Refrigeration System Report March 2017

Similar documents
Executive Summary. Number of Low Number of High Number of Faults , Number of OK

Public Services Building 155 N First Avenue Hillsboro, OR March 2012

Parilla Thermal Storage Project Case Study. May Page 1 of 11

PS & GPS SERIES PARALLEL RACK REFRIGERATION SYSTEMS

Energy consumption storage facilities examined in ICE-E

Copeland Scroll Outdoor Refrigeration Unit

Use of transcritical CO 2 in industrial applications

Copeland Scroll. Product Information. Outdoor condensing units for refrigeration applications

Application Engineering

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Commercial Refrigeration

Energy Performance of Low Charge NH3 Systems in Practice. Stefan S. Jensen

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017

July 2012 was a significant date for the HVAC and Refrigeration industry as it saw the introduction of the Carbon Tax and the HFC Levy.

Small Applications with Ammonia

5. ASSESSMENT RECOMMENDATIONS

Technical Information

System Design, Commissioning, Operation

The Energy Mist System

ABSTRACT. 2 CanmetENERGY

ACCENT AIR WATER TO WATER COMMERCIAL HEAT PUMPS

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

AE R20 January Cooling Requirements for Copelametic and Copeland Discus Compressors

THERMAL ICE STORAGE: Application & Design Guide

Study Final Report. Priority Cool Refrigerant Study

DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA

Partial Load Performance Of Refrigeration System

Measurement and modelling of a multifunctional solar plus heatpump system from Nilan. Experiences from one year of test operation.

Application Engineering

Installation and Operation Guide For

The R-404A Challenge. Commercial Opteon Refrigerant Solutions - The New Industry Standard

Pack Calculation Pro. Users guide. Version Morten Juel Skovrup

TRENDS IN RETAIL INDUSTRY REFRIGERATION & REVIEW OF EUROSHOP 2017 EXHIBITION

Checking the Charge on a Heat Pump in the Winter

Technical Information

Understanding Head Pressure Control. Walter H Langille, M.A.Sc., P.Eng Sales Engineer KeepRite Refrigeration

A Complete Line Of Remote Rack Refrigeration Systems

500 EX Fusion Compressor Series

Energy Use in Refrigeration Systems

Outdoor Condensing Unit - ZX Range. High Efficiency In Compact Design

APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller

Process glycol chillers

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications

commercial refrigeration products

Environmentally friendly systems for convenience stores

Case 8 Basic Performance of Screw Compressor

Closing the Loop What s best for your system?

Brazed Plate Heat Exchanger for CO Applications

Frequency Inverters to save energy. ASERCOM EPEE Symposium. John P. Gibson ASERCOM WG Inverter. Nuremberg,

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

Outdoor Refrigeration Unit - ZX Range High Efficiency In Compact Design

REFRIGERATION EQUIPMENT SCOPE - QUESTIONNAIRE

Understanding Applications for Alternative Refrigerants

DROP-IN + PLUG-IN UNITS

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

Installation and Operation Guide For MCF-49FD, MCF-23FD MCR-49FD, MCR-23FD

DeCA DESIGN CRITERIA HANDBOOK PRODUCT REFRIGERATION SYSTEM

SERVICE ASSISTANT OVERVIEW FDSI Online Training

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

On Balance: Heat Rejection Control a Packaged Solution

MAXIMUM SERIES. Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 70 F chilled water.

SUBCRITICAL & TRANSCRITICAL SYSTEMS

Copeland Scroll ( HP) ZB*KA and ZF*KA for Refrigeration

PRESSURE INDEPENDENT CONTROL VALVE TECHNOLOGY. 3/16/2012 Fred Ferrara 1

PRICE CHOPPER SARATOGA, NY. First cascade supermarket system in North America Installed and Started March of 2008

BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION. Business Name. Site physical address (Street, Suburb, City)

B. A. T. Basic Appliance Training

Air Conditioning Inspections for Buildings Condensers

REFRIGERATION EQUIPMENT SCOPE - QUESTIONNAIRE

Frequency Inverters to save energy. ASERCOM Association of European Refrigeration Component Manufacturers Annual Convention 2016

Kawasaki centrifugal chiller using water as a refrigerant. Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto

SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.

A Treatise on Liquid Subcooling

Wal-Mart HE.5 Supercenter

Transcritical CO2 Bottle Cooler Development

Application of a hybrid control of expansion valves to a 3-ton large room cooling system

Thermography Inspection SAMPLE REPORT

COOLING / HEATING COILS

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL

Distributed Systems Sales Brochure

Case 13 Food Storage & Processing Center

DX SERIES DIRECT EXPANSION ENERGY SAVING AIR DRYER

MicroTech Series-200 Flooded Screw Chiller

Mechanical Redesign, Proposal Elizabeth C. Krauss Mechanical Option September 18, 2013

Liebert CSU3000 Chiller

THE INSTITUTE OF REFRIGERATION

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

investment in R&D, the commitment to - name.

NATURAL REFRIGERANT SYSTEMS

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

Aprilaire Dehumidifier Troubleshooting Manual Models 1830, 1850, 1870

PAC, NQAC, HQAC, SQAC, EQAC AIR-COOLED CONDENSERS OPERATING AND INSTALLATION INSTRUCTIONS

2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment. AHRI Guideline T (I-P)

Development of multi-function CO2 Heat Pump Water Heater

Transcription:

New Seasons Market 7703 SW Nyberg Street Tualatin, OR 97062 Refrigeration System Report March 2017 Commissioning done by: N/A Manufacturer: Contractor: Report published by: Roupen Ohannessian, ClimaCheck Sweden AB Sean McCaffery, Emerging Energy Solutions

Executive Summary The refrigeration system installed at the New Seasons Market located in Tualatin, Oregon was monitored by the ClimaCheck Analyzer beginning February 21, 2017 to March 16, 2017. The purpose of the measurement was to help the customer understand how the system is currently operating and understanding how much this system is using in kwh demand. The date which was chosen to focus on was March 15 th at 11:09 am. There is no specific reason for this time, other than it representative of a normal business day. The total energy consumption for this plant is on average 600 kwh per day (MT compressors - 300 kwh, LT compressors is 200 240 kwh, Evap Tower 100-140 kwh). The LT and MT systems do not have consistent stable operation. This is caused by the poor fan operation in the evaporative condenser. The condensing strategy of the condenser should be looked at as condensing temperature fluctuates 10-20F. There is a significant amount of savings that can be achieved by correcting this operation. For every 1F degree of reduction in condensing temperature will result into 1-2% lower energy consumption. Further evaluation should be taken on the mechanical devices for each chiller and the subcooler for the LT rack. It is not 100% clear if these devices are working as designed or if there are upgrades needed to improve the efficiency of operation.

Contents Executive Summary... 1 Background... 3 1. System Design... 3 1.1 System Layout... 3 1.1.1 Medium Temperature Rack... 3 1.1.2 Low Temperature Rack... 4 2. Energy Consumption... 5 2.1 Energy Consumption Medium Temp - Total... 5 2.1.1 Energy Consumption Medium Temp Compressors... 5 2.1.2 Energy Consumption of Evaporation Tower... 6 2.2 Energy Consumption Low Temperature Compressors... 7 3. Unstable Fan Control... 7 4. Medium Temperature System... 8 4.1 High Condenser Approach... 9 4.2 High Discharge Temperature on Compressor one.... 4 5. Low Temperature System... 11 5.1 High Condenser Approach... 12 5.1.1 High Pressure... 13 5.1.2 Evaporation.14 6 Heat Reclaim.14 7 Suction Header of the Medium Temperature 15

Background This report is based on the operation of both the LT and MT Racks located at the New Seasons Market located in Tualatin, Oregon. The report will outline current operation and any deficiencies identified from our monitoring. 1. System Design Nyberg Rivers Medium Temperature refrigeration is provided by a multi- compressor system with a secondary glycol loop circulated thru all MT Cases. The low temperature refrigeration is provided by a standard multi-compressor DX rack with a sub cooler heat exchanger cooled by the MT rack. Each rack is independently controlled by an Emerson CPC controller. Medium Temperature Compressors Low Temperature Compressors Copeland Discus 3D 3DSDS12ML-TFD-C41 Digital Copeland Discus 2D 2DL3F20KL-TFD-C41 Copeland Discus 4D 4DJNR28ML-TSK-C55 Copeland Discus 3D 3DBDF33KL-TFD-C41 Digital Copeland Discus 4D 4DRNR28ML-TSK-C55 Unloader Copeland Discus 3D 3DF3F40KL-TFD-C41 Copeland Discus 4D 4DJNR28ML-TSK-C56 As noted above, each rack has a digital unloader, while the MT has a secondary mechanical unloader on compressor three. Both Racks use a water evaporative condenser. 1.1 System Layout 1.1.1 Medium Temperature Rack

1.1.2 Low Temperature Rack

2. Energy Consumption 2.1 Energy Consumption Medium Temp - Total In the following graph, Yellow line shows ambient temperature, red line is energy signature at prevailing outdoor temperature. Red bars are measured energy consumption. Evaporation tower and medium temperature compressors are included in the MT total. At the beginning of the monitoring the system was using 400kWh on average. After March 7 th the usage increased to 500kWh on average. Ambient temperature does contribute to this increase. 2.1.1 Energy Consumption Medium Temp Compressors Energy consumption can be separated between compressors and condenser fans. The below graph shows the energy usage for the compressors. During this period it is shown that the compressors use the majority of the energy usage with an average daily usage of 300 kwh per day. The same increase of usage is shown from March 7 th to the end of the monitoring period.

New Seasons Market Nyberg River System Compressor Energy 2.1.2 Energy Consumption of Evaporation Condenser Energy consumption is between 100 140 kwh. Condenser Energy

2.2 Energy Consumption Low Temperature Compressors Shown below, the Low Temperature compressors appear to consume the same amount of energy on a daily basis. Average use is between 200 240 kwh per day. 3. Unstable Fan Control In the following graph it is shown the fan control and how unstable it is. It will be shown in the following sections how this fan control is creating an unstable operation in both systems. As shown in orange this unstable operation affects the whole system, and decreases its reliability.

4. Medium Temperature System Below the Medium Temperature rack is in a constant stage of temperature and pressure changes. The system does not achieve a stable operation during the 24 hours outlined in the this graph.

4.1 High Condenser Approach There is a large difference between the condensing temperature of the MT system and the outdoor temperature, as shown below. The condensing temperature on the LT system behaves similarly. An increased condensing temperature as seen below significantly increases the power consumption of the system.

4.2 High Discharge Temperature on Compressor one. Compressor 1 of the Medium Temperature system is a digitally controlled compressor. This compressor is showing higher than normal discharge temperatures. A digital discus compressor will have up to a 15-20F higher discharge at low load. This compressor is showing at times a 50F higher discharge indicating low efficiency. This, with the small changes in the total compressor s power leads is likely caused by the running near minimum capacity for long periods of time which reduces the efficiency of the compressor and higher temperatures increase stress on compressor and oil. The controls should be looked at closer to see how compressor 3 is interacting with comp 1. Compressor 3 has a mechanical unloader and could be causing compressor 1 to run so hot. It should also be noted that the Compressor 3 discharge temperature is not decreasing as much as the others, when turned off.

5. Low Temperature System The Low Temperature System shows the same behavior on the condenser side as the Medium Temperature Rack since this rack shares the same evaporative condenser. Below the Low Temperature rack is in a constant stage of temperature and pressure changes. The system does not achieve a stable operation during the 24 hours outlined in the this graph.

5.1 High Condenser Approach As like the Medium Temperature Rack, the Low Temperature also has a very large difference between the condensing temperature of the Low Temperature system and the outdoor temperature, as shown below. Increasing the condensing temperature significantly increases the power consumption of the system.

5.1.1 High Pressure In the below graph it is shown how unstable the High Pressure is. Pressure fluctuates as much as 40 psi on both the LT and MT racks.

5.1.2 Evaporation Temperature Evaporation temperature on the LT rack fluctuates 10 15F throughout the day. Fluctuations are affected by load but also unstable condensing. 6 Heat Reclaim Heat reclaim is turned on with both systems. Medium Temperature Approximately 10-15 F of Heat is extracted from the discharge Low Temperature - Approximately 100 110 F of Heat is extracted from the discharge

7 Suction Header of the Medium Temperature Below it is shown the two suction lines coming from each chiller. Chiller 1 is in light blue and Chiller 2 in in light green. Chiller 2 should be looked at as the temperatures from this chiller fluctuates quite a bit more than Chiller 1. The Third temperature reading is the sub cool line coming from the Low Temperature side. It is not clear if the mechanical valves are working correctly. It is shown that the temperature stays constant for most of the day with periods of sudden drops in the temperature.