Uncertainty Analysis For Input Parameters Of Electrical Cabinet Fire Simulation By Coupling Latin Hypercube Sampling And CFAST

Similar documents
ZONE MODEL VERIFICATION BY ELECTRIC HEATER

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Y. ORMIERES. Fire risk analysis method for nuclear installations

METHODOLOGY. Definitions. A Collaboration of U.S. NRC Office of Nuclear Regulatory Research (RES) & Electric Power Research Institute (EPRI)

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

The Impact from Fire PSA Hazard Factor for the PWR Plant

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro

Fire Severity for Structural Design

Case Study 1 Underground Car Park

A Monte Carlo Approach for the Design of Thermal Fire Detection System

Considerations in the Design of Smoke Management Systems for Atriums

Fire Test Evaluation using the Kerosene and Aviation Fuel

Fire Risks of Loviisa NPP During Shutdown States

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

Application of Fire PSA in Defining System Reliability Criteria: Detection and Suppression Systems in I&C Electrical Panel Room

Application Note. Application Note for BAYEX

PERFORMANCE-BASED FIRE PROTECTION OF NUCLEAR PLANTS

FIRE HAZARD ASSESSMENT IN SUPPORTING FIRE PROTECTION SYSTEM DESIGN OF A CHEMICAL PROCESS FACILITY ABSTRACT

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Heat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings

Probabilistic-deterministic modelling of fire spread

Research on Decision Tree Application in Data of Fire Alarm Receipt and Disposal

Simulation of Full-scale Smoke Control in Atrium

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

Sprinklers Modeling for Tunnel Road Fire Fighting

Cable Selection and Detailed Circuit Analysis on Plant under Construction

How design fires can be used in fire hazard analysis

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

COMPARISON OF NFPA AND ISO APPROACHES FOR EVALUATING SEPARATION DISTANCES

Electrical failure during NPP cable fires

ICONE DRAFT Proceedings of the 16th International Conference on Nuclear Engineering ICONE16 May 11-15, 2008, Orlando, Florida, USA

Modeling a real backdraft incident fire

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

Advantages and Disadvantages of Fire Modelling

STUDY REPORT SR 292 (2013) B-RISK 2013 Software Benchmarking Examples. C.A. Wade

Event Tree Methodology as Analytical Tool for Fire Events

Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

Performance-based Fire Design of Air-supported Membrane Coal Storage Shed

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

FIRE PROBABILISTIC SAFETY ASSESSMENT FOR KUDANKULAM NPP IN INDIA. G.Tokmachev. Atomenergoproekt, Bakuninskaya 7, Moscow, Russia

Tunnel Fire Dynamics and Evacuation Simulations

SIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

VIRTUAL FIRES via COMPUTERS

Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development

A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS

Case Study of Underground Car Park. Team Japan

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

IAEA SAFETY STANDARDS

EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett

An Overview of Extinguishing Systems for Computer Equipment

CABLE TRAY FIRE IN OPEN ATMOSPHERE

Fire Patterns. Introduction. Skills Objectives. Fire Effects and Fire Patterns (2 of 2) 12/20/ Knowledge Objectives

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

Fire Research and Education at the University of Maryland

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

Fire Safety Design when Normal Limits Don t Apply

Recent BRANZFIRE enhancements and validation

Smoke Layer Height and Heat Flow through a Door

Video Smoke Detection using Deep Domain Adaptation Enhanced with Synthetic Smoke Images

Chapter 17, Initiating Devices

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS

A Priori Modelling of Fire Test One

Adrian Milford Sereca - a Jensen Hughes Company, Project Engineer Vancouver, BC, Canada

A DESCRIPTION OF THE PROBABILISTIC AND DETERMINISTIC MODELLING USED IN FIRECAM

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

FRANCE M & F RANKING ACCORDING TO NF F

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

Potential Impact of New UL Fire Test Criteria

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

Case Study 1 Underground car park

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

Fire Protection as the Underpinning of Good Process Safety Programs

DRAFT NFPA 805 TRANSITION PILOT PLANT OBSERVATION GUIDANCE

GAS DETECTOR LOCATION. Ø.Strøm and J.R. Bakke, GexCon AS, Norway

Developing a New Fire PRA Framework by Integrating Probabilistic Risk Assessment with a Fire Simulation Module

International Journal of Advance Engineering and Research Development

The Development of Automatic Fire Alarm Standards and Related Products in China

INSIGHTS GAINED FROM A REVIEW OF FIRE PRA RISK CONTRIBUTION BY IGNITION FREQUENCY BINS

An experimental study of the impact of tunnel suppression on tunnel ventilation

Collaboration on fire code benchmark activities around the international fire research program PRISME

PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR

ALTERNATIVE DESIGN AND ARRANGEMENTS FOR FIRE SAFETY

IJsbrand van Straalen, Ph.D. Senior scientist TNO The Netherlands

On Estimating Heat Release Rate for a Design Fire in Sprinkler Protected Area

Fundamentals is subdivided into Sources of Radiation, Biological Effects, Mathematics, Chemistry, Physics, and Units and Terminology.

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand

CFD Model of a Specific Fire Scenario

26 June 2001 GUIDELINES ON ALTERNATIVE DESIGN AND ARRANGEMENTS FOR FIRE SAFETY

Transcription:

Uncertainty Analysis For Input Parameters Of Electrical Cabinet Fire Simulation By Coupling Latin ypercube Sampling And CFAST Wanhong WANG a, Dahuan ZU b, ui BAO c, Yun GUO a, Changhong PENG a * a School of Nuclear Science and Technology, University of Science and Technology of China, efei, Anhui, China b Science and Technology on Reactor System Design Technology Laboratory, Nuclear Power Institute of China, Chengdu, Sichuan, China c Institute of Plasma Physics, Chinese Academy of Sciences, efei, Auhui, China Abstract: It has been proved that fire accident frequency in nuclear power plants is higher than we thought it was and fire accidents have a huge significant impact on the safety of nuclear power, so it is extremely necessary to analyze fire risks. Electrical cabinets are one of the most important fire ignition sources in nuclear power plants, since there are normally many combustible cable bundles inside them. When fire modeling has been performed in nuclear power plants, past studies have only considered a single fire scenario, which means that the uncertainties associated with fire combustion and propagation are ignored. The paper is based on electrical cabinet fire scenario simulations in nuclear power plants and analyze the uncertainty of input parameters related to fire combustion and fire detection by coupling Latin ypercube Sampling and software-cfast. Statistic results can be used for quantitative analysis in Fire Probabilistic Safety Assessment. Keywords: CFAST, Latin ypercube Sampling, Electrical Cabinet Fire, Uncertainty Analysis 1. INTRODUCTION The Main Control Room (MCR) is a special fire compartment which is constantly occupied with operators to control and monitor the whole nuclear power plants. The controllers, indicators and alarm windows are all located inside this room. A large fire in the MCR can be harmful to safe shutdown capability, since cable bundles inside electrical cabinets and other important equipment can possibly be damaged and lead to uninhabitable conditions for operators there. If the MCR environment becomes uninhabitable, operators there must evacuate the MCR and go to the alternative shutdown panel to shut down nuclear power plants [1]. CFAST is a two-zone fire model that predicts the thermal environment caused by a fire within a compartmented structure. Each compartment is divided into an upper and lower gas layer. The fire drives combustion products from the lower to the upper layer via the plume. The temperature within each layer is uniform, and its evolution in time is described by a set of ordinary different equations derived from the fundamental laws of mass and energy conservation. The transport of smoke and heat from zone to zone is dictated by empirical correlations. Because the governing equations are relatively simple, CFAST simulations typically require a few tens of seconds of CPU time on personal computers [2]. CFAST consists of environment simulation conditions, thermal properties, compartments, wall vents, ceiling/floor vents, mechanical ventilation, fires, targets, detection/suppression, surface connections and output. By setting appropriate input parameters, it calculates time-evolving distribution of smoke and gaseous combustion production as well as the temperature throughout compartments during a userprescribed fire scenarios. Latin ypercube sampling is a method of sampling that can be used produce input values for estimation of expectations of functions of output variables. By using this sampling approach, a near-random sample of parameter values from a multidimensional distribution can be generated. The sampling method is often used to construct computer experiments or for Monte-Carlo integration. *Corresponding Author:Changhong PENG,E-mail:pengch@ustc.edu.cn

Latin ypercube Sampling (LS) operates by dividing the subspace of each vector component ν i ; i=1, 2,, N into M=n disjoint subsets (strata) of equal probability Ω ik ; i=1, 2,, N; k=1, 2,, M. Samples of each vector component are drawn from the respective strata according to χ ik = D 1 Xi (U ik ); i = 1, 2,, N; k = 1, 2,, M (1) where U ik are iid uniformly distributed samples on [ξ l k, ξ u k ] with ξ l k =(k-1)/m and ξ u k =(k/m). The sample x are assembled by randomly grouping the terms of the generated vector components. That is, a term χ ik is randomly selected from each vector component (without replacement) and these terms are grouped to produce a sample. This process is repeated M=n times [3]. 2. FIRE MODELING 2.1. Design Feature in the MCR Figure. 1. The Layout Of The MCR Electrical Cabinet Return Vent Supply Vent eat Detector Desk Ignition Source The irregular geometry and layout of the referenced MCR are presented in Figure 1. The wall and ceiling are constructed out of concrete while the floors are constructed out of gypsum board. There are many electrical cabinets with lots of cable bundles in the MCR. During normal and emergency operations in the nuclear power plant, the volume flow rate of supply air to the MCR is 6 m 3 /s, while the volume flow rate of exhaust air from the MCR is 2 m 3 /s. The total number and the total area of these supply vents are 6 and 2.16 m 2, and those of the return vents are 2 and 2m 2. The door is assumed to be closed during the whole fire simulation. In this study, the location of operators in the MCR was assumed to be between two desks, and fire ignition was modeled m below top surface of the ignited electrical cabinet. Figure. 2. Fire Modeling For The MCR

Figure 2 shows the fire model by using CFAST. According the characteristics of irregular geometry, the referenced MCR was subdivided into three fire compartments. By coupling Latin ypercube sampling and the software-cfast, output parameters, such as layer temperatures, layer heights and optical densities in different fire scenarios were collected. All these output parameters were used to determine the abandonment probability and abandonment time. Additionally, heat detectors activation time were collected to determine how this output parameter is affected by response time index and activation temperature. 2.2. Input Parameters And Assumptions Table 1 shows distribution characteristics of input parameters for CFAST. In this study, heat release rate, soot yield, activation temperature and response time index were selected as input parameters used for uncertainty analysis, since these input parameters associate directly with fire intensity, fire products and fire detection time and operators habitability in the MCR, which are most important elements for fire simulations by using CFAST. Apart from that, other input parameters associated with fire combustion for CFAST fire simulations are presented in Table 2. Table. 1. Distribution Characteristics Of Input Parameters For CFAST Parameter Distribution Parameter1 Parameter2 eat Release Rate [4] Gamma α= β=216 Soot Yield [5] Gamma α=2.375 β=47 Activation Temperature Normal μ=80 σ=10 Response Time Index [6] Normal μ=5 σ=3 2.3. Abandonment Criteria Table. 2. Input Parameters Associated With Fire Simulation Parameter Value Effective fuel formula C 2 4.5Cl eat of combustion 28300kJ/kg CO yield 340kg/kg Radiative fraction 5 As mentioned above, abandonment probability and time should be considered when it comes to fire scenarios in the MCR, and it is critical to determine abandonment criteria when analyzing abandonment time. Generally speaking, the criteria are determined by layer temperature, visibility, or toxic gas concentration in the MCR. In this study, they were determined by the guidelines presented in NUREG- 6850 and NUREG-0700. According to NUREG/CR-6850, the temperature criterion for abandonment is 95 degree centigrade, which leads to radiant flux exceeding 1 kw/m 2, the minimum heat flux for pain to skins. owever, if the smoke layer were to immerse an operator, the exposure temperature thresholds are between 50 degree centigrade and 80 degree centigrade according to NUREG-0700. Conservatively, 50 degree centigrade would be appropriate temperature criterion when the smoke layer in the MCR immerses an operator (average height of operators in the MCR is assumed to be 6 ). According to NUREG/CR-6850, the visibility abandonment criterion for the MCRs is based on the optical density, and operators are forced to have to abandon the MCR for the sake of their safety when the optical density in the MCR is equal to or greater than m -1. In this study, the layer temperature, layer height and optical density in the MCR were collected and analyzed to determine whether operators should abandon the MCR and when operators are forced to abandon the MCR for the sake of their safety and health.

3. RESULTS 3.1 Abandonment Time Figure. 3. Abandonment Probability Based On Abandonment Criteria Probability Non-abandonment Abandonment The abandonment probability based on abandonment criteria is presented in Figure 3. The proportion of fire simulation cases where operators are forced to abandon the MCR for the sake of their safety and health is 74 %, while in only 26% of fire simulation cases it is not expected to do harm to operators safety and health according to the abandonment criteria, thereby operators unnecessarily abandoning the MCR. Figure. 4. Cumulative Probability And Complementary Cumulative Probability For Abandonment Time Cumulative Probability 0 200 400 600 800 1000 1200 1400 1600 Time /s Cumulative probability and complementary cumulative probability for abandonment time are presented in Figure 4. The -quantile for complementary cumulative probability curve is around 220 s, which can be seen as the abandonment time and conservatively used for Fire Probabilistic Safety Assessment in nuclear power plants. 3.2. Activation Time Cumulative probability and complementary cumulative probability for heat detectors activation time for fire simulations are presented in Figure 5, and the -quantile for complementary cumulative Complementary Cumulative Probability

probability curve in this figure is around 1240 s, which is way longer than the abandonment time from fire simulation results. Figure. 5. Cumulative Probability And Complementary Cumulative Probability For eat Detector s Activation Time Cumulative Probability 1200 1300 1400 1500 1600 1700 1800 1900 2000 Activation Time /s The relation among RTI, activation temperature and activation time is presented in Figure 6. The activation time increases with RTI and activation temperature increasing. In order to get accurate activation time from fire simulation, determining accurate RTI and activation temperature for fire simulation is necessary and important. Figure. 6. Relation Among Response Time Index, Activation Temperature And Activation Time Activation Time /s 2100 2000 1900 1800 1700 1600 1500 1400 1300 1200 3.3. Non-suppression Probability ActivationTemperature1 ActivationTemperature2 ActivationTemperature3 ActivationTemperature4 ActivationTemperature5 Complementary Cumulative Probability 65 70 75 80 85 90 95 RTI /(m s) In real fire scenarios, automatic suppression systems are possibly used to suppress fire and operators can also take some actions to prevent fire propagation, which means that there is the possibility that the fire is suppressed before targets are damaged. In Fire Probabilistic Safety Assessment, the probability of non-suppression is an estimate of the overall likelihood that given a fire scenario in the postulated fire ignition source, the damage to the target set will occur before the fire is finally suppressed. According to NUREG/CR-6850, the non-suppression probability can be calculated by the following equation: NS(t) = e λt (2)

where λ is the suppression rate constant and 3/min was used for the MCR fire in this study. t is the time from fire ignition to operators abandoning the MCR for the sake of their safety. In this study, t was assumed to be the abandonment time from fire simulation results and time used for fire detection in early phase was not considered in this paper. Figure. 7. Relation Among eat Release Rate, Soot Yield And Non-suppression Probability The relation among heat release rate, soot yield and non-suppression probability is presented in Figure 7. The relation is the reflection of how heat release rate and soot yield affect values of non-suppression probability. Non-suppression probability gradually increases with heat release rate and soot yield increasing, which means that the bigger values of heat release rate and soot yield are, the more difficult suppressing fire is. 4. CONCLUSION By coupling Latin ypercube Sampling and CFAST, this paper did uncertainty analysis for input parameters of electrical cabinet fire simulations. The sampling data not only quantitatively reflect how these input parameters affect output results, reminding analysts of the importance of parameters associated with fire combustion during fire simulations, but also help determine the abandonment time and abandonment probability for Fire Probabilistic Safety Assessment. eat release rate and soot yield are the most important factors associated with fire combustion for fire simulations, and can lead to the MCR s inhabitability. Abandonment probability is 74 %, which means that in most cases layer temperature and optical density will threaten operators habitability in the MCR and operators are forced to abandon the MCR for the sake of safety. The -quantile for complementary cumulative probability curve is around 220 s, which can be conservatively used for abandonment time in Fire Probabilistic Safety Assessment. Besides, heat detectors activation time is heavily affected by activation temperature and response time index, and constantly increases with both activation temperature and response time index rising. The non-suppression probability increases with heat release rate and soot yield increasing in the MCR fire scenarios, which means that analysts are expected to be careful when selecting appropriate input parameters, especially those associated with fire combustion, for fire simulation by using CFAST. The reasonability of the fire simulation model and how the size of sampling affects statistic results are supposed to be considered further. Dividing the MCR into many compartments instead of taking the MCR as the whole compartment for fire scenario simulations might be more accurate and appropriate in terms of output results. Additionally, the effect of toxic gases on operators habitability in the MCR was not analyzed in this paper. It is reasonable and sensible to consider toxic gases in fire simulations in the future.

Acknowledgements The author would like to thank the Science and Technology on Reactor System Design Technology Laboratory of Nuclear Power Institute of China for financial support of this work. References [1] Zhong Shan. Abandonment Times Evaluation of Main Control Room at Baya Bay Nuclear Plant [C]. 11 th International Probabilistic Safety Assessment and Management Conference & the Annual European Safety and Reliability Conference. Finland: 2012. [2] CFAST-Consolidated Fire and Smoke Transport (Version 7) volume 1: Technical Reference Guide [M]. Gaithersburg: National Institute of Standards and Technology, 2015. [3] Michael D. Shields, Jiaxin Zhang. The generalization of Latin hypercube sampling [J]. Reliability Engineering and System Safety, 2016, 148: 96-108. [4] EPRI, NRC-RES. NUREG/CR-6850 EPRI/NRC-RES Fire PRA Methodology for Nuclear Power Facilities Volume 2: Detailed Methodology [R]. U.S. Nuclear Regulatory Commission and Electric Power Research Institute, 2005. [5] Tom Elicson, Jim Bouchard, eather Lucek, Bentley arwood. Calculation of Fire Severity Factors and Fire Non-Suppression Probabilities for a DOE Facility Fire PRA [C]. ANS PSA 2011 International Topical Meeting on Probabilistic Safety Assessment and Analysis. Wilmington: ANS, 2011. [6] Jia Jia. Study on Assessment Methodology of Ship Fire survivability [D]. efei: University of Science and Technology of China, 2014.