LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

Similar documents
LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL

DMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual

LEAKSTOPPER RANGE Multizone water leak detection systems

LEAKSTOPPER 1 Single zone water leak detection system

21-light Remote Annunciator. Owner s Manual

Installation, Operating and Maintenance Manual

Gas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1

Excel-EN Conventional Fire Control Panel

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

GAS SUPRESSION CONTROL PANEL:

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Intelligent Security & Fire Ltd

USER MANUAL FOR OPERATING SYSTEM

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

QA16 Addressable System

Flostop TS D7E and A8E. Operation Manual

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Carbon Monoxide Transmitter

Introduction. OM-THA2

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

MPC-6000 / MPC-7000 / RND-2

THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free

Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Leak Detection and Flood Prevention

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

TECHNICAL DATA OBSOLETE

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

SMARTWALK DEMENTIA WANDERING SYSTEM

Entero Voice Alarm system.

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

U ser's Guide PC6010

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. SIL1 reliability. Gas Detection Control Panel

Multi-Gas-Controller MGC2

Rig Protector. Multipoint Critical Gas Detection and Monitoring System

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

Entero Voice Alarm system. User guide

Halton SAFE / 7.14 user guide and installation instructions

Flopurge TS. Operation Manual

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

Two-Channel Gas Controller

PERMACONN PM1030 Includes DI300. Installation Manual

ACP10 & ACP50 Security Systems

Product Manual SZ1145

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

Conventional Fire Alarm System 2014 V1.2

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

AquiTron. AT-LDM Liquid Detection Module INSTALLATION INSTRUCTIONS

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

P2267 NETWORK INTERFACE

Application, Installation, Operation & Maintenance Manual

OPERATION AND INSTALLATION MANUAL

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

QUICKFIT INSTALL HOOK-UP SHEET FOR ESL KIT REV 1.17 OP

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RE 102 RE Fire Alarm Control Panel. Installation, Commissioning & Operating Manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Product Manual SZ1144

Flair 500 Series Annunciators

ORENA BRAND CONVENTIONAL (ORENA Brand) CE

FEC400 Series. Installation Manual

LMS-188-4P-BMS 4 POINT DIGITAL MONITOR/ALARM WITH PROTOCOL CONVERTER OPERATING INSTRUCTIONS

Intelligent addressable fire alarm control panel

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

Noby-448 User Operating Manual & Log Book Page 1 of 12. Fire Control Panel. User Operating Manual & Log Book

TrueAlarm Fire Alarm Controls

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

MODEL 5100 VOTING LOGIC MODULE

Operation and Maintenance Manual

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

Pump-Down Controller MODEL 4052

Detection, Protection, Innovation

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

Variable Frequency Drive SERIES MP800 VFD

DESCRIPTION INSTALLATION

2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections.

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date:

Installation Manual Premier 412/816/832. Issue 10

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

Features. Omni2 Door Warning Sign Alarm Annunciator DATASHEET. Model C1190B Door Warning Sign

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

Smart Combiners Installation Guide. For Obvius A89DC-08 sensor modules

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

Ç Consilium Consilium US, Inc. 59 Porter Rd Littleton, MA USA

Safety Instructions MS 10B ALARM UNIT MS 10B ALARM UNIT. Used symbols. Always observe this information to prevent damage to the device

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Instruction Manual WARNING

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

PTE0705 Electric Fence Monitor

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

Transcription:

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL The LeakMonitor alarm panel is a microprocessor controlled fully adjustable alarm system suitable for multizone monitoring of sensor cable or distance monitoring depending on what outstation version is used. The Addressable alarm panel can monitor many different sensors including sensor cable (which senses water along its entire length). It can also monitor pads and probes, gas, temperature, oil, heat and smoke sensors as well as overflow sensor probes. Fault monitoring continuously monitors for breaks in continuity on the cables Green - All OK / Red - Fault Detected Alarm status light Off - All OK Red - Leak Detected (one per zone) The LeakMonitor interrogates addressable outstations situated in appropriate areas and reports back the location of the leak. The microprocessor controlled addressable alarm panel can simultaneously monitor all alarms and faults and log them chronologically in the memory. The LeakMonitor alarm panel is provided with output signalling relays to provide remote alarm and BMS connection for alarms, faults and power/battery fault. The unit comes with a battery backup and the control panel has been designed to be wall mounted and requires a 240V AC 2 amp power supply. Connections are direct to the Main PCB via easy wire un-pluggable terminal connectors the LeakMonitor leak detection system complies with class 3K5 of EN 60721-3-3:1995. The LeakMonitor provides continuous monitoring of the cabling system and provides a fault readout if the integrity of any cable is found (pulled apart or damaged). It also provides an outstation fault readout in the event of a data communication issues. The LeakMonitor control panel comes with audio output and mute button, a four-line LCD display, an alarm LED, a fault LED, mains fail and power healthy lights. It works on RS485 Protocol requiring the data cable to be continuous linear wiring with a maximum run of 3000 metres. The Alarm Panel is a fully electronic system with few moving parts and will not require any specific regular maintenance, the same applies to the outstations. The sensor cable is however, susceptible to site conditions and good housekeeping practices need to be observed. It is recommended to keep the cables free of contamination which could lead to false alarms. Power On Green - ON Power Off No Light Helpline Telephone: 0330 1595933 UserManual - LeakMonitor V1.0 Mains Fail Red - ON (fail) Power OK No Light Mute Button (press to silence the audio alarm) Further information is available on our website

3.0 The Outstation 1.0 Technical Specification Sensor or Outstation Fault Relay Alarm Detected Relay New Alarm Detected Relay Power Fault Relay Sounder level System operating Voltage Mains Fuse Battery Fuse 12 V supply Output Battery Backup System memory Battery LCD Alarm LED Fault LED Power Fault LED Power LED End Of Line Connector Dimensions 230Vac 8 amp change-over contacts DPDT 230Vac 8 amp change-over contacts DPDT 230Vac 8 amp change-over contacts DPDT 230Vac 2 amp change-over contacts SPDT 80db @ 10 cm oscillating tone 230Vac to 110 Vac self sensing SMPS 10 watt max 2 amp quick blow 20mm 1 amp quick blow 20mm 500 ma quick blow 20mm 2v 1.2Ah run time standby 1 6 hours fully charged Battery 3v CR123A 10 year non recharge 20 x 4 Liquid Crystal Red 5 mm 2.2v when on alarm condition detected Yellow 5 mm 2.2v when on sensor fault detected Red 5 mm 2.2v when on a power fault detected Green 5 mm 2.2v when on system power is healthy 47 K ohm resistor no polarity L 200mm x H 150mm x W 100.00 2.0 Key Features The alarm unit will monitor up to 100 remote outstations connected via a twisted pair combined communications and low power cable. Each outstation can have up to four water sensors connected. The unit will sound an alarm if: Ÿ Any sensor becomes faulty (either disconnected broken) Ÿ Any sensor detects a leak (alarm threshold is adjustable) Ÿ Any outstation fails to communicate Ÿ Power to the alarm system fails. In addition the unit will operate one of three relays to provide signals to other equipment. All alarm events are displayed on the Alarm Screen and all alarms and events are saved to memory. When an alarm or fault is detected the location of the occurrence is reported via the LCD screen. The sounder will sound if it is an alarm and the relevant fault or alarm relay will energise providing onward signalling. An alarm relay is standard and will reset when the mute button is pressed to silence the sounder. This stops nuisance alarms and prevents the system becoming congested with alarms. To clear the fault or alarm the problem must be rectified for example if it is a leak the cause needs to be fixed and the sensor dried. Modbus TCP/ip and RTU for onward signalling to building management systems are available as an option. Each outstation has 4 zones of detection as well as 2 x 8 amp 230v ac relays for local switching of valves, pumps etc. Every outstation has a unique address from 1 to 100, set via on board micro switches. This gives the possibility of 400 zones (areas) that can be monitored simultaneously. It is recommended that the sensor length is no greater than 50 metres. All alarms are kept in a log file. The alarm log screen shows the alarms and events that have occurred. The full list can be viewed by scrolling up or down on the keypad. The sensor status can be viewed manually in the view sensor menu, this can be a handy feature if a particular sensor is giving spurious alarms. Sensors have full sensitivity adjustment via the set points menu offering great flexibility to suit most environments. A distance monitoring outstation can provide the location of the leak and report where along the sensor cable the leak has occurred. RS232 LISTENING PORT ADDRESS SWITCH Rs485 INPUT 0v 12-24v input A -V +V B 0v -V +V A B RS485 LISTENING PORT SENSOR 1 SENSOR 3 Relay On Led Indicator SENSOR 4 SENSOR 2 RELAY 1 N/O COM N/C RELAY 2 N/O COM N/C Note: Sensor inputs are not polarity conscious Outstations require 12 to 24 VDC to operate (this can be taken from the LeakMonitor alarm panel) and all terminals are unpluggable for easy wiring connections. Relays 1 and 2 are rated at 230VAC 8 amps and have dry change over contacts (these are only fitted if ordered as an option). Relay 1 switches when sensors 1 or 2 detect a leak and relay 2 switches when sensors 3 or 4 detect a leak. Each outstation has four channels (zones) designed to monitor sensors using an open contact. An end of line resistor (47K ohms) must be fitted at the end of each zone. This is used as a reference that the sensing circuit is being completed. By shorting out the sensing circuit (water on the sensor) an alarm occurs and should detection of the resistor be lost (e.g. cable break) a fault appears on the main control panel.

3.1 Examples of setting the outstation unique address number Outstations must be addressed numerically with a unique address manually selected using the 8 way switch. This is required so that the LeakMonitor control panel can identify which outstation is located in what area. When all 8 switches are set in the off position, the outstation is OFF. To set a unique address the switches need to be moved to the on position. The order in which they are switched relates to the identification of the particular outstation. the switches are labelled 1 to 8 and each has a value as follows: 1 = 1 2 = 2 3 = 4 4 = 8 5 = 16 6 = 32 7 = 64 and 8 = 128. To set the unique address for an outstation the correct combination of switches need to be turned to the ON position. Example 1: To set an outstation as number 3, switches 1 and 2 will need to be ON Example 2: To set an outstation as number 9, switches 4 and 1 will need to be ON Example 3: To set an outstation as number 33, switches 6 and 1 will need to be ON below shows how to set outstations from 1 to 6 to have the correct address: has the unique address number 1. This is achieved by switching switch 1 to ON. All other switches are left in the OFF position. has the unique address number 3. This is achieved by switching switch 1 and 2 to ON. has the unique address number 2. This is achieved by switching switch 2 to ON. All other switches are left in the OFF position. has the unique address number 4. This is achieved by switching switch 3 to ON. All other switches are left in the OFF position. has the unique address number 5. This is achieved by switching switch 1 and 3 to ON. has the unique address number 6. This is achieved by switching switch 2 and 3 to ON. has the unique address number 24. This is achieved by switching switch 4 and 5 to ON. has the unique address number 96. This is achieved by switching switch 6 and 7 to ON. has the unique address number 20. This is achieved by switching switch 3 and 5 to ON. has the unique address number 128. This is achieved by switching switch 8 to ON. All other switches are left in the OFF position.

Number Outstation Location Zone 1 Location Zone 2 Location Zone 3 Location Zone 4 Location Please use this page to record the location of each outstation and the corresponding locations of the zones coming from the outstation. Should you require more locations, please copy this sheet for outstations 50 to 100

4.0 LeakMonitor Main Alarm Panel Connections MAINS POWER FAULT RELAY The mains power fault relay operates on the loss of mains power. The contacts are rated at 240VAC and can switch loads up to 2amps This relay has 1 set of volt free change over contacts. FAULT ALARM DETECTED RELAY RS485 Data Output Outstation Voltage Output The fault alarm detected relay will energise when any fault condition has been detected. The relay will self reset once the fault has been cleared. The contacts are rated at 240VAC and can switch loads up to 8amps This relay has 2 sets of volt free change over contacts. GENERAL INFORMATION SYSTEM FUNCTIONS The addressable alarm system constantly monitors its sensors for signs of leaks before they become serious. The Alarms are then displayed on the LCD display loca6ng which sensor in which area has a poten6al problem. On detection of an alarm, a soft audible pulsing sounder is activated to alert personnel to its status. Internally 2 relays will energise, one is called alarm detected and the other is called new alarm. These are for onward signalling to a BMS or for shutting off valves, turning on pumps or telephone diallers etc. 230VAC Mains Input L/E/N Fault Relay Leak Alarm Relay New Leak Alarm Relay Power Fault Relay NEW ALARM DETECTED RELAY The new alarm detected relay will energise when any new leak alarm condition has been detected. The relay will self-reset once the mute button has been pressed. This relay is to allow the user to externally monitor up to date alarm conditions. This relay is rated at 240 Volts AC and can switch loads up to 8 amps This Relay has 2 sets of volt free change over contacts LEAK ALARM DETECTED RELAY The fault relay will energise when a fault condition has been monitored. The relay will self-reset once the fault has rectified. This relay is rated at 240 Volts AC and can switch loads up to 8 amps This relay has 2 sets of volt free change over contacts. WHEN AN OUTSTATION DETECTS A LEAK When an alarm is detected on the system, the horn will sound, the alarm LED will flash red and the LCD display will report which area the alarm is in. Internally 2 relays will energise: New Alarm Detected & Leak Alarm Detected. Pressing the mute button will silence the horn and also tell the system that someone has acknowledged the leak. Once the sensor has dried the system will automa6cally reset and will now be ready to detect a leak again. If the mute button is not pressed the system will report an alarm un6l it has acknowledgement. pressing the mute button gives the system acknowledgement and only then will the system self-reset. NOTE: Sensors must be kept clean and free from debris to maintain full working ability. WHEN AN OUTSTATION REPORTS A FAULT When a system fault is detected on the system the Faults LED will flash and the LCD display will report which area the Fault is in and the nature of the fault. Internally the Fault Relay will energise. The fault will stay on the system until the fault is rectified then will self-reset. Faults are usually Sensors disconnected or the system is unable to interrogate the outstation It is best to telephone the supplier who will be happy to talk to help & explain the nature of the fault. MAINS POWER FAULT When a Power Fault is detected The green LED will turn off and the Mains Power Fault Red LED will turn on. This is not reported in the display and does not activate the sounder. Internally a relay will energise called power fault detected. This is used for onward signalling. The system will self-reset when the power is restored. BATTERY BACK UP When a Power Fault is detected The battery will automatically power the panel for up to 8 hours. The battery is float charged internally and should be replaced every 3 years.

/ Date: NO Have all the sensors been connected? Do each of the zones go into alarm? Does the mute function work? Does the alarm test work? Are there any visual defects? Are there valves connected? If yes, do they switch the water off when the panel goes into alarm? NO NO (please note any defects in the additional information area) Signature: Name: Company: Date: Client Representative (we accept that the system described has been tested and commissioned and is in proper working order): Signature: Name: Company: Date: Testing Engineer Additional Information: Is there power to the alarm panel? System Setup: Number of Zones: Type of Sensor/s Fitted: Location of the Alarm panel: Serial Number: Alarm Panel Name: System Details: Job Reference Number: Name of the Commissioning Engineer: Site Address: Name of the Site: Contact Details: Commissioning Sheet

Helpline Telephone: 0330 1595933 User Manual - LeakMonitor V1.0 Further information is available on our website