Flame detector FD 2011 / FD 2012

Similar documents
DATASHEET. Burner control unit FDA 601x

UV Flame Supervision System

LAE10 LFE10. Use. Series 02

Flame Safeguards LFE10. Building Technologies HVAC Products

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

UV - flame detector dual fuel burners for intermittent burner operations

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

EUROBOX SERIES TYPES CM...N SM...N MM...N

Flame Safeguards LFE10. Building Technologies HVAC Products

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR..

C Note! LGI16... Burner Controls. Building Technologies

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

DICTATOR Hold-Open Systems for Hazardous Areas

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products

Operating Manual MS220KA and MSR220KA

Burner Management System

Power Supply Display Module PSDM. Installation and Operation Manual

Old documentation - Only for your information! Product is not available anymore!

IRIS IP65 IRIS UNISCAN APPLICATION MANUAL

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

Burner control unit BCU 370

COMPACT FLAME CONTROLLER CFC 1000

EUROFLAT SERIES TYPES C... S... M...

Wide Band Flame Detector KLC 20 for all kind of oil flames with intermittent burnerr operations

Industrial Solid State Contactor TE10S. Static switching of resistive loads and shortwave infrared heating tubes up to 20 kw

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

EUROBOX SERIES TYPES CM... SM... MM...

UV - flame detector KLC 10 for oil -, gas- and dual fuel burners for intermittent burner operations

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

FDMM01S - FDMM02 - FDMM10- FDMM11S FDMM12 - Input / output mini modules

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

Safety. Operating instructions UV sensor UVS 10 DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place

DKG 972. Gas Burner Safety Control. For 2-stage atmospheric gas burners

Old documentation - Only for your information! Product is not available anymore!

LGA... Gas Burner Controls. Building Technologies Division

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

Burner control unit BCU 370

INPUT / OUTPUT MINI MODULES

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

Basic unit with integrated air-fuel ratio control for forced draft burners

COMPACT FLAME CONTROLLER CFC 2000

Protective system controls, automatic burner control units, burner control units. Industrial & Commercial Thermal. 6 Edition 06.

RIELLO 40 GS/M SERIES

COMPACT FLAME CONTROLLER CFC 200 (Formerly 8.XX)

Universal tank control WTS Installation and operating instructions for plant engineering companies

Operating Manual MS220DA

Smoke Vent Control Panel RZN 4202 V1

Gas Burner Safety Control DMG 970

MBCE-110/230FR Flame Sensor Module

Gas burner automatic safety control MMI / 811.1

Basic unit with integrated fuel-air ratio control for forced draft burners LMV Building Technologies Division

WaterLeakStop Z-8. 8-Zones Water Leak Detector Expansion Unit. User Manual

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)

FLAME AMPLIFIER MODULE 3001D

LFL Series Burner Flame Safeguard Control

AFMS Audible Flow Monitoring System TECHNICAL SPECIFICATION

FLAME AMPLIFIER MODULE 3001

Burner Management System

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

Use. The burner controls are certified to EN 230 and EN 298.

MICROFLAT SERIES TYPES C.../U T X

Forced draught gas burner

Burner control unit PFU 780

Flame detector. The QRA4.U is for use with the following types of burner control:

AC THOR. Assembly Instructions

Burner Management System

EN50438 TEST REPORT SUMMARY. Requirements for the connection of micro-generators in parallel with public low-voltage distribution networks

Instruction manual. Digital Radar Motion Detector with Infrared Remote Control MWD BF. FEIG ELECTRONIC GmbH Lange Straße Weilburg/Lahn

Process Alarm Module RTA 421

MBCE-110/230FR Flame Sensor Module

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Regulated Ex-Heater HEX with internal controller, HEX with external controller II 3 G II 3 D

COMPACT FLAME CONTROLLER CFC 100

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

Conventional Smoke Detectors KFAPO

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Leuze electronic. Dimensioned drawing. Electrical connection. Accessories: 150m ISO 9001

Safety. Operating instructions UV sensor UVS 5 DANGER. Contents WARNING CAUTION Elster GmbH Edition Please read and keep in a safe place

DECKMA. GmbH. Decksmaschinen und Automation Vertriebs GmbH BEDIENUNGSANLEITUNG FÜR FEUERMELDEANLAGE USER MANUAL FOR FIRE ALARM SYSTEM

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

Model Number Structure

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

System 800 Addressable Fire Detection & Alarm System

Forced draught gas burner

CATALOGUE PRODUITS - CSA - CSI - CSM - CSS - CSS2 - P16 - P19 - P20 - P25 - UV DETECTOR

UFM-T100H US ES CA Power Alarm Test TM

General information and installation instructions for Metal Detectors

SWARCO TRAFFIC SYSTEMS GMBH. TDD1-MW Traffic Detector User Manual TDD1-MW_BE_00

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Analogue addressable devices

Use. Burner controls for use with forced draught gas or gas / oil burners of small to medium capacity in intermittent operation.

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

FSW300 Series Flow Switch

FEC400 Series. Installation Manual

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

Transcription:

only for existing plants EN 298 / EN 230 2003 19 PCB 3HE / 6TE DIN 41612 2-chanal system continuous operation ionisation with common or separate spark and supervision electrode intermitted UV-mode integrated power supply 230V or 115V / 50-60Hz measuring points for flame signal The flame detector system FD 201x is designed for operation at continuous operating heat treating units. The universal use and also the easy integration in the main system are specific for this supervision unit. It also complies with the requirement of the European Standard EN 298 and EN 230. Fail safe ionization supervision is working with common or separate spark and supervision electrodes. UV-supervision is working in intermitted mode. Mixing mode UV and ionisation is possible with FD20xx. Operation is visualized by 2/3 LED s. Signal contacts are given potential free, measuring points for the flame signal on the front plate.

Technichal data operating voltage 115V or 230V, 50/60Hz; -10% / +15% current consumption at 230V - app. 26mA, losding app. 6,0VA power loss max. 4,2W contact load at 115V - app. 52mA AC: cos.φ = 1.0 max. load 50VA max. voltage 230V max. current 0,25A DC: max. load 6W max. voltage* 24V max. current 0,25A * do not use for low-voltage protection (VDE 0100 DIN 40803) VDE 0860/08.91 switching frequency at cos.φ = 0,6 and at cos.φ = 1,0: 2,5 x 10 5 model PCB 100x160 mm with front panel 3HE/6TE, socket for mounting on DIN 41612 model F, z + d, 32 pins. FD-flame signal >1...2µA, metering points on terminal, metering without current circuit interruption, maximum 30µA. Attention! High voltage! 2µA ON 1,5µA OFF temperature range 0 C / +60 C operation mode continuous operation ionisation EN298 and EN230 also with common spark- and supervising electrode UV-operation intermitted. weight app. 350g protection class IP00 CE marking No. 0063BT1339 protection for the contacts: a. AC: RC-combination or varistor (metalloxyd) b. DC: diodes (U block > 5 x U valve ) Safety shut-off devices can not be switched directly! maximum length of cable: Ionisation supervision max. 75m, ionisation cable separate from power, UV-supervision max. 50m, cable Ölflex YSLY-JZ 3 x 1,5mm². 2

Connection example 1/3 for FD 2011, FD 2012 Monitoring of ionisation with common spark- and monitoring electrode Connection example 2/3 for FD 2011, FD 2012 Monitoring of ionisation with separate ignition- and monitoring electrode 3

Connection example 3/3 for FD 2011, FD 2012 Monitoring with UV-tube All rights reserved. Transfer, processing and reproduction of this publication or parts thereof, without the express permission of the company HANS HENNIG GmbH, is forbidden. Technical modifications, which serve the progress, are reserved. 4

Appendix to flame detector FD 2011, FD 2012 For a failure-free operation of the Flade detector FD 201x, you should pay attention on the early stage of development. Additional modifications on existing plants increase the costs. To prevent unnecessary expenses, please follow the remarks: General The flame detector FD 201x is certificated and subjected to EN 298/ EN 230. Installation and handling of the flame detector by authorised specialists only. Advice for cable laying outside the switchboard: The flame detector FD 201x should be installed vibration-free. Electronically components should be installed in shielded areas, according to there sensitivity. Don t install the flame detector FD 201x close to a frequency converter or transformers. Separate laying of measuring- / data cores and high voltage cores or cables. In general we advice a separate laying of ignition cable. Advice for the installation inside the switchboard: If a power transformer is used, we advice a power transformer with shield winding. Valves, contactors, relays and ignition transformers must have a protective circuit as follows: DC voltage: recovery diode; AC voltage: RC-combination / varistor parallel to the coil; Eathing measures: Decide on a adequate central earth point, which receives all earth cores and shields. In an exceptional case it could be necessary to lay the shield on a separate terminal block. The cross-section of an earth core must be big enough. A loop laying of an earth core must be avoided. Every earthing must be direct on the central earth bar and on the feeder earth. Advice for the installation inside the switchboard: If a power transformer is used, we advice a power transformer with shield winding. Valves, contactors, relays and ignition transformers must have a protective circuit as follows: DC voltage: recovery diode; AC voltage: RC-combination / varistor parallel to the coil; Eathing measures: Decide on a adequate central earth point, which receives all earth cores and shields. In an exceptional case it could be necessary to lay the shield on a separate terminal block. The cross-section of an earth core must be big enough. A loop laying of an earth core must be avoided. Every earthing must be direct on the central earth bar and on the feeder earth. Before initial start-up of flame detector FD 201x check the following: The phasing of voltage must be adhered. Has the unit got fluctuation of temperature, otherwise it is for seeing, that no condensation water arose. Is the voltage supply identical to the specification on the flame detector (link on the blank). edition jan.2017 5