Cork Institute of Technology Higher Certificate in Engineering in Building Services Engineering Award

Similar documents
ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Gandhinagar Institute of Technology Mechanical Engineering (Thermal Engineering) Semester II. Design of Heat Exchange Equipments [ ]

R07. Answer any FIVE Questions All Questions carry equal marks *****

CHAPTER IV AIR DISTRIBUTION AND BALANCE

CRAFTSMAN EXAMINATION, NOVEMBER 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

KLIMA Active Chilled Beams

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

GUIDELINES FOR HIGHRISE BUILDING CONSTRUCTION PROJECTS (MECHANICAL VENTILATION)

OIL AND GAS INDUSTRY

Installation Manual. Instrucciones de instalación y manual de usuario 1

1.0 CONDITIONS FOR CHILLED WATER SUPPLY (PRIMARY SIDE BY DHCS SUPPLIER)

Refrigeration Technology in Building Services Engineering

Mechanical Engineering Department Sheet (1)

INSTITUTE OF AERONAUTICAL ENGINEERING

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

INSTALLATION DO S AND DON TS

Heat pump and energy recovery systems

Trade of Plumbing. Module 2: Domestic Hot and Cold Water Service Unit 10: Hot Water Supply Phase 2

RSES SERVICE APPLICATION MANUAL TABLE OF CONTENTS AUGUST 2016

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

II. OBJECTIVE OF RESEARCH

Technical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: ,

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers


A/C Cooling Load calculation and measurement

Exhaust Duct Design Page 1 of (C)

Heat emitters for Heat Pump systems. Bill Bucknell

Technical Selection. elevent ceiling diffusers. Swirl, Jet, Louvred and Curved ceiling diffusers

PVE SERIES POWER VENTER SYSTEM MANUAL

NEW. Hydronic HVAC Systems. FloCon Watchman TM. Patent Numbers: GB , GB , GB Rev: /2015

REGISTRATION EXAMINATION, JUNE 2015 LICENSED PLUMBER QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

RAC. Unit 1. Previous year Questions

SERVICE ASSISTANT OVERVIEW FDSI Online Training

Optimal work climate with open doors. Industrial air curtains Model IndAC

REGISTRATION EXAMINATION, NOVEMBER 2017 TRADESMAN PLUMBER QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

Experienced Worker Assessment Blueprint HVAC - Heating, Ventilation and Air Conditioning

Use each of the terms in the box to explain how heat is lost from inside a house through the window. conduction convection radiation

CE311 Fall 2016 Mid-Term Exam 1

Energy-efficient heat source provides comfort in large rooms

C o o l i n g a n d h e a t i n g s y s t e m s

2. CURRICULUM. Sl. No.

Introduction. General requirements when using the heat pump

Q1. The diagram shows an experiment to find out what happens to infrared waves when they strike different surfaces.

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Split units, (single room unit and single condenser linked by pipework)

Union County Vocational - Technical Schools Scotch Plains, New Jersey

UNIT 4: REFRIGERATION PRINCIPLE

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Duct Design and Installation

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

Frequently Asked Questions

SINGLE LEVER CERAMIC DISC MANUAL SHOWER VALVE

Polaris-I-60. active chilled beam. the future of space conditioning

INSTALLATION INSTRUCTIONS ONE LARGE ZONE

Chapter 14, Problem 27.

Use this Construction/HVAC Glossary to answer the questions below.

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM

Appendix 13. Categories of Cooling and Heating systems

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS

Page 1 of Relevant Provincial Jurisdictional legislation.

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

INDUSTRIAL AIR CURTAIN. IndAC 2

OWNER S GUIDE SEQUENTIAL THERMOSTATIC SHOWER VALVE. 150mm Inlet Pipe Centres. Shower Control. Handles and. may differ depending.

APPLICATION GUIDE FLATAIR FMC - H FIC - H FSC - H. Horizontal packaged air conditioners kw FLATAIR AGU-MSL E. lennoxemeia.

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

PLEASE READ AND FOLLOW THESE INSTRUCTIONS

Performance Optimization of the Evaporative Condenser Design

Partner. Peerless. Indirect-Fired. Water Heater. Installation, Operation & Maintenance Manual

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Cassette units Model Comfort Circle. - heating - cooling - ventilation

Cooling Load Analysis and Computation Worksheet Answers Part 1 Psychrometrics

Instruction Sheet. Press & Hold: Item, to view settings, to test. 24 V ±10% 50/60 Hz 3 VA 120 V (ac) 5 A 1/6 hp pilot 240 VA 20 to 260 V (ac) 2 VA

REFRIGERANT PIPING INTRODUCTION

PESIT-Bangalore South Campus

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Prescriptive Requirement for Smoke Control

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Pharmaceutical Facility Design

Primo Hotel. General. Indoor climate units for hotel rooms

HVACR Hydronic & Steam Systems

POWER VENTER. Model: PVE Series

IV SEMESTER DIPLOMA EXAMINATION, JANUARY-2013 THERMODYNAMICS

ARTESIAN 220 & 340 Instantaneous Indirect Water Heater By Dunkirk Boilers INSTALLATION AND OPERATING INSTRUCTIONS ENGINEERING MANUAL

POWER VENTER SYSTEM. Model: PVO-300, PVO-600

Transcription:

Cork Institute of Technology Higher Certificate in Engineering in Building Services Engineering Award Instructions Answer FIVE questions, All questions carry equal marks. (NFQ Level 6) Autumn 2006 Building Services and Equipment II (Time: 3 Hours) Examiners: Mr. William Bateman Dr. Neil Hewitt Mr. Declan Leonard Reference Material to be provided. Question Location 1. Table 1, 2, 3and 4 Hot and Cold Water Pipe work Design Q1 (attached) 2. CIBSE Table C4.18 Page C4-40 Water 10 0 C Copper Pipe. Q1 (attached) 3. Hot and Cold Water design Spreadsheet Q1 (attached) 4. CIBSE Table C4.11, Page 4-15 - Water 75 0 C Med Grade Steel Q4 (attached) 5. CIBSE Table C4.36. -Velocity press loss factors. Q4 (attached) 6. Ductwork Design Sheet Q5 (attached) 7. CIBSE Fig C4.2 Flow of Air in Round Ducts Q5 (attached) 8. CIBSE Table C4.33 Velocity Pressure in Pa v s Velocity m/s Q5 (attached) 9. CIBSE Table C4.35 Page 1&2 Velocity Press Loss Factors Q5 (attached)

Q1 (a ) Fig 1.1 shows the cold water pipe work layout for a changing room area within a school. Determine the most economical diameters of the copper distribution pipes labelled AB, BC, etc. Assume a continuous demand due to peak usage. Ensure you put your name on the sheet and attach the sheet to your answer book. [15 marks] STOP VALVE STORAGE TANK A FIG 1.1 COLD WATER PIPEWORK PLEASE SHOW ALL CALCULATIONS PLEASE WRITE YOUR NAME ON ALL SHEETS. DIMENSIONS SHOWN ARE IN MM. 4 x Shower (with nozzle) 15mm Isol v/v 3000 4 x W.C 15mm Isol v/v 13/15mm LP Ball Float v/v D 4 x Wash Basin 13/15mm Bib taps F 1900 H B 750 C E 2500 2500 3000 G (b) Having completed your detailed design it should show that insufficient head pressure is available to carry the desired volume of water to user point H. Calculate the shortfall in head pressure available (Pa) and suggest the minimum changes required to correct such a fault. [5 marks] Q2 (a) Fig 2.1 below shows a section of a wall. Using the data provided on the sketch calculate the thermal transmission (U Value) for the wall. Table 2 Rsi, Table 3 Rso and Table 4 Ra attached as reference. [8 marks] FIG 2.1 U - VALUE 110mm BRICK 50mm AIR GAP 110mm AERATED CONC 3mm THICK EXPANDED POLYSTYRENE 13mm PLASTER OUTSIDE SURFACE HIGH EMISSIVITY SHELTERED LOCATION 50mm AIR GAP HIGH EMISSIVITY INSIDE SURFACE HIGH EMISSIVITY Thermal Conductivities. Brick 1.00 W/m K Aerated Concrete 0.14 W/m K Plaster 0.70 W/m K Polystyrene 0.04 W/m K 2

Table 2 - Rsi Internal surface resistances R si in m 2 0 C / W Building element Heat flow Surface resistance (m 2 0 C / W) High Emissivity Low Walls Horizontal 0.123 0.304 Ceilings, floor, flat Upwards 0.106 0.218 Ceilings and floors Downwards 0.150 0.562 Table 3 - Rso External surface resistances R so in m 2 0 C / W Building Emissivity Surface resistance for stated exposure Sheltered Normal Severe Wall High 0.08 0.055 0.03 Low 0.11 0.067 0.03 Roof High 0.07 0.045 0.02 Low 0.09 0.053 0.02 Table 4 - Ra Unventilated Air Gap resistance R a in m 2 0 C / W Air Space Thickness Surface Emissivity Thermal resistance (m 2 0 C / W) Heat flow Horizontal or Upwards Heat flow Downwards 5 mm High 0.11 0.11 Low 0.18 0.18 20 mm High 0.18 0.21 Low 0.35 1.06 3

(b) Fig 2.2 shows the plan of an office on the second floor of a four storey building. The other floors have the same construction and heating design conditions. From the data given and using convection heating, calculate the total rate of heat loss for this office. [12 marks] Outside Temp minus 2 DegC Office Temp 20 DegC 6 m Window Area 5m 2 8 m Height of office = 3m Air Change = 1 per hour 2 U Values ( W / m K ) External wall 0.4 Internal wall 1.6 Door 2.3 Window 2.2 Floor 0.5 Ceiling 0.5 Office Temp 20 DegC Door Area 2m 2 Office Temp 20 DegC Fig 2.2 Heat Loss Corridor Temp 16 DegC 4

Q3 (a) A two pipe LPHW central heating system is shown in Fig 3.1. The pipe work is medium grade steel. The heat output from each radiator does not allow for a fixed percentage heat loss from the insulated pipe work supplying those radiators. Under the design conditions shown, find the following for pipe sections 1, 2 and 3. (i) Pipe diameter, (ii) Pressure drop per meter - dp l, (iii) Length equivalent factor - l e. NB: it is not necessary to compare the actual heat loss from the insulated pipe work with the theoretical value estimated. Table C4.12, Page C4-15, Medium Grade Steel Water at 75 0 C attached for reference. Table C3.14 heat emission from horizontal steel pipe Not required. [10 marks] FIG 3.1 LPHW HEATING TWO PIPE PARALLEL SYSTEM OUTPUT 7 kw 15.0 m OUTPUT 12 kw 6.0 m SECTION 1 (6m + 15m) x 2 SECTION 3 (12.5+4+1+2.5+12.5) = 32.5m 8 m SECTION 2 (8.0 m) x 2 1.0m 2.5m 12.5 m BOILER CIRCULATION PUMP ISOLATION VALVES TOTAL DISTANCE 4 METERS SPACE TEMPERATURE FLOW TEMPERATURE RETURN TEMPERATURE TARGET VELOCITY OF FLOW EMITTER HEAT CAPACITY SPECIFIC HEAT CAPACITY H 20 18.5 DEG C 87 DEG C 70 DEG C 1 m/s AS SHOWN 4.2 kj/kg K (b) For the same LPHW circuit find the effective pipe length of the straight pipe plus fittings for all sections. From this find the total pressure drop on the index run. Use this to derive a pump duty for the circulation pump in this circuit. Bends are welded mild steel elbows and isolation valves are gate valves. Table C4.36 Velocity Pressure Loss factors attached for reference. [10 marks] 5

Q4 (a) The production area and associated rooms shown in Fig 4.1 below are to be supplied with air conditioned air through the supply air duct shown. The air is supplied from point A to supply air grilles at B, C, D and E. There are no change in levels between A and E. Using the design criteria provided on the sketch and the ductwork design sheet attached, establish the most economical circular duct size for the layout shown in Fig 4.1. Include all relevant information on the ductwork design sheet. Ensure you put your name on the sheet and attach the sheet to your answer book. Fig C4.2, Table C4.33 and Table C4.35 Page 1&2 attached as ref. [15 marks] SUPPLY AIR GRILLE 1m 2m E D CORRIDOR 6m x 2m x 2.4m H 5 Air change/hr 144 m3/hr PREP ROOM 8m x 2.8m x 5m H 20 Air change/hr 2240 m3/hr ASSUME CIRCULAR DUCTWORK ASSUME CONSTANT dp 0.6 Pa/m ALL BENDS ARE 4 PIECE BEND r/d RATIO = 2 45 Deg GRADUAL TRANSITIONS 9 Pa dp AT GRILLES ALL ROOM SUPPLY AIR VOLUMES ARE QUOTED IN m3/hr FIRE DAMPERS WHERE DUCTWORK PASSES THROUGH ALL WALLS k FACTOR 0.2 PRODUCTION HALL 10m x 10m x 5m H 30 Air change/hr 15000 m3/hr 1m 1.3m 1.4m ALL DUCT DIMENSIONS ARE QUOTED IN METERS BETWEEN FITTINGS 2m C STORE 8m x 2.6m x 2.4m H 10 Air change/hr 500 m3/hr 2m 1.4m 5m B 5m A 1m FIG 4.1 - DUCTWORK DESIGN (b) Fig 4.1 shows fire dampers on each of the dividing walls between the rooms. With the aid of a neat sketch show the details of two different types of fire dampers commonly used in air conditioning ducting. [5 marks] 6

Q5 (a) Air conditioning is used to control the temperature, humidity, cleanliness and distribution of air within the air conditioned space. Filters are used in controlling the cleanliness of the air. Briefly describe three types of air filters that may be found in air conditioning systems indicating how each works. [6 marks] (b) Draw a schematic of a split system packaged air conditioning unit in room cooling mode, complete with compressor, heating and cooling coils, reversing valve, expansion device, fans and direction of flow of the refrigerant. Indicate on the schematic the state of the refrigerant immediately after the expansion device, i.e, High Pressure or Low Pressure, Liquid or gas. [8 marks] Use the Psychrometric Chart attached to plot and determine the following conditions. NB: It is not necessary to attach the chart to your answer book. (c) In winter, cold air at a dry bulb of 5 Deg C and 60 % relative humidity enters a building through a heater battery and is heated to a dry bulb temperature of 20 Deg C, without adding moisture. From the Psychrometric chart find, [2 marks] (c) i. The Wet Bulb temperature of the incoming air. (c) ii The Relative Humidity of the heated air. (d) The air in a room has a dry bulb temperature of 22 Deg C and a wet bulb temperature of 16 Deg C. From the Psychrometric chart find, [2 marks] (d) i The Relative Humidity of the air. (d) ii The temperature of the walls when condensation will occur. (e) Air enters an Air Handling unit at a dry bulb temperature of 25 Deg C and 70 % relative humidity. The final condition required is a dry bulb temperature of 20 Deg C and 50 % relative humidity. From the Psychrometric chart find, [2 marks] (e) i The reduction in moisture content of the air. (e) ii The lowest temperature the air must be cooled to in order to achieve the reduced moisture content. 7

Q6. (a) With the aid of a neat sketch show all the equipment associated with a typical wet sprinkler system for a two storey building. [6 marks] (b) Using a neat sketch show the general arrangement of an on site automatic sprinkler pump system including the water storage and water supply. [6 marks] (c) Outline the type of portable fire extinguishers you would recommend for use on fires involving four of the following materials :- [4 marks] No. (i) (ii) (iii) (iv) (v) Class A B C D E Fire Type Wood & Petroleum Gases Inflammable Electrical textiles metals (d) Briefly explain how each type of extinguisher described above is effective in fighting the relevant fire. [4 marks] Q7 (a) Global warming is a phenomenon attributed to increased industrialisation of our planet. With the aid of a neat sketch describe how global warming has come about. [10 marks] (b) Air pollution is a major contributor to global warming. Describe three types of air pollution, their sources, effects on humans and vegetation, and possible control measures to help reduce their level. [10 marks] 8

9

10

11

12

13

14

15

16

17

18