Advance Split

Similar documents
AQUAHEAT ADVANCE SPLIT

PAC BT LOW TEMPERATURE HEAT PUMP WITH DHW TANK INCLUDED

HT V2 HT Split

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

Split inverter air-to-water heat pump CERTIFIED BY CERTITA. option 30/35-40/45

PAC BT LOW TEMPERATURE HEAT PUMP

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

SOLUTIONS DE TRAITEMENT HEATING SOLUTIONS. Comfort Module 5-20 kw. Choose the easy heating solution!

2017 HYDRONIC SYSTEMS MINI CHILLER FULL DC INVERTER. AIR-TO-WATER HEAT PUMP cooling - heating

AIR TO WATER HEAT PUMPS. Hot water and comfortable ambient temperature all year round

BLUEWAY DC INVERTER AIR TO WATER HEAT PUMP

30AW. Reversible Air to Water Heat Pump PRODUCT SELECTION DATA. Monobloc inverter. Compact, reliable and efficient. More than a Heat Pump

Technical data LA 60TUR+

50A KP 70A KP 90A KP 120A KP 150A KP 210A

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

Technical data LA 9S-TU

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

Компрессорно-конденсаторные агрегаты. Chiller. AQH DCI 20 to 30. Air Cooled Water Inverter Heat Pump Engineering Data Manual. 20 to 30 kw.

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

Technical data LA 28TBS

PRODUCT GUIDE

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

Neosys Product catalogue

AGEO CALEO. Water-to-water high temperature heat pumps USE RANGE DESCRIPTION. Designed to replace a conventional boiler and produce domestic hot water

Product Line Introduction. Karl Zhang Technical support engineer

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser

Technical data LA 60TU

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017


CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

Tower Green HE Hybrid

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

Do you want a versatile solution

PHOENIX PNX DCI WALL MOUNTED RANGE AN AIRWELL GROUP COMPANY

Refrigerant R407C CW-AR. 2.4 to 3.1kW. Water Source Heat Pumps - Vertical Mounting Version Models 07 to to 2.7kW

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

High temperature air-to-water heat pumps

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY

BRAN Residential chillers and heat pumps. Reversible unit, air source for outdoor installation 4,81-27,2 kw <<< BACK INDEX.

AUDAX Air-water heat pumps reversible with inverter single and three-phase

ALFÉA EXCELLIA DUO. more. less AIR TO WATER HEAT PUMP

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

LZA High efficiency air to water heat pumps with HP compressor

TOSHIBA AIR CONDITIONING

30RBV/30RQV Inverter Air-Cooled Liquid chillers & Reversible Air to Water Heat Pumps PRODUCT SELECTION DATA INSTALLATION, OPERATION AND

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING

History List. Version Date Update Information New EHS SPLIT TDB Released. (Modify the Spec Note)

HIWARM kw. Air-water system with external and internal BLDC unit. Total heat recovery multi-purpose units HIWARM PLUS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

LZT High efficiency air to water heat pumps with E.V.I. compressors

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

Aquaflair TRAC-TRAF-TRAH

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING

30RQV NEW. Nominal cooling capacity kw Nominal heating capacity kw AIR-TO-WATER HEAT PUMPS HEATING. Easy and fast installation

.2 Section Waste Management and Disposal.

Air / Water Heat Pump - Compact Design Modulating 8 18 kw

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

VARIABLE REFRIGERANT FLOW (VRF) FULL LINE CATALOG

H4T R410A. refrigerant

Air to water Heat Pump System

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW

Starting current with soft starter Fuse protection

80HMA. Comfort Module Range for Monobloc Heat Pumps. Compact comfort module. DHW management possibility. Multi zone option control.

OLIMPIA SPLENDID S INVERTER DC TECHNOLOGY 100% 80% 70% DC INVERTER AC INVERTER NON INVERTER

PRODUCT RANGE HEAT PUMPS 2012

MAC N-407 Air-Cooled Chiller

CHAPTER 6 CONDENSING UNITS

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

CENTRAL SPLIT UNIT UNIC

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS

ELFOEnergy Extended Inverter

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

Blue Box Epsilon Echos +

80HMA. Comfort Module Range for Monobloc Heat Pumps. Nominal heating capacity 4-20 kw Nominal cooling capacity 4-20 kw. Features

SUBMITTAL DATA - OUTDOOR UNIT VEP075N432G VRF HEAT PUMP

CRIMSON & CRIMSON MAX

1

Starting current with soft starter Fuse protection. Connection heating Seal of approval MCS (valid until)

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

WZT High Efficiency Air to Water Split System Heat Pumps With E.V.I. Compressors

Air-to-Water Heat Pump (50Hz, R410A) 5BPM0-01G (Replace: 5BPM0-01F)

MACH N-407 Heat Pump Air-Cooled Chiller

Air to water Heat Pump System

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

ELFOEnergy Duct Inverter

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series

30RB/RQ Air-Cooled Liquid Chillers/Air-to-Water Heat Pumps. product selection data

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

Transcription:

Engineering Data Manual Aqu@Scop Advance Split Air-to-Water DC Inverter Split Heat Pumps Models 005, 008, 012 & 014 2 to 16 kw

Strength Points Most efficient heating technology with variable speed compressor. Gaining of sustainable renewable thermal energy from ambient outdoor air. Use of DC Inverter technology in both compressor and outdoor fan motor to adapt the unit capacity to the building heat demand. Energy saving : By avoiding compressor start-up and shutdown phases, DC Inverter enables unit to run continuously while modulating the compressor output in relation to the set temperature on part load. Silent running : Most of the time, unit is running at reduced speed. Quick reach of set temperature : DC Inverter starts with maximum speed to reach set temperature as quick as possible. Once the temperature setpoint is reached, the inverter will reduce and adapt speed according to the capacity needed only. Variable capacity : from 30 to 110% of nominal capacity. Great accuracy in maintaining the desired water temperature setpoint. Unit optimized in heating mode for radiator, fan coil and floor applications. High feed water temperature for domestic hot water (DHW). High efficiency COP values (unit designed and developed to meet Ecodesign Lot 1 and Ecolabel requirements) : - Air : 2 C / Water : 35 C, COP > 3.1 - Air : 7 C / Water : 35 C, COP > 4.1 High performance at partial load; high SCOP and SEER values measured according to new standard pren14825 and EN14511. Bi-flow electronic expansion valve ensures optimized filling of refrigerant in evaporator. Outdoor coil with blue fins (hydrophilic coated fins), facilitating the flow of condensates and providing corrosion protection to maintain performance levels and increase the life time. Wide operating limits : - Min. outdoor ambient temperature of -15 C - Max. leaving water temperature of 55 C Outdoor unit (ODU 1) - Advance split 005 Outdoor unit (ODU 2) - Advance split 008 Outdoor units (ODU 3 & 4) - Advance split 012 & 014 Indoor units (IDU 1 & 2) - Advance split 005 to 014 2

Specifications General The new family Aqu@Scop ADVANCE SPLIT R410A covers a capacity range from 2 to 16 kw, developed in 4 different sizes. This system is composed by an outdoor unit connected, through refrigerant pipes, to an indoor hydronic module that can be fitted in an hydraulic circuit to cover space heating and domestic hot water requirement of the building. To satisfy different application, hydronic module has been developed in 2 versions : First one is an heating/cooling version with auxiliary back-up electrical heater for "stand alone" application; Second one is an heating only version (without electrical heater) that can be fitted in an existing heating system with a 2nd heat generator (for example a fossil fuel boiler), to form a hybrid system. The outdoor unit uses the inverter technology "DC sinewave" that permits to achieve a continuous variable capacity depending on building load, an important advantage considering that heat pumps run 95% of the time in part load conditions. This implements a higher seasonal efficiency SCOP, reduced CO 2 emission and lower yearly operating cost with a higher comfort. The outdoor unit has been optimized for heating application, in order to reach high COP level higher than Ecolabel requirements for radiator, fan coil and floor heating applications. The feed water temperature of the heat pump to the system can be chosen between 35 C (LT), 45 C and 55 C (MT). Defrost algorithm optimization and blue fin coil on whole range are other 2 key factors that permits very high performances also at lower outdoor ambient temperature, down to -15 C. The system is optimized for average climate at +2 C ambient. The outdoor unit is available in 4 sizes (capacity at nominal point A7W35) : ODU 1 (5.3 kw), ODU 2 (8.1 kw), ODU 3 (12 kw), ODU 4 (14.5 kw). The indoor unit is available in 2 sizes : IDU 1 (5.3 to 8.1 kw), IDU 2 (12 to 14.5 kw). Depending on matching indoor and outdoor units, the following system combinations are possible : Outdoor unit Cabinet and structure : The unit cabinet and structure are made of galvanized steel elements assembled through tropicalized steel screws. All the galvanized steel parts are protected by polyester enamel, which makes the unit corrosion-proof and weatherproof. Compressor : Compressor is DC Inverter rotary (size 005), twin rotary (size 008) and scroll (sizes 012 & 014) type equipped with internal motor protection. Compressor is mounted on rubber vibration isolators and packed into sound insulation jacket, in order to eliminate vibration transmissions and noise. Motor is of direct start type, cooled by suction gas. Air/Refrigerant heat exchanger : Coil is made of copper tubes arranged in staggered rows and mechanically expanded into aluminium finned pack composed of blue fins. Fans : Fans are direct coupling propeller type, equipped with plastic aerodynamic blades to ensure better balance, enhance exchange process and generate very low sound level, Lw (power)<64 dba. Each fan is provided with a plastic safety guard. Motors are DC Inverter type equipped with thermal protection. A fan speed controller is provided to allow the unit to operate with ambient temperature from -15 to +45 C. Refrigerant circuit : Each unit is supplied with an electronic expansion valve (EEV) and reversing valve as well as other refrigerant components as shown in the functional diagrams (see section "Refrigerant flow diagrams"). The outdoor unit is burst-pressure safe and is in conformity with CE standard EN 378. ODU 1 ODU 2 ODU 3 ODU 4 IDU 1 IDU 2 IDU 1 IDU 2 The unit is equipped with advanced driver and EEV software to eliminate unefficient superheat on the outdoor coil, to better control the variable refrigerant flow at full and part load conditions, and to increase the gain of free heat from the ambient. The unit is slipped with full refrigerant charge to eliminate refrigerant charging on site. The refrigerant charge is lower than 3 kg to satisfy the European F-Gas regulation. 3

Specifications (continued) Indoor unit Hydraulic connections are located at bottom side. Cables leave the unit at the top. Main components in the hydraulic module are : Water pump (3 speed), Brazed plate heat exchanger, Communication between indoor and outdoor units The communication between indoor unit and outdoor unit is managed by the AVI-board, which is integrated in the indoor unit. On the AVI-board are connected two temperature sensors, suction gas and water, and one refrigerant pressure sensor. The AVI board is a gateway which permits the communication between the intelligence of IDU and ODU. 3-way valve for heating/dhw operation, Water expansion vessel, Control, Freeze protection, Electrical heater on "cooling/heating" version, Water pressure gauge, Water safety valve, Air vent valve. Control features The management system control board is fitted inside indoor unit and communicate (via bus connection) with outdoor unit through gateway. This system control can manage following feature : PID control on leaving water temperature, Manage priority between domestic hot water and heating system need driving a 3 way water valve included into the IDU, Options and accessories Room thermostat, Domestic hot water tank, Electrical back up heater (Heating only). Advanced user interface display, Manage diagnostic and logging for both IDU and ODU units, Hybrid configuration possible. Control panel - User interface 4

Example of Applications "Stand alone" mono energetic application Aqu@Scop system for space heating, domestic hot water and cooling (cooling/heating indoor unit version) for residential application with floor heating, fan coil or radiator systems or as a mixed zone system. Hybrid application with zoning Aqu@Scop system for 2 zone space heating, domestic hot water (heating only IDU version) for bivalent operation in combination with a fossil fuel boiler and buffer tank. M M 5

Refrigerant Flow Diagrams of Outdoor Units ODU 1 and ODU 2 - Refrigerant flow direction in heating mode OAT Reverse valve OCT OMT Outdoor coil temperature Outdoor coil middle temperature OAT Outdoor air temperature CTT Compressor discharge temperature FAN Strainer Compressor CTT OMT EEV Strainer Outdoor coil OCT Accumulator ODU 3 and ODU 4 - Refrigerant flow direction in heating mode OAT FAN Strainer Compressor Reverse valve CTT HPS OCT OMT OAT CTT HPS Outdoor coil temperature Outdoor coil middle temperature Outdoor air temperature Compressor discharge temperature High pressure switch OMT EEV Strainer Outdoor coil OCT Accumulator 6

Refrigerant and Water Flow Diagrams of Indoor Units Heating only 8 LWT θ 5 1 Temperature sensor (return hot water) 2 Pump 3 Temperature sensor (leaving hot water) AVI 4 3-way valve (domestic hot water/space heating) 5 Manual air vent valve 6 Water pressure gauge 7 Expansion vessel 1 θ 8 Indoor plate heat exchanger ρ PS θ LRT 2 θ 3 P 6 9 Water safety valve AVI Interface gateway LWT Temperature sensor (leaving water temperature, AVI board kit) IRT Temperature sensor (inlet refrigerant temperature, AVI board kit) PS Pressure sensor (liquid line, AVI board kit) 7 a & b Refrigerant 4 M c d e DHW feed water Return water Space heating feed water 9 a b c d e Heating and cooling 8 LWT θ 5 1 Temperature sensor (return hot water) 2 Pump 3 Temperature sensor (leaving hot water) AVI 4 3-way valve (domestic hot water/space heating) 5 Manual air vent valve 6 Water pressure gauge ρ PS θ LRT 1 θ 2 10 θ 3 P 6 7 Expansion vessel 8 Indoor plate heat exchanger 9 Water safety valve 10 Electrical backup heater AVI Interface gateway LWT Temperature sensor (leaving water temperature, AVI board kit) IRT Temperature sensor (inlet refrigerant temperature, AVI board kit) 7 PS Pressure sensor (liquid line, AVI board kit) 4 M 9 a & b c d e Refrigerant DHW feed water Return water Space heating feed water a b c d e 7

Operating Limits Heating mode 60 55 Leaving water temperature ( C) 50 45 40 35 30 25-20 -15-10 -5 0 5 10 15 20 25 30 35 40 Outdoor air temperature ( C) Cooling mode 28 26 24 Leaving water temperature ( C) 22 20 18 16 14 12 10 8 6 4 10 15 20 25 30 35 40 45 50 Outdoor air temperature ( C) 8

Technical Data - Outdoor Units Aqu@Scop models advance split 005 advance split 008 advance split 012 advance split 014 Outdoor unit ODU 1 ODU 2 ODU 3 ODU 4 Heating capacity kw 1.2 5.7 2.0 9.5 5.3-13.5 6.0 16.0 Heating capacity at nominal point A 7/W 35 kw 5.30 8.10 12.00 14.50 COP (according to EN 14511) at A 7/W 35 4.25 4.10 4.40 4.30 Cooling capacity kw 2.4-5.0 3.0-9.0 5.3-13.5 8-15 Cooling capacity at nominal point A 35/W 18 kw 4.40 8.60 12.0 14.0 EER at A35/W18 3.61 3.62 3.80 3.61 Sound power Outdoor unit (according to DIN EN 12102) at A 7/W 35 db(a) 59 62 63 64 Limits of use (heating) Max leaving water temperature at A 2 C C 55 55 55 55 Max leaving water temperature at A -15 C C 55 55 55 55 Min. outdoor air temperature C -15-15 -15-15 Max. outdoor air temperature at W 55 C 35 35 35 35 Limits of use (cooling) Max. outdoor air temperature C 45 45 45 45 Min. outdoor air temperature C 15 15 15 15 Min. leaving water temperature at A 40 C 5 5 5 5 Max. leaving water temperature at A 40 C 25 25 25 25 unit Domestic hot water Temperature at A2 inside tank > 50 C heat pump only Voltage heat pump 230 V / 1/50 Hz Compressor DC Inverter Expansion valve Electronic expansion valve Factory refrigerant charge R410A g 1200 2150 2950 2950 Max. distance between units (as nominal refrigerant charge) m 12.5 (single length) Min. distance between units (as nominal refrigerant charge) m 3.0 (single length) Max. distance between units m 25 30 30 30 Max. height difference between units m 10 15 15 15 Condensate flow Bottom Outdoor evaporator coil Hydrophilic fins Outdoor fan speed Variable dimensions and weight Max. dimensions (height x length x depth) mm 610 x 870 x 290 865 x 1040 x 340 1255 x 900 x 340 1255 x 900 x 340 Weight (including refrigerant) kg 60 70 110 110 Connections refrigerant side Liquid line 1/4" 3/8" 3/8" 3/8" Discharge line 1/2" 5/8" 5/8" 5/8" conformity with standards Standards RoHS conform EN 14511 pren 14825 Ecodesign Lot 1 EN 60335-1, EN60335-2-40, EN 378 A : Source side outdoor air temperature. W : Sink side water temperature. 9

Technical Data - Indoor Units Heating only Aqu@Scop models advance split 005 & 008 advance split 012 & 014 Indoor unit IDU 1 IDU 2 Heating capacity kw 1.2 up to 9.5 5.3 up to 16 Heat exchanger Type Plate heat exchanger Application Condenser for R410A Number of plates 26 44 Volume inner circuit (theoretical value) litre 1.33 2.33 Refrigerant distributor Yes Yes Safety valve (heating circuit) Open at 2.5 bar Manometer (heating circuit) Integrated Electrical backup heater Optional, 9 kw (3 stage) Heating circuit pump consumption @ stage 3/2/1 W 132/92/62 under ~ 230 V 3 way Valve integrated Function Change from domestic water to heating circuit Type ~ 230 V / spring return Mechanical expansion vessel (capacity) litre 10 Dimensions and weight Height x Length x Depth mm 850 x 480 x 360 Weight (without water) kg 30 35 Connection (water) Outlet (heating site), outlet (Domestic hot water site), common inlet G 1 ¼ (threaded) Connection (refrigerant) Liquid line 3/8" 3/8" Discharge line 5/8" 5/8" Color White Factory charge of the refrigerant side Nitrogen / 1 bar overpressure conformity with standards Standards RoHS conform, EN 60335-1, EN60335-2-40, EN 378 Heating and cooling Aqu@Scop models advance split 005 & 008 advance split 012 & 014 Indoor unit IDU 1 IDU 2 Heating capacity kw 1.2 up to 9.5 5.3 up to 16 Cooling capacity kw 2.4 up to 9.0 5.3 up to 15 Heat exchanger Type Plate heat exchanger Application Condenser/Evaporator for R410A Number of plates 26 44 Volume inner circuit (theoretical value) litre 1.33 2.33 Refrigerant distributor Yes Yes Safety valve (heating circuit) Open at 2.5 bar Manometer (heating circuit) Integrated Electrical backup heater 9 kw (3 stage) Heating circuit pump consumption @ stage 3/2/1 W 132/92/62 under ~ 230 V 3 way Valve integrated Function Change from domestic water to heating circuit Type ~ 230 V / spring return Mechanical expansion vessel (capacity) litre 10 Dimensions and weight Height x Length x Depth mm 850 x 480 x 360 Weight (without water) kg 35 40 Connection (water) Outlet (heating site), outlet (Domestic hot water site), common inlet G 1 ¼ (threaded) Connection (refrigerant) Liquid line 3/8" 3/8" Discharge line 5/8" 5/8" Color White Factory charge of the refrigerant side Nitrogen / 1 bar overpressure conformity with standards Standards RoHS conform, EN 60335-1, EN60335-2-40, EN 378 10

Electrical Data - Outdoor Units Aqu@Scop models advance split 005 advance split 008 advance split 012 advance split 014 Outdoor unit ODU 1 ODU 2 ODU 3 ODU 4 Outdoor unit Power supply 1/N/PE/230 V~/50 Hz 1/N/PE/230 V~/50 Hz 1/N/PE/230 V~/50 Hz 1/N/PE/230 V~/50 Hz Control unit (ODU) Voltage, control unit / electronics 1/N/PE/230 V~/50 Hz 1/N/PE/230 V~/50 Hz 1/N/PE/230 V~/50 Hz 1/N/PE/230 V~/50 Hz Max. power control unit W 150 150 150 150 Max. power consumption internal fans W 65 70 130 130 Fuse (internal) A 3.5 3.5 3.15 3.15 Heat pump Power supply 1/N/PE/230 V~/50 Hz 1/N/PE/230 V~/50 Hz 1/N/PE/230 V~/50 Hz 1/N/PE/230 V~/50 Hz Rated current (Nominal A7/W35) A 5 9 10 15 Starting current A 10.5 15 10 10 Power input - Maximum kw 1.5 3.1 4.6 5.8 Circuit breaker rating A 20 25 25 32 Fuse A 20 25 25 32 Cable section mm 2 3 x 2.5 3 x 2.5 3 x 4 3 x 6 Max. cable length m 25 25 25 30 Heating power input - Nominal (A2/W35) kw 0.92 1.87 2.24 3.25 Heating power input - Nominal (A7/W35) kw 0.96 1.95 2.34 3.43 Cooling power input - Nominal (A35/W7) kw 1.08 2.40 2.69 3.72 Cooling power input - Nominal (A35/W18) kw 1.13 2.63 2.80 4.23 Electrical Data - Indoor Units Aqu@Scop models advance split 005 & 008 advance split 012 & 014 Indoor unit IDU 1 IDU 2 Indoor unit Power supply 1/N/PE/230 V~/50 Hz 1/N/PE/230 V~/50 Hz Electronics max. rated power consumption W 1000 1000 Max. power control unit W 5 5 Max. power consumption internal pumps W 132 132 Fuse (internal) T 6.3 A / 250 V T 6.3 A / 250 V Fuse 1 x B16A 1 x B16A Cable section mm 2 3 x 1.5 3 x 1.5 electric heater (optional) Rated voltage 1/N/PE/230 V~/50 Hz or 3/N/PE/400 V~/50 Hz 1/N/PE/230 V~/50 Hz or 3/N/PE/400 V~/50 Hz Capacity kw max. 9 max. 9 Fuse 3 x B16A 3 x B16A Degree of protection IP20 IP20 Cable section 400 V ~ (phase symmetrical/ asymmetrical) mm 2 5 x 2.5 5 x 2.5 Cable section 230 V ~ (phase asymmetrical) mm 2 7 x 2.5 7 x 2.5 Max. cable length m 25 25 11

Performance Data Aqu@Scop models advance split 005 advance split 008 advance split 012 advance split 014 A7W35 A2W35 * A-7W35 * A12W35 Nominal heating capacity kw 5.30 8.10 12.00 14.50 Nominal COP 4.25 4.10 4.40 4.30 Total power input kw 1.25 1.98 2.73 3.37 Capacity range min - max. kw 1.2-5.7 2-9.5 5.3-13.5 6.0-16.0 Heating capacity kw 3.50 6.20 9.00 11.00 COP 3.15 3.20 3.25 3.20 Heating capacity kw 3.50 5.89 8.91 9.41 COP 2.65 2.32 2.55 2.50 Heating capacity kw 5.65 8.46 12.6 15.66 COP 4.51 4.39 4.71 4.58 A-15W35 * Heating capacity kw 1.66 3.35 4.5 5.82 A7W55 A2W55 A-7W55 * A12W55 A7W45 A35W18 A35W7 Heating capacity kw 3.63 5.92 9.12 12.08 COP 2.71 2.16 2.61 2.39 Heating capacity kw 2.63 5.05 7.14 8.57 COP 2.09 1.94 2.11 2.06 Heating capacity kw 2.03 3.77 5.02 6.51 COP 1.68 1.54 1.56 1.53 Heating capacity kw 3.98 6.55 10.0 13.43 COP 2.95 2.37 2.87 2.67 Heating capacity kw 4.41 6.73 10.17 12.97 COP 3.51 2.95 3.53 3.10 Nominal cooling capacity kw 4.40 8.60 12.00 14.00 Nominal EER 3.61 3.62 3.80 3.61 Cooling capacity kw 4.00 6.20 7.50 10.10 EER 2.80 2.80 2.80 2.60 Note : All data measured according to EN 14511 with pump included. * : With deicing. 12

Heat Pump Available Pressure Curves Heating only version - Sizes 005 & 008 Available pressure (mbar) Heating only version - Sizes 012 & 014 700 Speed 3 600 Speed 2 500 400 Speed 1 300 200 100 0 0.00 0.50 1.00 1.50 2.00 2.50 Water flow (m 3 /h) Available pressure (mbar) 700 Speed 3 600 Speed 2 500 400 Speed 1 300 200 100 0 0.00 0.50 1.00 1.50 2.00 2.50 3.00 Water flow (m 3 /h) Heating and cooling version - Sizes 005 & 008 Available static pressure (mbar) 700 Speed 3 600 Speed 2 500 400 Speed 1 300 200 100 0 0.00 0.50 1.00 1.50 2.00 2.50 Heating and cooling version - Sizes 012 & 014 Water flow (m 3 /h) Available pressure (mbar) 700 Speed 3 600 Speed 2 500 400 Speed 1 300 200 100 0 0.00 0.50 1.00 1.50 2.00 2.50 3.00 Water flow (m 3 /h) 13

1255 mm Dimensions Outdoor units Advance split 005 Advance split 008 610 mm 865 mm 290 mm 870 mm 1040 mm 340 mm Advance split 012 & 014 900 mm 340 mm 14

Dimensions (continued) Indoor units 1 & 2 - Advance split 005 to 014 480 mm 360 mm 850 mm Minimum Clearances - Outdoor Units B Air inlet A C D Air outlet Models Dimensions in mm A B C D Advance split 005 100 100 300 1000 Advance split 008 100 100 300 1000 Advance split 012 100 200 300 1000 Advance split 014 100 200 300 1000 15

Ref. : EDM AQHAS-A.2GB/07.12 - Supersedes : EDM AQHAS-A.1GB/10.10 As part of our ongoing product improvement programme, the technical data and colours of our products are subject to change without prior notice. Non contractual photos. www.airwell.com AIRWELL France SAS 1bis, Avenue du 8 mai 1945 - Saint Quentin en Yvelines 78284 GUYANCOURT - France Tel. +33 (0)1 39 44 78 00 Fax +33 (0)1 39 44 65 17