Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions

Similar documents
solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem

Experimental Investigation on Vapour Pressure of Desiccant for Air Conditioning Application

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

Regenerator Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

A Statistical Analysis of a Liquid Desiccant Dehumidifier/Regenerator in an Air Conditioning System

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Feasibility Analysis of Regeneration of Silica Gel Used in Dehumidification Process of Air Conditioning by the Condenser Waste Heat of Air Conditioner

EXPERIMENTAL STUDY OF COUNTER FLOW AIR DEHUMIDIFIER FOR DIFFERENT PACKING HEIGHTS

A study of tea leaves drying using dehumidification process and regeneration of liquid desiccant in a closed-cycle dehumidification-humidification

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Study on an Air-Side Heating Source Liquid Desiccant Regeneration Model

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Optimization of Moisture condensation rate of Liquid Desiccant Dehumidifier through Genetic Algorithm

Experimental Investigation of the Padding Tower 1. for Air Dehumidifier

Performance of non-cfc refrigerator driven by chilled water from 35 kw LiBr/H2O solar absorption cooling system

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device

CHAPTER 2 LITERATURE REVIEW

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Experimental Performance of Solar Collector cum Regenerator for Coupling with a Liquid Desiccant Cooling System

A Liquid Desiccant System for Solar Cooling and Dehumidification

Potential and Simulation of Open-Cycle Solar-Assisted Climatisation-Plants in Single-Family-Houses

Chapter 10. Refrigeration and Heat Pump Systems

Performance evaluation of a liquid desiccant solar air conditioning system

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Performance analysis of a liquid desiccant evaporative cooling airconditioning system powered by solar energy

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Experimental Analysis on Chemical Dehumidification of Air and Desiccant Regeneration with H2O/LiCl Solution

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Performance of the Cross Flow Regenerator Used in Liquid Desiccant Dehumidification.

GAS FREE REFRIGERATOR USING PELTIER MODULE

Performance Analysis of a Solid Desiccant Air Dehumidifier

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

Variable far infrared radiation (VFIR) technique for cubic carrot drying

CLOVER DRYING PROCESS BY FORCED CONVECTION

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer

Desiccant cooling systems: a review

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

DESIGN AND FABRICATION OF A PORTABLE REFRIGERATOR BASED ON PELTIER EFFECT

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Design and Experimental Studies on Modified Solar Dryer

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Experimental Investigation to Assess the Performance of Desiccant Integrated Chilly Dryer

Thermodynamics II Chapter 5 Refrigeration

Recent Advances in Energy, Environment and Economic Development

International Journal of Advance Research in Engineering, Science & Technology SOLAR HUMIDIFIER

The Primary Research on Liquid Desiccant Dehumidifier With Cooling Capacity Using Compression Heat Pump System

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

An Experimental Study on Evacuated Tube Solar Collector for Heating of Air in India Avadhesh Yadav, V.K. Bajpai

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air

Experimental Efficiency Investigation on Heat Recovery System Used in a Solar-Powered Desalination Process

ANALYSIS OF DESICCANT COOLING SYSTEM

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

K.F. Fong *, C.K. Lee, T.T. Chow

Chapter 11 REFRIGERATION CYCLES

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Heyam Daod. Keywords Fine-grained soils, liquid limit, microwave drying, moisture content

CHAPTER 1 INTRODUCTION

Desiccant Cooling with Solar Energy

Compressor Explosion Accident at Pump-Down of Air Conditioners

Corn drying experiments by pilot dryer

Preliminary Findings on the Performance of a New Residential Solar Desiccant Air-Conditioner

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

ISSN: [Ghatol* et al., 6(12): December, 2017] Impact Factor: 4.116

EXPERIMENTAL PERFORMANCE ANALYSIS OF SOLAR AIR HEATER WITH THREE DIFFERENT MODIFICATIONS IN ABSORBER PLATE

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER

The Effect of Quantity of Salt on the Drying Characteristics of Fresh Noodles

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Access from the University of Nottingham repository: %20paper_v8.

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Australian Solar Cooling Interest Group (ausscig) Conference

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

EXPERIMENTAL INVESTIGATION OF VAPOUR ABSORPTION SYSTEM

COOLING SYSTEMS FOR CONTINOUS GALVANIZING LINE Miroslav Raudensky a, Milan Hnizdil a, Jaroslav Horsky a, FrédéricMarmonier b

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Chapter 11 REFRIGERATION CYCLES

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

Transcription:

International Conference on Renewable Energies and Power Quality (ICREPQ ) Cordoba (Spain), th to th April, 0 exçxãtuäx XÇxÜzç tçw céãxü dâtä àç ]ÉâÜÇtÄ (RE&PQJ) ISSN 1-03 X, No., April 0 Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions S. Bouzenada 1, T. Salmon, L. Fraikin 3, A. Kaabi, A. Léonard. 1, Department of Climatic Engineering, Faculty of Engineering Sciences, University Constantine-Algeria Corresponding Author: bouzenada_@yahoo.fr (Saliha Bouzenada),3, Department of Applied Chemistry, Laboratory of Chemical Engineering, University of Liège, Belgium Abstract. This paper experimentally studies the mass transfer during the dehumidification/regeneration operation using the hygroscopic material calcium chloride and calcium chloride dehydrate as desiccant. These desiccants are compared on the basis of the same operation conditions. According to the analysis of heat and mass transfer processes, the key influencing factors are relative humidity and regeneration temperature. It can be observed that the CaCl.H O is more rapidly diluted than the CaCl at the same time during dehumidification, while the CaCl solution can be more dried than CaCl.H O solution during regeneration. Then the CaCl is able to absorb more moisture in the cycle of LDCS system. Also, the obtained experimental results can help to select liquid desiccant. Key words: Mass transfer, Liquid desiccants comparison, Solar desiccant cooling system. 1. Introduction In recent years ozone layer depletion green house effect gases have increased due to the use of the halogenated chlorofluorocarbons (CFC) and hydrochlorofluorocarbons (HCFC) which have been used in the refrigeration and air-conditioning industry. The search for new refrigerants and the adaptation of the existing systems to the alternative refrigerants have created considerable research activities. Growing demand for air conditioning has caused a significant increase in demand for energy resources. Solar powered cooling is one of the environmentally friendly techniques which may help alleviate the problem. Conventional closed cycle require heat source temperatures that are significantly higher than the temperatures of corresponding heat sinks. Thus, they have to be operated with high grade heat extracted from natural gas, steam, concentrating solar collectors. With dramatic climatic changes in recent years, demand for research concerning cooling systems with solar dehumidification is significant. The application of solar energy in cooling systems can reduce energy demand and decrease the use of theses gases (CFC, HCFC). The focus of the directive is on the reduction of environmental impact through changes in product design. The use of liquid desiccants in an open cycle system is a promising solution for solar assisted airconditioning. A possible concept for this system is shown in Fig. 1. The area marked in green represents the air-conditioning system; yellow indicates the solar thermal system and blue the building. Fig. 1: Design of a solar driven liquid desiccant airconditioning system (M. Krause) [1]. The main components of this air conditioning open system are the absorber and regenerator. In the absorber, moisture absorbed from the process air stream dilutes the desiccant solution by loading the desiccant with water vapour. The solution weakened by absorption of moisture is re-concentrated in the regenerator, where it is heated. The heat drives out the moisture and the strengthened solution is returned to the dehumidifier. Liquid desiccant is the salt solution in water and lithium bromide, tri-ethylene glycol, lithium chloride, and calcium chloride are some types of these salt solutions. https://doi.org/.0/repqj. RE&PQJ, Vol.1, No., April 0

Dehumidification using a chemical desiccant was proposed by researchers as a potentially good method to remove the latent load. Compared to solid desiccant systems, liquid desiccant systems are more efficient, easy to install, and have low maintenance costs. The idea of using a liquid chemical substance (desiccant) for dehumidification was first applied to industrial processes in the early 130s. Kathabar [] produced the first cooling and dehumidifying desiccant system in 13 for a large central system used for an industrial plant. Several studies have been conducted on the mass transfer in operation of the liquid desiccant dehumidification/regeneration. Al-Farayedi [3] studied the heat and mass transfer between air and liquid desiccant in a gauze type structured packing tower. Three different types of liquid desiccants are compared. It was found that the mixture of calcium chloride and lithium chloride has a significant increase in the mass transfer coefficient compared with the other two solutions. Mass transfer rate studies were conducted by Li Zhang [] and dimensionless mass transfer coefficient correlations were obtained for a packed column dehumidifier/regenerator using lithium chloride solution as a liquid desiccant. It was found that, when the air velocity increased from 0. to 1. m/s, the overall mass transfer coefficient in the structured packing dehumidifier and regenerator varied from.0 to. g/m²s and from.0 to. g/m²s, respectively. The study presented by Jaradat [] designed a plate type cross-flow desiccant based on heat and mass exchanger, built and evaluated as an adiabatic and non-adiabatic absorber and regenerator. The experimental results of supply air dehumidification and cooling show an effective air dehumidification and cooling. The reduction in the supply air humidity ratio, ω could reach. g/kg and a reduction in the supply air temperature, T of 3. K. Desiccant regeneration was possible by using hot water with a temperature started from - 0 ºC, which suit flat plate solar thermal collectors. In the present study, experimental equipment is setup for dehumidification/regeneration process. The effects of air parameters on mass transfer of two desiccants are experimentally investigated and analyzed. The results of calcium chloride are compared with those of calcium chloride dehydrate. The experimental results can help in the choice of liquid desiccant.. Instrumentation and experimental study The layout of the experimental setup and photograph of the apparatus are shown in Fig.. The Conditioning Drying Oven equipment type Memmert HCP, with the good overall accuracy was used during absorption and regeneration process. This apparatus includes thermocouples for measure air temperature and relative humidity. The air flow rate is controlled by a valve. The specifications of instrument are listed in Table 1. Table 1 Specifications of Conditioning Drying Oven Type MEMMERT HCP Temperature From C to 0 C Relative humidity From 0 % to 0 %. Initially, the air flows over the surface area of the thin layer of desiccant and becomes in direct contact with this desiccant. The air is introduced horizontally into the Conditioning Drying Oven apparatus; and uniformly distributed over its whole surface to achieve the flow conditions while the desiccant solution is placed on plate inside of the apparatus. Fig.. Conditioning Drying Oven Different experimental tests were carried out. The Calcium chloride desiccant and Calcium chloride dehydrate were used as desiccant. When the partial vapour pressure of process air is higher than that of the desiccant solution at the interfacial area, the moisture of air is then absorbed into the desiccant solution a dehumidification process occurred. On the other hand, when the partial vapour pressure on the air side was lower than that on the desiccant side, a desiccant regeneration process occurred. 3. Measurements Totally, 1 experimental runs were conducted with four test sequences for dehumidification/ regeneration process. The ranges of operating conditions used in dehumidification are presented in Table. All data measurements are made where each of them, the climatic conditions were maintained constant. All these data are collected during several days with a time interval of 30 minutes at each test. The measured air and desiccant parameters are used to analyse the process. https://doi.org/.0/repqj. RE&PQJ, Vol.1, No., April 0

A fixed quantity of desiccant was placed on a plate into the Conditioning Drying Oven apparatus. In the dehumidification process the moisture is directly removed from the air by absorbing the moisture by using a strong solution of liquid desiccant. At the surface of plate, moisture absorbed from the process air stream dilutes the desiccant solution by loading the desiccant with water vapour. Table - Experimental measurements: Conditioning Drying Oven Parameter Range Accuracy Air temperature for absorption 0 to C + 0.1 C Relative humidity to 0 % Mass initial of dry salt 0.1 to 0 g + 0.001 g Exchange surface diameter. 1 cm Table 3 summarizes the experimental sets; each set consists of four test runs. Experiments are conducted to measure the moisture transfer from air to desiccant during the absorption process. Measurements are carried out at nearly constant ambient conditions. Table 3: Summary of the operation conditions for air dehumidification Quantity Exchange Air Relative of area Temperature humidity desiccant diameter C % g cm Test 1 0 Test / Test 3 0 3 0.1 Test 0. - An air stream called regeneration air flows through the dilute solution placed into the Conditioning Drying Oven equipment. After, the desiccant solution reaches its suitable regeneration temperature. By this way, the strong solution is then ready to be concentrated and maintained a continuous dehumidification process. Experimental runs were conducted with heating air temperature of 0 0 C, relative humidity 0 3 %, and air flow rate is constant.. Results and Discussion Experimental runs have been conducted with different parameters. The principal process of the experimental runs is mass transfer between air and desiccant in dehumidification/regeneration tests in order to compare these two desiccants. Samples of the experimental results, at constant values of air parameters are presented to illustrate the transfer of moisture between the air and desiccant. The mass transfer is the core of dehumidification/regeneration process. As shown in fig. 3(a), the mass increases when the Cacl absorbs moisture from air and Fig. 3(b) illustrates the regeneration process when desiccant releases moisture. It can be seen that the mass transfer potential decreases with time. This is mainly due to the decrease in vapour pressure on the desiccant surface, during regeneration, and due to vapour pressure rise on the desiccant surface during absorption. - CaCl - CaCl 0 1 1 1 1 1 3 1 1 1 1 0-1 0 1 3 1 0 Time [h ] D e s u m idific a tion T = 0 C, H r= % d = c m Fig. 3 (a). Absorption process Regeneration of CaCl T =0 C 0 1 0 Fig. 3 (b). Regeneration process To validate the results of mass transfer, an identical experiment was carried out with the same salt and under the similar operation conditions. Fig. (a) shows the reproducibility of the absorption process of CaCl, and Fig. (b) shows the reproducibility of the regeneration process of CaCl.H O, and it can be observed the same results, these curves are superimposed. Validation of absorption Test 1 Test 0 Fig. (a). Validation of absorption process https://doi.org/.0/repqj. RE&PQJ, Vol.1, No., April 0

of a yellow color at the surface of CaCl desiccant but for CaCl.HO the color of obtained liquid solution is white color Fig. (c, d). In addition, in the final phase of dehumidification process the CaCl is more viscous than CaCl.HO. 1 1 Validation of Regeneration Experience n 1 Experience n 0 Fig. (a): CaCl.HO Fig. (b): CaCl: absorption Fig. (b). Validation of regeneration process. 1. The effect of amount of desiccant - CaCl.HO The effect of increasing the initial quantity of desiccant during the absorption process at a fixed air temperature, air flow rate and exchange area is shown in Fig.. It can be clearly observed that a higher quantity of desiccant increases the potential mass transfer between the air and desiccant. In addition, this graph illustrates the evolution of the regeneration process as a function time for the same temperature and exchange area but for two initial masses of solution. It can be observed that the regeneration duration is shorter when the quantity of desiccant used decreases. 1 1 1 1 13 11 3 1 Fig. (c): CaCl Yellow color After absorbing, the diluted desiccant is through the solution into the plate. The salt solution swells during regeneration phase and yellow color was observed at the surface Fig. (e) and finally the desiccant became concentrated and it looks like a block of hard salt, Figs. (f, g). In addition, it can be pointed out that the CaCl.HO has become liquid before CaCl but during the regeneration phase it was observed the appearance of grain of salt CaCl before CaCl.HO. (,g) absorption ( g) absorption (,g) Draying (g) Draying 0 Fig. (d): CaCl.HO: white color Fig. (e). Swelling of desiccant Fig.. Effect of quantity of desiccant.. Comparison between two desiccants In order to compare desiccants CaCl.HO and CaCl the experiment for absorption/regeneration processes has been carried out, under the similar operating conditions. The following figures show the physical state of these two salts during these processes. It can be seen through Fig. (a, b) that the CaCl.HO is more rapidly diluted than the CaCl at the same time, in the absorption phase. On the other hand, it can be pointed out the appearance https://doi.org/.0/repqj. Fig. (f). Hard salt Fig. (g). Hard salt RE&PQJ, Vol.1, No., April 0

The comparison results of moisture removal express the mass transfer of the dehumidification and regeneration process, which is defined as the moisture variance of the air through these two desiccants. In the dehumidification experimental presented in Fig. (a) the absolute difference between these solutions is that the water absorbed by CaCl is higher then that absorbed by CaCl.H O, due to the presence of the water molecules (H O) in the latter desiccant. Therefore, the higher mass transfer potential will be the higher moisture removal rate in the same operating conditions. In the desiccant regeneration experiments, the desiccant is heated to the required temperature. The moisture from the desiccant was released when the desiccant came in contact with the regenerating air and finally the obtained desiccant is concentrated. The comparison of regeneration results at the same air flow rate and similar operating conditions are shown in Fig. (b). It can be observed that the CaCl solution can be more dried than CaCl.H O solution. Then the CaCl is able to absorb more moisture in the cycle of the LDCS system. In addition, Fig. (c) illustrates the comparison of regeneration in function of the effect of temperature. It can be observed that the CaCl is regenerated with less temperature 0 C compared with CaCl.H O which is regenerated at 0 C. Mass [mg] - DVS 3 1 0 1 0 0 0 0 0 0 0 0 CaCl CaCl.HO Fig. (a). Comparison of absorption 0 00 00 00 00 00 00 00 Time [min] CaCl.HO CaCl Fig. (b). Regeneration at 0 C 13 11 0 CaCl at 0 C CaCl.HO at 0 C Fig. (c). Regeneration at 0 and 0 C. Conclusion Conventional air conditioning using (CFC) and (HCFC) refrigerants and having high electrical consumption has a negative environmental impact. The present study aims to eliminate the environment negative impact by using liquid desiccants in the Liquid Desiccant Cooling System; and allows to select the best liquid desiccant according to its properties. One of them is an appropriate alternative for dehumidifying air and for the environment protection. The mass transfer of two liquid desiccants, CaCl aqueous solution and CaCl.H O aqueous solution, is compared in this paper, including both dehumidification and regeneration processes. The comparison basis of this study is the regeneration temperature, the relative humidity ratio, and the exchange area. At these operating conditions and from the analysis of the experimental data, the following conclusions can be summarized: (1) In the dehumidification process, the mass transfer potential of Cacl solution is better than that of CaCl.H O solution in the same desiccant mass flow rate condition due to water molecules present in the letter salt. () In the regeneration process, CaCl solution can be more dried than CaCl.H O solution, especially in the same operating conditions. Then the CaCl is able to absorb more moisture in the cycle of the LDCS system. (3) Increasing the air regeneration temperature increasing the mass transfer potential, while the period of process is reduced. References [1] M. Krause, W. Saman, K. Vajen. Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations. Renewables ANZSES (00). Sustainable Energy. [] Kathabar. Website http://www.kathabar.com avril 30, 003. [3] A. Al-Farayedhi, P. Gandhidasan, M.A. Al-Mutairi. Evaluation of heat and mass transfer coefficient in a gauze type structured packing air dehumidifier operating with liquid desiccant. Int. J. Refrig. (3) (00) 330 33. https://doi.org/.0/repqj. RE&PQJ, Vol.1, No., April 0

[] Ll Li Zhang, Eiji Hihara, Fumio Matsuoka, Chaobin Dang. Experimental analysis of mass transfer in adiabatic structured packing dehumidifier/ regenerator with liquid desiccant. International Journal of Heat and Mass Transfer 3 (0) 3. [] Jaradat Mustafa, Martin Mützel, Ulrike Jordan, Klaus Vajen. Solar thermal driven liquid desiccant dehumidifier/ regenerator for comfort airconditioning and industrial applications. Proceedings of International Conference on Solar energy for MENA region (INCOSOL). Amman, Jordan, -3 October (0). Paper Number: INCOSOL 3 https://doi.org/.0/repqj. 0 RE&PQJ, Vol.1, No., April 0