TRENCH HEATING LIMITED

Similar documents
TRENCH HEATING LIMITED

Katherm NE - Natural convection with electric heating element 2.45

Installation instructions

Wall Mountable Electric Fireplace with remote control

8 LITRE INSTANTANEOUS HOT WATER SYSTEM

Dale Power Solutions Ltd

Portable Air Conditioners

Residential Electric Water Heater

ATD Gallon Parts Washer Owner s Manual

Miniature Steam Custom Steam Plant Kit

PEDO Bench Includes Models: PB4000 & PB4001

Residential Electric Water Heater

Residen al Electric Water Heater

Residential Atmospheric Gas Water Heater with the Flammable Vapor Igni on Resistant Safety System

WHITE PAPER: IMPROVED RELIABILITY AND SAFETY IN A NEW STATE OF THE ART FABWIDE HEAT SOURCING AND CONTROL SYSTEM

Portable Garment Steamer User Manual

CERALIS GAS FIRE CERALIS XE GAS FIRE

Portable Air Conditioners

Residential Gas Water Heater Residen al Atmospheric Gas Water Heater with the Flammable Vapor Igni on Resistant Safety System

Portable Air Conditioners

INSTRUCTIONS WATER CHILLERS. Active Aqua Chiller, 1/10 HP. Active Aqua Chiller, 1/4 HP. DISTRIBUTED BY

Quick Start Guide X2

Residential Gas Water Heater

Residential Gas Water Heater Residen al Atmospheric Ultra Low Nox Gas Water Heater with the Flammable Vapor Igni on Resistant Safety System

POWERED ANODE SYSTEM

Clean Water Made Easy

Residen al Electric Water Heater

1/2 CONDENSATE TRAP INDEX

Direct Vent Tankless Water Heater Installa on and Opera on Manual

INSTRUCTION MANUAL BREAD MILL MODEL MPAL

Residential Electric Water Heater

Important safety instruc ons. Read carefully to reduce the risk of personal injury or damage to appliance.

FP EZ4F 4 Zone Controller

INSTALLATION INSTRUCTIONS MODELS JR-1 & JR-2 240/208 VOLTS 1 PHASE

Product Guide. Fiberglass Specialties Incorporated

BALANCED FLUE ROOM SEALED GAS FIRE

Installa ons will not be scheduled un l this form is returned to Service.

Bosch Non-Pressurized Flow Centers

Owner s Manual Safety, Installa on, Opera on, & Maintenance Guidelines

Hybrid Electric Heat Pump Water Heater

17th ARCTIC ISA EXHIBIT & SYMPOSIUM

Professional Instruments. Safe Gates. Regulations overview Safety for gates and doors Notice on the EN Certification

User Instructions for Remote Controlled 2kW Rotisserie Effect Fan Heater Model 1276

CHILL-CUBE MULTIBANK BY FRIULAIR

VIDEOLIFT MOTORIZED CEILING BRACKET. Videolift

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Owner s Manual Safety, Installa on, Opera on, & Maintenance Guidelines

Capability in. Electrical Safety. Services. Leaders in Risk Engineering and Safety Solu ons. An ISO 9001:2008 CERTIFIED CONSULTING ORGANISATION

USERS GUIDE. Installa on, Opera on, and Maintenance for your wine cooler. DUAL ZONE WINE COOLER Model- AWC460DZ.

Kitchen Care Guide. HomePro. connect with the best. The kitchen is the heart of the home - we want to help you look a er it. Wri en on March 14, 2017

Emergency Action Plan Office of Emergency Services University of California, Santa Cruz. Building Department Name Procedure Last updated

EH Fin Oil-Filled Radiator with timer

CONTROL PANELS for 2 Q2P series ELECTRIC PUMPS

FW821 extra large integrated larder fridge Manual for Installation, Use and Maintenance

Vanity Installa on Guide Model: AACCS-3001

IDEAL AIR Portable Air Condi oners Model:

TT302 (200W) Wireless receiver Pull cord Dimmer

Chair Side Unit (CSU) Includes CSU Models: 320, 351, 356, 362, 370, 3351 & AP 11

INSTALLATION INSTRUCTIONS MODELS SG-9, SG-14, SG-18, SG-23, SG-27, & SG-36 COMMERCIAL STEAM GENERATORS

Competency and Task List Supplement for program alignment to nationally established standards

Com-Pak Heater Benefits You Can Depend On Com-Pak Models Line Model w/o Model w/ Voltage Thermostat Thermostat Watts Amps (1) (2)

Installation Instructions & Operating Manual IMPORTANT

AC500T, AC1000T, AC1500T, AC2000T

About the Safety Program

Hybrid Electric Heat Pump Water Heater

Health Service Execu ve. Guidance for the Applica on of. Standards and Recommended Prac ces. for. Local Decontamina on Units (LDUs) in

15KW ELECTRIC FAN HEATER

Gobi II. English. Condensate Pump Instruction manual Gobi II

EH kW 11-Fin Oil-Filled Radiator

5KW ELECTRIC FAN HEATER

Installation & Service Manual. Models ALF 20, 30, 40, 50, 60, 80

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

UNIVERSAL PUMP CONTROLLER

University of Alaska Fairbanks Police Department Emergency Communica ons Center. Usage and Service Report December 31, 2015

T-RECESSED RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

NON-SUBMERSIBLE WATER PUMP

FAN HEATER. Models: DEVIL OPERATING & MAINTENANCE INSTRUCTIONS

At 06:29 PM 2/24/2011, you wrote: >>>>>Jim, thank you for your inquiry. We charge $0.20 per sq.. ($ >>>>>min.)

User and Installation Instructions. Opus 700 Electric Wet Well Bain Marie OE7601 IS195 ECN2396

BR342 Ducted Installation Instructions Australian Version Electronic Wall Control

EH kW Panel Heater

hp Dust Collector With Vacuum Attachment

STORM TACOMA 02. Potential permitting requirements STANDARD DETAILS FOR RAIN GARDEN CONSTRUCTION. How to use this document

4471 Walden Avenue Lancaster, New York

Installation and Maintenance

ATD INDUSTRIAL NON-OSCILLATING WALL MOUNTED FAN OWNER S MANUAL

ISCG90SS _03 ISCG90SS

Machine Brochure. Deway Glass Processing Eagle Machines Aluminium Processing Waterjet SA. Version 1.2

FF820 freestanding full height larder fridge Manual for Installation, Use and Maintenance

POWER SWEEP N VAC 1800W Model No. 101BV1800

ATD INDUSTRIAL OSCILLATING WALL MOUNTED FAN OWNER S MANUAL

Electric Tankless Water Heater

FW422. Integrated In Column Larder Fridge. Installation, use and maintenance.

UNIVERSAL PUMP CONTROLLER

MAXI Blower Vac 2200W Model No. 101BV2200

AUTOMATION. Operator s Manual LOE-2126 LOE-3136 LOE Internet Enabled Ultrasonic Sensor. Rev. B, 1/12

KOLDWAVE Portable Air Condi oners

XC Portable Air Conditioning

identity installation & maintenance instructions customer/technical services guarantee

30KW ELECTRIC FAN HEATER

Transcription:

TRENCH HEATING LIMITED www.trenchhea ng.com AQUAFAN-ELECTROFAN-ELECTROTRENCH WIRING/INSTALLATION INSTRUCTIONS AQUAFAN/ELECTROFAN Cross flow fan assisted convec on with ready to install in- floor units with LPHW/electric hea ng element. ELECTROTRENCH Natural Convec on Electric Table of Contents 1. Correct and proper use 2. Safety Informa on 3. Models/Scope of delivery 4. Alignment & Fixing 5. Screeding 6. Fixing of grilles 7. Wiring 7.1 Safety Informa on 7.2 Fi ng Instruc ons 7.3 230 v Connec on and Controls. Electrofan & Aquafan 7.4 230 v Connec on. Electrotrench 7.5 Wall Controllers 7.6 Electrofan safety cut out switches 7.7 Electrical ra ngs 7.8 Fan Acous c db 7.9 Maintenance 8.0 Test Cer ficates Explana on of symbols: Cau on: Danger Danger of electrocu on The non-observance of this informa on can result in serious injury to persons or property. Danger of electrocu on The non-observance of this informa on can result in serious damage to persons or property from electrical power. Read this manual carefully prior to assembly and installa on work. All persons involved in the installa on, commissioning and use of this product are obliged to pass this manual on to all persons working simultaneously or subsequently on the equipment, including the end user. Retain this manual un l the equipment is ul mately decommissioned. We reserve the right to make changes to the content or design without prior no fica on. 1

1. Correct and proper use AQUAFAN/ELECTROFAN/ ELECTROTRENCH units are manufactured in accordance with state-ofthe-art and recognised safety regula ons. Personal danger or damage to the equipment or other property can nevertheless be caused if the units are not installed, commissioned and used correctly and properly. AQUA/ELECTROFAN/ELECTROTRENCH units should only be used indoors (for example in residen- al and office buildings, salesrooms etc). They cannot be used in damp areas, such as swimming pools or outdoors. The products should be protected from moisture during installa on. In case of doubt discuss the proposed use with the manufacturer. Any damage resul ng from improper use is the sole responsibility of the user/operator of the equipment. Correct and proper use will also be deemed to include observance of all informa on regarding safety, opera on and maintenance/ servicing, contained in this manual. The installa on and electrical wiring of these products require specialist knowledge in the field of hea ng, cooling, ven la on and electrical engineering. This knowledge is generally taught as part of a voca onal training course in the aforemen oned fields and so is not described separately here. Damage resul ng from improper installa on is the sole responsibility of the operator. 2

2. Safety informa on Installa on, assembly and maintenance of electrical equipment should only be conducted by a qualified electrician. Wiring should comply with current BS7671: 2008 amended 2011. Non observance of these guidelines and the opera ng manual can lead to malfunc ons with subsequent damage to the equipment and risk personal injury. Incorrect wiring can result in fatal injury owing to crossed wires! Prior to all wiring and maintenance work, all parts of the system have to be made voltage-free and prevented from being reconnected accidentally! The installer of this unit should have adequate knowledge about: -Safety and accident preven on regula ons -Guidelines and recognised technical regula ons e.g E.N standards-en 60730 (Part 1) 3. AQUAFAN/ELECTROFAN/ElECTROTRENCH units are supplied as standard with: Height adjustment feet, with rubber bases. Grille removal tool. Fixings. 4. Alignment and Fixing Remove the blind grommets in the base of the heater. These are the floor fixing points. Posi- on the AQUAFAN/ELECTROFAN/ ELECTROTRENCH in the trench and adjust the height using the height adjustment feet. Mark through the fixing holes where the fixing holes are to be drilled. Remove the Heater and drill the fixing holes. Insert the drop in anchor into the holes. Replace the Trench Heater and fix in place. Tighten nuts on Adjustable Feet. Ensure that the installa on manual is visible on the unit for the subsequent trades. Cover the grille and the AQUAFAN/ELECTROFAN/ ELECTROTRENCH unit to protect it from dirt or cement. 5. Screeding Prior to commencing screeding, check whether the electrical connec on has been made correctly the AQUAFAN/ELECTROFAN/ELECTROTRENCH is aligned correctly in terms of height and distance to the window the grille has been covered (Cau on! Cement can destroy the surface of the grille!), sound insula on (not with raised floors) has been fi ed under the units where specified. ensure rubber/felt feet pads are in place (Aquafan/Electrofan ONLY) there are no sound bridges to the concrete slab, especially around the height adjustment feet all openings in the AQUAFAN/ELECTROFAN/ELECTROTRENCH have been sealed with suitable material against the ingress of screed Cau on the AQUAFAN/ELECTROFAN/ ELECTROTRENCH units should not be used as form work for final floor finish. Installa on drawings show a recommended working space allowance for best prac ce. 6. Fi ng grilles Grilles should be handled with care when removing and re-fi ng into unit. 3

7. Wiring 7.1 Safety Informa on The installa on and electrical wiring of this product requires specialist knowledge in the field of hea ng, cooling, ven la on and electrical engineering. This knowledge is generally taught as part of a voca onal training course in the aforemen oned fields and so is not described separately here. The installer of this unit should have adequate knowledge about -Safety and accident preven on regula ons -Guidelines and recognised technical - EN standards -Accident preven on direc ves -EN 60730 (Part 1) It is mandatory that the following safety-related informa on is adhered to prior to working on the controller and the units: Disconnect the unit from the mains power supply and ensure that it cannot be reconnected accidentally. Wire the unit in accordance with the wiring diagrams supplied. Wiring should comply with BS 7671: 2008 amended 2011. The unit should only be wired to fixed cables. Modifica ons to the units: Do not undertake any modifica ons, conversions or addi ons to the units without consul ng the manufacturer, as this would impair the safety and opera on of the equipment. Incorrect wiring or modifica ons to the unit can result in damage to the units. The manufacturer cannot be held liable for the damage caused by incorrect wiring and/or incorrect installa on and opera ons. Disregard of the regula ons and informa on contained in the opera ng manual can cause malfunc on of the unit with possible damage to the unit and risk of possible injury. Incorrect wiring and crossed wires can cause fatal injury! Please see the next page for wiring connec on details. 4

7.2 Fi ng Installa on 1 Remove Grille Remove End Panel bolts both ends for easy marking and drilling of fixing holes (only if required for ease of access) 2 Remove End Panel both ends Remove End Protec on Panels (slide towards end and pull up only if required for ease of access). 3 For Double Units Remove Centre Panel for Levelling & Fixing 5

Mark fixing posi ons Both ends & centre. Remove TH from opening and drill fixing holes 4 6 5 220-240 V Control Wires 7 LEVEL 8 5: Replace both ends 6: Cable in Control Box End (Do Not Connect yet) LEVEL 7: Adjust feet to Level Both ends & centre 8: Tighten Lock Nut to secure 9 Screw fixing in both ends & centre 6

7.3 ELECTROFAN/AQUAFAN: HEATER WIRING CONNECTIONS 230V SUPPLY required to each Trench Heater. Connect the 230 v supply to the Terminal block in each external enclosure L = Brown E = Green/Yellow N = Blue SIEMENS WALL STAT to Master Unit. CP+ = Red CP- = White MASTER TO SLAVE to the Terminal block in each external enclosure Terminal 1 = 0-10v Green Terminal 2 = 0v Black Terminal 3 = 24vDC Red IMPORTANT: ELECTROFAN & AQUAFAN HEATERS. AFTER POWER IS APPLIED TO THE MASTER UNIT, THE WALL STAT REQUIRES UP TO 10 MINUTES TO SYSTEM BOOT. DO NOT TOUCH THE WALL STAT DURING THIS PERIOD. CP+ CP- CP+ CP- SIEMENS WALL CONTROLLER SINGLE UNIT/MASTER-MASTER/SLAVE L N ELECTROFAN/AQUAFAN 230v SUPPLY CP+ CP- CP+ CP- SIEMENS WALL CONTROLLER 1 2 3 CONTROL FROM MASTER UNIT SINGLE UNIT/MASTER-MASTER/SLAVE SLAVE L N ELECTROFAN/AQUAFAN L N 230v SUPPLY 230v SUPPLY 2/0v 3/24vDC Aquafan: If a Motorised Valve is required to be operated from the Master unit 7

7.4 ELECTROTRENCH (NATURAL CONVECTION): HEATER WIRING CONNECTIONS 230V SUPPLY required to each Trench Heater. Connect the 230 v supply to the Terminal block in each external enclosure L = Brown E = Green/Yellow N = Blue Refer to the SIEMENS RAK-TR data sheet AND FOLLOW THE instruc ons when se ng the required temperature. Cau on: prior to opening the RAK Thermostat housing, disconnect the thermostat from the mains SIEMENS RAK THERMOSTAT THERMAL SENSOR PLAN VIEW L N 230v SUPPLY 7.5 Controls The AQUAFAN and ELECTROFAN Heaters are designed to be controlled via a SIEMENS wall mounted controller. The QAX34.3 or the QAX84.1/PPS2 Both of these units provide the following func ons: Auto temperature control Auto Fan Speed control to achieve desired temperature and minimise Fan use Fan speed manual override Fan only mode for cool air Frost protec on mode Please refer to the appropriate SIEMENS Control data sheet 7.6 Safety Cut-out Switches The Hea ng elements for AQUAFAN and ELECTROFAN have 3 Safety cut-out switches. The first switch (Re-set switch) will cut power to the Electric Element If it senses an unusual rise in temperature, that would occur in the event of material being placed over the heater and blocking the air flow. This switch will cut the power as the temperature rises and restart the unit when the temperature has lowered significantly. The other two switches will cut power to the Electric Heater if the temperature rises beyond the cut-off temperature of the first Re-set switch. The unit will not re-start and a fully qualified electrician must be called to inves gate if the reason for excessive heat is not obvious. A er inves ga on by a qualified electrician and having iden fied and resolved the problem the unit can be re-started by disconnec ng power to it and then re-connec ng power to it. 8

7.7 Electrical Ra ngs AQUAFAN Electrical Ra ngs Rated voltage 220-240 volts Rated frequency 50 Hz Rated power input 50 wa s at 230 volts ELECTROFAN Electrical Ra ngs Rated voltage 220-240 volts Rated frequency 50 Hz Rated power input 1250 wa s at 230 volts ELECTROTRENCH Electrical Ra ngs Rated voltage 220-240 volts Rated frequency 50 Hz ET-1: Rated power input 650 wa s at 230 volts ET-2: Rated power input 1300 wa s at 230 volts TYPE OF UNIT ELECTROTRENCH AQUAFAN ELECTROFAN MASTER AND SLAVE SINGLE UNIT 6 AMPS 1 AMP 12 AMPS MASTER SINGLE 3 AMPS 1 AMP 6 AMPS SLAVE SINGLE - 1 AMP 6 AMPS 7.8 Fan Acous c emissions (Standard: 2352012 Rev 1) AQUAFAN & ELECTROFAN Fan speed Low: 28 Db Fan speed medium: 33 Db Fan speed High: 45 Db 7.9 Maintenance Turn off power to the unit/s. Remove the Grille and carefully vacuum clean any debris-dust that is on the protec ve mesh. When re-applying power, follow the instruc ons on page 7 and allow 10 minutes for the Wall stat to system boot before using. 8. Test Cer ficates Tes ng Laboratory: York EMC Services Ltd EMC Test Standards: EN 55014-1:2006+A1:2009 EN 55016-2-3:2006 EN 55014-1:2006 EN 61000-3-2:2006+A1:2009+A2:2009 EN 61000-3-3:2008 LVD Test Standards: Report No: 10779TR1 EN 60335-1:2002 + A1:2004 + A2:2006 + A11:2004 + A12:2006 + A13:2008 + A14: 2010 EN 60355-2-30: 2009 db (Acous c certs) Test Standard: Report No: B998TR1 & B999TR1. Standard: 2352012 Rev 1 9