Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Similar documents
Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

Sprinkler Identification Numbers. TY3351 Horizontal TY3451 Vertical. Technical Data

Series TY-FRB 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General Description

Sprinkler Identification Numbers

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

* Temperature rating is FIGURE K-FACTOR QUICK RESPONSE SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

WRENCH FLATS NPT 1/2" 7/16" (11,1 mm) NOMINAL MAKE-IN. 1-1/2" (38,1 mm) 2-3/16" (55,6 mm) WRENCH NPT. (12,7 mm) NOMINAL MAKE-IN.

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16" (42,7 mm) CROSS SECTION

Sprinkler Identification Numbers

Submittal Packages Detailed with Items and Reviewers

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

special request FACTORY ASSEMBLED UPRIGHT WITH SCREW FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) WRENCH FLATS *

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response)

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

Series TY-FRL 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Sprinkler Identification Number. Page 1 of 6 AUGUST 2018 TFP288. Worldwide Contacts.

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Horizontal Sidewall Wet Pipe and Dry Pipe Systems General Description

Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description

Series TY-B & TY-FRB, 10 mm Orifice, ISO 7/1-R3/8 Upright, Pendent, and Recessed Pendent Sprinklers Standard and Quick Response General Description

RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

RAPID RESPONSE Series LFII Residential Sprinklers 5.6 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

O-RING UPRIGHT SHIELD WRENCH FLATS WRENCH FLATS FIGURE 1 SERIES TY-B UPRIGHT (TY3153) AND PENDENT (TY3251) SPRINKLERS

ESCUTCHEON PLATE SEATING 3/4" NPT SURFACE. 1-1/2" (38,1 mm) CROSS SECTION PENDENT RECESSED PENDENT

Model/Sprinkler Identification Number JULY, 2011 WARNINGS

Model TY-FRFS, TY-FS Special, and TY-FS 57, 80, and 115 K-factor Upright and Pendent Flat Spray Sprinklers General Description

Series DS-1 Stainless Steel Dry-Type Sprinklers 5.6K Pendent, HSW, and Extended Coverage HSW Standard and Quick Response General Description

Page 1 of 8 DECEMBER 2018 TFP408. Worldwide Contacts.

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

Model TY-FRFS, TY-FS Special, and TY-FS Flat Spray Sprinklers, Upright and Pendent 57, 80, and 115 K-factor General Description

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

Sprinkler Identification Number (SIN)

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

Model/Sprinkler Identification Numbers

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description

RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

FIGURE 1 MODEL RFIII ECLH CONCEALED HSW SPRINKLER ASSEMBLY AND FEATURES. 5/16" (7,9 mm) MIN. 9/16" (14,3 mm) MAX.

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

Sprinkler Identification Number (SIN) TY4234. Page 1 of 8 APRIL 2012 TFP Technical Services

Series RFII 5.6 K-factor. Flush II Concealed Pendent Sprinklers

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description

Series LFII Residential Pendent Sprinklers 4.9 K-factor General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard)

Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description

The Series LFII (TY3596) Residential

5.6K Pendent, Upright, and Horizontal Sidewall Standard Response, Standard Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

G3/8" DIN ISO 228 THREAD SHOULDER AND DUST CAP MATING SURFACE. STYLE H ESCUTCHEON (SEPARATELY ORDERED) 85 mm DIA. (3-3/8")

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description

11.2K * Pendent Extended Coverage, Light and Ordinary Hazard General Description. Model/Sprinkler Identification Numbers (SINs) Technical Data

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-Factor General Description

Model WS TM 5.6 K-factor Specific Application Window Sprinklers, Horizontal and Pendent Vertical Sidewall General Description

Series DS-1 Stainless Steel Dry-Type Sprinklers 5.6K Pendent, HSW, and Extended Coverage HSW Standard and Quick Response General Description

Sprinkler Identification Numbers

Automatic Sprinklers

Sprinkler Identification Number TY ECLH HSW, 8.0K, 3/4"NPT

Series LFII Residential Horizontal Sidewall Sprinklers 4.2 K-factor General Description

MODEL: FA003U FA004U FA005P FA006P STANDARD SPRAY, STANDARD QUICK RESPONSE, 5 3 mm BULB TYPE, K5.6, 1/2" CONNECTING THREAD

Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model/Sprinkler Identification Number (SIN) Technical Data

Automatic Sprinklers

Worldwide Contacts.

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Series LFII Residential Horizontal Sidewall Sprinklers 4.4 K-factor General Description

UL LISTED. SPRINKLER HEADS IN STOCK: Pendent Upright Horizontal sidewall Concealed. RESPONSE Quick response Standard response

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Series LFII Residential Flush Pendent Sprinklers 4.2 K-factor General Description

Model F1 LO K 8.0 (115 metric) Standard Response Sprinklers

MICROFAST AND MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS TECHNICAL DATA

Model G5 Series Sprinkler Summary. Listings and Approvals. G4/G5 QR Gasket culus QR G4/G5 SR Gasket culus, FM SR G4/G5

RAPID RESPONSE Series LFII Residential Sprinklers 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe and Dry Pipe Systems

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed.

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description

quick response Sprinkler 105a October 25, 2010

TECHNICAL DATA. Page 1 of 6

Model F1FR Series Quick Response Standard Spray

Transcription:

Worldwide Contacts www.tyco-fire.com Series 2.8,.2,.6, 8.0 K-Factor Upright, Pendent, Recessed Pendent Sprinklers Quick Response, Stard Coverage General Description The TYCO Series, 2.8,.2,.6, 8.0 K-factor, Upright, Pendent, Recessed Pendent Sprinklers described in this data sheet are quick response, stard coverage, decorative mm glass bulb-type spray sprinklers designed for use in light or ordinary hazard, commercial occupancies such as banks, hotels, shopping malls. The recessed version of the Series TY- FRB Pendent Sprinkler, where applicable, is intended for use in areas with a finished ceiling. This recessed pendent sprinkler uses one of the following: A two-piece Style 10 (1/2 inch NPT) or Style 0 (/ inch NPT) Recessed Escutcheon with 1/2 inch (12,7 mm) of recessed adjustment or up to / inch (19,1 mm) of total adjustment from the flush pendent position, or a A two-piece Style 20 (1/2 inch NPT) or Style 0 (/ inch NPT) Recessed Escutcheon with 1/ inch (6, mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjustment from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. IMPORTANT Always refer to Technical Data Sheet TFP700 for the INSTALLER WARNING that provides cautions with respect to hling installation of sprinkler systems components. Improper hling installation can permanently damage a sprinkler system or its components cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Corrosion-resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although corrosion-resistant coated sprinklers have passed the stard corrosion tests of the applicable approval agencies, the testing is not representative of all possible corrosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. An intermediate level of the Series TY- FRB Pendent Sprinklers is detailed in Technical Data Sheet TFP6, Sprinkler Guards are detailed in Technical Data Sheet TFP780. NOTICE The Series, 2.8,.2,.6, 8.0 K-factor, Upright, Pendent, Recessed Pendent Sprinklers described herein must be installed maintained in compliance with this document with the applicable stards of the National Fire Protection Association, in addition to the stards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintaining their fire protection system devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Sprinkler Identification Number (SIN) TY111: Upright 2.8K, 1/2 NPT TY121: Pendent 2.8K, 1/2 NPT TY211: Upright.2K, 1/2 NPT TY221: Pendent.2K, 1/2 NPT TY11: Upright.6K, 1/2 NPT TY21: Pendent.6K, 1/2 NPT TY11: Upright 8.0K, / NPT TY21: Pendent 8.0K, / NPT TY81: Upright 8.0K, 1/2 NPT TY91: Pendent 8.0K, 1/2 NPT Page 1 of 10 OCTOBER 201

Page 2 of 10 * Temperature rating ** Pipe thread connections per is indicated on ISO 7-1 can be provided on Deflector. special request. ESCUTCHEON SEATING 1 - Frame 2 - Button - Sealing - Compression Assembly Screw - Bulb 6 - Deflector * 7 - Bushing 7 7/16" (11,1 mm) NOMINAL MAKE-IN 1-9/16" (9,7 mm) 2-1/" 1/2" NPT** STYLE 10 or 20 2-7/8" (7,0 mm) DIA. FLATS ESCUTCHEON CROSS SECTION 1 2 6 * FIGURE 1 QUICK RESPONSE (TY111) AND (TY121) S 2.8 K-FACTOR, 1/2 INCH NPT * Temperature rating ** Pipe thread connections per is indicated on ISO 7-1 can be provided on Deflector. special request. ESCUTCHEON SEATING 1-2 - Frame Button - Sealing - Compression Assembly Screw - Bulb 6 - Deflector * 1 7/16" (11,1 mm) NOMINAL MAKE-IN 1-1/2" (8,1 mm) 2 1/2" NPT** STYLE 10 or 20 2-7/8" (7,0 mm) DIA. FLATS ESCUTCHEON CROSS SECTION 6 * FIGURE 2 QUICK RESPONSE (TY211) AND (TY221) S.2 K-FACTOR, 1/2 INCH NPT

Page of 10 * Temperature rating ** Pipe thread connections per is indicated on ISO 7-1 can be provided on Deflector. special request. ESCUTCHEON SEATING 1 - Frame 2 - Button - Sealing - Compression Assembly Screw - Bulb 6 - Deflector * 1 7/16" (11,1 mm) NOMINAL MAKE-IN 1-1/2" (8,1 mm) 2 1/2" NPT** STYLE 10 or 20 2-7/8" (7,0 mm) DIA. FLATS ESCUTCHEON CROSS SECTION 6* FIGURE QUICK RESPONSE (TY11) AND (TY21) S.6 K-FACTOR, 1/2 INCH NPT * Temperature rating ** Pipe thread connections per is indicated on ISO 7-1 can be provided on Deflector. special request. ESCUTCHEON SEATING 1 - Frame 2 - Button - Sealing - Compression Assembly Screw - Bulb 6 - Deflector * 1 1/2" (12,7 mm) NOMINAL MAKE-IN 2-1/" 1-9/16" (9,7 mm) 2-/16" (8,7 mm) 2 /" NPT** STYLE 0 or 0 2-7/8" (7,0 mm) DIA. FLATS ESCUTCHEON CROSS SECTION 6 * FIGURE QUICK RESPONSE (TY11) AND (TY21) S 8.0 K-FACTOR, / INCH NPT

Page of 10 1/2" NPT ** 7/16" (11,1 mm) NOMINAL MAKE-IN FLATS CEILING SEATING 1-9/16" (9,7 mm) 2-1/" CROSS SECTION 1 2 6 * 1 - Frame 2 - Button - Sealing Assembly - Bulb * ** - Compression Screw 6 - Deflector * Temperature rating is indicated on Deflector. Pipe thread connections per ISO 7-1 can be provided on special request. Technical Data FIGURE QUICK RESPONSE (TY81) AND (TY91) S 8.0 K-FACTOR, 1/2 INCH NPT Approvals UL C-UL Listed FM, LPCB, NYC Approved Refer to Table A B for complete approval information including corrosion-resistant status. Maximum Working Pressure Refer to Table C. Discharge Coefficient K=2.8 GPM/psi 1/2 (0, LPM/bar 1/2 ) K=.2 GPM/psi 1/2 (60, LPM/bar 1/2 ) K=.6 GPM/psi 1/2 (80,6 LPM/bar 1/2 ) K=8.0 GPM/psi 1/2 (11,2 LPM/bar 1/2 ) Temperature Rating Refer to Table A B. Finishes Sprinkler: Refer to Table D. Recessed Escutcheon: White Coated, Chrome Plated, or Brass Plated. Physical Characteristics Frame... Bronze Button....Brass/Copper Sealing Assembly.........Beryllium Nickel w/teflon Bulb...Glass Compression Screw........ Bronze Deflector....Copper/Bronze Bushing (K=2.8)........... Bronze Operation The glass bulb contains a fluid that exps when exposed to heat. When the rated temperature is reached, the fluid exps sufficiently to shatter the glass bulb, allowing the sprinkler to activate water to flow. Design Criteria The TYCO Series, 2.8,.2,.6, 8.0 K-factor, Upright, Pendent, Recessed Pendent Sprinklers are intended for fire protection systems designed in accordance with the stard installation rules recognized by the applicable Listing or Approval agency (such as, UL Listing is based on the requirements of NFPA 1, FM Approval is based on the requirements of FM s Loss Prevention Data Sheets). Only the Style 10, 20, 0, or 0 Recessed Escutcheon, as applicable, is to be used for recessed pendent installations. Installation The TYCO Series, 2.8,.2,.6, 8.0 K-factor, Upright, Pendent, Recessed Pendent Sprinklersmust be installed in accordance with this section. General Instructions Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 1 F (7 C) /2 inch (2, mm) for the 286 F (11 C) temperature ratings. A leak-tight 1/2 inch NPT sprinkler joint shold be obtained by applying a minimum to maximum torque of 7 to 1 ft.-lbs. (9, to 19,0 Nm). A leak tight / inch NPT sprinkler joint should be obtained with a torque of 10 to 20 ft.- lbs. (1, to 26,8 Nm). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Escutcheon Plate by under- or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit. Series Upright Pendent Sprinklers The Series Pendent Upright Sprinklers must be installed in accordance with the following instructions. Step 1. Install Pendent sprinklers in the pendent position. Install upright sprinklers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, htighten the sprinkler into the sprinkler fitting. Step. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Figure 1). With reference to Figures 1 through, apply the W-Type 6 Sprinkler Wrench to the sprinkler wrench flats. Series Recessed Pendent Sprinklers The Series Recessed Pendent Sprinklers must be installed in accordance with the following instructions. Step A. After installing the Style 10, 20, 0, or 0 Mounting Plate, as applicable, over the sprinkler threads with pipe-thread sealant applied to the pipe threads, h-tighten the sprinkler into the sprinkler fitting. Step B. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Figure

Page of 10 K FACTOR 2.8.2 TYPE (TY121) (TY111) (TY121)* Figure 6 (TY121)** Figure 7 (TY221) (TY211) (TY221)* Figure 8 (TY221)** Figure 9 1). With reference to Figures 1 to, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Step C. After ceiling installation finishing, slide on the Style 10, 20, 0, or 0 Closure over the Series Sprinkler push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. TEMPERATURE BULB LIQUID COLOR 1 F (7 C) Orange 1 F (68 C) Red 17 F (79 C) Yellow 200 F (9 C) Green 286 F (11 C) Blue 1 F (7 C) Orange 1 F (68 C) Red 17 F (79 C) Yellow 200 F (9 C) Green 1 F (7 C) Orange 1 F (68 C) Red 17 F (79 C) Yellow 200 F (9 C) Green 1 F (7 C) Orange 1 F (68 C) Red 17 F (79 C) Yellow 200 F (9 C) Green 286 F (11 C) Blue 1 F (7 C) Orange 1 F (68 C) Red 17 F (79 C) Yellow 200 F (9 C) Green 1 F (7 C) Orange 1 F (68 C) Red 17 F (79 C) Yellow 200 F (9 C) Green FINISH (See Note ) NATURAL BRASS CHROME D 1, 2,, 1, 2, NOTES: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.. Approved by the City of New York under MEA -01-E.. Where Polyester Coated Sprinklers are noted to be UL C-UL Listed, the sprinklers are UL C-UL Listed as Corrosion-Resistant Sprinklers. * Installed with Style 10 () or Style 0 (/ NPT) / Total Adjustment Recessed Escutcheon, as applicable. ** Installed with Style 20 () or Style 0 (/ NPT) 1/2 Total Adjustment Recessed Escutcheon, as applicable. *** Frame Deflector only. Listings approvals apply to color (Special Order). N/A: Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND.2 K-FACTOR S 1, 2 SIGNAL*** WHITE

Page 6 of 10 FINISH (See Note 8) K FACTOR TYPE TEMPERATURE BULB LIQUID COLOR NATURAL BRASS CHROME D SIGNAL*** WHITE LEAD COATED (TY21) (TY11) 1 F (7 C) Orange 1 F (68 C) Red 17 F (79 C) Yellow 200 F (9 C) Green 286 F (11 C) Blue 1 F (7 C) Orange 1 F (68 C) Red 17 F (79 C) Yellow 200 F (9 C) Green 286 F (11 C) Blue 1 F (7 C) Orange 1 F (68 C) Red 17 F (79 C) Yellow 200 F (9 C) Green 286 F (11 C) Blue 1 F (7 C) Orange 1 F (68 C) Red 17 F (79 C) Yellow 200 F (9 C) Green 286 F (11 C) Blue 1 F (7 C) Orange 1 F (68 C) Red 17 F (79 C) Yellow 200 F (9 C) Green 286 F (11 C) Blue 1 F (7 C) Orange 1 F (68 C) Red 17 F (79 C) Yellow 200 F (9 C) Green 286 F (11 C) Blue 1 F (7 C) Orange 1 F (68 C) Red 17 F (79 C) Yellow 200 F (9 C) Green 286 F (11 C) Blue 1, 2,,,, 6, 7 1, 2,,.6 (TY21)* Figure 10 1, 2,, N/A (TY21)** Figure 11 1, 2,,, N/A (TY21) (TY11) 1, 2,,,, 6, 7 1, 2, 8.0 / NPT (TY21)* Figure 12 1, 2, N/A (TY21)** Figure 1 1, 2,, N/A 8.0 (TY91) (TY81) 1, 2,,, 6 1, 2, NOTES: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/0) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed sprinklers.. Approved by the City of New York under MEA -01-E. 6. VdS Approved (For details, contact Tyco Fire Suppression & Building Products, Enschede, Netherls, Tel. 1--28-/Fax 1--28-77.) 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 09a/06) as Quick Response Sprinklers. 8. Where Polyester Coated Lead-Coated Sprinklers are noted to be UL C-UL Listed, the sprinklers are UL C-UL Listed as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers. * Installed with Style 10 () or Style 0 (/ NPT) / Total Adjustment Recessed Escutcheon, as applicable. ** Installed with Style 20 () or Style 0 (/ NPT) 1/2 Total Adjustment Recessed Escutcheon, as applicable. *** Frame Deflector only. Listings approvals apply to color (Special Order). N/A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS FOR.6 AND 8.0 K-FACTOR S

Page 7 of 10 FINISH K FACTOR TYPE NATURAL BRASS CHROME D SIGNAL WHITE LEAD COATED 2.8 (TY121) (TY111) (TY121) 17 PSI (12,1 BAR) N/A.2 (TY221) (TY211) (TY221) 17 PSI (12,1 BAR) N/A.6 (TY21) (TY11) 20 PSI (17,2 BAR) OR 17 PSI (12,1 BAR) (SEE NOTE 1) (TY21) 17 PSI (12,1 BAR) N/A 8.0 / NPT (TY21) (TY11) (TY21) 17 PSI (12,1 BAR) 17 PSI (12,1 BAR) N/A 8.0 (TY91) (TY81) 17 PSI (12,1 BAR) 17 PSI (12,1 BAR) NOTES: 1. The maximum working pressure of 20 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C-UL);, the Approval by the City of New York. Care Maintenance The TYCO Series must be maintained serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to TABLE C MAXIMUM WORKING PRESSURE corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers - before, during, after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section.) The owner is responsible for the inspection, testing, maintenance of their fire protection system devices in compliance with this document, as well as with the applicable stards of the National Fire Protection Association (e.g., NFPA 2), in addition to the stards of any other authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are recommended to be inspected, tested, maintained by a qualified Inspection Service in accordance with local requirements /or national codes. Care must be exercised to avoid damage to the sprinklers -before, during, after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section). Initial frequent visual inspections of rom samples are recommended for corrosion-resistant sprinklers to verify the integrity of the corrosion-resistant material of construction. Thereafter, annual inspections per NFPA 2 should suffice. Inspections of corrosion-resistant sprinklers are recommended at close range, instead of from the floor level per NFPA. Inspection at close range can better determine the exact sprinkler condition the long-term integrity of the corrosion-resistant material, which can be affected by the corrosive conditions present.

Page 8 of 10 /8±1/" (1,9±6, mm) (7,0 mm) 2-1/" DIA. /" (19,1 mm) 1/" (6, mm) (,2 mm) 1/2± (12,7±,2 mm) (7,0 mm) 2-1/" DIA. 1/2" (12,7 mm) 1/" (6, mm) (,2 mm) 1-/16" (, mm) 1/16" (20,6 mm) FIGURE 6 WITH TWO-PIECE / INCH TOTAL ADJUSTMENT STYLE 10 ESCUTCHEON 2.8 K-FACTOR, 1/2 INCH NPT 1-/16" (, mm) 1-1/16" (27,0 mm) FIGURE 7 WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 ESCUTCHEON 2.8 K-FACTOR, 1/2 INCH NPT /8±1/" (1,9±6, mm) (7,0 mm) 2-1/" DIA. /" (19,1 mm) 1/" (6, mm) (,2 mm) 1/2± (12,7±,2 mm) (7,0 mm) 2-1/" DIA. 1/2" (12,7 mm) 1/" (6, mm) (,2 mm) 1-1/" (1,8 mm) /" (19,1 mm) FIGURE 8 WITH TWO-PIECE / INCH TOTAL ADJUSTMENT STYLE 10 ESCUTCHEON.2 K-FACTOR, 1/2 INCH NPT 1-1/" (1,8 mm) 1" (2, mm) FIGURE 9 WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 ESCUTCHEON.2 K-FACTOR, 1/2 INCH NPT

Page 9 of 10 /8±1/" (1,9±6, mm) (7,0 mm) 2-1/" DIA. /" (19,1 mm) 1/" (6, mm) (,2 mm) 1/2± (12,7±,2 mm) (7,0 mm) 2-1/" DIA. 1/2" (12,7 mm) 1/" (6, mm) (,2 mm) 1-1/" (1,8 mm) /" (19,1 mm) FIGURE 10 WITH TWO-PIECE / INCH TOTAL ADJUSTMENT STYLE 10 ESCUTCHEON.6 K-FACTOR, 1/2 INCH NPT 1-1/" (1,8 mm) 1" (2, mm) FIGURE 11 WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 ESCUTCHEON.6 K-FACTOR, 1/2 INCH NPT /8±1/" (1,9±6, mm) (7,0 mm) 2-1/" DIA. /" (19,1 mm) 1/" (6, mm) (,2 mm) 1/2± (12,7±,2 mm) 2-1/" DIA. (7,0 mm) 1/2" (12,7 mm) 1/" (6, mm) (,2 mm) 1-/16" (, mm) 1/16" (20,6 mm) FIGURE 12 WITH TWO-PIECE / INCH TOTAL ADJUSTMENT STYLE 0 ESCUTCHEON 8.0 K-FACTOR, / INCH NPT 1-/16" (, mm) 1-1/16" (27,0 mm) FIGURE 1 WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 0 ESCUTCHEON 8.0 K-FACTOR, / INCH NPT RECESS RECESS (END "A" USED FOR 1/2" NPT MODELS) RECESS (END "B" USED FOR /" NPT MODELS) FIGURE 1 W-TYPE 6 PUSH IN TO ENSURE ENGAGEMENT WITH ING AREA FIGURE 1 W-TYPE 7

Page 10 of 10 P/N 7 XXX X XXX SIN FINISH TEMPERATURE RATINGS 0 2.8K (1/2 NPT) TY111 1 NATURAL BRASS 1 1 F (7 C) 1 2.8K (1/2 NPT) TY121 PURE WHITE (RAL9010)* 1 1 F (68 C) 0.2K (1/2 NPT) TY211 SIGNAL WHITE (RAL900) 17 17 F (79 C) 1.2K (1/2 NPT) TY221 JET BLACK (RAL900)** 200 200 F (9 C) 70.6K (1/2 NPT) TY11 71.6K (1/2 NPT) TY21 90 8.0K (/ NPT) TY11 91 8.0K (/ NPT) TY21 60 8.0K (1/2 NPT) TY81* 7 LEAD COATED 9 CHROME D * Eastern Hemisphere sales only. ** Available in only 2.8K,.2K, 8.0K, 1 F (68 C) 200 F (9 C); requires lead time to manufacture. 286 286 F (11 C) 61 8.0K (1/2 NPT) TY91* Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series (Specify SIN), (specify K-factor), (specify Pendent or Upright) Sprinkler (specify) temperature rating, (specify) finish or coating, P/N (specify from Table D) Recessed Escutcheon: Specify: Style (10, 20, 0, or 0) Recessed Escutcheon with (specify*) finish, P/N (specify*) Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 6-000-6-87 Specify: W-Type 7 Sprinkler Wrench, P/N 6-80--001 * Refer to Technical Data Sheet TFP770 TABLE D AND S PART NUMBER SELECTION GLOBAL HEADQUARTERS 100 Pennbrook Parkway, Lansdale, PA 196 Telephone +1-21-62-0700 Copyright 201 Tyco Fire Products, LP. All rights reserved. TEFLON is trademark of The DuPont Corporation.