. INTRODUCTION

Transcription:

International Journal of Research in Engineering and Science (IJRES) ISSN (Online): -9364, ISSN (Print): -9356 Volume 4 Issue 1 ǁ January. 16 ǁ PP.56-61 The Low-Temperature Radiant Floor Heating System Design and Experimental Study on its Thermal Comfort Sun Rui 1, Hang Xin 1, Liu Tuo 1 Chen Yu 1 (1.College of Mechanical Engineering, Shanghai University of Engineering Science, Shanghai 16, China) Abstract: In order to analyze the temperature distribution of the low-temperature radiant floor heating system that uses the condensing wall-hung boiler as the heat source, the heating system is designed according to a typical house facing south in Shanghai. The experiments are carried out to study the effects of the supply water temperature on the thermal comfort of the system. Eventually, the supply water temperature that makes people in the room feel more comfortable is obtained. The result shows that in the condition of that the outside temperature is 8~15 and the relative humidity is 30~70%RH, the temperature distribution in the room is from high to low when the height is from bottom to top. The floor surface temperature is highest, but its uniformity is very poor. When the heating system reaches the steady state, the air temperature of the room is uniform. When the supply water temperature is 63 The room is relatively comfortable at the above experimental condition. Key words: low-temperature radiant floor heating system; condensing wall hung boiler; temperature distribution; comfort I. Introduction Low-temperature radiant floor heating uses the low temperature water as the heat medium, and its heat coils are buried in the floor of building. It s a heating mode that uses the mechanical circulating hot water to heat the room[1]. It is comfortable, healthy, energy-saving, clean and easy to be decorated. Gradually it has attracted people s attention, and it s recognized as the ideal heating way at home and abroad. With the continuous development of floor heating technology, the relevant research is also developing. Many scholars at home and abroad have got a series of achievements in the theoretical and experimental aspects. S.Sattari and B.Farhanieh analyzed the effect of design parameters of floor heating on thermal performance, and they concluded that the floor layer material and the thickness have biggest effect on thermal performance[2]. South Korea's Gook-Sup Song had do some research that the influence of change of the floor thickness and supply water temperature on the surface temperature through the experiment measurement[3].zhou Xinghong had done the numerical simulation about low-temperature floor radiant heating and concluded some laws about heating. These could provide theoretical basis for design, construction and operation of heating system[4]. Zhao Leilei analyzed heat transfer performance of low-temperature radiant floor heating comprehensively[5]. In Yanshan University, Dong Wei and Wu Lei, had done the research and about new control strategy and temperature controller of low-temperature radiant floor heating respectively[6,7]. Xiao Yonguan simplified the average surface temperature, non-radiative average surface temperature. He established a single-valued function whose total costs is the supply and return water temperature difference and determined the optimum supply and return water temperature difference eventually[8]. These studies had an important significance for the further development of radiant floor heating. This article mainly introduces the design and other problem of radiant floor heating system. The system uses the condensing boiler as the heating resource and the experimental heating room is faced the south in Shanghai. Through the experimental methods, the surface and air temperature distribution have been analyzed in the condition of different supply water temperature in a typical heating season. Also the supply water temperature that makes people more comfortable is obtained. II. 1 The design of the low-temperature radiant floor heating system The design of the low-temperature radiant floor heating system is calculating the thermal load of the 56 Page

experimental room which is based on the building envelope characteristics. It includes heat consumption of the exterior-protected structure, cold air infiltration heat loss and cold air invasion. According to the calculation results, it has been calculated that the thermodynamic calculations of the low-temperature radiant floor heating system. The calculations mainly include heating load, the heat per unit floor area, tube spacing, and average temperature of the earth's surface and so on. 1.1 The heat load analysis of the laboratory The total construction area of the room is about 39.78m2 and its area could be used is 33.6 m2. The interior includes office chairs, lockers and other facilities, and the plane diagram of the house is shown in Fig.1. Fig.1. The Laboratory plan The design heat load is the basis for the design of the heating system. The design heat load includes three parts, the main part is the basic heat consumption of the building structure and the other two parts are infiltration heat loss and the cold wind invasion heat loss. Because the room doesn t have the outside door, so there is no need to consider the cold invasion of consumption. The total heat consumption of the experimental room isq 3159. W. 1.2 The surface temperature and the heat dissipation of the floor When floor heat dissipation of the room is calculated, the impact of the indoor office desks and chairs should be taken into consideration. Q is modified, and the modified coefficient is 1.[9]. So the result is Q 3949.00 W. Combined with figure1, the preliminary design is that the laying area of the heating pipe is 33.6m2, and the pipe is 300mm away from the wall. So the unit area of the reuired heat dissipation is x 117.53w. The relationship between surface average temperature t and the unit heat of the floor t 100 x 0.969 tn 9.82( ) (1) x is as follows, x will be substituted into the euation (1), and average temperature of the earth's surface t=31.48, which matches the provisions[9]. 1.3 Determination of distance between heating pipes According to design selection table in radiant heating and cooling technical specification in China[9], the nominal diameter of the heating pipe in the system is mm. Its filling layer thickness is 50mm, and the 0.041w/( m k) polystyrene foam insulation layer thickness is mm, and its thermal conductivity is. The 57 Page

2 ground layer material is stone, and its thermal resistance is R 0.02 m K / W. The water temperature difference is designed as 10. Combined with x and t, A=0mm is chosen as the heating pipe spacing. III. Experimental studies on temperature distribution of floor radiant heating 2.1 Experimental system of floor radiant heating In the experimental system, condensing gas boiler is heat source and low-temperature radiant floor heating is the heating end. By heating the internal circulating water of condensing boiler, the radiant floor heating makes the experimental room warm. The pipes are arranged for double circuit type. The temperature measurement points in the room are shown in Fig.2. Through the experimental measurement, temperature distribution are obtained in different supply water temperatures when the outdoor temperature and humidity are within the range of 8~15 and 30~70%RH respectively. And then the supply water temperature that makes the room more comfortable is got. 5 4 3 1 2 Fig.2.Support distribution Fig.3. Temperature points distribution In the experimental room, there are 5 measuring supports, and there are 4 measuring points in every bracket. The height of measuring points are 0m, 0.5m, 1.0m, 1.5m, and the total amount is. Their distribution is shown in Fig.3. The measuring points in the height of 0m are used to measure the earth s surface temperature, and the other measuring points are measuring the air temperature in the experimental room. 2.2 Experimental results and analysis When the supply water temperature is 50, in the case of No.3 support, temperature variation in the unsteady and steady state are shown in Fig.3, 4. 58 Page

Z=0m Z=0.5m Z=1.0m Z=1.5m 28 27 Z=0m Z=0.5m Z=1.0m Z=1.5m 21 19 21 18 0 40 60 80 100 1 140 160 180 0 0 Fig.3. Temperature distribution at the beginning 0 40 60 80 100 1 140 160 180 0 0 Fig.4. Temperature distribution in steady state From Fig.3, it can be seen that the surface temperature is on the rise gradually at the beginning of the system operation, while the air temperature is on the gradual rise. During the experimental period, the surface temperature is about 3 higher than the air temperature. According to Fig.4, when the heating system reaches steady state, the surface temperature keeps about.5, and the indoor temperature in the height of 0.5m, 1.0m and 1.5m are about 21. It shows that the height has little effect on the change of temperature. The air temperature distribution is more uniform, and the temperature has no obvious change in the vertical distribution. So it can be judged that the air temperature difference between the other supports is very small. In the same height, the air temperature distribution of all supports in the experimental room is shown in Fig.5..5.0 support-1 support-2 support-3 support-4 support-5 21.5 21.0.5.0 0 40 60 80 100 1 140 160 180 0 0 Fig.5. The temperature in different supports It can be seen that the whole indoor air temperature is maintained at about 21 from Fig.5. It has about 0.5 temperature fluctuation, and the air temperature is uniform in horizontal distribution. It can be concluded that in the condition of that the supply water temperature is 50, when the heating system reached the steady state, the indoor temperature reaches 21. In the same way, the distribution of the surface temperature of the supports is shown in Fig.6 and Fig.7, when the heating system is in the unsteady and steady state. 59 Page

温度 / 27 support-1 support-2 support-3 support-4 support-5 28 27 support-1 support-2 support-3 support-4 support-5 21 0 40 60 80 100 1 140 160 180 0 0 Fig.6. Ground temperature at the beginning 0 40 60 80 100 1 140 160 180 0 0 Fig.7.Ground temperature in steady state At the beginning operation of heating system, the surface temperature distribution of 5 supports is shown in Fig.6. The surface temperature increases with the growth of time gradually. Their rise trends of the surface temperature are almost the same, but there is a certain difference in temperature between the various measuring supports. The maximum temperature difference is closed to 2. The distribution of surface temperature system is shown in Fig.7 when the system reaches steady state. It is obvious that the surface temperature of every support is different, and the maximum temperature difference is about 3.5, which shows that the uniformity of the surface temperature distribution is poor. This is related to the position of the measuring point. When the temperature measuring points are located above the pipe, the heat transfer is better and the temperature is higher. While the other points are located at the top of the two heating tube, the temperature is lower than the former. When the supply water of condensing boiler is 55,60,63,67,71,75 respectively, indoor temperature can be obtained and their distribution are shown in Fig.8. 32 30 28 供水温度 t=55 供水温度 t=60 供水温度 t=63 供水温度 t=67 供水温度 t=71 供水温度 t=75 18 0 40 60 80 100 1 140 160 180 0 0 时间 /min Fig.8. Temperature distribution of the room in different temperature of supply water With the increase of supply water temperature, the indoor air temperature increase. When supply water temperature increase from 60 to 63, and from 63 to 67, indoor temperature has a large rise. The water supply temperature rise 3~4, and air temperature will increase about 2. Combined with the human factors and PMV relational table [10], it shows that when the indoor air temperature reached to, the human will feel more comfortable. Based on Fig.8, the indoor air temperature is close to when the supply water temperature is 63. IV. Conclusion According to the condensing boiler and floor radiant heating system test, conclusions can be got as follows: (1) The indoor temperature distribution of the floor radiant heating is generally from high to low when the 60 Page

height is from lower to upper. The floor surface temperature is the highest, but the uniformity is poor. The indoor air temperature has little change, and the distribution is relatively uniform. (2) In the condition of that outdoor temperature is 8~15 and outdoor humidity is from 30 to 70 %, when the supply water temperature of condensing boiler is 63, the heating system could bring better comfort to people. Reference [1] Ran Chunyu. Heating engineering [M]. Beijing: Chemical Industry Press, 09. [2] S.Sattari, B.Farhanieh. A Parametric study on radiant floor heating system performance. Renewable Energy 31 (06):1617-16 [3] Gook-Sup Song. Buttock temperature in a sedentary posture on plywood flooring of varying thickness over the ONDOL heating system. J Wood SCI (04)50:498 503. [4] Zhou Xinghong. Numerical simulation of low-temperature floor radiant heating and its performance analysis [D]. Nanjing: Nanjing University of Science and Technology, 04 [5] Zhao Leilei. Performance Research on low-temperature Radiant floor Heat-supply System [D]. Beijing: Beijing University of Chemical Technology.10. [6] Dong Weimin. Study on new control strategy of low-temperature floor radiant heating system [D]. Hebei: Yanshan University.10. [7] Wu Lei. Research on low-temperature radiation ground heating temperature controller [D]. Hebei: Yanshan University, 10. [8] Xiao Yonguan,Yuan Qingtao, Zhao Ju. The decision of optimal temperatures of the supply and return water about the floor heating with geothermal energy [J]. Journal of Shandong University, 07, (3): 2~9. [9] Technical specification for radiant heating and cooling [S] JGJ142-12. [10] Chen Cuiping. Study on air-condition energy-saving way based on PMV index [D]. Shanghai: Donghua University.11. 61 Page