Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

Similar documents
Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers

Purdue e-pubs. Purdue University. Ian H. Bell Purdue University. Eckhard A. Groll Purdue University

Key words: heat exchanger, fouling, pressure drop

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

A Literature Review On Heat Exchanger Air Side Fouling In Heating, Ventilation And Airconditioning

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Purdue e-pubs. Purdue University

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners

Air-Cooled Heat Exchanger Performance for R410A

Low GWP Refrigerants for Air Conditioning Applications

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Design Optimization of Variable Geometry Microchannel Heat Exchangers

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Two-Phase Evaporation Pressure Drop Experimental Results for Low Refrigerant Mass Flux

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Control Method Of Circulating Refrigerant Amount For Heat Pump System

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Experimental Study on the Performance of Twisted Capillary Tube

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Efficiency of Non-Azeotropic Refrigerant Cycle

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Fifteen Years of Dehumidification Results from Heat Pump Water Heaters

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Heat Transfer of R-22 and Alternatives in a Plate- Type Evaporator

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Effect of Inclination Angle on the Air-Side Performance of Aluminum Parallel Flow Heat Exchangers Under Wet Conditions

Application of a hybrid control of expansion valves to a 3-ton large room cooling system

The Effects of Hydrophilicity on Water Drainage and Condensate Retention on Air-Conditioning Evaporators

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

System Using Exhaust Heat from Residential GHPs

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Performance Analysis of a Miniature-Scale Vapor Compression System for Electronics Cooling: Bread Board Setup

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Application of a Hybrid Control of Expansion Valves to a 5-ton Domestic Heat Pump

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Performance of CO2 Cycles with a Two-Stage Compressor

Virtual Refrigerant Pressure Sensors for Use in Monitoring and Fault Diagnosis of Vapor- Compression Equipment

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Manufacturing & Testing of Air-to-Refrigerant Heat Exchangers Based on 0.8mm Diameter Tubes

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Experimental Investigation of Purification Function of Air Conditioner

Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Sub-Critical Operation of the CO2 Expander/ Compressor

Performance Measurement of R32 Vapor Injection Heat Pump System

2. HEAT EXCHANGERS MESA

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Real Time Upright Freezer Evaporator Performance Under Frosted Conditions

Evaluation of Mechanical Dehumidification Concepts (Part 2)

Analysis of Fin-and-Tube Evaporators in No-frost Domestic Refrigerators

Evaluation of a Virtual Refrigerant Charge Sensor

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Heat Transfer Characteristics and Heat Exchanger Performances for R407C Using Herringbone Heat Transfer Tube

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

R32 Compressor for Air conditioning and Refrigeration applications in China

Investigation of Port Level Refrigerant Flow Mal-distribution in Microchannel Heat Exchanger

Refrigerant Mass and Oil Migration During Start-up Transient

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Investigation of Evaporator Performance with and without Liquid Overfeeding

The Use Of Attic Space For Cooling and Dehumidification

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Transcription:

University of Nebraska - Lincoln DigitalCommons@University of Nebraska - Lincoln Architectural Engineering -- Faculty Publications Architectural Engineering and Construction, Durham School of 2018 Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers Mehdi Mehrabi University of Nebraska - Lincoln, mmehrabi@unomaha.edu David Yuill University of Nebraska-Lincoln, dyuill@unl.edu Follow this and additional works at: http://digitalcommons.unl.edu/archengfacpub Part of the Architectural Engineering Commons, Construction Engineering Commons, Environmental Design Commons, and the Other Engineering Commons Mehrabi, Mehdi and Yuill, David, "Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers" (2018). Architectural Engineering -- Faculty Publications. 139. http://digitalcommons.unl.edu/archengfacpub/139 This Article is brought to you for free and open access by the Architectural Engineering and Construction, Durham School of at DigitalCommons@University of Nebraska - Lincoln. It has been accepted for inclusion in Architectural Engineering -- Faculty Publications by an authorized administrator of DigitalCommons@University of Nebraska - Lincoln.

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2018 Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers Mehdi Mehrabi University Of Nebraska-Lincoln, mmehrabi@unomaha.edu David P. Yuill University of Nebraska-Lincoln, dyuill@unl.edu Follow this and additional works at: https://docs.lib.purdue.edu/iracc Mehrabi, Mehdi and Yuill, David P., "Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers" (2018). International Refrigeration and Air Conditioning Conference. Paper 1884. https://docs.lib.purdue.edu/iracc/1884 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2216, Page 1 Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers Mehdi Mehrabi 1 *, David Yuill 1 1 University of Nebraska-Lincoln, Architectural Engineering Omaha, NE, USA mmehrabi@unomaha.edu dyuill@unl.edu * Corresponding Author ABSTRACT Air cooled condensers are commonly used in rooftop units and residential air-conditioners to reject heat outdoors. Airborne particles in the environment, such as dust, grass, leaves, seeds, and anthropogenic agents, can foul the air side of the condensers. Therefore, it is common practice to regularly clean the air side of condensers. Seven fouled wavy fin, and two fouled spine fin condensers from residential condensing units were collected at the end of their service lives, and examined in the laboratory to study the effect of the fouling on heat transfer capacity and air-side flow resistance. A test apparatus was designed and built to investigate the flow resistance and heat transfer of these coils before and after cleaning. After testing each condenser in the fouled condition, the fouling material was collected and its mass was measured. Then, the coil was washed with water and tested again in the test apparatus. Finally, to investigate the effectiveness of commercial detergents, these coils were cleaned with a detergent and tested again. Surprisingly, the show that the effect of washing on the heat transfer capacity of the coil is very small, and in some cases, the fouled condenser performed better before cleaning than afterward. Similarly, cleaning the coils with detergent had negligible differences compared with the effects from cleaning with water only, and in some cases, the detergent caused performance degradation in terms of flow resistance and heat transfer. 1. INTRODUCTION Airside fouling deposition on condensers is widely believed to degrade the performance of air conditioners. There are a few scientific documentation about the effects of cleaning the fouling of field heat exchangers. Ahn et al. (2003) and Ahn and Lee (2005) studied the fouling on evaporator and condenser samples of window air conditioners for some seaside inns. In evaporators, particulate fouling was the dominant agent, and in condensers, corrosion was the dominant agent because of the presence of chloride in the environment. Lankinen et al. (2003) tested a three-pass compact heat exchanger by injecting pure quartz and ASHRAE standard test dust. With ASHRAE standard test dust, the overall heat transfer decreased by 8 to 18% while the airside pressure drop increased about 200%. The effect of pure quartz s on thermal and hydraulic performance was negligible. Pak et al. (2005) tested six condensers clean as received, after injection of ASHRAE standard test dust, and after cleaning. The fouling mostly deposited on the coil front side. Fouling had a more significant effect on the pressure drop than the heat transfer. The original performance of the coils was entirely recovered after washing the coils. Yang et al. (2007) tested four different coils under varying loads of fouling agents. In many cases, the decrease in heat transfer was less than the uncertainty of the measurements while the impact of fouling on pressure drop was significant. In one case, a moderate amount of fouling increased the heat transfer. Ali and Ismail (2008) studied the effect of airside fouling on a plate fin and tube evaporator. The fouling material was gathered from the field, on the surface of condensing units. They imposed 100, 200, and 300 grams of the fouling material. The fouling on the front side was found to contain fibers and dust particles, and the rear side was free of fiber. Pu et al. (2009 and 2010) studied the effects of biofouling on three fin and tube heat exchangers. They found that biofouling might increase the heat transfer when it covered less than 10% of the surface area, due to increases in

2216, Page 2 local air velocity. Bell and Groll (2010 and 2011) tested a plate fin and two microchannel coils, using ASHRAE test dust and Arizona road test dust. The microchannel coils were more sensitive to fouling than the plate-fin coil. Bell et al. (2011) tested a hybrid dry cooler by injecting ASHRAE standard test dust in two 300 g increments. In the dry coil condition, the effect of fouling on heat transfer with airflow rate held constant was negligible. The two main effects of airside fouling are the buildup of material that can impose an additional conductive resistance on the coil surface, and the change of the aerodynamic shape of airflow paths through the coil. The changes to the aerodynamics may cause changes to the convection from the surfaces, in particular by inducing turbulence, which can enhance the heat transfer, as reported by Yang et al. (2007) and Pu et al. (2009 and 2010). For uncontrolled fan (i.e. constant speed) condensers, according to the majority of the literature, the dominant effect on the overall heat transfer is caused by the reduction of the airflow rate. This reduction has a detrimental effect on convection, and also reduces the log mean temperature difference (LMTD) between the refrigerant and air. In the current paper, nine field-deployed condensers were collected from the Omaha area. Figure 1 shows the collected condensing units, and Table 1 shows the specifications of the collected condensing units. Two of the condensers are spine fin coils, and the others are plate fins. The two spine fin coils are indicated by S 1 and S 2 in this paper. The seven plate fin coils are indicated from P 1 to P 7. For the most fouled spine and plate fin coil, S 1 and P 7, tests were done on two sides of the condenser coil (named S 1-1, S 1-2, P 7-1, and P 7-2). Figure 1: Collected condensers

Net Face Area (sq. ft.) Fins per inch No. of Rows Fin Type Tube Diameter (in.) Nominal Cooling Capacity (tons) Manufacturing Date Condenser Name 2216, Page 3 Table 1: Specifications of the condensers S 1 Mar-93 3.5 3/8 Spine 1 24 16.12 S 2 May-03 4 3/8 Spine 1 24 13.75 P 1 Jun-01 3 5/16 Herringbone wavy Slit louver 2 22 16.04 (15.56 inner coil) P 2 May-06 3 5/16 Herringbone wavy Slit louver 1 22 18.67 P 3 NA 2.5 3/8 Herringbone wavy Offset louver 1 20 10.2 P 4 Jan-01 2.5 5/16 Herringbone wavy Slit louver 1 18 13.22 P 5 Dec-90 2.5 3/8 Herringbone wavy Slit louver 1 20 9.2 P 6 Sep-01 2.5 5/16 Herringbone wavy Slit louver 1.36 18 15.21 (5.44 inner coil) P 7 Jul-92 2.5 3/8 Herringbone wavy Slit louver 1 16 15.8 2. METHODOLOGY First, the coils were disconnected and separated from the condensing units. The test method involves the use of hot water, rather than refrigerant inside the tubes, because it can be controlled more easily to repeatable conditions. Then, 1.55 square feet of the air side of each coil was tested in a test apparatus that is shown in Figure 2. The test area reasonably represents the surface of the condenser except the curved sections, which could have different internal airflow patterns. Although in-situ airflow patterns may be different, we do not believe that this effect would change the outcome of the experiments with this apparatus. The apparatus was developed for another research project and is fully described in Mehrabi and Yuill (2018a), including a full discussion of the measurement uncertainty and instrument specifications. The other surfaces of the coil were well insulated during the tests. The air side section of the test apparatus includes a wind tunnel in a draw-through configuration, and two air straighteners before and after the coil. The water side section consists of a water loop that passes hot water through the coil (Figure 2). Figure 2: Test apparatus configuration

2216, Page 4 On the water side section of test apparatus, RTD sensors are installed before and after the coil. On the airside downstream, nine RTD sensors are installed to get the average temperature. On the upstream side an RTD sensor is installed to measure the intake, which is at room temperature. Water flow rate, airflow rate, fan speed, coil air side pressure drop, room relative humidity and absolute pressure are measured with laboratory grade sensors. Air side and water side heat transfer, which should agree, are calculated from Equations (1) and (2). Q a = m a(h a,o h a,i ) (1) Q w = m w(h w,i h w,o ) (2) where a and w indicate the air side and water side, m is mass flow rate, and h i and h o are inlet and outlet enthalpies. Uncertainty analysis showed that the propagated sensor measurement uncertainty in the heat transfer calculation is less than 1% on the water side, and about 3% on the air side. For each coil under test, the coil pressure drop and heat transfer were measured at three different airflow rates. One airflow rate is the rate associated with the manufacturer s nominal face velocity for the condensing unit, if available. A higher and a lower flow rate was tested to provide more generalized. After the initial test, the coil was removed from the test apparatus, and fouling material was collected from the coil test area as much as possible, using tweezers, small brushes, and similar instruments. After all possible fouling was removed and stored, the coil s air side was washed with water, then dried. After drying, the coil was installed on the test apparatus again and retested. After testing the washed coil, the coil was removed again from the test apparatus and washed with detergent. After drying, the coil was installed on the test apparatus and tested a third time. In each condition, the coil pressure drop and heat transfer were measured at constant airflow, at the same flow rate as the fouled coil tests, as well as constant fan speed. In this way, the two effects of fouling discussed earlier changes to heat conduction and changes to convection cause by airflow rate can be isolated. During testing, if the fan speed differs by less than one percent for the matched air flow rate and matched fan speed tests, only the matched fan speed test was conducted. The tests at constant airflow rate mimic the effect of fouling for constant airflow condensers, and the tests at constant fan speed mimic the effect on typical condensers, which have constant speed motors. The constant speed tests assume that the fan curve for our fan matches the fan curve for the condensing unit within the working region, which is the case. Within the small performance region of the tests, the variations in fan characteristics between typical condenser fans and the test apparatus fan are negligible. To compare the effect of washing on different capacity coils, the measured airflow rate, pressure drop, and calculated heat transfer are normalized. Normalized Value = Current value / Measured value in nominal working condition (3) The nominal working condition in this paper is the condition in nominal airflow rate as mentioned by the manufacturer (if available) for each coil. The nominal heat transfer and nominal pressure drop are the values in fouled coil condition as received. 3- RESULTS Visual observations on the collected coils show that most of the fouling collects on the coil s face, while the rear side appears clean. It seems that fibers have a significant effect on the fouling deposition. The collected fibers on the coil s face trap other small particles. For the nine coils in this sample, there was no correlation between the visually apparent fouling level on the coil, and its service life.

2216, Page 5 Table 2 shows the test condition, nominal values and collected mass of fouling material before washing for each coil. The m w value is the water mass flow rate in the coil. The T wi value is the water inlet temperature in nominal condition. For each coil m w and T wi were kept constant during all the tests. Coil m w [kg/s] Table 2: Test condition, nominal values, and collected dust T wi [ C] Nominal Airflow Rate [CFM] Nominal P Coil [Pa] Nominal Q w [kw] Collected Dust Before Washing [g] S 1-1 0.0247 47.7 292 20.9 1.598 12.79 S 1-2 0.0248 55.1 298 44.4 2.033 25.88 S 2 0.0317 52.0 298 18.8 2.205 0.47 P 1 0.0233 55.8 338 21.6 1.374 0.06 P 2 0.0287 45.8 289 11.2 1.171 0.29 P 3 0.0443 40.2 217 8.6 1.050 0.79 P 4 0.0315 45.2 291 10.0 1.374 1.82 P 5 0.0450 47.3 334 56.8 1.972 0.07 P 6 0.0336 54.0 291 12.2 1.227 0.04 P 7-1 0.0343 44.1 292 14.1 1.286 9.75 P 7-2 0.0342 44.2 294 16.4 1.110 12.19 Figures 3 and 4 show the test for spine fin and plate fin coils. The left charts show the normalized pressure drop versus normalized airflow rate, and the right charts show the normalized waterside heat transfer versus normalized airflow rate, before and after washing the coils. For example, on the left chart for S 1-1 coil in Figure 3, the red curve shows the fouled test. As can be seen on this curve, the normalized pressure drop in nominal condition (normalized airflow rate equal to one) by the definition of Equation 3, is one. The other two points on the red curve show the values at higher and lower airflow rates. The blue and green curves show the normalized pressure drop after washing the coil only with water and washing with detergent, respectively. While the washing has a significant effect on pressure drop as can be seen on the left charts, the fouled and the washed curves are clustered very tightly on right side charts, which indicates that washing has a negligible effect on heat transfer. Unexpectedly, for some coils, washing even decreased the heat transfer. For example, for S 1-2 coil the heat transfer slightly increased after washing, even though the pressure drop decreased by 64%. After washing with detergent, for coils P2 and P4, the pressure drop increased compared to for washing only with water. This might be attributed to the fact that the applied basic detergent that is typically used for condensers is relatively corrosive. For aluminum coils (such as the spine fin coils) manufacturers recommend ph neutral detergents. After washing the spine fin coils with a no-rinse neutral detergent, the pressure drop slightly increased compared to washing only with water. Washing with detergent did not have a significant effect on heat transfer compared to washing with water. After washing, for most of the coils, the fan speed for constant airflow tests did not change significantly compared to the fouled tests. Therefore, the constant airflow can also represent the effect of fouling on typical condensing units with constant fan speed. However, for coil S 1-2 (the dirtiest coil), the fan speed for the constant airflow rate test differs from the speed in the fouled tests. For this coil, additional tests were done to study the effect of fouling at constant fan speed condition. For these tests, the pressure drop and heat transfer are higher compared to constant airflow tests.

2216, Page 6 S1-1 coil S1-2 coil Same fan speed Same Airflow S2 coil Figure 3: Effect of washing the condensers on spine fin coils

2216, Page 7 P1 coil P2 coil P3 coil Figure 4 Continued: Effect of washing the condensers on plate fin coils

2216, Page 8 P4 coil P5 coil P6 coil Figure 4 Continued: Effect of washing the condensers on plate fin coils

2216, Page 9 P7-1 P7-2 Figure 4 Continued: Effect of washing the condensers on plate fin coils DISCUSSION The show that the effect of washing on heat transfer capacity of the coils is usually negligible. Unexpectedly, in some cases washing the coil can decrease the heat transfer. Because it was unexpected, a careful check was made of all the experimental apparatus to make sure there were no measurement errors, and for two coils that exhibited the unexpected result, a second portion of the coil was tested. Although it is not possible to determine the cause of the increased heat transfer capacity from fouling in some of the coils, a plausible explanation is that the fouling material induces turbulence on the air side, which enhances the heat transfer. This is the reason that coil manufacturers add fin enhancements to coils, even though they typically increase pressure drop. If washing of a condenser coil provides no clear and significant benefit, maintenance practices for hundreds of millions of air conditioners may need to be revisited. Thus, this work may have high impact. The sample size should be increased in future work, to add certainty to the. For typical split system condenser fans, the difference in fan curves is small enough that these, considering the small changes to the working point caused by typical levels of field fouling, can be considered applicable for any typical condenser. One factor that has not been considered in the current study is the effect of fouling on condenser

2216, Page 10 fan power. This will be examined in future work. Also, the effects on coil capacity, though small, should be considered in the context of overall system efficiency and capacity. This can be achieved by using generalized from multiple laboratory tests of condenser fault testing, presented by Mehrabi and Yuill (2018b). CONCLUSION The effects of washing the air side fouling of condensers of air conditioners were studied in this paper. Based on the, washing does not have a significant effect on heat transfer capacity, even though it significantly decreases the coil s air side pressure drop. In some cases, fouling even can increase the heat transfer capacity. Washing with detergent had no meaningful advantage when compared to washing with water only. In some cases, it even increased the pressure drop through the coil compared to washing with water. Future work will further examine the ramifications of these on overall system performance and maintenance. REFERENCES Ahn, Y. C., J. M. Cho, H. S. Shin, Y. J. Hwang, C. G. Lee, J. K. Lee and T. W. Kang. 2003. An experimental study of the air-side particulate fouling in fin-and-tube heat exchangers of air conditioners. Korean Journal of Chemical Engineering, 20(5), 873-877. Ahn, Y. C. and J. K. Lee. 2005. Characteristics of air-side particulate fouling materials in finned-tube heat exchangers of air conditioners. Particulate science and technology, 23(3):297-307. Ali, A. H. H. and I. M. Ismail. 2008. Evaporator air-side fouling: effect on performance of room air conditioners and impact on indoor air quality. HVAC&R Research, 14(2):209-219. Bell, I. H. and E. A. Groll. 2010. Experimental comparison of the impact of air-side particulate fouling on the thermo-hydraulic performance of microchannel and plate-fin heat exchangers. International Refrigeration and Air Conditioning Conference at Purdue. Bell, I. H. and E. A. Groll. 2011. Air-side particulate fouling of microchannel heat exchangers: experimental comparison of air-side pressure drop and heat transfer with plate-fin heat exchanger. Applied Thermal Engineering,31(5), 742-749. Bell, I. H., E. A. Groll and H. König. 2011. Experimental analysis of the effects of particulate fouling on heat exchanger heat transfer and air-side pressure drop for a hybrid dry cooler. Heat Transfer Engineering, 32(3-4): 264-271. Lankinen, R., J. Suihkonen and P. Sarkomaa. 2003. The effect of air side fouling on thermal hydraulic characteristics of a compact heat exchanger. International Journal of Energy Research, 27(4):349-361. Mehrabi, M., and D.P. Yuill. 2018a. Development of a method for testing air-side fouling effects on outdoor heat exchangers (RP-1705). 2018 ASHRAE Winter Conference. Mehrabi, M. and D.P. Yuill. 2018b. Generalized effects of faults on normalized performance variables of air conditioners and heat pumps. International Journal of Refrigeration 85 (2018): 409-430. Pak, B. C., E. A. Groll and J. E. Braun. 2005. Impact of fouling and cleaning on plate fin and spine fin heat exchanger performance. ASHRAE Transactions, 111(1). Pu, H., G. L. Ding, X. K. Ma, H. T. Hu and Y. F. Gao. 2009. Effects of biofouling on air-side heat transfer and pressure drop for finned tube heat exchangers. International journal of refrigeration, 32(5), 1032-1040. Pu, H., G. L. Ding, X. K. Ma, H. T. Hu and Y. F. Gao. 2010. Air-side heat transfer and friction characteristics of biofouled evaporator under wet conditions. Frontiers of Energy and Power Engineering in China, 4(3), 306-312. Yang, L., J. E. Braun and E. A. Groll. 2007. The impact of fouling on the performance of filter evaporator combinations. International Journal of Refrigeration, 30(3):489-498.